Combined Footing - Format
Combined Footing - Format
Nadim Hassoun
Foundations
Before starting with the foundations design, a soil investigation has to be performed to check the
soil characteristics and propertires. The site soil must be checked if its capable to hold the load
transferred to it through the footings (Shear test, Ultimate Bearing Capacity "qu", etc...).
The Bearing Capacity is required for designing the foundation. If the soil investigation indicates
poor ground conditions, (Such as the bearing capacity is less than the allowable), A Ground
Improvement technique must be performed to treat and improve the soil that support the footing
and make it safe to build with.
Geogrids
Grouting
Piles
Designing Notes
It is preferable to check the sizes or dimensions of each footing before starting designing them.
This must be done to choose the required and preferred system of footing (Single, Combined, etc.).
A fast calculation can be performed using the following formula:
Service Load / Stress
Where the Service load can be taken = 1.5 of the Ultimate Load that is being transferred from
The Columns. And the Stress is the one that is provided from the soil tests (i.e. 3 Kg/cm²)
Example
Pu = 250 Ton Area of footing = (250,000/1.5) / 3 = 55555.55 cm²
qu = 3 kg/cm² or A = 5.55 m²
Page 1 of 9
Project Name TWO STOREY RESDL BLDG
Subject Design of Combined Footing
Element Number CF3
fc' = 21 Mpa
fy = 275 Mpa
Concrete Density = 23.5 kN/m³ 200cm 200cm
Weight of Soil = 17.6 kN/m³ 350cm I II 350cm
Column Dimentions:
Column I 200 x 350 mm
Column II 200 x 350 mm
Column Spaces Center-Center = 1.6 m 0m 1.6m 0.6m
Space from Property line to center of 2.2m
Column I 0 m Property Line
Resultant
Loads Carried By Columns:
Column I D.L. = 58 kN 0m 1.05m
L.L. = 46.08 kN
Page 2 of 9
Project Name TWO STOREY RESDL BLDG
Subject Design of Combined Footing
Element Number CF3
Factored moment
Mu1 (at outer face column I) = 1.066903 Kg.m
Mu2 (at outer face column II) = 26.67258 Kg.m
As = 2380 mm²
Min. As (Shrinkage) = 1071 mm² Hence, As = 2380 mm² Controls
Page 3 of 9
Project Name TWO STOREY RESDL BLDG
Subject Design of Combined Footing
Element Number CF3
Page 4 of 9
Project Name TWO STOREY RESDL BLDG
Subject Design of Combined Footing
Element Number CF3
6 # 16 3 # 16 6 # 16 3 # 16
350cm 350cm
1.7m 1.7m
Exterior Footing I Interior Footing II
Shrinkage
Steel
-1m 200cm 200cm -0.4m
3 # 16 6 # 16 12 # 16 bars 6 # 16 3 # 16 350cm
2.2m
Page 5 of 9
Project Name TWO STOREY RESDL BLDG
Subject Design of Combined Footing
Element Number CF3
Page 6 of 9
Project Name Two Storey Resdl Bldg
Subject Design of Combined Footing
fc' = 4 Ksi
fy = 40 Ksi
Concrete Density = 150 lb/ft³ 15.744" 15.744"
Weight of Soil = 100 lb/ft³ 15.744" I II 15.744"
Column Dimentions:
Column I 15.744 x 15.744 in
Column II 15.744 x 15.744 in
Column Spaces Center-Center = 8.2021 ft 4.265' 8.20209973753281' 4.06290026246719'
Space from Property line to center of 16.53'
Column I 4.265 ft Property Line
Resultant
Loads Carried By Columns:
Column I D.L. = Kips 4.265' 4'
L.L. = 151 Kips
Point of zero shear, x: distance between interior faces of columns I and II is:
x = 3.344041 ft
Page 7 of 9
Project Name Two Storey Resdl Bldg
Subject Design of Combined Footing
Factored moment
Mu1 (at outer face column I) = 190.3378 K.ft
Mu2 (at outer face column II) = 169.6173 K.ft
As = 6.381341 in²
Min. As (Shrinkage) = 3.690709 in² Hence, As = 6.381341 in² Controls
The bars are extended between the columns at the top of the footing with a concrete cover 3 in. Place
minimum reinforcement at the bottom of the projecting ends of the footing beyond the columns to take care
of the positive moments. Extend the bars a development length ld beyond the side of the column.
The minimum shrinkage reinforcement As = 3.691 in2.
Page 8 of 9
Project Name Two Storey Resdl Bldg
Subject Design of Combined Footing
5#8 15 # 8 5#8 15 # 8
1.14829396325459' 1.14829396325459'
12.4' 12.4'
Exterior Footing I Interior Footing II
Shrinkage
Steel
3.609' 15.744" 15.744" 3.407'
16.53'
Page 9 of 9