Data Sheets PDF
Data Sheets PDF
Potential-free contacts
Project number: 191103/8.377 DA433
Offer No.: --377 Printing date: 06.02.2020
No. Designation
Subject to change
Page 1 of 1
Load securing device
Explanation of symbols
Lifting equipment to be fastened here, only centre of gravity Lashing equipment
Dimension(s)
L1 L3 L6 L8 L9 B 1 2) H1 1)
[mm] [mm] [mm] [mm] [mm] [mm] [mm]
6470 3030 735 100 50 2268 2593
Subject to change
Page 1 of 1
Main dimensions
Explanation of symbols
Warning: dangerous electrical Lifting equipment to be fastened Warning: hot surface, e. g. uninsu-
voltage here, only lated fitting
Subject to change
Page 1 of 2
Main dimensions
Base frame
L4 L5 L7 L8 L9 L 10 2) B3 wide flange beam
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [IPB - HEB - DIN1025]
3750 3400 600 425 175 225 1655 180
References and defaults to Requirements for the boiler installation room see technical information TI024.
Dimensions with ± 1 % tolerance; operating / maximum weight indication with ± 2 % tolerance
The scope of delivery is defined in the order confirmation.
The indicated transport weight already includes the surcharges for normal sheet metal thickness tolerances, hence difference
downwards is possible.
Dimensioning insertion opening:
Positioning height: addition of at least 100 mm to dimension H1 resp. dimension H2
(mounted / not mounted fittings)
Positioning width: addition of at least 200 mm to dimension B1 resp. dimension B2
(mounted / not mounted fittings)
1)
Smallest transport dimensions once fittings, burner and terminal box have been removed (without cable ducting; with cable ducting
+ 75 mm on right).
2)
The boiler operating weight must be absorbed by the foundation in the area of the front and rear supports.
3)
Maximum weight incl. 100 % filled with water
4)
Height to top edge Flue gas connection
Subject to change
Page 2 of 2
Individual dimensions
D03.000 Flue gas connection socket D12.503 Connection for drainage flue gas condensate
D05.000 Inspection opening steam-side D14.500 Connection for manostat pipe
D05.001 Inspection opening water side D15.501 Connection for Level indicator 1
D05.002 Inspection opening flue gas side Connection for Level indicator 2
D05.004 cleaning opening flue gas side D16.501 Connection for Desalting shut-off valve
D08.500 Connection for Pressure safeguard valve 1 D19.501 Connection for vent shut-off valve option
D08.600 Connection for Pressure safeguard valve 2 W32.509 Connection for Water inlet flue gas heat exchanger
D09.500 Connection for Steam shut-off valve W32.510 Connection for Water outlet flue gas heat exchanger
D12.500 Connection for drain
Subject to change
Page 1 of 2
Individual dimensions
Nozzle position
L3 L4 L5 L6 L7 L8 L9 L 10 L 12 L13
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
2250 2550 1850 1500 1150 1100 800 420
Nozzle position
L 15 B3 B5 H3 H4 H5 H6 H8
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
18 950 457 2415 1740 1215 1700 340
References and defaults to Requirements for the boiler installation room see technical information TI024.
Missing dimensions are not contained in scope of delivery.
The scope of delivery is defined in the order confirmation.
Dimensions with ± 1 % tolerance
1)
Nominal diameter of pipe connection based on DIN 24154 Part 4
2)
Nominal diameter for flanges in accordance with DIN 2633 / 2634 / 2635 or EN 1092-1/-2 / DN65PN16 with 4 holes
3)
Pipe thread according to DIN 2999 / EN10241
4)
Height to top edge Flue gas connection
Subject to change
Page 2 of 2
Piping diagram
Subject to change
Page 1 of 2
Piping diagram
Subject to change
Page 2 of 2
Piping diagram
Subject to change
Page 1 of 1
Main and individual dimensions
Subject to change
Page 1 of 2
Main and individual dimensions
connection line
Mean working gauge pressure Transportation weight Maximum weight 1)
Type [bar] [kg] [kg]
4000 10 39,7 45
Dimension(s)
L1 L2 L3 L4 L5 L6 B1
[mm] [mm] [mm] [mm] [mm] [mm] [mm]
1154 973 669 378 278 178 457
Dimension(s)
H1 H2 H3 H 4 4) H 5 5) H 6 6) H 7 7)
[mm] [mm] [mm] [mm] [mm] [mm] [mm]
2718 2118 1704 1150 1150 1150 1265
References and defaults to Requirements for the boiler installation room see technical information TI024.
Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 %
tolerance
The scope of delivery is defined in the order confirmation.
1)
Maximum weight incl. 100 % filled with water
2)
Nominal diameter for flanges in accordance with DIN 2633 / 2634 / 2635 or EN 1092-1/-2 / DN65PN16 with 4 holes
3)
The temperature indicator is installed towards the operating side.
4)
Water inlet Eco
5)
Water outlet Eco
6)
Supply boiler
7)
Dimensions between boiler centre and lower edge of base frame (i.e. supporting surface of the boiler)
Subject to change
Page 2 of 2
Main dimensions
Subject to change
Page 1 of 1
Main and individual dimensions
Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 % tolerance
The scope of delivery is defined in the order confirmation.
1)
Space requirement for spring removal GDR
Subject to change
Page 1 of 1
Main and individual dimensions
Pump module PM
Project number: 191103/8.377 DA004
Offer No.: --377 Printing date: 06.02.2020
Pump module discharge Min. required positive suction Transportation Operating Connected load
pressure head weight weight (electrical)
Discharge
flow
[kg/h] [bar] [mm] [kg] [kg] [kW]
4309 12,71 995 90 100 4
Dimension(s)
L1 L2 L3 B1 B3 B4 H1 H2 H3 H4
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
1043 732 662 240 201 191,3 1528 540 235 160
References and defaults to Requirements for the boiler installation room see technical information TI024.
During assembly, please note the specified flow direction
The scope of delivery is defined in the order confirmation.
Install the consoles onto anti-vibration supports
Missing dimensions are not contained in scope of delivery.
Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 %
tolerance
1)
Nominal diameter for flanges in accordance with DIN 2633 / 2634 / 2635 or EN 1092-1/-2 / DN65PN16 with 4 holes
Subject to change
Page 1 of 2
Main and individual dimensions
Pump module PM
Project number: 191103/8.377 DA004
Offer No.: --377 Printing date: 06.02.2020
Subject to change
Page 2 of 2
Piping diagram
Depiction of the feed water supply from the tank to the boiler
Subject to change
Page 1 of 2
Piping diagram
Subject to change
Page 2 of 2
technical specification
Pump curve
Project number: 191103/8.377 DA398
Offer No.: --377 Printing date: 06.02.2020
Subject to change
Page 1 of 2
technical specification
Pump curve
Project number: 191103/8.377 DA398
Offer No.: --377 Printing date: 06.02.2020
Subject to change
Page 2 of 2
Main dimensions
Feed pump
with frequency converter
Project number: 191103/8.377 DA399
Offer No.: --377 Printing date: 06.02.2020
Feed pump Discharge discharge Min. required positive suction Transportation Connected load
flow pressure head weight (electrical)
Type [kg/h] [bar] [mm] [kg] [kW]
CRE 5-29 4309 12,71 995 62 4
X
Subject to change
Page 1 of 1
Individual dimensions
L1
W33.030
0-90° 0-90°
L2
W33.000
W33.030
W33.037
H1
H2
H3
W33.540 W33.541
H5
W33.509 W33.008 W33.008
H4
W33.506 W33.507
200 200
W33.002 B3 L4 80 80 L3
B5
B1
B2
B4
W33.000 flue gas heat exchanger W33.507 Connection for flue gas condensate
W33.002 flue gas control valve W33.509 Connection for Water inlet
W33.008 Inspection opening flue gas side W33.510 Connection for Water outlet
W33.030 Lifting lug W33.540 Connection for flue gas intake
W33.037 Lashing eye W33.541 Connection for flue gas outlet
W33.506 Connection for drainage
Explanation of symbols
Lifting equipment to be fastened here, only
Subject to change
Page 1 of 2
Individual dimensions
Dimension(s)
L1 L2 L3 L4 B1 B2 B3
[mm] [mm] [mm] [mm] [mm] [mm] [mm]
1385 548 341 495 1237 658 600
Dimension(s)
B4 B5 H1 H2 H3 H4 H5
[mm] [mm] [mm] [mm] [mm] [mm] [mm]
800 650 1115 909 427 238 452
References and defaults to Requirements for the boiler installation room see technical information TI024.
Dimensions with ± 1 % tolerance; operating / maximum weight indication with ± 2 % tolerance
The lashing eye must only be used for securing the heat exchanger during transport and not for lifting purposes.
The indicated transport weight already includes the surcharges for normal sheet metal thickness tolerances, hence difference
downwards is possible.
Missing dimensions are not contained in scope of delivery.
The scope of delivery is defined in the order confirmation.
1)
Nominal diameter for flanges in accordance with DIN 2633 / 2634 / 2635 or EN 1092-1/-2 / DN65PN16 with 4 holes
2)
Maximum weight incl. 100 % filled with water
3)
Nominal diameter of pipe connection based on DIN 24154 Part 4
4)
Pipe thread according to DIN 2999 / EN10241
Subject to change
Page 2 of 2
Piping diagram
References and defaults to Requirements for the boiler installation room see technical information TI024.
The scope of delivery is defined in the order confirmation.
Subject to change
Page 1 of 1
System diagram
Configuration of single boiler system with minimum make-up water flow rate control
Subject to change
Page 1 of 2
System diagram
For more information, see the operating instructions and pipework diagrams of the components.
Distribution of flows with several feed water coolers according to the steam capacity of the relevant boiler (throttling via valves
W43.031, W43.131, W43.231 and W43.033). See the operating instructions for the particular component.
Distribution of flows in the case of several flue gas heat exchangers with flue gas condensation (ECO6) based on the steam
output of the particular boiler (throttling by means of valves W33.036, W33.136, W33.236 and W33.037). See the operating
instructions for the particular component.
Only the make-up water side and selected components that are essential for control and distribution of the partial flows are
shown.
The make-up water valves B30.030 and B30.031 can also be implemented twice (connected in parallel) (valves B30.130 and
B30.131)
Either a two-stage (valves B30.030 and B30.072) or a steady (valve B30.057) make-up water control is required.
The scope of delivery is defined in the order confirmation.
Subject to change
Page 2 of 2
Load securing device
Explanation of symbols
Lifting equipment to be fastened here, only centre of gravity Lashing equipment
Dimension(s)
L1 L3 L6 L8 L9 B 1 2) H1 1)
[mm] [mm] [mm] [mm] [mm] [mm] [mm]
6470 3030 735 100 50 2268 2593
Subject to change
Page 1 of 1
Main dimensions
Explanation of symbols
Warning: dangerous electrical Lifting equipment to be fastened Warning: hot surface, e. g. uninsu-
voltage here, only lated fitting
Subject to change
Page 1 of 2
Main dimensions
Base frame
L4 L5 L7 L8 L9 L 10 2) B3 wide flange beam
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [IPB - HEB - DIN1025]
3750 3400 600 425 175 225 1655 180
References and defaults to Requirements for the boiler installation room see technical information TI024.
Dimensions with ± 1 % tolerance; operating / maximum weight indication with ± 2 % tolerance
The scope of delivery is defined in the order confirmation.
The indicated transport weight already includes the surcharges for normal sheet metal thickness tolerances, hence difference
downwards is possible.
Dimensioning insertion opening:
Positioning height: addition of at least 100 mm to dimension H1 resp. dimension H2
(mounted / not mounted fittings)
Positioning width: addition of at least 200 mm to dimension B1 resp. dimension B2
(mounted / not mounted fittings)
1)
Smallest transport dimensions once fittings, burner and terminal box have been removed (without cable ducting; with cable ducting
+ 75 mm on right).
2)
The boiler operating weight must be absorbed by the foundation in the area of the front and rear supports.
3)
Maximum weight incl. 100 % filled with water
4)
Height to top edge Flue gas connection
Subject to change
Page 2 of 2
Individual dimensions
Subject to change
Page 1 of 2
Individual dimensions
Nozzle position
L3 L4 L5 L6 L7 L8 L9 L 10 L 12 L13
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
2250 2550 1850 1500 1150 1400 800 420
Nozzle position
L 15 B3 B5 H3 H4 H5 H6 H8
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
18 950 457 2415 1740 1215 1700 340
References and defaults to Requirements for the boiler installation room see technical information TI024.
Missing dimensions are not contained in scope of delivery.
The scope of delivery is defined in the order confirmation.
Dimensions with ± 1 % tolerance
1)
Nominal diameter of pipe connection based on DIN 24154 Part 4
2)
Nominal diameter for flanges in accordance with DIN 2633 / 2634 / 2635 or EN 1092-1/-2 / DN65PN16 with 4 holes
3)
Pipe thread according to DIN 2999 / EN10241
4)
Height to top edge Flue gas connection
Subject to change
Page 2 of 2
Main and individual dimensions
Subject to change
Page 1 of 2
Main and individual dimensions
connection line
Mean working gauge pressure Transportation weight Maximum weight 1)
Type [bar] [kg] [kg]
4000 10 39,7 45
Dimension(s)
L1 L2 L3 L4 L5 L6 B1
[mm] [mm] [mm] [mm] [mm] [mm] [mm]
1154 973 669 378 278 178 457
Dimension(s)
H1 H2 H3 H 4 4) H 5 5) H 6 6) H 7 7)
[mm] [mm] [mm] [mm] [mm] [mm] [mm]
2718 2118 1704 1150 1150 1150 1265
References and defaults to Requirements for the boiler installation room see technical information TI024.
Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 %
tolerance
The scope of delivery is defined in the order confirmation.
1)
Maximum weight incl. 100 % filled with water
2)
Nominal diameter for flanges in accordance with DIN 2633 / 2634 / 2635 or EN 1092-1/-2 / DN65PN16 with 4 holes
3)
The temperature indicator is installed towards the operating side.
4)
Water inlet Eco
5)
Water outlet Eco
6)
Supply boiler
7)
Dimensions between boiler centre and lower edge of base frame (i.e. supporting surface of the boiler)
Subject to change
Page 2 of 2
technical specification
Pump curve
Project number: 191103/8.377 DA398
Offer No.: --377 Printing date: 06.02.2020
Subject to change
Page 1 of 2
technical specification
Pump curve
Project number: 191103/8.377 DA398
Offer No.: --377 Printing date: 06.02.2020
Subject to change
Page 2 of 2
Individual dimensions
L1
W33.030
L2 0-90° 0-90°
W33.000
W33.030
W33.037
H3
W33.541 W33.540
H5
W33.008 W33.008 W33.509
H4
W33.507 W33.506
200 200
L3 80 80 L4 B3 W33.002
B5
B1
B2
B4
W33.000 flue gas heat exchanger W33.507 Connection for flue gas condensate
W33.002 flue gas control valve W33.509 Connection for Water inlet
W33.008 Inspection opening flue gas side W33.510 Connection for Water outlet
W33.030 Lifting lug W33.540 Connection for flue gas intake
W33.037 Lashing eye W33.541 Connection for flue gas outlet
W33.506 Connection for drainage
Explanation of symbols
Lifting equipment to be fastened here, only
Subject to change
Page 1 of 2
Individual dimensions
Dimension(s)
L1 L2 L3 L4 B1 B2 B3
[mm] [mm] [mm] [mm] [mm] [mm] [mm]
1385 548 341 495 1237 658 600
Dimension(s)
B4 B5 H1 H2 H3 H4 H5
[mm] [mm] [mm] [mm] [mm] [mm] [mm]
800 650 1115 909 427 238 452
References and defaults to Requirements for the boiler installation room see technical information TI024.
Dimensions with ± 1 % tolerance; operating / maximum weight indication with ± 2 % tolerance
The lashing eye must only be used for securing the heat exchanger during transport and not for lifting purposes.
The indicated transport weight already includes the surcharges for normal sheet metal thickness tolerances, hence difference
downwards is possible.
Missing dimensions are not contained in scope of delivery.
The scope of delivery is defined in the order confirmation.
1)
Nominal diameter for flanges in accordance with DIN 2633 / 2634 / 2635 or EN 1092-1/-2 / DN65PN16 with 4 holes
2)
Maximum weight incl. 100 % filled with water
3)
Nominal diameter of pipe connection based on DIN 24154 Part 4
4)
Pipe thread according to DIN 2999 / EN10241
Subject to change
Page 2 of 2
Load securing device
Explanation of symbols
Lifting equipment to be fastened here, only centre of gravity Lashing equipment
Dimension(s)
L1 L3 L6 L8 L9 B 1 2) H1 1)
[mm] [mm] [mm] [mm] [mm] [mm] [mm]
6470 3030 735 100 50 2268 2593
Subject to change
Page 1 of 1
Main dimensions
Explanation of symbols
Warning: dangerous electrical Lifting equipment to be fastened Warning: hot surface, e. g. uninsu-
voltage here, only lated fitting
Subject to change
Page 1 of 2
Main dimensions
Base frame
L4 L5 L7 L8 L9 L 10 2) B3 wide flange beam
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [IPB - HEB - DIN1025]
3750 3400 600 425 175 225 1655 180
References and defaults to Requirements for the boiler installation room see technical information TI024.
Dimensions with ± 1 % tolerance; operating / maximum weight indication with ± 2 % tolerance
The scope of delivery is defined in the order confirmation.
The indicated transport weight already includes the surcharges for normal sheet metal thickness tolerances, hence difference
downwards is possible.
Dimensioning insertion opening:
Positioning height: addition of at least 100 mm to dimension H1 resp. dimension H2
(mounted / not mounted fittings)
Positioning width: addition of at least 200 mm to dimension B1 resp. dimension B2
(mounted / not mounted fittings)
1)
Smallest transport dimensions once fittings, burner and terminal box have been removed (without cable ducting; with cable ducting
+ 75 mm on right).
2)
The boiler operating weight must be absorbed by the foundation in the area of the front and rear supports.
3)
Maximum weight incl. 100 % filled with water
4)
Height to top edge Flue gas connection
Subject to change
Page 2 of 2
Individual dimensions
D03.000 Flue gas connection socket D12.503 Connection for drainage flue gas condensate
D05.000 Inspection opening steam-side D14.500 Connection for manostat pipe
D05.001 Inspection opening water side D15.501 Connection for Level indicator 1
D05.002 Inspection opening flue gas side Connection for Level indicator 2
D05.004 cleaning opening flue gas side D16.501 Connection for Desalting shut-off valve
D08.500 Connection for Pressure safeguard valve 1 D19.501 Connection for vent shut-off valve option
D08.600 Connection for Pressure safeguard valve 2 W32.509 Connection for Water inlet flue gas heat exchanger
D09.500 Connection for Steam shut-off valve W32.510 Connection for Water outlet flue gas heat exchanger
D12.500 Connection for drain
Subject to change
Page 1 of 2
Individual dimensions
Nozzle position
L3 L4 L5 L6 L7 L8 L9 L 10 L 12 L13
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
2250 2550 1850 1500 1150 1100 800 420
Nozzle position
L 15 B3 B5 H3 H4 H5 H6 H8
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
18 950 457 2415 1740 1215 1700 340
References and defaults to Requirements for the boiler installation room see technical information TI024.
Missing dimensions are not contained in scope of delivery.
The scope of delivery is defined in the order confirmation.
Dimensions with ± 1 % tolerance
1)
Nominal diameter of pipe connection based on DIN 24154 Part 4
2)
Nominal diameter for flanges in accordance with DIN 2633 / 2634 / 2635 or EN 1092-1/-2 / DN65PN16 with 4 holes
3)
Pipe thread according to DIN 2999 / EN10241
4)
Height to top edge Flue gas connection
Subject to change
Page 2 of 2
Main and individual dimensions
Subject to change
Page 1 of 2
Main and individual dimensions
connection line
Mean working gauge pressure Transportation weight Maximum weight 1)
Type [bar] [kg] [kg]
4000 10 39,1 44,4
Dimension(s)
L1 L2 L3 L4 L5 L6 B1
[mm] [mm] [mm] [mm] [mm] [mm] [mm]
1154 973 669 378 278 178 457
Dimension(s)
H1 H2 H3 H 4 4) H 5 5) H 6 6) H 7 7)
[mm] [mm] [mm] [mm] [mm] [mm] [mm]
2718 2118 1704 1150 1150 1150 1265
References and defaults to Requirements for the boiler installation room see technical information TI024.
Dimensions with ± 1 % tolerance; transport weight indication with ± 4 % tolerance and operating weight indication with ± 2 %
tolerance
The scope of delivery is defined in the order confirmation.
1)
Maximum weight incl. 100 % filled with water
2)
Nominal diameter for flanges in accordance with DIN 2633 / 2634 / 2635 or EN 1092-1/-2 / DN65PN16 with 4 holes
3)
The temperature indicator is installed towards the operating side.
4)
Water inlet Eco
5)
Water outlet Eco
6)
Supply boiler
7)
Dimensions between boiler centre and lower edge of base frame (i.e. supporting surface of the boiler)
Subject to change
Page 2 of 2
technical specification
Pump curve
Project number: 191103/8.377 DA398
Offer No.: --377 Printing date: 06.02.2020
Subject to change
Page 1 of 2
technical specification
Pump curve
Project number: 191103/8.377 DA398
Offer No.: --377 Printing date: 06.02.2020
Subject to change
Page 2 of 2
Individual dimensions
Explanation of symbols
Lifting equipment to be fastened here, only Warning: hot surface, e. g. uninsulated fitting
Subject to change
Page 1 of 2
Individual dimensions
Dimension(s)
L 1 5) L2 L3 L4 L5 L6 L7 L8 L9
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
3560 1750 1750 2205 2005 1770 1670
Dimension(s)
L 10 L 11 L 12 L 13 L 14 L 15 L 16 L 17 L 18
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
945 980 1045 915 745 830 665
Dimension(s)
L 19 L 20 L 21 B 1 5) B2 B3 B4 B5
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
665 200 1830 1155 800 899 855
Dimension(s)
B6 B7 B8 H 1 5) H2 H3 H4 D
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
840 630 1810 1200 225 50 1700
Connection for B30.501 2) B30.504 2) B30.506 2) B30.507 2) B30.508 3) B30.509 3) B30.510 2) B30.512 2) B30.519 3)
DN [mm] 65 40 1/2“ 1/2“ 550 3/8“
PN [bar/120°C] 16 16 16 16 16 16
3) 3) 2) 2)7) 2) 2) 3) 3)
Connection for B30.520 B30.521 B30.522 B30.523 B30.525 B30.527 B30.528 B30.529 B30.531 2)
DN [mm] 1/2“ 1 1/2“ 25 50 100 1/2“ 1/2“ 80
PN [bar/120°C] 16 16 40 40 16 16 16 16
Subject to change
Page 2 of 2
Individual dimensions
Explanation of symbols
Lifting equipment to be fastened here, only Warning: hot surface, e. g. uninsulated fitting
Subject to change
Page 1 of 1
Piping diagram
Subject to change
Page 1 of 2
Piping diagram
References and defaults to Requirements for the boiler installation room see technical information TI024.
The scope of delivery is defined in the order confirmation.
Two-stage level regulator is also possible.
Subject to change
Page 2 of 2
Main dimensions
Explanation of symbols
Warning: dangerous electrical Lifting equipment to be fastened Warning: hot surface, e. g.
voltage here, only uninsulated fitting
08.001 Pressure safeguard blowoff line B30.510 Connection for Pump idling option
08.002 Pressure safeguard drainage line B30.527 Connection for Pressure safeguard blowoff line
51.000 Control panel B30.528 Connection for Overflow valve option
A49.000 Chemicals dosing plant B30.562 Connection for oxygenic, unpressurized condensate
B30.000 Feed water tank B30.563 Connection for make-up water
B30.013 support structure B34.000 Blow-down, expansion and cooling tank
B30.020 Level controller B34.006 Shut-off valve for Cooling water (throttle cone)
B30.023 Negative pressure safeguard valve B34.007 Control valve for Cooling water (magnetic)
B30.025 Pressure safeguard valve B34.012 Inspection opening water side
B30.026 Heating-up adjustment valve (motorized) B34.100 Connection for venting
B30.030 Control valve for make-up water (magnetic) B34.101 Connection for Blow-down water over ambient
pressure at saturation temperature
B30.031 Shut-off valve for make-up water (throttle cone) B34.102 Connection for Drain to canal
B30.060 trickle deaeration device B34.103 Connection for Blow-down water below ambient
pressure at saturation temperature
B30.501 Connection for extraction B34.104 Connection for Draining
B30.503 Connection for vapours B34.105 Connection for Cooling water
B30.504 Connection for Heating-up steam D05.001 Inspection openings steam and water side
B30.506 Connection for oxygen-free, directly returning D06.002 Lifting lug
condensate option
B30.507 Connection for oxygen-free, directly returning W69.000 Water sample cooling device
condensate option
B30.508 Connection for Chemical dosing W69.501 Connection for Boiler water sample
Subject to change
Page 1 of 2
Main dimensions
Water service module Transportation weight Operating weight Maximum weight 1) Connected load (electrical) Dimension(s)
L1 B1 H1
Type [kg] [kg] [kg] [kW] [mm] [mm] [mm]
WSM-V 8.0 1978 5914 8042 0,8 4543 2028 3933
Dimension(s)
L4 B8 B9 H2 H3
[mm] [mm] [mm] [mm] [mm]
765 238 238 3420 2510
Bearing area
L2 L3 B2 B3 B4 B5 Surface area
[mm] [mm] [mm] [mm] [mm] [mm] [cm²]
3633 2995 1225 900 60 60 4360
Subject to change
Page 2 of 2
Individual dimensions
Explanation of symbols
Warning: dangerous electrical Lifting equipment to be fastened Warning: hot surface, e. g.
voltage here, only uninsulated fitting
B34.005 temperature switch option B34.101 Connection for Blow-down water over ambient pressure at
B34.006 Shut-off valve (throttle cone) saturation temperature
B34.007 Control valve (magnetic) B34.102 Connection for Drain to canal
B34.008 Shut-off valve B34.103 Connection for Blow-down water below ambient pressure
B34.009 temperature sensor at saturation temperature
B34.010 temperature indicator option B34.104 Connection for Draining
B34.012 Inspection opening (water side) B34.105 Connection for Cooling water
B34.021 Pressure indicator B34.106 Connection for Draining feed water
B34.100 Connection for venting
Subject to change
Page 1 of 2
Individual dimensions
Dimension(s)
L1 L3 L4 L5 B1 B3 H1 H2 H3
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
831 425 225 406 921 840 1541 953 703
Subject to change
Page 2 of 2
Piping diagram
Subject to change
Page 1 of 1
Main and individual dimensions
Dimension(s) Connection
L1 B1 B2 H1 H2 H3 H4 A41.002 2) A41.003 A41.010
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [DN] [DN] [DN]
3030 1200 330 2486 1200 1800 280 2“ 65 100
Subject to change
Page 1 of 1
Individual dimensions
steam distributor
Project number: 191103/8.377 DA076
Offer No.: --377 Printing date: 06.02.2020
Subject to change
Page 1 of 2
Individual dimensions
steam distributor
Project number: 191103/8.377 DA076
Offer No.: --377 Printing date: 06.02.2020
steam distributor
Nominal output Mean working gauge pressure Transportation weight Operating weight Maximum weight 2)
[kg/h] [bar] [kg] [kg] [kg]
8000 10 398 793 1156
Dimension(s)
L1 L2 L3 L4 L5 L6 L7 L8 L9 L 10
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
4738 205 370 500,0 500,0 440,0 390,0 390,0 370,0
Dimension(s)
L 11 L 12 L 13 L 14 L 15 L 16 L 17 H1 H2 D
[mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm]
370,0 340,0 300,0 340,0 999 662 323,9
Connection for A63.501 A63.502 A63.503 A63.504 A63.505 A63.506 A63.510 A63.511 A63.512
DN 1) [mm] 20 20 20 125 125 125 65 100
PN [bar/120°C] 40 40 40 16 16 16 16 16
Connection for A63.513 A63.514 A63.515 A63.520 A63.521 A63.522 A63.523 A63.524 A63.525
DN 1) [mm] 80 80 80 50 50 65
PN [bar/120°C] 16 16 16 40 40 16
Subject to change
Page 2 of 2