Gs01c50h01-01en - 012 Yta610

Download as pdf or txt
Download as pdf or txt
You are on page 1of 17

<<Contents>> <<Index>>

General YTA610
Specifications Temperature Transmitter

GS 01C50H01-01EN

The YTA610 is the highly accurate temperature


transmitter that accepts Thermocouple, RTD, ohms or
DC millivolts inputs and converts it to a 4 to 20 mA DC
or Fieldbus signal for transmission.
The YTA610 supports HART and FOUNDATION fieldbus
communication protocols.
HART types are certified as complying with SIL 2 for
safety requirement.

 FEATURES  STANDARD SPECIFICATIONS


High reliability
Dual-compartment housing realizes high resistance ■ PERFORMANCE SPECIFICATIONS
capability to harsh environments. Accuracy
Variety of sensor inputs HART communication type:
The type of sensor input is user-selectable from A/D accuracy/span + D/A accuracy
thermocouples (T/C), RTDs, ohms, or DC millivolts. (See Table 1 on page 4.)
Digital communication Fieldbus communication type:
HART protocol revision is 7 and FOUNDATION fieldbus. A/D accuracy (See Table 1 on page 4.)
The instrument configuration can be changed by the Cold Junction Compensation Accuracy
user with using the Fieldmate or Handheld terminal. ± 0.5°C (± 0.9 °F) for T/C only
Local Parameter Setting Ambient Temperature Effect (per 10°C change)
Parameter configuration by the push button offers See Table 2 on page 5.
easy and quick setup for parameters. Stability
Self-diagnostics function RTD: ±0.1% of reading or ±0.1°C per 2 years,
Continuous self-diagnostics capability ensures whichever is greater at 23±2°C.
longterm performance and lower cost of ownership. T/C: ±0.1% of reading or ±0.1°C per year, whichever
Dual universal inputs is greater at 23±2°C.
Dual input can accept two thermocouple, RTD, 5 Year Stability
ohm or DC millivolt inputs. Differential or average RTD: ±0.25% of reading or ±0.25°C,
temperature measurement is selectable. The sensor whichever is greater at 23±2°C.
backup function for automatically switches-over from T/C: ±0.5% of reading or ±0.5°C,
the primary to the backup upon sensor failure. whichever is greater at 23±2°C.
Vibration Effect
The YTA610 is tested to the following specifications
with no effect on performance per IEC 60770-1
10 to 60 Hz 0.21 mm peak displacement
60 to 2000 Hz 3g
Power Supply Effect (HART type)
±0.005% of calibrated span per volt

Yokogawa Electric Corporation GS 01C50H01-01EN


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan ©Copyright Sep. 2016 (YK)
Tel.: 81-422-52-5690 Fax.: 81-422-52-2018 12th Edition Mar. 2, 2018 (YK)
<<Contents>> <<Index>> 2
■ FUNCTIONAL SPECIFICATIONS Fieldbus Functions (Fieldbus type)
Functional specifications for Fieldbus communication
Input Signals conform to the standard specifications (H1) of
Input number: single and dual input FOUNDATION Fieldbus.
Input type is selectable: Thermocouples, 2-, 3-, and
4-wire RTDs, ohms and DC millivolts. Function Block (Fieldbus type)
See Table 1. on page 4. Resource block
Input Signal Source Resistance (for T/C, mV) The resource block contains physical transmitter
1 kΩ or lower information.
Input Lead Wire Resistance (for RTD, ohm) Transducer block
10 Ω per wire or lower The transducer block contains the actual
measurement data and information about sensor
Span & Range Limits type and configuration and diagnostics.
See Table 1. on page 4.
LCD display block
Output Signals The LCD display block is used to configure the local
Two wire 4 to 20 mA DC type display, if an LCD display is being used.
Output range: 3.68 to 20.8 mA Analog input (AI)
HART protocol is superimposed on the 4 to 20 mA Four independent AI blocks can be selected.
signal. Any single value among followings can be
selected as the analog output signal. Digital input (DI)
Sensor 1, Terminal Temperature. Four DI function blocks can be used as a limit
Dual input type, same as above plus; switch for those temperature.
Sensor 2, Average, and Differential Temperature. Other function block
Also, up to three of the above values can As other Function blocks, Arithmetic (AR), Signal
be displayed on LCD display or read via Characterizer (SC), Input Selector (IS), and two PID
communication. function blocks are available.
Fieldbus type Function block Execution time (ms)
Output signal based on FOUNDATION fieldbus AI 30
communication protocol.
DI 30
Isolation SC 30
Input/Output/GND isolated to 500V DC
IS 30
Except lightning protector option.
AR 30
Manual Test Output Function
PID 45
The output value can be set manually.
Sensor Burnout (HART type) Link master function
High (21.6 mA DC) or Low (3.6 mA DC), user This function enables backup of network manager
selectable. and local control only by field devices.
Output in Transmitter Failure (HART type) Alarm function
Down-scale: –5%, 3.2 mA DC or less, sensor burnout Fieldbus models securely support various alarm
–2.5%, 3.6 mA (Optional code C1) functions, such as High/Low alarm, notice of
Down-scale: –5%, 3.2 mA DC or less (Optional code block error, etc. based on FOUNDATION fieldbus
C2) specifications.
Up-scale: 110%, 21.6 mA DC or more (Standard or Software download function
Optional code C3) This function permits to update YTA software via a
Update Time (HART type) FOUNDATION fieldbus.
Approximately 0.5 seconds for a single sensor (0.8 Based on Foundation fieldbus specifications (FF883)
second for dual sensors) at damping time 0 Download class: Class 1
Turn-on Time (HART type) EMC Conformity Standards
Approximately 6 seconds for a single sensor (7 EN61326-1 Class A, Table2
seconds for dual sensors) EN61326-2-3
Damping Time Constant EN61326-2-5 (for fieldbus type)
Selectable from 0 to 100 seconds SIL Certification
Self-Diagnostics Hart type certified in compliance with IEC 61508:
Self-diagnostic function based on the NAMUR 2010.
NE107 standard detects failures in the hardware, Functional Safety of Electrical/electronic/
configuration and communications. Programmable electronic related systems;
SIL 2 capability for single transmitter use
Sensor-Diagnostics SIL 3 capability for dual transmitter use
Sensor failure: Detect the disconnection of sensor.
Sensor line information: Measure the line resistance.
Sensor drift: Detect the difference between sensor1
and sensor2.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50H01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 3
Safety Requirement Standards ■ PHYSICAL SPECIFICATIONS
EN61010-1, C22.2 No.61010-1
• Installation category: I Enclosure
(Anticipated transient overvoltage 330 V) Material & coating
• Pollution degree: 2 • Low copper cast aluminum alloy
• Indoor/Outdoor use [for aluminum housing]
EN61010-2-030, C22.2 No.61010-2-030 Urethane-cured polyester powder coating
• Measurement category: O (Other) Mint-green paint (Munsell 5.6BG 3.3/2.9 or its
(Measurement Input voltage: 150mVdc max) equivalent)
EU RoHS Directive [for option code /P or /X2]
Applicable standard: EN 50581 Epoxy and polyurethane resin solvent coating
• ASTM CF-8M Stainless steel
■ NORMAL OPERATING CONDITION Degrees of protection
(Optional features or approval codes may affect limits.) IP66/IP67, TYPE 4X
Ambient Temperature Limits Name plate and tag
–40 to 85°C (–40 to 185°F) 316 SST
–30 to 80°C (–22 to 176°F) (with indicator model) Mounting
Ambient Humidity Limits Optional mounting brackets can be used either for
0 to 100% RH at 40°C (104°F) two-inch pipe or flat panel mounting.
Supply Voltage Requirements Terminal screws
M4 screws
HART type
10.5 to 42 V DC for general use and flameproof type Integral Indicator (with indicator model)
10.5 to 32 V DC for lightning protector (option code /A) 5-digit numerical display, 6-digit unit display and bar
10.5 to 30 V DC for intrinsically safe and graph.
non-incendive type Local Parameter Setting (with indicator model)
Minimum voltage limited at 16.6 V DC for digital Parameter configuration by the push button offers
communications HART easy and quick setup for parameters.
With 24 V DC supply, up to a 550Ω load can be Accessible parameters are different with each output
used. See graph below. cord.
Weight
Aluminum housing:
1.3 kg (2.9 lb) without integral indicator and mounting
600 Integral indicator: 0.2 kg (0.4 lb)
Bracket for horizontal pipe: 0.3 kg
E-10.5
R= Bracket for vertical pipe: 1.0 kg
External 0.0244 Digital
load Communication
Stainless housing:
resistance range 3.1 kg (6.8 lb) without integral indicator and mounting
HART Integral indicator: 0.3 kg (0.7 lb)
250 Connections
Refer to “MODEL AND SUFFIX CODE.”
R (Ω)

10.5 16.6 25.2 42


Power supply voltage E (V)
F01E.ai

Figure 1. Relationship Between Power Supply


Voltage and External Load Resistance

Fieldbus type
9 to 32V DC for general use, flameproof type, and
non-incendive type
9 to 30 V DC for intrinsically safe type
9 to 17.5 V DC for FISCO field device
Communication Requirements
Supply Voltage: 9 to 32 V DC
Current Draw:
Steady state: 15 mA (max)
Software download state: 24 mA (max)
Load Requirements (HART type)
0 to 1290Ω for operation
250 to 600Ω for digital communication

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50H01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 4
Table 1. Sensor type, measurement range, and accuracy

Measurement Range Minimum A/D Accuracy D/A


Sensor Type Standard
°C °F Span °C °F Accuracy
100 to 300 212 to 572 ± 3.0 ± 5.4
B
300 to 1820 572 to 3308 ± 0.77 ± 1.39
-200 to -50 -328 to -58 ± 0.4 ± 0.72
E
-50 to 1000 -58 to 1832 ± 0.2 ± 0.36
-200 to -50 -328 to -58 ± 0.35 ± 0.63
J
-50 to 1200 -58 to 2192 ± 0.25 ± 0.45
-200 to -50 -328 to -58 ± 0.5 ± 0.9
K
-50 to 1372 -58 to 2501 ± 0.3 ± 0.54
-200 to -50 -328 to -58 ± 0.5 ± 0.9
N
IEC60584 -50 to 1300 -58 to 2372 ± 0.4 ± 0.72
-50 to 0 -58 to 32 ± 1.0 ± 1.8
R 0 to 600 32 to 1112 ± 0.7 ± 1.26
600 to 1768 1112 to 3214 25°C ± 0.5 ± 0.9
T/C
-50 to 0 -58 to 32 (45°F) ± 1.0 ± 1.8
S
0 to 1768 32 to 3214 ± 0.6 ± 1.08
-200 to -50 -328 to -58 ± 0.35 ± 0.63
T
-50 to 400 -58 to 752 ± 0.2 ± 0.36
0 to 2000 32 to 3632 ± 0.7 ± 1.26
C ±0.03%
2000 to 2300 3632 to 4172 ± 1.0 ± 1.8
of span
0 to 400 32 to 752 ± 0.9 ± 1.62
ASTM 400 to 1400 752 to 2552 ± 0.6 ± 1.08
W3
E988 1400 to 2000 2552 to 3632 ± 0.7 ± 1.26
2000 to 2300 3632 to 4172 ± 1.0 ± 1.8
-200 to -50 -328 to -58 ± 0.35 ± 0.63
L
DIN43710 -50 to 900 -58 to 1652 ± 0.3 ± 0.54
U -200 to 600 -328 to 1112 ± 0.35 ± 0.63
Pt100 -200 to 850 -328 to 1562 ± 0.14 ± 0.25
Pt200 -200 to 850 -328 to 1562 ± 0.25 ± 0.45
IEC60751
Pt500 -200 to 850 -328 to 1562 ± 0.18 ± 0.32
Pt1000 -200 to 300 -328 to 572 10°C ± 0.18 ± 0.32
RTD
JPt100 — -200 to 500 -328 to 932 (18°F) ± 0.16 ± 0.29
SAMA
Cu10 -70 to 150 -94 to 302 ± 1.3 ± 2.34
RC21-4
Ni120 — -70 to 320 -94 to 608 ± 0.14 ± 0.25
mV — -10 to 120 [mV] 3 mV ±0.015 [mV]
ohm — 0 to 2000 [Ω] 20 Ω ±0.45 [Ω]
Note 1: Total Accuracy = (A/D Accuracy / Span + D/A Accuracy) or (± 0.1% of calibrated span), whichever is greater.
Accuracy of Fieldbus type: A/D Accuracy.
For T/C input, add Cold Junction Compensation Error (± 0.5°C) to the total accuracy.
Example: when selecting Pt100 with measurement range of 0 to 400 °C
0.14°C / 400°C×100% of span +0.03% of span = 0.065% of span
Since the value is smaller than ±0.1% of span, the total accuracy is ±0.1%.
Note 2: T/C C type is same as W5 (ASTM E988).

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50H01-01EN Jan. 15, 2018-00
<<Contents>> <<Index>> 5
Table 2. Temperature coefficient

Sensor Type Temperature Coefficient


Thermocouples E, J, K, N, T, L, U 0.08°C + 0.02% of abs.reading
Thermocouples R, S, W3, C 0.25°C + 0.02% of abs.reading
Thermocouple B 100°C ≤ Reading < 300°C 1°C + 0.02% of abs.reading
300°C ≤ Reading 0.5°C + 0.02% of abs.reading
RTD 0.08°C + 0.02% of abs.reading
mV 0.002 mV + 0.02% of abs.reading
ohm 0.1 Ω + 0.02% of reading
Note1: The “abs.reading” for thermocouples and RTD means the absolute value of the reading in °C.
Example of “abs.reading”
When the temperature value is 250 Kelvin, “abs.reading” is 23.15.
|250−273.15|= 23.15
Note2: Ambient Temperature Effect per 10 °C change is ±0.1% or ±(temperature coefficient/span), whichever is greater.
Example of Ambient Temperature Effect
Conditions:
1) Input Sensor: Pt100
2) Calibration Range: −100 to 100°C
3) Reading value: −50°C
Ambient Temperature Effect per 10°C
Temperature Coefficient/Span=(0.08°C+0.02/100×|−50°C|)/{100°C−(−100°C)}= 0.00045 → 0.045%
Therefore, Ambient Temperature Effect is ±0.1%/10°C

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50H01-01EN Sep. 30, 2016-00
<<Contents>> <<Index>> 6
 MODEL AND SUFFIX CODES
Model Suffix Codes Description
YTA610 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Temperature Transmitter
Output signal -J. . . . . . . . . . . . . . . . . . . . . . . . . . . 4 to 20 mA DC with digital communication HART protocol
-F. . . . . . . . . . . . . . . . . . . . . . . . . . . Digital communication (FOUNDATION Fieldbus protocol)
— A. . . . . . . . . . . . . . . . . . . . . . . Always A
Sensor input 1 . . . . . . . . . . . . . . . . . . . . Single
2 . . . . . . . . . . . . . . . . . . . . Double
Housing code A. . . . . . . . . . . . . . . . Aluminum
C. . . . . . . . . . . . . . . . Stainless
Electrical connection 0 . . . . . . . . . . . . . G1/2 female
2 . . . . . . . . . . . . . 1/2 NPT female
4 . . . . . . . . . . . . . M20 female
Integral indicator D. . . . . . . . . . Digital indicator with Local Operating Switch
N. . . . . . . . . . None
Mounting bracket B. . . . . . SUS304 stainless steel 2-inch horizontal pipe mounting bracket *1
D. . . . . . SUS304 stainless steel 2-inch vertical pipe mounting bracket
J . . . . . . SUS316 stainless steel 2-inch horizontal pipe mounting bracket *1
K. . . . . . SUS316 stainless steel 2-inch vertical pipe mounting bracket
N. . . . . . None
Option codes / Optional specification
*1: For flat-panel mounting, please prepare bolts and nuts.

 OPTIONAL SPECIFICATION
Item Description Code
Lightning protector *4 Allowable current: Max. 6000A(8×20µs), repeating 1000A(8×20µs), 100 times A
Painting*1*6 Color and coating change Color: Munsell code N1.5 Black
P1
Amplifier cover only*3 Coating: High anti-corrosion coating
Color: Munsell code 7.5BG4/1.5, Jade green
P2
Coating: High anti-corrosion coating
Color: Metallic silver
P7
Coating: High anti-corrosion coating
Color and coating change Color: Munsell code 7.5 R4/14, Red
PR
Amplifier and terminal Covers*3 Coating: High anti-corrosion coating
Coating change High anti-corrosion coating X2
Output signal low-side in Output signal Low-side: –5%, 3.2 mA DC or less.
C1
transmitter failure*2 Sensor burnout is also set to 'Low': –2.5%, 3.6 mA DC.
NAMUR NE43 compliant*2 Output signal limits: Failure alarm down-scale: output status at CPU failure and
3.8 mA to 20.5 mA hardware error is –5%, 3.2 mA or less. C2
Sensor burnout is also set to Low: –2.5%, 3.6 mA DC.
Failure alarm up-scale: output status at CPU failure and hardware
error is 110%, 21.6 mA or more. C3
In this case Sensor burnout is High: 110%, 21.6 mA DC.
Data configuration*2 Description into “Descriptor” parameter of HART protocol (max. 16 characters) CA
Wired tag plate SUS316 stainless steel tag plate wired onto transmitter N4
Sensor matching RTD sensor matching function CM1
Attached flameproof Electrical connection G1/2 female
2pc. V52
packing adapter*5*7 Applicable cable: O.D.8.0 to 12 mm
EAC approval and Russian EAC approval and Russian pattern approval marking
VR
pattern approval marking*8
EAC approval marking EAC approval marking without Russian pattern approval marking
without Russian pattern VE
approval marking*8
Note: The indication of the nameplate shows an initial shipment state.
*1: Not applicable for Stainless housing.
*2: Not applicable for Fieldbus type.
*3: Except for Amplifier and terminal cover, color and coating are general specification.
*4: Lightning protector (surge absorber) can be remove from, or added to the equipment.
*5: Combination with other Explosion protected other than TIIS flameproof is not possible.
*6: The combination of X2 and P is not possible.
*7: Applicable for Electrical Connection code 4. (The thread of connection between YTA and CABLE GLAND is M20,
and the thread of connection between CABLE GLAND and CABLE is G1/2.)
*8: Combination with other Explosion protected other than EAC Explosion-proof type is not applicable.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50H01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 7
 OPTIONAL SPECIFICATION (For Explosion Protected type)
Item Description Code
ATEX 4-20mA:
[Intrinsically safe ia approval]
Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-11:2012
Certificate No. FM16ATEX0019X
II 1 G Ex ia IIC T5…T4 Ga
Ambient Temperature: –40 to 70°C for T4, –40 to 50°C for T5
Enclosure: IP66/IP67
Electrical parameters:
Supply/Output circuit: Terminals: +, –
Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Intrinsically safe ic]
Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-11:2012
Certificate: Not Applicable as per Annex VIII to ATEX 2014/34/EU
II 3 G Ex ic IIC T5...T4 Gc
KU2
Ambient Temperature: –30 to 70°C for T4, –30 to 50°C for T5
Enclosure: IP66/IP67
Overvoltage category: I
Electrical parameters:
Supply/Output circuit: Terminals: +, –
Ui=32V, Ci=2.2nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Flameproof and Dust Ignition Proof Approval]
Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014
Certificate: KEMA 07ATEX0130
II 2 G Ex db IIC T6/T5 Gb, II 2 D Ex tb IIIC T70°C/T90°C Db
Ambient Temperature for Gas Atmospheres: –40 to 75°C for T6, –40 to 80°C for T5
Ambient Temperature for Dust Atmospheres: –30 to 65°C for T70°C, –30 to 80°C for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female*1
Fieldbus:
[Intrinsically safe ia approval]
Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-11:2012
Certificate No. FM16ATEX0019X
II 1 G Ex ia IIC T4 Ga
Ambient Temperature: –55 to 60°C
Enclosure: IP66/IP67
Electrical parameters:
Supply/Output circuit: Terminals: +, –
FISCO field device or
Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Intrinsically safe ic] KU25
Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-11:2012
Certificate: Not Applicable as per Annex VIII to ATEX 2014/34/EU
II 3 G Ex ic IIC T4 Gc
Ambient Temperature: –30 to 70°C
Enclosure: IP66/IP67
Electrical parameters:
Supply/Output circuit: Terminals: +, –
FISCO field device or
Ui=32V, Ci=2.2nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Flameproof and Dust Ignition Proof Approval]
Same as KU2

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50H01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 8
Item Description Code
IECEx 4-20mA:
[Intrinsically safe ia, ic pproval]
Applicable Standard: IEC 60079-0:2011, IEC 60079-11:2011
Certificate No. IECEx FMG 16.0014X
Ex ia IIC T5…T4 Ga
Ex ic IIC T5...T4 Gc
Ambient Temperature: –40 to 70°C for T4, –40 to 50°C for T5(Ex ia)
Ambient Temperature: –30 to 70°C for T4, –30 to 50°C for T5(Ex ic)
Enclosure: IP66/IP67
Over voltage category: I
Electrical parameters (Ex ia)
Supply/Output circuit: Terminal: +, –
Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Electrical parameters (Ex ic) SU2
Supply/Output circuit: Terminal: +, –
Ui=30V, Ci=22nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Flameproof and Dust Ignition Proof Approval]
Applicable standard: IEC 60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013
Certificate: IECEx KEM 07.0044
Ex db IIC T6/T5 Gb, Ex tb IIIC T70°C/T90°C Db
Ambient Temperature for Gas Atmospheres: –40 to 75°C (–40 to 167°F) for T6,
–40 to 80°C (–40 to 176°F) for T5
Ambient Temperature for Dust Atmospheres: –30 to 65°C (–22 to 149°F) for T70°C,
–30 to 80°C (–22 to 176°F) for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female*1
Fieldbus:
[Intrinsically safe ia approval]
Applicable Standard: IEC 60079-0: 2011, IEC 60079-11: 2011
Certificate No. IECEx FMG 16.0014X
Ex ia IIC T4 Ga
Ex ic IIC T4 Gc
Ambient Temperature: –55 to 60°C (Ex ia)
Ambient Temperature: –30 to 70°C (Ex ic)
Enclosure: IP66/IP67
Overvoltage category: I
Electrical parameters (Ex ia)
Supply/Output circuit: Terminals: +, –
FISCO field device or SU25
Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Electrical parameters (Ex ic)
Supply/Output circuit: Terminals: +, –
FISCO field device or
Ui=32V, Ci=2.2nF, Li=0mH
Sensor circuit:Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Flameproof and Dust Ignition Proof Approval]
Same as SU2

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50H01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 9
Item Description Code
FM (US) 4-20mA:
[Intrinsically safe approval/non-incendive approval]
Applicable standard: FM Class 3600:2011, FM Class 3610:2015, FM Class 3611:2004,
FM Class 3810:2005, ANSI/ISA-60079-0:2013, ANSI/ISA-60079-11:2014, NEMA 250:2003,
ANSI/IEC 60529:2004
Intrinsically safe for
Class I, II, III Division 1, Groups A, B, C, D, E, F, G, T5…T4
Class I Zone 0 AEx ia IIC T5…T4
Non-incendive for
Class I, II, Division 2, Groups A, B, C, D, F, G, T5…T4
Class III, Division 1 T5…T4
Class I Zone 2 Group IIC T5…T4
Ambient Temperature: –40 to 70°C for T4, –40 to 50°C for T5
Enclosure Type 4X, IP66/IP67
Electrical parameters:
Intrinsically safe for
Supply/Output circuit: Terminals: +, –
Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
FU1
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Non-incendive for
Supply/Output circuit: Terminals: +, –
Ui=30V, Ci=22nF, Li=0mH
Sensor circuit:Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Explosionproof approval]
Applicable standard: FM Class 3600: 2011, FM Class 3615: 2006, FM Class 3810: 2005,
NEMA250: 2014
Class I, Division 1, Groups A, B, C and D.;
Class II/III, Division 1, Groups E, F and G.
"FACTORY SEALD, CONDUIT SEAL NOT REQUIRED."
Enclosure Ratings: TYPE 4X
Temperature Class: T6
Ambient Temperature: –40 to 60°C (–40 to 140°F)
Electrical Connection: 1/2NPT female*2
Fieldbus:
[Intrinsically safe approval/non-incendive approval]
Applicable standard: FM Class 3600:2011, FM Class 3610:2015, FM Class 3611:2004,
FM Class 3810:2005, ANSI/ISA-60079-0:2013, ANSI/ISA-60079-11:2014, NEMA 250:2003,
ANSI/IEC 60529:2004
Intrinsically safe for
Class I, II, III Division 1, Groups A, B, C, D, E, F, G T4
Class I Zone 0 AEx ia IIC T4
Non-incendive for
Class I, II, Division 2, Groups A, B, C, D, F, G T4
Class III, Division 1 T4 Class I Zone 2 Group IIC T4
Ambient Temperature: –55 to 60°C
Enclosure Type 4X, IP66/IP67
Electrical parameters:
FU15
Intrinsically safe for
Supply/Output circuit: Terminals: +, –
FISCO field device or
Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Non-incendive for
Supply/Output circuit: Terminals: +, –
Ui=32V, Ci=2.2nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Explosionproof approval]
Same as FU1

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50H01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 10
Item Description Code
CSA*3 4-20mA:
[Intrinsically safe approval/non-incendive approval]
FM (Canada)*4 Applicable standard: CAN/CSA-C22.2 No. 94.2-07, C22.2 No.213:1987,
CAN /CSA-C22.2 No. 60079-0:11, CAN/CSA-C22.2 No. 60079-11:14,
CAN/CSA-C22.2 No. 60529:05, CAN/CSA-C22.2 No. 61010-1-12,
CAN/CSA-C22.2 No. 61010-2-030-12
Intrinsically safe for
Class I, II, III, Division 1, Groups A, B, C, D, E, F, G, T5…T4
Ex ia IIC T5…T4 Ga
Non-incendive for
Class I, II, Division 2, Groups A, B, C, D, F, G T5…T4
Class III Division 1 T5…T4
Ambient Temperature: –40 to 70°C for T4, –40 to 50°C for T5
Enclosure Type: 4X, IP66/IP67
Electrical parameters:
Intrinsically safe for
Supply/Output circuit: Terminals: +, –
Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH CU1
Non-incendive for
Supply/Output circuit: Terminals: +, –
Ui=30V, Ci=22nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Explosionproof approval]
Applicable standard: C22.2 No. 0-10, C22.2 No. 0.4-04, C22.2 No. 25-M1966, C22.2 No. 30-M1986,
C22.2 No. 94-M1991, C22.2 No. 142-M1987, C22.2 No. 157-92, C22.2 No. 213-M1987,
C22.2 No.61010-1-12, C22.2 No. 61010-2-030-12
Class I, Groups B, C and D,
Class II, Groups E, F and G,
Class III.
For Class I, Division2 Groups ABCD Locations “FACTORY SEALED, CONDUIT SEAL NOT
REQUIRED”
Enclosure TYPE 4X
Temperature Class: T6
Ambient Temperature: –40 to 60°C
Electrical Connection: 1/2 NPT female*2
Fieldbus:
[Intrinsically safe approval/non-incendive approval]
Applicable standard: CAN/CSA-C22.2 No. 94.2-07, C22.2 No.213:1987,
CAN /CSA-C22.2 No. 60079-0:11, CAN/CSA-C22.2 No. 60079-11:14,
CAN/CSA-C22.2 No. 60529:05, CAN/CSA-C22.2 No. 61010-1-12,
CAN/CSA-C22.2 No. 61010-2-030-12
Intrinsically safe for
Class I, II, III, Division 1, Groups A, B, C, D, E, F, G T4
Ex ia IIC T4 Ga
Non-incendive for
Class I, II, Division 2, Groups A, B, C, D, F, G T4
Class III Division 1 T4
Ambient Temperature : –55 to 60°C
Enclosure Type: 4X, IP66/IP67
Electrical parameters: CU15
Intrinsically safe for
Supply/Output circuit: Terminals: +, –
FISCO field device or
Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Non-incendive for
Supply/Output circuit: Terminals: +, –
Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit: Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
[Explosionproof approval]
Same as CU1

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50H01-01EN Mar. 2, 2018-00
<<Contents>> <<Index>> 11
Item Description Code
NEPSI 4-20mA and Fieldbus:
[Flameproof and Dust Ignition Proof Approval]
Applicable Standard: GB3836.1-2010, GB3836.2-2010, GB12476.1-2013, GB12476.5-2013
Certificate No. GYJ16.1396X
Ex d IIC T6/T5 Gb, Ex tD A21 IP66/IP67 T70°C/T90°C NF2
Ambient Temperature for Gas Atmospheres: –40 to 75°C for T6, –40 to 80°C for T5
Ambient Temperature for Dust Atmospheres: –30 to 65°C for T70°C, –30 to 80°C for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female*1
4-20mA:
[Intrinsically safe approval ]
Applicable Standard: GB 3836.1-2010, GB 3836.4-2010 GB 3836.20-2010
Certificate No. GYJ16.1423X
Ex ia IIC T4/T5 Ga
Ambient Temperature: –40 to 70°C for T4, –40 to 50°C for T5
Enclosure: IP66/IP67 in accordance with only IEC 60529 NS2
Entity Parameters:
Supply/Output circuit: Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit: Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min
[+, -, C, 1, 2, 3, 4, 5] to Earth terminal
[+, -, C] to [1, 2, 3, 4, 5]
Fieldbus:
[Intrinsically safe approval]
Applicable Standard: GB 3836.1-2010, GB 3836.4-2010, GB3836.20-2010
Certificate No. GYJ16.1423X
Ex ia IIC T4 Ga
Ambient Temperature: –55 to 60°C for T4
Enclosure: IP66/IP67 in accordance with only IEC 60529
NS25
FISCO field device
Entity Parameters:
Supply/Output circuit: Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit: Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min
[+, -, 1, 2, 3, 4, 5] to Earth terminal
[+, -] to [1, 2, 3, 4, 5]

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50H01-01EN Sep. 13, 2017-00
<<Contents>> <<Index>> 12
Item Description Code
INMETRO [4-20mA & Fieldbus: Flameproof and dust ignition proof approval]
Applicable Standard: ABNT NBR IEC 60079-0:2013 Versão Corrigida 2: 2016,
ABNT NBR IEC60079-1:2016, ABNT NBR IEC 60079-31:2014
Certificate: DEKRA 16.0009
Ex db IIC T6/T5 Gb, Ex tb IIIC T70°C/ 90°C Db UF1
Ambient Temperature for Gas: –40 to +75°C for T6, –40 to +80°C for T5
Ambient Temperature for Dust: –30 to +65°C for T70°C, –30 to +80°C for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female*1
4-20mA:
[Intrinsically safe approval ]
Applicable Standard: ABNT NBR IEC 60079-0:2013 Versão Corrigida 2:2016,
ABNT NBR IEC 60079-11:2013
Certificate: ABNT 17.0001X
Ex ia IIC T5...T4 Ga
Ambient Temperature: –40 to 70 °C for T4, –40 to 50 °C for T5 US1
Enclosure: IP66/IP67
Supply/Output circuit:
Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit:
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
Fieldbus:
[Intrinsically safe approval "ia" ]
Applicable Standard: ABNT NBR IEC 60079-0:2013 Versão Corrigida 2:2016,
ABNT NBR IEC 60079-11:2013
Certificate: ABNT 17.0001X
Ex ia IIC T4 Ga
Ambient Temperature: –55 to 60 °C
Enclosure: IP66/IP67
Supply/Output circuit:
FISCO field device and
Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit:
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
US15
[Intrinsically safe approval "ic" ]
Applicable Standard: ABNT NBR IEC 60079-0:2013 Versão Corrigida 2:2016,
ABNT NBR IEC 60079-11:2013
Certificate: ABNT 17.0001X
Ex ic IIC T4 Gc
Ambient Temperature: –30 to 70 °C
Enclosure: IP66/IP67
Overvoltage category: I
Supply/Output circuit:
FISCO field device and
Ui=32V, Ci=2.2nF, Li=0mH
Sensor circuit:
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50H01-01EN Dec. 18, 2017-00
<<Contents>> <<Index>> 13
Item Description Code
KOSHA [4-20mA & Fieldbus: Flameproof and dust ignition proof approval]
Applicable Standard: Notice of Ministry of Labor No. 2016-54, harmorized with IEC
60079-0:2011, IEC 60079-1:2014, IEC 60079-31:2013
Certificate: 17-AV4BO-0457 (Flameproof)
17-AV4BO-0458 (Dust Ignition Proof)
PF2
Ex d IIC T6/ T5, Ex tD A21 IP66/IP67 T70°C/ T90°C
Ambient Temperature for Gas Atmospheres: –40 to 75°C for T6, –40 to 80°C for T5
Ambient Temperature for Dust Atmospheres: –30 to 65°C for T70°C, –30 to 80°C for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female*1
4-20mA:
[Intrinsically safe approval]
Applicable Standard: Notice of Ministry of Labor No. 2016-54, harmorized with
IEC 60079-0: 2011, IEC 60079-11: 2011
Certificate: 17-AV4BO-0459X
Ex ia IIC T5…T4
Ambient Temperature: –40 to 70 °C for T4, –40 to 50 °C for T5
Enclosure: IP66/IP67
PS2
Supply/Output circuit:
Terminals: +, –
Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit:
Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
Electrical Connection: 1/2 NPT female and M20 female*1
Fieldbus:
[Intrinsically safe approval]
Applicable Standard: Notice of Ministry of Labor No. 2016-54, harmorized
with IEC 60079-0: 2011, IEC 60079-11: 2011
Certificate: 17-AV4BO-0459X
Ex ia IIC T4
Ambient Temperature: –55 to 60°C
Enclosure: IP66/IP67
Supply/Output circuit: PS25
Terminals: +, –
FISCO field device and
Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit:
Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
Electrical Connection: 1/2 NPT female and M20 female*1

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50H01-01EN Jan. 15, 2018-00
<<Contents>> <<Index>> 14
Item Description Code
EAC [4-20mA & Fieldbus: Flameproof and dust ignition proof approval]
Applicable Standard: ГОСТ 31610.0-2014
ГОСТ IEC 60079-1-2013
ГОСТ IEC 60079-31-2013
Certificate: TC RU C-JP.ПБ98.B.00040
GF1*5
1Ex db IIC T6…T5 Gb, Ex tb IIIC T70 °C…T90 °C Db
Ambient Temperature for Gas Atmospheres: –40 to 75°C for T6, –40 to 80°C for T5
Ambient Temperature for Dust Atmospheres: –30 to 65°C for T70°C, –30 to 80°C for T90°C
Enclosure: IP66/IP67
Electrical Connection: 1/2 NPT female and M20 female*1
4-20mA:
[Intrinsically safe approval]
Applicable Standard: ГОСТ 31610.0-2014
ГОСТ 31610.11-2014
Certificate: TC RU C-JP.ПБ98.B.00040
0Ex ia IIC T4…T5 Ga X
Ambient Temperature: –40 to 70 °C for T4, –40 to 50 °C for T5
Enclosure: IP66/IP67
GS1*5
Supply/Output circuit:
Terminals: +, –
Ui=30V, Ii=200mA, Pi=1.0W, Ci=22nF, Li=0mH
Sensor circuit:
Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
Electrical Connection: 1/2 NPT female and M20 female*1
Fieldbus:
[Intrinsically safe approval]
Applicable Standard: ГОСТ 31610.0-2014
ГОСТ 31610.11-2014
Certificate: TC RU C-JP.ПБ98.B.00040
0Ex ia IIC T4 Ga X
Ambient Temperature: –55 to 60°C
Enclosure: IP66/IP67
Supply/Output circuit: GS15*5
Terminals: +, –
FISCO field device and
Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH
Sensor circuit:
Terminals: 1, 2, 3, 4, 5
Uo=6V, Io=90mA, Po=135mW, Co=10μF, Lo=3.9mH
Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A)
Electrical Connection: 1/2 NPT female and M20 female*1
*1: Applicable for Electrical Connection Code 2 and 4.
*2: Applicable for Electrical Connection Code 2.
*3: For Explosionproof approval.
*4: For Intrinsically safe approval/non-incendive approval.
*5: GF1, /GS1 and /GS15 shall be combined with either /VE or /VR.

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50H01-01EN Jan. 15, 2018-00
<<Contents>> <<Index>> 15
 DIMENSIONS
Unit: mm (Approx. inch)
 2-inch horizontal pipe mounting
111(4.37) 65.4(2.57) 66.1(2.60)
Electrical Connection
Electrical Connection 47.1 18.5
(Input signal) Terminal Cover
(Output signal) (1.85) (0.73)
With Indicator
(Optional)

ø93(3.66)
102(4.02)
164(6.46)

Shrouding Bolt Ground Terminal

(1.57)
(For Explosionproof type)

40
Tag Plate

Horizontal Pipe

(0.98)
25
Mounting Bracket
(Optional)

56(2.21) 2-inch pipe


ø60.5(ø2.38)

 2-inch vertical pipe mounting


111(4.37) 65.4(2.57) 66.1(2.60)
Electrical Connection
Electrical Connection (Input signal) 47.1 Terminal Cover
18.5
(Output signal) (1.85) (0.73)
With Indicator
(Optional)

ø93(3.66)
Shrouding Bolt
(For Explosionproof type)
209.5(8.25)
191.5(7.54)

Ground Terminal
Tag Plate
Vertical Pipe
Mounting Bracket
(1.81)

(Optional)
46

2-inch pipe
64(2.52)
ø60.5(ø2.38) 101(3.98)
70(2.76)
98(3.86)
F02E.ai

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50H01-01EN Jan. 15, 2018-00
<<Contents>> <<Index>> 16
 Terminals

Terminal Configuration

Power supply and output terminal


Communication
Terminals External indicator (ammeter) termial *1
Connection hook
Ground terminal
CHECK METER *1 : When using an external indicator or a check meter,
Connection hook *1 the internal resistance must be 10Ω or less.
The hook is not available for Fieldbus
M10×1.5 12-deep female communication type.
for mounting bracket
F03E.ai

 Input Wiring

Single input Dual input


(A) (A1)
1 1 1 (+) 1 (B1)
(+)
2 2 2 2 (B1)
(B)
3 (–)
3 3 (–) 3
(B2)
4 4 4 4 (B2)
5 5 5 (+)
5 (A2)

Thermocouple and RTD and resistance Thermocouple and RTD and resistance
DC voltage (2-wire) DC voltage (3-wire)
(A) (A) (A1)
1 1 1 (+) 1
(B) (A) (B1)
2 2 2 (–) 2
(B) (B)
3 3 3 (B2) 3
(B) (B2)
4 4 4 (B2) 4
(A2)
5 5 5 (A2) 5
RTD and resistance RTD and resistance Thermocouple + RTD and resistance
(3-wire) (4-wire) RTD and resistance (2-wire)
(3-wire)
(A1)
1 (B1)
2 (B1)
3 (–)

4
5 (+)

RTD and resistance


(3-wire)
+ Thermocouple
F04E.ai

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50H01-01EN Jan. 15, 2018-00
<<Contents>> <<Index>> 17
< Ordering Information > 6. Output scale unit
Specify the following when ordering Model, suffix Specify only one unit from the table, ‘Settings when
codes, and optional codes. shipped.’ For sensor input code-2, specify the unit
If not specified, the instrument is shipped with the for two inputs.
settings shown in Table A and B. Specify the following 7. Tag Number
when necessary. Specify Tag number (up to 16 Characters) to be
engraved on the tag plate.
8. Software Tag (PD_TAG)
4-20mA type (HART type) Specify software tag (up to 32 Characters) to be
1. Sensor type. written on the amplifier memory.
For RTD and resistance input, specify the number 9. Node Address
of wire as well. (Example: Pt100 3-wire system) 10. Operation Functional Class
For sensor input code-2, specify the type for two Select ‘BASIC’ or ‘LINK MASTER’.
inputs. In this case, PV (Sensor1 value) and SV 11. Sensor back up
(Sensor2 value) are alternately displayed on the Select ‘DISABLE’ or ‘ENABLE’.
integral indicator with sensor back up DISABLE.
2. Calibration range and unit
1) Calibration range can be specified within the < Factory Setting >
measurement range shown in Table 1. Also, set
the upper limit is larger than the lower limit. Table A. 4-20mA type
2) Specify one range from °C, K, °F or °R for
temperature input. It is not necessary to specify Input sensor type *1 “Pt100” or as specified in order
the unit of mV and ohm inputs, for these units Wire connection “3-wire system” or as specified in
automatically will be mV or Ω. (For RTD) *1 order
3. Tag Number (if required) Calibration range “0 to 100” or as specified in order
Specify Tag number (up to 16 Characters) to be Calibration unit “°C” or as specified in order
engraved on the tag plate. The specified letters (TC and RTD)
are written on Tag (16 Characters) in the amplifier Sensor burnout *2 High (110%, 21.6 mA DC)
memory. Output in Transmitter High (110%, 21.6 mA DC or more)
4. Software tag failure *2
Specified characters (up to 32 characters) are Sensor backup ‘DISABLE’ or as specified
set as “Tag” (the first 8 characters) and “Long
Tag No. “Blank” or as specified in order
tag (32 characters) in the amplifier memory.
Use alphanumeric capital letters. When the *1: For sensor input code-2, sensor 2 is set in
“SOFTWARE TAG” is not specified, “TAG NO” is set nonconnection.
as “Tag” (the first 8 characters) and “Long tag” (32 *2: Except when Optional code C1 or C2 is specified.
characters) in the amplifier memory.
5. Other factory configurations Table B. Fieldbus type
Specifying option code CA will allow further
configuration at factory. Input sensor type *1 “Pt100” or as specified in order
Descriptor (up to 16 characters) Wire connection “3-wire system” or as specified in
6. Sensor back up (For RTD) *1 order
Select ‘DISABLE’ or ‘ENABLE’. Calibration range *1 “0 to 100” or as specified in order
Calibration unit “°C” or as specified in order
Fieldbus type (TC and RTD)
1. Sensor type. Output Scale *1 “0 to 100%”
For RTD and resistance input, specify the number Output mode “Direct”
of wire as well. For sensor input code-2, specify the
Node Address ‘0xF3’ unless otherwise specified in
type for two inputs. (Example: Pt100 3-wire system) (in hexadecimal) order
In this case, AI1 (Sensor1) value and AI2 (Sensor2)
Operation functional ‘BASIC’, or as specified in order
value are alternately displayed on the integral
Class
indicator with sensor back up DISABLE.
2. Calibration range (XD_SCALE) Sensor backup *2 ‘DISABLE’ or as specified in order
For sensor input code-2, specify the range for two Tag Number “Blank” or as specified in order
inputs. (Tag plate)
3. Units of calibration range: Software Tag ‘TT1001’ unless otherwise specified
Specify only one unit from the table, ‘Settings when (PD_TAG) in order.
shipped.’ For sensor input code-2, specify the unit *1: For sensor input code-2, sensor 2 is set in
for two inputs. nonconnection.
4. Output mode (L_TYPE) *2: Channel settings of AI function blocks depend on
Select ‘Direct’ or ‘Indirect .’ sensor backup setting.
5. Output scale (OUT_SCALE) Disable: AI1= Sensor1,
AI2= If Sensor2 type is specified then
For sensor input code-2, specify the scale for two
Sensor2 else Terminal temperature
inputs. Enable: AI1= Backup temperature,
AI2= Terminal temperature

All Rights Reserved. Copyright © 2016, Yokogawa Electric Corporation GS 01C50H01-01EN Mar. 2, 2018-00
Subject to change without notice.