This document provides calculations for CO2 fire protection requirements for a project. It lists the input data used, including an area of 30 square meters, a height of 3.5 meters, a ventilation area of 12 square meters, a volumes factor of 1.35 kg/m3, a time of discharge of 2 minutes, and a forced ventilation rate of 5 kg/min. The output data calculated is a required CO2 mass of 201.75 kg and a required flow rate of 100.875 kg/min.
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
228 views

CO2 System Calculations

This document provides calculations for CO2 fire protection requirements for a project. It lists the input data used, including an area of 30 square meters, a height of 3.5 meters, a ventilation area of 12 square meters, a volumes factor of 1.35 kg/m3, a time of discharge of 2 minutes, and a forced ventilation rate of 5 kg/min. The output data calculated is a required CO2 mass of 201.75 kg and a required flow rate of 100.875 kg/min.
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

CO2 REQUIREMENTS

Project Name CO2 Fire Protection


Calculated By A. Badran
Checked By A. Badran
Date AUG-25-2016

Input Data: Value Unit


AREA 30 m2

HEIGHT 3.5 m

VENTILATION AREA 12 m2

VOLUMES FACTOR 1.35 Kg/m3

TIME OF DISCHARGE 2 min

FORCED VENTILATION 5 Kg/min

Output Data:

CO2 Mass 201.75 Kg

FLOW RATE 100.875 Kg/min