PLC Connection Manual PDF
PLC Connection Manual PDF
Up until now it has been necessary to debug the data by repeatedly disconnecting and reconnecting
the two computer-PLC and V7-PLC cables when the V7 series is directly connected to a PLC
equipped with only one CPU port. With the ladder transfer function, however, it is possible to write
ladder programs or monitor the PLC memory using the V7 series without disconnecting and
reconnecting the cables.
Applicable PLCs
The following PLC models support the ladder transfer function.
Ladder Communication
Manufacturer Select PLC Type CPU
Program
SPB (N mode) and
Fuji Electric Refer to page 8-1. FlexCpu.lcm
FLEX-PC CPU
Matsushita MEWNET Refer to page 15-1. Mewnet.lcm
*1 V706 is available only with DU-01, the optional unit, because both MJ1 and MJ2 are nessesary for this
connection.
Connection
• Use Hakko Electronics’ V6-CP cable when connecting the computer and the V7 series (MJ1/2).
(Use Hakko Electronics’s V6-CP-A cable when using MITSUBISHI ELECTRIC’s A series CPU.)
• When connecting the V7 series (CN1) to the PLC, use a 1 : 1 communication cable as previously
described.
App8-2 Appendix 8 Ladder Transfer Function
1 : 1 communication cable
V6-CP
disc COM1 MJ1 SYSTEM
F1
CN1 CPU port MELSEC
GPPW F2
V7
F3
(V-SFT)
F4
F5
RESET
F6
F7
POWER
It is not possible to transfer both V-SFT screen data and PLC programming software at the same time.
Stop either transfer.
Screen data transfer from the V-SFT editor is carried out via MJ1. The use of MJ1 is recommended if
executing both the ladder transfer function and screen data transfer is necessary. In this case, screen
data transfer via the V6-CP cable is possible through the Main Menu screen displayed on the V7. For
more information, refer to page App8-4.
When the computer is equipped with two COM ports and two V6-CP cables are used:
1 : 1 communication cable
V6-CP
disc
COM1 MJ1 SYSTEM
F1
CN1 CPU port MELSEC
GPPW F2
V7
F3
RESET
(V-SFT) F4
F5
F6
F7
POWER
COM2 MJ2
Computer (PC) V6-CP V7 series PLC
Different COM ports and V6-CP cables are used respectively for transferring the V-SFT editor data and
the PLC programming software. However, it is not possible to transfer both at the same time.
1 : 1 communication cable
V6-CP-A
disc
COM1 MJ1 SYSTEM
CN1 CPU port
GPPW
F1
F2
V7
F3
RESET
(V-SFT) F4
F5
F6
F7
MJ2
POWER
Setting
3. Environment setting
Click [System Setting] → [Extended Communication] → [Ladder Tool].
The [Ladder communication is not used in Local mode.] option is relevant to the operation that will
take place while the Main Menu screen is displayed.
- Unchecked: Transferring the V-SFT data or the PLC programming software is possible.
Choose either transfer using the F2 switch.
- Checked: Transferring only the V-SFT data is possible. Transferring the PLC programming
software is disabled.
App8-4 Appendix 8 Ladder Transfer Function
Different V7 operations depending on item settings (“2” and “3” in the previous
section)
Depending on which items are selected in the [Modular Jack] dialog and the [Ladder Tool Setting]
dialog, operations possible on the V7 (communication with the computer enabled/disabled) are
determined.
S S
Y
S
Y
S Main Menu V710iTD 2002-4 -1 07:23:30
T T
E E
M M
System Information FONT I/F DRV VER.1.240
M M
O O SYSTEM PROG. VER. 1.000 VER.1.300 / 1.000 / 1.000 MELSEC QnH Q
D D
E E ENGLISH CPU Port
BR BR
Screen Data PLC Type : MITSUBISHIQnH(Q) series CPU Error : Stop
Information Comment : Time-Out : 1.00 sec
BR BR
Size : 5783552 Retry : 3
“Editor:---” appears, indicating the ladder transfer mode, in the lower left corner of the screen.
At this time, screen data transfer via MJ1 is not possible as shown below.
Use the F2 switch to switch between “Editor:---” and “Editor:MJ1” displayed on the screen.
Hold down the switch for 3 seconds or more.
Main Menu V710iTD 2002-4 -1 07:23:30 Main Menu V710iTD 2002-4 -1 07:23:30
Screen Data PLC Type : MITSUBISHIQnH(Q) series CPU Error : Stop Screen Data PLC Type : MITSUBISHIQnH(Q) series CPU Error : Stop
Information Comment : Time-Out : 1.00 sec Information Comment : Time-Out : 1.00 sec
Size : 5783552 Retry : 3 Size : 5783552 Retry : 3
Connection : 1:1 Baud Rate :19200 Connection : 1:1 Baud Rate :19200
Signal Level : RS232C Data Length : 8 Signal Level : RS232C Data Length : 8
PLC Stat. No. : 0 Stop Bit : 1 PLC Stat. No. : 0 Stop Bit : 1
Parity : Odd Parity : Odd
Send Delay : 0msec Send Delay : 0msec
* Since V609E is not equipped with function switches, switching between “Editor:---” and
“Editor:MJ1” on the Main Menu screen is not possible. Therefore, check [Ladder communication is
not used in Local mode.].
At this time, check the system program version and update it if the version is old before
transferring the screen data. (adapted to V-SFT editor version 2.0.9.0 or later, V7 system program
version 1.080 or later, and V6 system program version 1.570 or later)
• On-line editing between the V-SFT editor and the V7 series is not possible. If attempted,
communications between the PLC programming software and the PLC will not be performed
correctly.
• Communicating statuses with the PLC programming software and the PLC during communications
between the V-SFT editor and the V7 series