Generator Earthing and Stator Earth Fault Protection
Generator Earthing and Stator Earth Fault Protection
Generating unit is a pretty complex system made up of the generator stator winding, its
transformer and unit transformer (if present), the rotor with its field winding and excitation
system, and the prime mover with its associated auxiliaries.
Generator earthing and stator earth fault protection (photo credit: Greg Moss)
Many different faults can occur within this generating unit system for which wide range of of
electrical and mechanical protection are required.
As (almost) always, the financial considerations decide the amount of protection that will
be applied, taking into account the value of the machine, and the value of its output to the
plant owner.
This technical article deals with generator earthing methods and only the stator earth fault
protection.
1. Generator earthing
2. Earth fault protection
1.
1. Direct-Connected Generators
1. Neutral Overcurrent Protection
2. Sensitive Earth Fault Protection
3. Neutral Voltage Displacement Protection
2. Indirectly-Connected Generators
1. High Resistance Earthing – Neutral Overcurrent Protection
2. Distribution Transformer Earthing Using a Current Element
3. Distribution Transformer Earthing Using a Voltage Element
4. Neutral Voltage Displacement Protection
3. Restricted Earth Fault Protection
1. Low-Impedance Biased REF Protection
2. High Impedance REF Protection
4. Earth Fault Protection for the Entire Stator Winding
1. Measurement of Third Harmonic Voltage
2. Use of Low-Frequency Voltage Injection
<="" ins="" data-adsbygoogle-status="done" style="box-sizing: border-box; height: 250px;
width: 300px; display: block;">
1. Generator earthing
The neutral point of a generator is usually earthed to facilitate protection of the stator
winding and associated system. Earthing also prevents damaging transient overvoltages
in the event of an arcing earth fault or ferroresonance.
For HV generators, impedance is usually inserted in the stator earthing connection to limit
the magnitude of earth fault current.
There is a wide variation in the earth fault current chosen, common values being:
rated current
200A-400A (low impedance earthing)
10A-20A (high impedance earthing)
The main methods of impedance-earthing a generator are shown in Figure 1. Low values of
earth fault current may limit the damage caused from a fault, but they simultaneously make
detection of a fault towards the stator winding star point more difficult.
Except for special applications, such as marine, LV generators are normally solidly
earthed to comply with safety requirements.
Where a step-up transformer is applied, the generator and the lower voltage winding of the
transformer can be treated as an isolated system that is not influenced by the earthing
requirements of the power system.
Figure 1 – Methods of generator earthing
An earthing transformer or a series impedance can be used as the impedance. If an
earthing transformer is used, the continuous rating is usually in the range 5-250kVA. The
secondary winding is loaded with a resistor of a value which, when referred through the
transformer ratio, will pass the chosen short-time earth-fault current.
The resistor prevents the production of high transient overvoltages in the event of an arcing
earth fault, which it does by discharging the bound charge in the circuit capacitance. For this
reason, the resistive component of fault current should not be less than the residual
capacitance current.
This is the basis of the design, and in practice values of between 3-5 Ico are used.
It is important that the earthing transformer never becomes saturated. Otherwise a very undesirable
The normal rise of the generated voltage above the rated value caused by a sudden loss of
load or by field forcing must be considered, as well as flux doubling in the transformer due to
the point-on-wave of voltage application.
It is sufficient that the transformer be designed to have a primary winding knee-point e.m.f. equal to 1.3
Go back to contents ↑
The type of protection required will depend on the method of earthing and connection of the
generator to the power system.
Go back to contents ↑
For the unearthed generators, a simple measurement of the neutral current is not possible,
and other methods of protection must be used.
The following paragraphs describe the methods available:
Manufacturers normally provide the fault interrupting time at rated interrupting capacity
and this value is invariably used in the calculation of grading margin.
The timing error must be taken into account when determining the grading margin.
3. Overshoot
When the relay is de-energized, operation may continue for a little longer until any stored
energy has been dissipated.
For example, an induction disc relay will have stored kinetic energy in the motion of the disc;
static relay circuits may have energy stored in capacitors. Relay design is directed to
minimizing and absorbing these energies, but some allowance is usually necessary.
The overshoot time is defined as the difference between the operating time of a relay at a specified value of
input current and the maximum duration of input current, which when suddenly reduced below the relay
4. CT Errors
Current transformers have phase and ratio errors due to the exciting current required to
magnetize their cores. The result is that the CT secondary current is not an identical scaled
replica of the primary current.
This leads to errors in the operation of relays, especially in the operation time. CT errors
are not relevant for independent definite-time delay overcurrent relays.
5. Final Margin
After allowances have been made for circuit breaker interrupting time, relay timing error,
overshoot and CT errors, the discriminating relay must just fail to complete its operation.
Some extra safety margin is required to ensure that relay operation does not occur.
The setting should not be more than 33% of the maximum earth fault current of the generator, and a lower
Go back to contents ↑
The earth fault (residual) current can be obtained from residual connection of line CTs,
a line-connected CBCT, or a CT in the generator neutral. The latter is not possible if
directional protection is used. The polarising voltage is usually the neutral voltage
displacement input to the relay, or the residual of the three phase voltages, so a suitable VT
must be used.
For direct connected generators operating in parallel, directional sensitive earth fault
protection may be necessary. This is to ensure that a faulted generator will be tripped
before there is any possibility of the neutral overcurrent protection tripping a parallel healthy
generator.
When being driven by residually-connected phase CTs, the protection must be stabilised
against incorrect tripping with transient spill current in the event of asymmetric CT
saturation when phase fault or magnetising inrush current is being passed.
Stabilizing techniques include the addition of relay circuit impedance and/or the application
of a time delay. Where the required setting of the protection is very low in comparison to the
rated current of the phase CTs, it would be necessary to employ a single CBCT for the earth
fault protection to ensure transient stability.
Since any generator in the paralleled group may be earthed, all generators will require to be fitted with both
The setting of the sensitive directional earth fault protection is chosen to co-ordinate with
generator differential protection and/or neutral voltage displacement protection to ensure
that 95% of the stator winding is protected.
Figure 2 illustrates the complete scheme, including optional blocking signals where
difficulties in co-ordinating the generator and downstream feeder earth-fault protection
occur.
Figure 2 –
Comprehensive earth-fault protection scheme for direct-connected generators operating in parallel
For cases (b) and (c) above, it is not necessary to use a directional facility. Care must be
taken to use the correct Relay Characteristic Angle (RCA) setting – for instance if the
earthing impedance is mainly resistive, this should be 0°.
On insulated or very high impedance earthed systems, an RCA of –90° would be used, as
the earth fault current is predominately capacitive.
Directional sensitive earth-fault protection can also be used for detecting winding earth
faults. In this case, the relay element is applied to the terminals of the generator and is set
to respond to faults only within the machine windings.
Hence earth faults on the external system do not result in relay operation. However, current
flowing from the system into a winding earth-fault causes relay operation. It will not
operate on the earthed machine, so that other types of earth-fault protection must also be
applied.
All generators must be so fitted, since any can be operated as the earthed machine.
Go back to contents ↑
Any earth fault will set up a zero sequence system voltage, which will give rise to a non-zero
residual voltage.
This can be measured by a suitable relay element. The voltage signal must be
derived from a VT that is suitable – i.e. it must be capable of transforming zero-sequence
voltage, so 3-limb types and those without a primary earth connection are not
suitable.
The relay element must be insensitive to third harmonic voltages that may be present in the
system voltage waveforms, as these will sum residually.
As the protection is still unrestricted, the voltage setting of the relay must be greater than
the effective setting of any downstream earth fault protection. It must also be time-delayed
to co-ordinate with such protection.
Sometimes, a second high-set element with short time delay is used to provide fast-acting
protection against major winding earth faults.
Go back to contents ↑
The following paragraphs detail the protection methods for the various forms
of impedance earthing of generators:
Go back to contents ↑
This is to ensure that the protection will not maloperate with zero sequence
current during operation of a primary fuse for a VT earth fault or with any transient surge
currents that could flow through the interwinding capacitance of the step-up transformer for
an HV system earth fault.
A time-delayed relay is more secure in this respect, and it may have a setting to cover
95% of the stator winding.
The portion of the winding left unprotected for an earth fault is at the neutral end. Since the
voltage to earth at this end of the winding is low, the probability of an earth fault occurring is
also low.
Go back to contents ↑
An overcurrent relay element energized from a current transformer connected in the resistor
circuit is used to measure secondary earth fault current. The relay should have an effective
setting equivalent to 5% of the maximum earth fault current at rated generator voltage,
in order to protect 95% of the stator winding.
The relay element response to third harmonic current should be limited to prevent incorrect
operation when a sensitive setting is applied.
It also must grade with generator VT primary protection (for a VT primary earth fault). An
operation time in the range 0.5s-3s is usual.
Less sensitive instantaneous protection can also be applied to provide fast tripping for a heavier earth fault
condition.
Go back to contents ↑
2.2.3 Distribution Transformer Earthing Using a Voltage Element
Earth fault protection can also be provided using a voltage-measuring element in the
secondary circuit instead. The setting considerations would be similar to those for the
current operated protection, but transposed to voltage.
However, neither scheme will operate in the event of a flashover on the primary
terminals of the transformer or of the neutral cable between the generator and the
transformer during an earth fault.
A CT could be added in the neutral connection close to the generator, to energize a high-set
overcurrent element to detect such a fault, but the fault current would probably be high
enough to operate the phase differential protection.
Go back to contents ↑
Go back to contents ↑
It is cheaper than full differential protection, but only provides protection against earth faults.
The principle is that used for transformer REF protection.
However, in contrast to transformer REF protection, both biased low-impedance and high-
impedance techniques can be used.
Go back to contents ↑
Relay bias is required, but the formula for calculating the bias is slightly different and also
shown in Figure 7.
Figure 7 – Low
impedance biased REF protection of a generator
The initial bias slope is commonly set to 0% to provide maximum sensitivity, and applied up
to the rated current of the generator. It may be increased to counter the effects of
CT mismatch. The bias slope above generator rated current is typically set to 150% of rated
value.
The initial current setting is typically 5% of the minimum earth fault current for a fault at the
machine terminals.
Go back to contents ↑
Go back to contents ↑
However, a fault can occur anywhere along the stator windings in the event of insulation
failure due to localized heating from a core fault.
In cases where protection for the entire winding is required, perhaps for alarm only, there are various
methods available:
Go back to contents ↑
When a fault occurs in the part of the stator winding nearest the neutral end, the
third harmonic voltage drops to near zero, and hence a relay element that responds to
third harmonic voltage can be used to detect the condition. As the fault location moves
progressively away from the neutral end, the drop in third harmonic voltage from healthy
conditions becomes less, so that at around 20-30% of the winding distance, it no
longer becomes possible to discriminate between a healthy and a faulty winding.
Hence, a conventional earth-fault scheme should be used in conjunction with a third
harmonic scheme, to provide overlapping cover of the entire stator winding.
The measurement of third harmonic voltage can be taken either from a star-point VT or the
generator line VT. In the latter case, the VT must be capable of carrying residual flux, and
this prevents the use of 3-limb types.
If the third harmonic voltage is measured at the generator star point, an undervoltage
characteristic is used.
An overvoltage characteristic is used if the measurement is taken from the generator line
VT. For effective application of this form of protection, there should be at least 1% third
harmonic voltage across the generator neutral earthing impedance under all operating
conditions.
A problem encountered is that the level of third harmonic voltage generated is related to the
output of the generator. The voltage is low when generator output is low.
In order to avoid maloperation when operating at low power output, the relay element can
be inhibited using an overcurrent or power elements (kW, kVAr or kVA) and internal
programmable logic.
Go back to contents ↑
An earth fault at any winding location will result in the flow of a measurable injection
current to cause protection operation. This form of protection can provide earth fault
protection when the generator is at standstill, prior to run-up.
It is also an appropriate method to apply to variable speed synchronous machines. Such
machines may be employed for variable speed motoring in pumped-storage generation
schemes or for starting a large gas turbine prime mover.
Go back to contents ↑