ASHRAE Standard 22-2007 - Methods of Testing For Rating Water-Cooled Refrigerant Condensers
ASHRAE Standard 22-2007 - Methods of Testing For Rating Water-Cooled Refrigerant Condensers
ASHRAE Standard 22-2007 - Methods of Testing For Rating Water-Cooled Refrigerant Condensers
ASHRAE STANDARD
Methods of Testing for
Rating Water-Cooled
Refrigerant
Condensers
Approved by the ASHRAE Standards Committee on June 23, 2007; by the ASHRAE Board of Directors on June 27,
2007; and by the American National Standards Institute on June 28, 2007.
ASHRAE Standards are scheduled to be updated on a five-year cycle; the date following the standard number is
the year of ASHRAE Board of Directors approval. The latest copies may be purchased from ASHRAE Customer
Service, 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. E-mail: [email protected]. Fax: 404-321-5478. Tele-
phone: 404-636-8400 (worldwide) or toll free 1-800-527-4723 (for orders in US and Canada).
www.ansi.org
*Denotes members of voting status when the document was previously approved for publication
Claire B. Ramspeck, Assistant Director of Technology for Standards and Special Projects
SPECIAL NOTE
qÜáë=^ãÉêáÅ~å=k~íáçå~ä=pí~åÇ~êÇ=E^kpF=áë=~=å~íáçå~ä=îçäìåí~êó=ÅçåëÉåëìë=ëí~åÇ~êÇ=ÇÉîÉäçéÉÇ=ìåÇÉê=íÜÉ=~ìëéáÅÉë=çÑ=íÜÉ=^ãÉêáÅ~å
pçÅáÉíó=çÑ=eÉ~íáåÖI=oÉÑêáÖÉê~íáåÖ=~åÇ=^áêJ`çåÇáíáçåáåÖ=båÖáåÉÉêë=E^peo^bFK= Consensus=áë=ÇÉÑáåÉÇ=Äó=íÜÉ=^ãÉêáÅ~å=k~íáçå~ä=pí~åÇ~êÇë
fåëíáíìíÉ=E^kpfFI=çÑ=ïÜáÅÜ=^peo^b=áë=~=ãÉãÄÉê=~åÇ=ïÜáÅÜ=Ü~ë=~ééêçîÉÇ=íÜáë=ëí~åÇ~êÇ=~ë=~å=^kpI=~ë=ëìÄëí~åíá~ä=~ÖêÉÉãÉåí=êÉ~ÅÜÉÇ=Äó
ÇáêÉÅíäó=~åÇ=ã~íÉêá~ääó=~ÑÑÉÅíÉÇ=áåíÉêÉëí=Å~íÉÖçêáÉëK=qÜáë=ëáÖåáÑáÉë=íÜÉ=ÅçåÅìêêÉåÅÉ=çÑ=ãçêÉ=íÜ~å=~=ëáãéäÉ=ã~àçêáíóI=Äìí=åçí=åÉÅÉëë~êáäó=ìå~åáãáíóK
`çåëÉåëìë=êÉèìáêÉë=íÜ~í=~ää=îáÉïë=~åÇ=çÄàÉÅíáçåë=ÄÉ=ÅçåëáÇÉêÉÇI=~åÇ=íÜ~í=~å=ÉÑÑçêí=ÄÉ=ã~ÇÉ=íçï~êÇ=íÜÉáê=êÉëçäìíáçåKÒ=`çãéäá~åÅÉ=ïáíÜ=íÜáë
ëí~åÇ~êÇ=áë=îçäìåí~êó=ìåíáä=~åÇ=ìåäÉëë=~=äÉÖ~ä=àìêáëÇáÅíáçå=ã~âÉë=Åçãéäá~åÅÉ=ã~åÇ~íçêó=íÜêçìÖÜ=äÉÖáëä~íáçåK
^peo^b=çÄí~áåë=ÅçåëÉåëìë=íÜêçìÖÜ=é~êíáÅáé~íáçå=çÑ=áíë=å~íáçå~ä=~åÇ=áåíÉêå~íáçå~ä=ãÉãÄÉêëI=~ëëçÅá~íÉÇ=ëçÅáÉíáÉëI=~åÇ=éìÄäáÅ=êÉîáÉïK
^peo^b=pí~åÇ~êÇë=~êÉ=éêÉé~êÉÇ=Äó=~=mêçàÉÅí=`çããáííÉÉ=~ééçáåíÉÇ=ëéÉÅáÑáÅ~ääó=Ñçê=íÜÉ=éìêéçëÉ=çÑ=ïêáíáåÖ=íÜÉ=pí~åÇ~êÇK=qÜÉ=mêçàÉÅí
`çããáííÉÉ=`Ü~áê=~åÇ=sáÅÉJ`Ü~áê=ãìëí=ÄÉ=ãÉãÄÉêë=çÑ=^peo^bX=ïÜáäÉ=çíÜÉê=ÅçããáííÉÉ=ãÉãÄÉêë=ã~ó=çê=ã~ó=åçí=ÄÉ=^peo^b=ãÉãÄÉêëI=~ää
ãìëí=ÄÉ= íÉÅÜåáÅ~ääó=èì~äáÑáÉÇ=áå=íÜÉ= ëìÄàÉÅí=~êÉ~=çÑ= íÜÉ=pí~åÇ~êÇK=bîÉêó=ÉÑÑçêí=áë= ã~ÇÉ= íç=Ä~ä~åÅÉ=íÜÉ=ÅçåÅÉêåÉÇ=áåíÉêÉëíë=çå=~ää= mêçàÉÅí
`çããáííÉÉëK=
qÜÉ=^ëëáëí~åí=aáêÉÅíçê=çÑ=qÉÅÜåçäçÖó=Ñçê=pí~åÇ~êÇë=~åÇ=péÉÅá~ä=mêçàÉÅíë=çÑ=^peo^b=ëÜçìäÇ=ÄÉ=Åçåí~ÅíÉÇ=ÑçêW
~K=áåíÉêéêÉí~íáçå=çÑ=íÜÉ=ÅçåíÉåíë=çÑ=íÜáë=pí~åÇ~êÇI
ÄK=é~êíáÅáé~íáçå=áå=íÜÉ=åÉñí=êÉîáÉï=çÑ=íÜÉ=pí~åÇ~êÇI
ÅK=çÑÑÉêáåÖ=ÅçåëíêìÅíáîÉ=ÅêáíáÅáëã=Ñçê=áãéêçîáåÖ=íÜÉ=pí~åÇ~êÇI=çê
ÇK=éÉêãáëëáçå=íç=êÉéêáåí=éçêíáçåë=çÑ=íÜÉ=pí~åÇ~êÇK
DISCLAIMER
^peo^b=ìëÉë=áíë=ÄÉëí=ÉÑÑçêíë=íç=éêçãìäÖ~íÉ=pí~åÇ~êÇë=~åÇ=dìáÇÉäáåÉë=Ñçê=íÜÉ=ÄÉåÉÑáí=çÑ=íÜÉ=éìÄäáÅ=áå=äáÖÜí=çÑ=~î~áä~ÄäÉ=áåÑçêã~íáçå=~åÇ
~ÅÅÉéíÉÇ=áåÇìëíêó=éê~ÅíáÅÉëK=eçïÉîÉêI=^peo^b=ÇçÉë=åçí=Öì~ê~åíÉÉI=ÅÉêíáÑóI=çê=~ëëìêÉ=íÜÉ=ë~ÑÉíó=çê=éÉêÑçêã~åÅÉ=çÑ=~åó=éêçÇìÅíëI=ÅçãéçåÉåíëI
çê= ëóëíÉãë= íÉëíÉÇI= áåëí~ääÉÇI= çê= çéÉê~íÉÇ= áå= ~ÅÅçêÇ~åÅÉ= ïáíÜ= ^peo^bÛë= pí~åÇ~êÇë= çê= dìáÇÉäáåÉë= çê= íÜ~í= ~åó= íÉëíë= ÅçåÇìÅíÉÇ= ìåÇÉê= áíë
pí~åÇ~êÇë=çê=dìáÇÉäáåÉë=ïáää=ÄÉ=åçåÜ~ò~êÇçìë=çê=ÑêÉÉ=Ñêçã=êáëâK
NOTE
When addenda, interpretations, or errata to this standard have been approved, they can be downloaded
free of charge from the ASHRAE Web site at http://www.ashrae.org.
This is a revision of ASHRAE Standard 22-2003. 4.1 Terms Recommended for Expressing Test Results
This standard prescribes methods for testing water- 4.1.1 In expressing test results, the following factors
cooled refrigerant condensers. To attain this objective, the should be stated:
standard lists and defines the terms suggested for rating
water-cooled refrigerant condensers and establishes testing a. condensing heat rejection (qc), Btu/h (kW),
methods that may be used as a basis for obtaining ratings of b. subcooling heat rejection (qs), Btu/h (kW),
water-cooled refrigerant condensers. c. saturated temperature of entering refrigerant vapor,
This standard was prepared under the auspices of the °F (°C),
American Society of Heating, Refrigerating and Air-Condi- d. temperature of entering water, °F (°C),
tioning Engineers (ASHRAE). It may be used, in whole or e. water mass flow rate (ww), lbm/h (kg/s), and
in part, by an association or government agency with due
f. water pressure drop through condenser, psi (kPa).
credit to ASHRAE. Adherence is strictly on a voluntary
basis and merely in the interests of obtaining uniform stan-
dards throughout the industry. 5. TEST METHODS
The changes made for the 2007 revision were that the ref-
erences were updated. 5.1 Standard Test Methods
5.1.1 Tests shall consist of a primary test and a simulta-
1. PURPOSE neous confirming test at the conditions specified.
This standard prescribes methods of testing the thermal 5.1.2 Specified conditions will include
performance of water-cooled refrigerant condensers.
a. either the total heat rejection, Btu/h (kW), or the satu-
2. SCOPE rated temperature of entering refrigerant vapor, °F (°C),
b. temperature of entering water, °F (°C),
To attain this objective, this standard c. water mass flow rate, lbm/h (kg/s),
a. lists and defines the terms suggested for the rating of d. minimum superheat of entering vapor, °R (K),
water-cooled refrigerant condensers and e. minimum ambient temperature, °F (°C),
b. establishes methods of test that can be used as a basis f. subcooling, °F (°C), and
for obtaining ratings of water-cooled refrigerant con- g. refrigerant used.
densers.
5.1.3 The results of the confirming test shall be within 3%
3. DEFINITION OF TERMS of the primary test, but the primary test shall govern for rating
purposes.
condensing heat rejection (qc ): the portion of the total heat
rejection of a condenser that is used for desuperheating and 5.1.4 Refrigerant flow through the condenser shall be pro-
condensing the entering refrigerant vapor to a saturated liq- duced by one of the following means (see Figures 1a and 1b):
uid. This is the product of the mass rate of refrigerant flow
(wr) and the difference between the enthalpy of the entering a. refrigerating compressor and low-side evaporator or
refrigerant vapor and that of the saturated refrigerant liquid at calorimeter (preferred method) or
the leaving pressure. b. refrigerant boiler.
subcooling heat rejection (qs ): the total heat rejection minus 5.2 Primary Test Methods
the condensing heat rejection. This is the product of the mass
5.2.1 The primary test for closed condensers (see
rate of refrigerant flow (wr) and the difference between the
Figure 2) shall consist of determination of the heat rejected
enthalpy of a saturated refrigerant liquid at the pressure of the
from the refrigerant by
leaving refrigerant and that of the refrigerant liquid at the
actual leaving temperature. a. measurement of heat rejected to the water and
total heat rejection (qt ): the total useful capacity of a water- b. calculation of heat rejected through the external sur-
cooled refrigerant condenser for removing heat from the faces of the condenser to the ambient air.
qL = Us As ( tc – ta ) (1)
be measured by two of the confirming tests in accordance
where with Section 5.3.
qL = heat rejected through external surfaces, Btu/h (kW); 5.3 Confirming Test Methods
1 5.3.1 The confirming test shall consist of a secondary
Us = --------------------------- ; (2) measurement of the heat rejected from the refrigerant by
x ⁄ k + 1 ⁄ hs
using one of the optional methods described in Sections 5.3.2,
x/k = 0 if insulation is not used; 5.3.3, and 5.3.4 below (see also Figure 3).
x = insulation thickness, in. (m); 5.3.2 Condenser Refrigerant Side. This method deter-
k = thermal conductivity of insulation, Btu⋅in./h⋅ft2⋅°F mines condenser heat rejection by calculating the product of
(W/m2⋅°C); the enthalpy difference of refrigerant fluid entering and leav-
ing the condenser and the mass rate of refrigerant flow. Mass
hs = film coefficient of ambient air, Btu/h⋅ft2⋅°F
rate of refrigerant flow shall be determined by using one of the
(W/ m2⋅°C) [for natural convection, use
following:
hs = 2.0 Btu/h⋅ft2⋅°F (11 W/(m2⋅°C)];
As = exposed external surface through which heat is lost, a. A refrigerant flow-measuring instrument.
ft2 (m2); b. A water or brine cooler arranged such that the refriger-
tc = saturated condensing temperature, °F (°C); and ant mass flow rate is the same in the condenser and the
cooler. The cooler shall be insulated if necessary such
ta = average ambient air temperature, °F (°C).
that the calculated heat gains through external surfaces
5.2.6 The heat rejected through the external surfaces of do not exceed 3% of the heat removed from water or
the condenser shall not exceed 3% of the heat rejected to the brine. The mass rate of refrigerant flow is obtained by
water. dividing the cooler heat input, including leakage gains,
5.2.7 For shell-and-tube, open-type condensers where the by the enthalpy difference between entering and leav-
primary method cannot be carried out, the heat rejection shall ing refrigerant.
c. A refrigerant calorimeter that provides a means of essary, so that calculated heat leakage loss does not
accurately measuring the amount of heat required to exceed 3% of the heat rejected to the liquid flowing
evaporate and superheat the refrigerant fluid flowing through the evaporator. Heat leakage loss shall be
through it. The rate of refrigerant flow is given by determined using the equations of Section 5.2.5 except
dividing the heat input, including leakage gains, by the that a film coefficient h = 4.0 Btu/h⋅ft2⋅°F (23 W/
enthalpy difference of the entering and leaving refrig- m2 ⋅°C), which includes both convection and radiation,
erant fluid. shall be used for compressor heads. The heat loss area
shall be equal to the actual total external area of com-
5.3.3 Refrigerant Boiler. This method determines con- pressor heads. Total condenser heat rejection, qtc , shall
denser heat rejection as the heat needed to evaporate the liq- be calculated as follows:
uid refrigerant in the boiler when this apparatus is used in
place of a complete refrigerating system, as allowed in Sec- q tc = q E – q L + W M (3)
tion 5.1.4(b).
where
5.3.4 Energy Balance Method. This method determines
condenser heat rejection using an energy balance on the entire qE = evaporator heat flow rate, Btu/h (kW)
refrigerating system. It may be used if the following condi- qL = algebraic sum of heat losses from condenser,
tions are met: compressor heads, piping, and evaporator,
Btu/h (kW)
a. the condenser is installed in a closed refrigerant circuit WM = electric power input to compressor, Btu/h (kW)
served by a water-heated evaporator and a hermetic or
semihermetic electric motor-compressor powered by a 6. INSTRUMENTS AND TEST APPARATUS
sinusoidal single-phase or three-phase electric power
supply; 6.1 General
b. the compressor and evaporator are closely matched in 6.1.1 Instruments, whose types and accuracies are listed
capacity to the condenser; below, shall be calibrated against standards before and after
c. no means of compressor cooling is used, other than each test.
free convection of ambient air; and 6.1.2 Physical data shall be obtained from the current edi-
d. the mass rate of refrigerant flow through the compres- tion of the ASHRAE Handbook—Fundamentals1 or from the
sor, condenser, and evaporator is to be substantially the International Critical Tables.
same. Hot gas bypass can be used to trim the steady-
state operating point but should not exceed 25% of the 6.2 Temperature-Measuring Instruments
condenser refrigerant mass flow. Condenser, refriger- 6.2.1 Temperature measurements shall be made with one
ant piping, and compressor heads are insulated, if nec- or more of the following instruments:
^peo^b=áë=ÅçåÅÉêåÉÇ=ïáíÜ=íÜÉ=áãé~Åí=çÑ=áíë=ãÉãÄÉêëÛ=~ÅíáîáíáÉë=çå=ÄçíÜ=íÜÉ=áåÇççê=~åÇ=çìíÇççê=ÉåîáêçåãÉåíK=^peo^bÛë
ãÉãÄÉêë= ïáää= ëíêáîÉ= íç= ãáåáãáòÉ= ~åó= éçëëáÄäÉ= ÇÉäÉíÉêáçìë= ÉÑÑÉÅí= çå= íÜÉ= áåÇççê= ~åÇ= çìíÇççê= ÉåîáêçåãÉåí= çÑ= íÜÉ= ëóëíÉãë= ~åÇ
ÅçãéçåÉåíë= áå= íÜÉáê= êÉëéçåëáÄáäáíó= ïÜáäÉ= ã~ñáãáòáåÖ= íÜÉ= ÄÉåÉÑáÅá~ä= ÉÑÑÉÅíë= íÜÉëÉ= ëóëíÉãë= éêçîáÇÉI= ÅçåëáëíÉåí= ïáíÜ= ~ÅÅÉéíÉÇ
ëí~åÇ~êÇë=~åÇ=íÜÉ=éê~ÅíáÅ~ä=ëí~íÉ=çÑ=íÜÉ=~êíK
^peo^bÛë=ëÜçêíJê~åÖÉ=Öç~ä=áë=íç=ÉåëìêÉ=íÜ~í=íÜÉ=ëóëíÉãë=~åÇ=ÅçãéçåÉåíë=ïáíÜáå=áíë=ëÅçéÉ=Çç=åçí=áãé~Åí=íÜÉ=áåÇççê=~åÇ
çìíÇççê= ÉåîáêçåãÉåí= íç= ~= ÖêÉ~íÉê= ÉñíÉåí= íÜ~å= ëéÉÅáÑáÉÇ= Äó= íÜÉ= ëí~åÇ~êÇë= ~åÇ= ÖìáÇÉäáåÉë= ~ë= Éëí~ÄäáëÜÉÇ= Äó= áíëÉäÑ= ~åÇ= çíÜÉê
êÉëéçåëáÄäÉ=ÄçÇáÉëK
^ë= ~å= çåÖçáåÖ= Öç~äI= ^peo^b= ïáääI= íÜêçìÖÜ= áíë= pí~åÇ~êÇë= `çããáííÉÉ= ~åÇ= ÉñíÉåëáîÉ= íÉÅÜåáÅ~ä= ÅçããáííÉÉ= ëíêìÅíìêÉI
ÅçåíáåìÉ=íç=ÖÉåÉê~íÉ=ìéJíçJÇ~íÉ=ëí~åÇ~êÇë=~åÇ=ÖìáÇÉäáåÉë=ïÜÉêÉ=~ééêçéêá~íÉ=~åÇ=~ÇçéíI=êÉÅçããÉåÇI=~åÇ=éêçãçíÉ=íÜçëÉ=åÉï
~åÇ=êÉîáëÉÇ=ëí~åÇ~êÇë=ÇÉîÉäçéÉÇ=Äó=çíÜÉê=êÉëéçåëáÄäÉ=çêÖ~åáò~íáçåëK
qÜêçìÖÜ=áíë=HandbookI=~ééêçéêá~íÉ=ÅÜ~éíÉêë=ïáää=Åçåí~áå=ìéJíçJÇ~íÉ=ëí~åÇ~êÇë=~åÇ=ÇÉëáÖå=ÅçåëáÇÉê~íáçåë=~ë=íÜÉ=ã~íÉêá~ä=áë
ëóëíÉã~íáÅ~ääó=êÉîáëÉÇK
^peo^b=ïáää=í~âÉ=íÜÉ=äÉ~Ç=ïáíÜ=êÉëéÉÅí=íç=ÇáëëÉãáå~íáçå=çÑ=ÉåîáêçåãÉåí~ä=áåÑçêã~íáçå=çÑ=áíë=éêáã~êó=áåíÉêÉëí=~åÇ=ïáää=ëÉÉâ
çìí= ~åÇ= ÇáëëÉãáå~íÉ= áåÑçêã~íáçå= Ñêçã= çíÜÉê= êÉëéçåëáÄäÉ= çêÖ~åáò~íáçåë= íÜ~í= áë= éÉêíáåÉåíI= ~ë= ÖìáÇÉë= íç= ìéÇ~íáåÖ= ëí~åÇ~êÇë= ~åÇ
ÖìáÇÉäáåÉëK
qÜÉ= ÉÑÑÉÅíë= çÑ= íÜÉ= ÇÉëáÖå= ~åÇ= ëÉäÉÅíáçå= çÑ= ÉèìáéãÉåí= ~åÇ= ëóëíÉãë= ïáää= ÄÉ= ÅçåëáÇÉêÉÇ= ïáíÜáå= íÜÉ= ëÅçéÉ= çÑ= íÜÉ= ëóëíÉãÛë
áåíÉåÇÉÇ=ìëÉ=~åÇ=ÉñéÉÅíÉÇ=ãáëìëÉK=qÜÉ=Çáëéçë~ä=çÑ=Ü~ò~êÇçìë=ã~íÉêá~äëI=áÑ=~åóI=ïáää=~äëç=ÄÉ=ÅçåëáÇÉêÉÇK
^peo^bÛë= éêáã~êó= ÅçåÅÉêå= Ñçê= ÉåîáêçåãÉåí~ä= áãé~Åí= ïáää= ÄÉ= ~í= íÜÉ= ëáíÉ= ïÜÉêÉ= ÉèìáéãÉåí= ïáíÜáå= ^peo^bÛë= ëÅçéÉ
çéÉê~íÉëK= eçïÉîÉêI= ÉåÉêÖó= ëçìêÅÉ= ëÉäÉÅíáçå= ~åÇ= íÜÉ= éçëëáÄäÉ= ÉåîáêçåãÉåí~ä= áãé~Åí= ÇìÉ= íç= íÜÉ= ÉåÉêÖó= ëçìêÅÉ= ~åÇ= ÉåÉêÖó
íê~åëéçêí~íáçå=ïáää=ÄÉ=ÅçåëáÇÉêÉÇ=ïÜÉêÉ=éçëëáÄäÉK=oÉÅçããÉåÇ~íáçåë=ÅçåÅÉêåáåÖ=ÉåÉêÖó=ëçìêÅÉ=ëÉäÉÅíáçå=ëÜçìäÇ=ÄÉ=ã~ÇÉ=Äó
áíë=ãÉãÄÉêëK
86045
PC 8/07