SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD WIRE - Rev-0

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 20

SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD

WIRE
1.0.0 DESIGN INPUT

1.1.0 SYSTEM PARAMETERS

1.1.1 Conductor type & strands = TWIN ACSR Moose

1.1.2 Initial Tension (Max.) T1 = 3000 kg

1.1.3 C/C Distance of Tower (Maximum Span) = 64 m

1.1.4 Girder Width Lg = 1.5 m

1.1.5 Tower height H1 = 22 m

1.1.6 Height of Main bus H2 = 15 m

1.1.7 Number of Conductors nc = 2 Nos.

1.1.8 Number of Insulator Strings ns = 2 Nos.

1.1.9 Spacer Span Ds = 4 m

1.1.10 Basic Wind Speed Vb = 47 m/s (AS PER TECH. SPEC)

1.1.11 Span (c/c tower - lg) Ls = 62.5 m

Equivalent Conductor. Span (L) L 61.61 m

1.1.12 Every day Temperature To = 55 °C (AS PER TECH. SPEC)

1.1.13 Minimum Temperature Tmin = -5 °C (AS PER TECH. SPEC)

1.2.0 ACSR Conductor

1.2.1 Conductor unit weight m's = 2.004 kg/m

1.2.2 Conductor Area Ac = 5.97E+00 cm2

1.2.3 Conductor overall diameter dc = 3.177 cm

1.2.4 Expansion coefficient of conductor α = 2.15E-05 /°C

1.2.5 Elasticity modulus E = 7.0E+05 kg/cm2

1.2.6 Weight of the spacer mc = 2 kg

1.3.0 Tension Insulator

1.3.1 Total no. of insulator string nd = 1

1.3.2 Weight of Insulator Wd = 99 kg

1.3.3 Weight of hardware/ string Wh = 18 kg

1.3.4 Mean Diameter of Insulator di = 0.14 m

1.3.5 Length of discs per string Ld = 0.09886364 m

LITL-021-ELV-302-R-003 REV - 00 1 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE
1.3.6 Length of hardware Lh = 0.5 m

2.0.0 DESIGN CRITERIA

2.1.0 The design calculation for maximum sag of lower most conductor is based on the "Generation, Transmission
and Utilization of Electrical Power" by A. T. Starr
2.2.0
Maximum initial tension is assumed at 55˚ C temperature and Full Wind.

2.3.0
It may be noted that in short dead ended span, insulator strings have considerable effect on the sag of the
conductors. The conductor assumes one catenary and the insulator string another.

3.0.0 REFERENCES

3.1.0 Standards

IEC 60826

IEC 865-1 (1993)

IEEE 605 (1998)

3.2.0 Books

"Generation, Transmission and Utilization of Electrical Power" by A. T. Starr

4.0.0 CALCULATION OF BASIC DESIGN PARAMETERS

4.0.1 Weight of the insulator string

Wi = nd x Wd = 99 x 1 = 99 kg

4.0.2 String Weight per conductor

Wwi = (Wi + Wh) x ns /nc = (99+18)x2 / 4 = 58.5 kg

4.0.3 String length

Lstr = (nd x Ld) + Lh = (1 x 0.0988636363636364) + = 0.599 m

4.0.4 Conductor Chord length

Lc = (L - Lg) - (2 x Lstr) = (64 - 1.5) - (2 x 0.599) = 61.302 m

4.0.5 Total number of spacers

np = (Lc /Ds)-1 = (61.302 / 4) - 1 = 14

5.0.0 DESIGN CALCULTION

5.1.0 Design wind speed (Vd)

LITL-021-ELV-302-R-003 REV - 00 2 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE
Basic wind speed VRB = 40.2 m/s

5.2.0 Unit action of wind speed (q0)

q0 = 1/2xtxm(KRVRB)2 = = 674.749479 N/m2

Where,

air mass per unit volume m = 1.225 kg/m3

air density correction factor t = 0.94351

Terrain roughness co efficient kR = 0.85

5.3.0 Equivalent Self weight of conductor (m'sc)

m'sc = m's + ((np x mc) / (nc x Lc)) = 2.004 + ((14 x 2) / (2 x 61.302))

m'sc = 2.233 kg/m

5.3.1 Wind pressure on conductor (Ac)

Full wind pressure on conductor,

Ac = q0 x Cxc x Gc x GL x d x L x sin2Ω = 51.450 N

where,

Drag Co efficient for conductor Cxc = 1 (As per IEC 60826, Clause 6.2.6, Pg no:49)

Combined wind factor for conductors Gc = 2.4

span factor GL = 1 (As per IEC 6082, Clause 6.2.6, Pg no:50)

diameter of the conductor d = 0.03177

wind span of the support L = 1

Ω = 90
Ω is the angle between the wind
direction and the conductor

Ac = 5.24465 kg/m

6.00 For initial condition of 100% wind loading at ### 0


C

Temp (in deg C) = 55

Wind Factor = 1

Equivalent Self weight of conductor (m'sc) = 2.233 kg/m

Equivalent wind load on Conductor p(eq) = Ac x 1 = 5.24465 kg/m

LITL-021-ELV-302-R-003 REV - 00 3 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE
Loading factor q1 = 2.55

Temp (in deg C) = 75

Wind Factor = 0.00

Equivalent Self weight of conductor (m'sc) = 2.233 kg/m

Equivalent wind load on Conductor p(eq) = 0.00

Loading factor q2 = 1.00

Stress (f1) at initial temperature( 550 c)

f1 = T1 / Ac = (3000 / 5.97) = 5.0251E+02 kg / cm2

Weight per unit area (&) = 2.233/5.97 = 3.7404E-01 kg/m/cm2

Initial Design Wind load Factor = 1.00

Initial loading factor q1 = 2.55

( Loading Factor q = ( p 2 + m'sc 2 ) ^1/2 / m'sc )

6.1.1 Calculating Stress at final stringing condition t2 & loading conditions q2 :

f2 2x ( f2 - ( K1 - e x t x E)) = K2 x q 2 2

K1 = f1 - L 2x & 2x q1 2x E / 24 x( f1 ) 2

= 101.77

K2 = L 2x & 2x E / 24

= 1.56E+07

Sag in conductor = m'sc x L^2/(8*T1 )

6.1.2 Sag - Tension at Initial conditions.

Temp ( deg C) = 55 Tension = 3000 kg

Wind factor = 1 Sag = 0.35315 m

6.1.3 Sag - Tension at specific conditions.

Temp ( deg C) = 75 t = 75-55 = 20 deg C

Wind factor = 0.00

f2 2 x ( f2 - ( K1 - e x t x E)) = K2 x q2 2

f2^2 X (f2-(101.77 X 0.0000215 X 20 X 703364)) = 15562490.1458 x 1^2

691215.0649 = 15562490.15

LITL-021-ELV-302-R-003 REV - 00 4 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE
f2 = 52.2743355350618 kg/cm2

Tension = 312 kg

Sag = 3.39567058909058 m

7.00 SAG CALCULATION AT ANY TEMPERATURE AND WIND LOAD CONDITION

7.1.0 Constant (a1) for conductor catenary

a1 = T / W2 = 312 / 2.233 = 139.73

7.1.1 Constant (a2) for insulator catenary

a2 = T / Wi2 = 312 / (58.5 / 0.599) = 3.2

7.1.2 Assumed half inclined length of conductor span (X ass)

Xass = ((Ls /2) - Lstr) x 1.005 = ((62.5 / 2) - 0.599) x 1.005 = 30.8

7.1.3 Projected length of catenary arc (X1)

X1 = a2 x Xass / a1 = 3.2 x 30.8 / 139.73 = 0.71

7.1.4 Arc from insulator catenary centre to end of string (SP)

SP = a2 x sinh(X1 / a2) = 3.2 x sinh(0.71/3.2) = 0.72

7.1.5 Total arc length (RSP)

RSP = Lstr + SP = 0.599 + 0.72 = 1.319 m

7.1.6 Projected length of total Arc (X2)

X2 = a2 x sinh-1(RSP / a2) = 3.2 x sinh-1 (1.319 / 3.2) = 1.29

7.1.7 Projected length of insulator string (X3)

X3 = X 2 - X1 = 1.29 - 0.71 = 0.58

7.1.8 Actual Half inclined length of conductor Span (X)

X = (Ls / 2) - X3 = (62.5/2) -0.58 = 30.67

7.1.9 Sag at centre of insulator catenary, below end of string (D1)

D1 = a2x(cosh(X1/a2) - 1) = 3.2 x (cosh(0.71/3.2) - 1) = 0.08

7.2.0 Sag at centre of insulator catenary, below support (D2)

D2 = a2x(cosh(X2/a2) - 1) = 3.2 x (cosh(1.29/3.2) - 1) = 0.27

8.00 Conductor Sag below end of insulator string (D3)

D3 = a1x(cosh(X/a1) - 1) = 139.73 x (cosh(30.67/139.73) - 1) = 3.38

LITL-021-ELV-302-R-003 REV - 00 5 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE
8.0.1 Total Sag at temperature = 75 with wind factor = 0

S = D3 + D2 - D1 = 3.38 + 0.27 - 0.08 = 3.57 m

CONCLUSION

SAG TENSION TABLE FOR DIFFERENT TEMPERATURES AND WIND CONDITIONS

Temperature Full wind condition Still wind condition

Tension (kg) Sag (m) Tension (kg) Sag (m)

-10 1132.00 2.48 459.00 2.43


-5 1103.00 2.54 445.00 2.5

0 1075.00 2.62 432.00 2.58

5 1049.00 2.67 421.00 2.65

10 1025.00 2.74 410.00 2.7

15 1003.00 2.8 400.00 2.78

20 982.00 2.86 390.00 2.84

25 962.00 2.92 382.00 2.91

30 943.00 2.98 374.00 2.97

35 925.00 3.04 366.00 3.04

40 908.00 3.09 359.00 3.1

45 892.00 3.15 352.00 3.16

50 877.00 3.2 345.00 3.22

55 862.00 3.26 339.00 3.28

60 849.00 3.31 333.00 3.34

65 835.00 3.36 328.00 3.4

70 823.00 3.41 323.00 3.45

75 811.00 3.47 318.00 3.5

80 817.00 3.45 308.00 3.61

8.0.2 Maximum Working Tension T = 3000 kg

8.0.3 Maximum sag of Lower most conductor S = 3.5 m

8.0.4 Height of tower H = 22 m

LITL-021-ELV-302-R-003 REV - 00 6 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE
8.0.5 Height of Main Bus h = 15 m
Insulator sag of main bus (total sag - Sag -
8.0.6 = -48.66
Tension at specific conditions)
Vertical Clearance between lower most
8.0.7 Vclr = 5.449 m (taken from drawing)
Conductor and equipment
Minimum clearance between phase to phase for
8.0.7 = 4.2 m
400kV

Since the calculated vertical clearance between Equipment and Lower most conductor is greater than the
minimum clearance between phase to phase, The selected height of tower 22m is adequate.

LITL-021-ELV-302-R-003 REV - 00 7 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE

LITL-021-ELV-302-R-003 REV - 00 8 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE
1.0.0 DESIGN INPUT

1.1.0 SYSTEM PARAMETERS

1.1.1 Conductor type & strands = QUAD AAC BULL

1.1.2 Initial Tension (Max.) T1 = 1100 kg

1.1.3 C/C Distance of Tower (Maximum Span) = 54 m

1.1.4 Girder Width Lg = 2 m

1.1.5 Tower height H1 = 15 m

1.1.6 Height of Main bus H2 = 8 m

1.1.7 Number of Conductors nc = 4 Nos.

1.1.8 Number of Insulator Strings ns = 2 Nos.

1.1.9 Spacer Span Ds = 6 m

1.1.10 Basic Wind Speed Vb = 40.2 m/s (AS PER TECH. SPEC)

1.1.11 Span (c/c tower - lg) Ls = 52 m

Equivalent Conductor. Span (L) L 48.99 m

1.1.12 Every day Temperature To = 55 °C (AS PER TECH. SPEC)

1.1.13 Minimum Temperature Tmin = -10 °C (AS PER TECH. SPEC)

1.2.0 AAC Conductor

1.2.1 Conductor unit weight m's = 2.4 kg/m

1.2.2 Conductor Area Ac = 8.65E+00 cm2

1.2.3 Conductor overall diameter dc = 3.825 cm

1.2.4 Expansion coefficient of conductor α = 2.30E-05 /°C

1.2.5 Elasticity modulus E = 5.9E+05 kg/cm2

1.2.6 Weight of the spacer mc = 1.999 kg

1.3.0 Tension Insulator

1.3.1 Total no. of insulator string nd = 1

1.3.2 Weight of Insulator Wd = 165 kg

1.3.3 Weight of hardware/ string Wh = 60.1 kg

1.3.4 Mean Diameter of Insulator di = 0.225 m

1.3.5 Length of discs per string Ld = 0.145 m

LITL-021-ELV-302-R-003 REV - 00 8 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE
1.3.6 Length of hardware Lh = 1.484 m

2.0.0 DESIGN CRITERIA

2.1.0 The design calculation for maximum sag of lower most conductor is based on the "Generation, Transmission
and Utilization of Electrical Power" by A. T. Starr
2.2.0
Maximum initial tension is assumed at 55˚ C temperature and Full Wind.

2.3.0
It may be noted that in short dead ended span, insulator strings have considerable effect on the sag of the
conductors. The conductor assumes one catenary and the insulator string another.

3.0.0 REFERENCES

3.1.0 Standards

IEC 60826

IEC 865-1 (1993)

IEEE 605 (1998)

3.2.0 Books

"Generation, Transmission and Utilization of Electrical Power" by A. T. Starr

4.0.0 CALCULATION OF BASIC DESIGN PARAMETERS

4.0.1 Weight of the insulator string

Wi = nd x Wd = 165 x 1 = 165 kg

4.0.2 String Weight per conductor

Wwi = (Wi + Wh) x ns /nc = (165+60.1)x2 / 6 = 75.033 kg

4.0.3 String length

Lstr = (nd x Ld) + Lh = (1 x 0.145) + 1.484 = 1.629 m

4.0.4 Conductor Chord length

Lc = (L - Lg) - (2 x Lstr) = (54 - 2) - (2 x 1.629) = 48.742 m

4.0.5 Total number of spacers

np = (Lc /Ds)-1 = (48.742 / 6) - 1 = 7

5.0.0 DESIGN CALCULTION

5.1.0 Design wind speed (Vd)

LITL-021-ELV-302-R-003 REV - 00 9 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE
Basic wind speed VRB = 40.2 m/s

5.2.0 Unit action of wind speed (q0)

q0 = 1/2xtxm(K RVRB)2 = = 674.749479 N/m2

Where,

air mass per unit volume m = 1.225 kg/m3

air density correction factor t = 0.94351

Terrain roughness co efficient kR = 0.85

5.3.0 Equivalent Self weight of conductor (m'sc)

m'sc = m's + ((np x mc) / (nc x Lc)) = 2.4 + ((7 x 1.999) / (4 x 48.742))

m'sc = 2.472 kg/m

5.3.1 Wind pressure on conductor (Ac)

Full wind pressure on conductor,

Ac = q0 x Cxc x Gc x GL x d x L x sin2Ω = 61.950 N

where,

Drag Co efficient for conductor Cxc = 1 (As per IEC 60826, Clause 6.2.6, Pg no:49)

Combined wind factor for conductors Gc = 2.4

span factor GL = 1 (As per IEC 6082, Clause 6.2.6, Pg no:50)

diameter of the conductor d = 0.03825

wind span of the support L = 1

Ω = 90
Ω is the angle between the wind
direction and the conductor

Ac = 6.31498 kg/m

6.00 For initial condition of 100% wind loading at ### 0


C

Temp (in deg C) = 55

Wind Factor = 1

Equivalent Self weight of conductor (m'sc) = 2.472 kg/m

Equivalent wind load on Conductor p(eq) = Ac x 1 = 6.31498 kg/m

LITL-021-ELV-302-R-003 REV - 00 10 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE
Loading factor q1 = 2.74

Temp (in deg C) = 75

Wind Factor = 0.00

Equivalent Self weight of conductor (m'sc) = 2.472 kg/m

Equivalent wind load on Conductor p(eq) = 0.00

Loading factor q2 = 1.00

Stress (f1) at initial temperature( 550 c)

f1 = T1 / Ac = (1100 / 8.6536) = 1.2711E+02 kg / cm2

Weight per unit area (&) = 2.472/8.6536 = 2.8566E-01 kg/m/cm2

Initial Design Wind load Factor = 1.00

Initial loading factor q1 = 2.74

( Loading Factor q = ( p 2 + m'sc 2 ) ^1/2 / m'sc )

6.1.1 Calculating Stress at final stringing condition t2 & loading conditions q2 :

f2 2x ( f2 - ( K1 - e x t x E)) = K2 x q 2 2

K1 = f1 - L 2x & 2x q1 2x E / 24 x( f1 ) 2

= -2097.56

K2 = L 2x & 2x E / 24

= 4.79E+06

Sag in conductor = m'sc x L^2/(8*T1 )

6.1.2 Sag - Tension at Initial conditions.

Temp ( deg C) = 55 Tension = 1100 kg

Wind factor = 1 Sag = 0.67407 m

6.1.3 Sag - Tension at specific conditions.

Temp ( deg C) = 75 t = 75-55 = 20 deg C

Wind factor = 0.00

f2 2 x ( f2 - ( K1 - e x t x E)) = K 2 x q2 2

f2^2 X (f2-(-2097.56 X 0.000023 X 20 X 586850.152905199)) = 4788043.5731 x 1^2

6612320.4954 = 4788043.57

LITL-021-ELV-302-R-003 REV - 00 11 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE
f2 = 52.2743355350618 kg/cm2

Tension = 452 kg

Sag = 1.64043436575015 m

7.00 SAG CALCULATION AT ANY TEMPERATURE AND WIND LOAD CONDITION

7.1.0 Constant (a1) for conductor catenary

a1 = T / W2 = 452 / 2.472 = 182.85

7.1.1 Constant (a2) for insulator catenary

a2 = T / Wi2 = 452 / (75.033 / 1.629) = 9.82

7.1.2 Assumed half inclined length of conductor span (Xass)

Xass = ((Ls /2) - Lstr) x 1.005 = ((52 / 2) - 1.629) x 1.005 = 24.49

7.1.3 Projected length of catenary arc (X1)

X1 = a2 x Xass / a1 = 9.82 x 24.49 / 182.85 = 1.32

7.1.4 Arc from insulator catenary centre to end of string (SP)

SP = a2 x sinh(X1 / a2) = 9.82 x sinh(1.32/9.82) = 1.32

7.1.5 Total arc length (RSP)

RSP = Lstr + SP = 1.629 + 1.32 = 2.949 m

7.1.6 Projected length of total Arc (X2)

X2 = a2 x sinh-1(RSP / a2) = 9.82 x sinh-1 (2.949 / 9.82) = 2.91

7.1.7 Projected length of insulator string (X3)

X3 = X2 - X1 = 2.91 - 1.32 = 1.59

7.1.8 Actual Half inclined length of conductor Span (X)

X = (Ls / 2) - X3 = (52/2) -1.59 = 24.41

7.1.9 Sag at centre of insulator catenary, below end of string (D1)

D1 = a2x(cosh(X1/a2) - 1) = 9.82 x (cosh(1.32/9.82) - 1) = 0.09

7.2.0 Sag at centre of insulator catenary, below support (D2)

D2 = a2x(cosh(X2/a2) - 1) = 9.82 x (cosh(2.91/9.82) - 1) = 0.44

8.00 Conductor Sag below end of insulator string (D3)

LITL-021-ELV-302-R-003 REV - 00 12 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE
D3 = a1x(cosh(X/a1) - 1) = 182.85 x (cosh(24.41/182.85) - 1) = 1.64

8.0.1 Total Sag at temperature = 75 with wind factor = 0

S = D3 + D2 - D1 = 1.64 + 0.44 - 0.09 = 1.99 m

CONCLUSION

SAG TENSION TABLE FOR DIFFERENT TEMPERATURES AND WIND CONDITIONS

Temperature Full wind condition Still wind condition

-10 1396.00 1.69 529.00 1.7

-5 1365.00 1.72 516.00 1.74

0 1335.00 1.76 504.00 1.79

5 1308.00 1.81 492.00 1.82

10 1282.00 1.84 482.00 1.85

15 1257.00 1.88 472.00 1.9

20 1234.00 1.9 462.00 1.94

25 1212.00 1.94 453.00 1.98

30 1191.00 1.97 445.00 2.01

35 1171.00 2.01 437.00 2.04

40 1152.00 2.04 429.00 2.08

45 1134.00 2.07 422.00 2.12

50 1117.00 2.11 415.00 2.16

55 1100.00 2.14 409.00 2.19

60 1084.00 2.17 403.00 2.23

65 1069.00 2.19 397.00 2.25

70 1054.00 2.23 391.00 2.29

75 1040.00 2.27 386.00 2.32

80 1184.00 1.99 375.00 2.39

8.0.2 Maximum Working Tension T = 1100 kg

8.0.3 Maximum sag of Lower most conductor S = 2.32 m

8.0.4 Height of tower H = 15 m

LITL-021-ELV-302-R-003 REV - 00 13 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE
8.0.5 Height of Main Bus h = 8 m

Vertical Clearance between lower most


8.0.6 = 4.61
Conductor and equipment
Minimum clearance between phase to phase for
8.0.7 = 4.2 m
400kV

Since the calculated vertical clearance between Equipment and Lower most conductor is greater than the
minimum clearance between phase to phase, The selected height of tower 15m is adequate.

LITL-021-ELV-302-R-003 REV - 00 14 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE
1.0.0 DESIGN INPUT

1.1.0 SYSTEM PARAMETERS

1.0.1 Shield wire type & strands = EARTH WIRE

1.1.1 Initial Tension (Max.) T1 = 800 kg

1.1.2 Height of tower H1 = 29.5 m

1.1.3 Height of equipment H2 = 22 m

1.1.4 Basic Wind Speed Vb = 40.2 m/s (AS PER TECH. SPEC)

1.1.5 Span L 57 m

1.1.6 Every day Temperature To = 55 °C (AS PER TECH. SPEC)

1.1.7 Minimum Temperature Tmin = -10 °C (AS PER TECH. SPEC)

1.0.8 Shield wire

1.1.8 Shield wire unit wieght m's = 0.583 kg/m

1.0.9 Shield wire Area Ac = 9.47E-01 cm2

1.1.9 Shield wire overall diameter dc = 1.098 cm

1.0.10 Expansion coefficient of Shield wire α = 1.15E-05 /°C

1.1.10 Elasticity modulus E = 1.9E+06 kg/cm2

2.0.0 DESIGN CRITERIA

2.1.0 The design calculation for maximum sag of lower most Shield wire is based on the "Generation, Transmission
and Utilization of Electrical Power" by A. T. Starr

2.2.0 Maximum initial tension is assumed at 55˚ C temperature and Full Wind.

3.0.0 REFERENCES

3.1.0 Standards

IEC 60826

IEC 865-1 (1993)

IEEE 605 (1998)

3.2.0 Books

"Generation, Transmission and Utilization of Electrical Power" by A. T. Starr

3.0.0 DESIGN CALCULTION

3.1.0 Design wind speed (Vd)

LITL-021-ELV-302-R-003 REV - 00 14 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE
Basic wind speed VRB = 40.2 m/s

3.2.0 Unit action of wind speed (q0)

q0 = 1/2xtxm(K RVRB)2 = = 674.749479 N/m2

Where,

air mass per unit volume m = 1.225 kg/m3

air density correction factor t = 0.94351

Terrain roughness co efficient kR = 0.85

3.3.0 Equivalent Self weight of Shield wire (m'sc)

m'sc = 0.583 kg/m

3.3.1 Wind pressure on Shield wire (Ac)

Full wind pressure on conductor,

Ac = q0 x Cxc x Gc x GL x d x L x sin2Ω = 17.050 N

where,

Drag Co efficient for conductor Cxc = 1 (As per IEC 60826, Clause 6.2.6, Pg no:49)

Combined wind factor for conductors Gc = 2.3

span factor GL = 1 (As per IEC 6082, Clause 6.2.6, Pg no:50)

diameter of the conductor d = 0.01098

wind span of the support L = 1

Ω = 90
Ω is the angle between the wind
direction and the conductor

Ac = 1.73802 kg/m

4.00 For initial condition of 100% wind loading at ### 0


C

Temp (in deg C) = 55

Wind Factor = 1

Equivalent Self weight of Shield wire (m'sc) = 0.583 kg/m

Equivalent wind load on Shield wire p(eq) = Ac x 1 = 1.73802 kg/m

LITL-021-ELV-302-R-003 REV - 00 15 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE
Loading factor q1 = 3.14

Temp (in deg C) = 55

Wind Factor = 0.00

Equivalent Self weight of Shield wire (m'sc) = 0.583 kg/m

Equivalent wind load on Shield wire p(eq) = 0.00

Loading factor q2 = 1.00

Stress (f1) at initial temperature( 550 c)

f1 = T1 / Ac = (800 / 0.947) = 8.4477E+02 kg / cm2

Weight per unit area (&) = 0.583/0.947 = 6.1563E-01 kg/m/cm2

Initial Design Wind load Factor = 1.00

Initial loading factor q1 = 3.14

( Loading Factor q = ( p 2 + m'sc 2 ) ^1/2 / m'sc )

4.1.1 Calculating Stress at final stringing condition t2 & loading conditions q2 :

f2 2x ( f2 - ( K1 - e x t x E)) = K2 x q 2 2

K1 = f1 - L 2x & 2x q1 2x E / 24 x( f1 ) 2

= -527.63

K2 = L 2x & 2x E / 24

= 9.93E+07

Sag in shield wire = m'sc x L^2/(8*T1 )

4.1.2 Sag - Tension at Initial conditions.

Temp ( deg C) = 55 Tension = 800 kg

Wind factor = 1 Sag = 0.29596 m

4.1.3 Sag - Tension at specific conditions.

Temp ( deg C) = 50 t = 55-55 = 0 deg C

Wind factor = 0.00

f2 2 x ( f2 - ( K1 - e x t x E)) = K2 x q2 2

f2^2 X (f2-(-527.63 X 0.0000115 X 0 X 1936100)) = 99335253.885 x 1^2

99335253.89 = 99335253.89

f2 = 338.631397040969 kg/cm2

LITL-021-ELV-302-R-003 REV - 00 16 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE
Tension = 321 kg

Sag = 0.738 m

CONCLUSION

SAG TENSION TABLE FOR DIFFERENT TEMPERATURES AND WIND CONDITIONS

Temperature Full wind condition Still wind condition

Tension (kg) Sag (m) Tension (kg) Sag (m)

-10 1337.00 0.177 962.00 0.246

-5 1276.00 0.186 876.00 0.27

0 1219.00 0.194 794.00 0.298

5 1166.00 0.203 718.00 0.33

10 1116.00 0.212 649.00 0.365

15 1070.00 0.221 588.00 0.403

20 1027.00 0.231 534.00 0.443

25 987.00 0.24 488.00 0.485

30 950.00 0.249 448.00 0.529

35 915.00 0.259 414.00 0.572

40 883.00 0.268 385.00 0.615

45 853.00 0.278 360.00 0.658

50 826.00 0.287 339.00 0.698

55 800.00 0.296 321.00 0.738

LITL-021-ELV-302-R-003 REV - 00 17 of 17
SAG TENSION CALCULATION FOR CONDUCTOR AND SHIELD
WIRE

LITL-021-ELV-302-R-003 REV - 00 18 of 17