Relay Settings
Relay Settings
Manufacturer : ALSTOM
Type : MICOM P142
Model :
Rated Current (In) : 1A
1 . Sn
Maximum primary through fault current Ifp :
Zcc Unp.√3
Ifp : 1217.31 A
1 . Sn
Maximum secondary through fault current Ifs :
Zcc Uns.√3
Ifs : 9703.16 A
110/13.8kV POWER TRANSFORMER
Ins .
Required setting Isr : R
K
Isr : 1.13 A
k
t = TMS a +c
Ii - 1
K. Is
110/13.8kV POWER TRANSFORMER
1
tRI = kRI
0.339 - 0.236
Ii
Is
The minimum tripping time (calculated with the minimum value between 20.K.Is, limit of the curve,
and Iphf, the maximum fault current) shall be less than the fault withstanding duration and higher
than the main protections tripping time.
Max through fault current 9703.2 A
Iphf = 25 kA
Ii = 9.703 kA
TMS = 0.060 s
t = 1.317 sec
110/13.8kV POWER TRANSFORMER
1.2.4 HIGHSET OVER CURRENT SETTING - 2ND TRESHOLD : " I >> "
To be considered more than 1.5 times the max. through fault current to allow discrimination with MV.
Ifp
I >> : 1.5 x
K
Isup .
Required setting Isrn : Rn
Kn
Isrn : 0.045 A
k
t = TMS a +c
Ii - 1
K. Is
110/13.8kV POWER TRANSFORMER
1
tRI = kRI
0.339 - 0.236
Ii
Is
t = 1.400 sec
110/13.8kV POWER TRANSFORMER
1.4.4 HIGHSET EARTH FAULT SETTING - 2ND TRESHOLD : " Io >> "
To be considered 1.5 times the max. through fault current to allow discrimination with MV.
Ifp
Io >> : 1.5 x
K