Operating Instructions en RDG100


RDG110
RDG110U

RDG – the electronic room thermostat that allows you to set the ideal room temperature you want. The
thermostat satisfies your individual needs in all operating modes: Comfort, Economy and Protection. The
fan operates either in Automatic mode or at the selected speed when using Manual mode. You can
either rely on the factory settings or make adjustments that suit your individual needs.

Main display Operating mode


Room
Heating mode
temperature
Room temperature in
Electric heater on
degrees Celsius
Room temperature in
Cooling mode
degrees Fahrenheit
Button lock active Comfort

Alert indicator Economy


Condensation in the Protection mode:
room Protection against frost
Temporary timer function Indicator for selecting
active mode
Additional user
information

Operating mode button Fan mode


Fan mode button Automatic
Rotary knob Manual:

Low / medium / high

Changing the room temperature


• The room temperature setpoint can be adjusted with the rotary knob when
Comfort mode is active
• Turn the rotary knob clockwise (+) to increase, or counterclockwise (-) to
decrease the current room temperature setpoint for Comfort mode
The setting range is from 5...40 °C (41 … 104 °F), unless limited by parameters P09 and P10
(for parameter settings, see reverse side).

Adjusting the fan speed


• Press the fan mode button until the desired fan mode is reached
• In Automatic mode , the fan speed is automatically selected by the
thermostat depending on the setpoint and the actual room temperature.
When the room temperature reaches the setpoint, the fan stops (factory
setting) or runs at low speed (P15).
• In Manual mode, the fan operates independently and always runs at the
same speed: Low / medium / high

Note:
If desired, you can change the fan mode selector option via P03: Manually only, or manually including
Protection mode. Use P15 to set the fan speed in dead zone.

Selecting Comfort mode

• Press the operating mode button until symbol appears, indicating


that Comfort mode is selected

• In Comfort mode, the thermostat maintains the setpoint which can be


readjusted with the rotary knob

Selecting Protection mode

• Press the operating mode button until symbol appears, indicating


that Protection mode is selected
• In Protection mode, the plant stops operating. If the room temperature
falls
below 8 °C, heating is switched on however to protect the room against
frost

The setpoints for Protection mode can be changed by your HVAC installer if desired:
Changes made by installer: Frost protection: ____________ °C / °F Heat protection: ______________°C / °F

Selecting Economy mode


In Economy mode, the room temperature is maintained at a lower or higher setpoint, thus saving energy
and money.

• When selecting Economy, make sure that parameter P02 is set to 2


• Press the operating mode button until symbol appears
• You can change the preselected setpoint by adjusting parameters P11 and
P12 (for parameter settings, see reverse side)

Important: The setpoint for Economy can be set to OFF. This means that the thermostat is deactivated!
Risk of frost, i.e. no protective heating or cooling function is provided!

Energy saving tips without sacrificing comfort:


• Air out rooms for short periods of time only, but properly, with the windows wide open
• Never allow the room temperature to exceed 21 °C (70 °F) through heating, and to fall below 25.5 °C (78 °F) through
cooling

Button lock
• To lock or unlock the buttons manually, press and hold the fan mode
button for
3 seconds. The buttons are locked or unlocked in this manner if P14 is set
to 2
• If P14 is set to 1, the thermostat automatically locks the buttons 10
seconds after the last adjustment
Temporary timer for extended presence or absence
The Comfort and Economy modes can be temporarily extended by 0.5 to 9.5 hours using the temporary
timer.

1. To set the temporary timer, press and hold the operating mode button for maximum 3 seconds. While
holding the button, turn the rotary knob clockwise or counterclockwise as required.
a) Turn the rotary knob clockwise to extend Comfort mode.
Display: 0....+9:30
b) Turn the rotary knob counterclockwise to extend Economy mode.
Display: 0....-9:30
2. Release the operating mode button and the mode is temporarily changed, indicated by .
After the temporary timer has elapsed, the thermostat will resume operation in the operating mode that
was active before:
Extended Comfort mode New operating mode = Economy
Extended Economy mode New operating mode = Comfort
• If Economy cannot be selected via the operating mode button (P02≠2), Protection mode will be used
for extended absence instead!
• The temporary timer function is aborted whenever a new setting is made.

Note:
Extended Comfort mode is also possible when an external contact such as a keycard switch or central time clock is active
To enable this function, the time for the extended period must be set via parameter P68.

Changing from heating to cooling mode


• Depending on the type of plant, the changeover from heating to cooling
(or vice versa) is made either automatically by a changeover sensor or a
remote changeover switch, or manually by pressing the operating mode
button (see parameter P01)
• To select cooling or heating manually (P01=2), press the operating mode
button until the desired mode appears
• With automatic changeover or continuous heating / cooling, symbols /
indicate that the system currently operates in heating or cooling mode
• With manual changeover, symbol appears, indicating that the system
currently
operates in heating or cooling mode

Control parameters

If you want to change control parameters, proceed as follows:


1. Press both buttons simultaneously for at least 3 seconds.
2. Release them and, within 2 seconds, press the right button again for 3 seconds.
The display shows P01.
3. Select the required parameter by turning the rotary knob.
4. Press button (OK). The current value of the selected parameter starts blinking and can be changed
by turning the rotary knob.
5. Press button (OK) to confirm the adjusted value, or (Esc) to cancel the change.

If you wish to adjust additional parameters, repeat steps 3 through 5, or press (Esc) to leave the
parameter setting mode.

Parameter list
No. Parameter name Default value* Setting range* Adj.
P01 Control sequence 2-pipe / 2-stage: 1 0 = heating only
4-pipe: 4 1 = cooling only
2 = H/C changeover, manually
3 = H/C changeover, auto
4 = heating and cooling
P02 Mode selection via 1 1 = Comfort / Protection mode
operating mode button 2 = Comfort / Economy /
Protection mode
P03 Mode selection via fan 0 0 = Auto / Manual
mode button 1 = Manual
2 = Auto / Manual /
Protection mode
P04 Selection of °C or °F RDG100/110: 0 0 = °C
RDG110U: depends on 1 = °F
wizard setting
P05 Sensor calibration 0.0 K –3…3 K
(0.0 °F) (–6...6 °F)
P06 Standard temperature 0 0 = Room temperature
display 1 = Setpoint
P07 Additional display 0 0 = --- (no display)
information 1 = ˚C and ˚F
P08 Comfort basic setpoint 21 °C 5…40 °C
(70 °F) (41 °F …104 °F)
P09 Minimum setpoint 5 °C 5…40 °C
limitation in Comfort (41 °F) (41 °F…104 °F)
mode
P10 Maximum setpoint 35 °C 5…40 °C
limitation in Comfort (95 °F) (41 °F…104 °F)
mode
P11 Setpoint for heating in 15 °C OFF, 5 °C…WcoolEco
Economy mode (59 °F) (OFF, 41 °F…WcoolEconomy)
(WheatEco)
P12 Setpoint for cooling in 30 °C OFF, WheatEco…40 °C
Economy mode (86 °F) (OFF, WheatEconomy…104 °F)
(WcoolEco)
P13 Electric heater in ON OFF = Disabled
cooling mode ON = Enabled
P14 Button lock 0 0 = Disabled
1 = Automatic
2 = Manual
P15 Fan speed in dead zone 0 0 = Disabled
(Comfort mode) 1 = Stage 1 (H or C)
2 = Stage 1 (Cooling only)
* Degree Fahrenheit parameter selections are only applicable to RDG110U version
The control parameters displayed depend on the DIP switch settings made
Siemens Switzerland Ltd
Subject to change
B3181.1en
2014-10-20