LV Panel Data Sheet
LV Panel Data Sheet
LV Panel Data Sheet
HP Amine Project
Purchaser Review & Comments shall not be assumed to indicate either responsibility or liability for
accuracy & completeness of this document or to alter any contractual terms & conditions
Purchase Order
No: 4531438800
Equip Tag
Number(s): LT12-2 (EXTENSION)
Vendor Doc
Number & Rev: 2TES020020-5001 Rev. No. A
Date: Sign:
Rated Voltage: 440V, AC Wiring Type * Control Wiring: 0.6/1kV 110⁰C, Flame Retardant, Halogen Free.
System 440V, 60Hz, 3 Phase, 4 Wire Power Wiring: (Line side on 8E4-8E2): 1.8/3kV, 90⁰C, Halogen Free, NSHXAFÖ
Fault Level: 80 kA 1 sec Power Wiring: (Load side on 8E4-8E2): 450/750V, 90⁰C, Hologen Free H07Z-K
Insulation Level: 1000V (Outgoing Modules 690V) Power Wiring: (35mm2 and 70mm2): 1.9/3.3kV, 110⁰C, Halogen Free, SDI
A
Earthing System: TN-S Power Wiring (Elsewhere): Min: 0.6/1kV, 90⁰C, Radox
Diversity factor: 1
Design Temperature: 35 °C Wiring Size * Control : max 1.0 mm2 For 8E/2 modules
min 1.0 mm2 Elsewhere
2. CONSTRUCTION: Power: min 2.5 mm2
Power CT & VT: min 4.0 mm2
Type: MNS 3.0 Low Voltage Switchgear Earth: min 2.5 mm2
Double Sided (Duplex)
Degree of Protection: IP41
Form of Segregation: Form 3B (MCC Panels), Internal Separation to IPXXB Wiring Colour * CT & VT: Red / White / Blue / Black / G-Y (L1 / L2 / L3 / N / PE)
Standard: IEC 61439-1 Power: Red / White / Blue / Black / G-Y (BLK cable w/- sleeving)
Size Distribution Busbar: Phase + Neutral 1 x 50 x 30 x 5 (L-Bar) * - Sizes and colours stated apply to wiring outside pre-assembled
Earth: 1 x 40 x 5 (Cable Zone) equipment and component parts ie Protection relays
8. CONTROL TERMINALS
Insulation: Bars: Fully Insulated
Joints: Fully Insulated Control Terminals: MNS Module Weidmuller MNS Specific design type
Elsewhere Weidmuller WDU4 (up to 4mm sq Cable)
Finish: Distribution bar: Silver Plated Test Terminals: Weidmuller WTL 6/1/STB
Main BusBar Electro Tin Plated
Elsewhere: Electro Tin Plated 9. PAINT FINISH: RAL 7032 Smooth Finish
C
Colour (L1/ L2/ L3/ N/ PE): Identified at 1m Intervals 10. LABELS:
(Red / White / Blue / Black / Green-Yellow)
via self adhesive labels External:
Refer to ABB standard label drawing: 2TES020020-4001
4. CABLE ENTRY DETAILS:
Internal
Cable entry Bottom All labels self adhesive type.
Gland Plate Material Galvanised Steel
For dimensions refer to General Arrangement drawing 11. PACKING DETAILS: Seet bag and Case
Client to ensure lifting facilities are available.
5. MOTOR PROTECTION RELAY: Thermal Overload Relay
12. INSPECTION: Switchboard Inspection and Test plan as per ITP - 2TES020020-ITP-01
PHILIPPINES 1 1
REVISION
A
REV
EX
BY
31.03.2020 FIRST ISSUE
DATE DESCRIPTION
HL
CKD ABB
TITLE:
ABB Australia Pty Limited
DOCUMENT NUMBER
A
DIM IN MM MANUFACTURE TO COMPLY WITH RELEVANT SPECS DO NOT SCALE DWG FOR WORKING DIM
TECHNICAL DATA SHEET FOR
WE RESERVE ALL RIGHTS IN THIS DOCUMENT AND IN THE INFORMATION CONTAINED THEREIN. REPORDUCTION, USE OR DISCLOSURE TO THIRD PARTIES WITHOUT EXPRESS AUTHORITY IS STRICTLY FORBIDDEN - ABB
AUSTRALIA PTY LIMITED LT12-2 EXTENSION 2TES020020-5001