RDG – the electronic room thermostat that allows you to set the ideal room temperature you want. The
thermostat satisfies your individual needs in all operating modes: Comfort, Economy and Protection. The
fan operates either in Automatic mode or at the selected speed when using Manual mode. You can
either rely on the factory settings or make adjustments that suit your individual needs.
Note:
If desired, you can change the fan mode selector option via P03: Manually only, or manually including
Protection mode. Use P15 to set the fan speed in dead zone.
The setpoints for Protection mode can be changed by your HVAC installer if desired:
Changes made by installer: Frost protection: ____________ °C / °F Heat protection: ______________°C / °F
Important: The setpoint for Economy can be set to OFF. This means that the thermostat is deactivated!
Risk of frost, i.e. no protective heating or cooling function is provided!
Button lock
• To lock or unlock the buttons manually, press and hold the fan mode
button for
3 seconds. The buttons are locked or unlocked in this manner if P14 is set
to 2
• If P14 is set to 1, the thermostat automatically locks the buttons 10
seconds after the last adjustment
Temporary timer for extended presence or absence
The Comfort and Economy modes can be temporarily extended by 0.5 to 9.5 hours using the temporary
timer.
1. To set the temporary timer, press and hold the operating mode button for maximum 3 seconds. While
holding the button, turn the rotary knob clockwise or counterclockwise as required.
a) Turn the rotary knob clockwise to extend Comfort mode.
Display: 0....+9:30
b) Turn the rotary knob counterclockwise to extend Economy mode.
Display: 0....-9:30
2. Release the operating mode button and the mode is temporarily changed, indicated by .
After the temporary timer has elapsed, the thermostat will resume operation in the operating mode that
was active before:
Extended Comfort mode New operating mode = Economy
Extended Economy mode New operating mode = Comfort
• If Economy cannot be selected via the operating mode button (P02≠2), Protection mode will be used
for extended absence instead!
• The temporary timer function is aborted whenever a new setting is made.
Note:
Extended Comfort mode is also possible when an external contact such as a keycard switch or central time clock is active
To enable this function, the time for the extended period must be set via parameter P68.
Control parameters
If you wish to adjust additional parameters, repeat steps 3 through 5, or press (Esc) to leave the
parameter setting mode.
Parameter list
No. Parameter name Default value* Setting range* Adj.
P01 Control sequence 2-pipe / 2-stage: 1 0 = heating only
4-pipe: 4 1 = cooling only
2 = H/C changeover, manually
3 = H/C changeover, auto
4 = heating and cooling
P02 Mode selection via 1 1 = Comfort / Protection mode
operating mode button 2 = Comfort / Economy /
Protection mode
P03 Mode selection via fan 0 0 = Auto / Manual
mode button 1 = Manual
2 = Auto / Manual /
Protection mode
P04 Selection of °C or °F RDG100/110: 0 0 = °C
RDG110U: depends on 1 = °F
wizard setting
P05 Sensor calibration 0.0 K –3…3 K
(0.0 °F) (–6...6 °F)
P06 Standard temperature 0 0 = Room temperature
display 1 = Setpoint
P07 Additional display 0 0 = --- (no display)
information 1 = ˚C and ˚F
P08 Comfort basic setpoint 21 °C 5…40 °C
(70 °F) (41 °F …104 °F)
P09 Minimum setpoint 5 °C 5…40 °C
limitation in Comfort (41 °F) (41 °F…104 °F)
mode
P10 Maximum setpoint 35 °C 5…40 °C
limitation in Comfort (95 °F) (41 °F…104 °F)
mode
P11 Setpoint for heating in 15 °C OFF, 5 °C…WcoolEco
Economy mode (59 °F) (OFF, 41 °F…WcoolEconomy)
(WheatEco)
P12 Setpoint for cooling in 30 °C OFF, WheatEco…40 °C
Economy mode (86 °F) (OFF, WheatEconomy…104 °F)
(WcoolEco)
P13 Electric heater in ON OFF = Disabled
cooling mode ON = Enabled
P14 Button lock 0 0 = Disabled
1 = Automatic
2 = Manual
P15 Fan speed in dead zone 0 0 = Disabled
(Comfort mode) 1 = Stage 1 (H or C)
2 = Stage 1 (Cooling only)
* Degree Fahrenheit parameter selections are only applicable to RDG110U version
The control parameters displayed depend on the DIP switch settings made