Lab Manual Exp 1 - Gas Pressure Process Control
Lab Manual Exp 1 - Gas Pressure Process Control
LABORATORY: SECTION of 1
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT:GAS PRESSURE 2014
PROCESS CONTROL AMENDMENT
DATE:
COURSE CODE
EXPERIMENT NO. EXPERIMENT 4
INTRODUCTION: /5%
PROCEDURE: /5%
RESULTS& CALCULATIONS /15%
ANALYSIS /15%
DISTRIBUTION OF MARKS FOR DISCUSSIONS: /20%
LABORATORY REPORT: ADDITIONAL QUESTIONS /15%
CONCLUSION /10%
SUGGESTIONS& RECOMENDATIONS /5%
REFERENCES: /5%
TOTAL: /100%
I hereby declare that I have prepared this report with my own efforts. I also admit to
not accept or provide any assistance in preparing this report and anything
that is in it is true.
3.0 INTRODUCTION
Pressure vessels play an important role in chemical industries as storage
vessels for gas phase components, reaction vessels to carry out a gas phase
reaction, etc. Precise control of pressure in the pressure vessels is necessary in
order to:
(i) Maintain a constant concentration of components in the vessel,
(ii) Maintain the number of moles in the vessel, and
(iii) Protect the vessel from being damaged due to very high pressures.
13) From the process air supply, trace the two pipe lines PLI and PLII
as follows: Pipeline PLI: Single capacity process:
AR91-MV91-T91-PLI-B92- FI92 -P CV9 1 –VP
Two-capacity process
AR9 1 -MV9 1 -T91 -PLI-MVI-T92-MV92-FI92 -PCV 9 1 –VP
Pipeline II (PLII):
AR9 1 -MV9 1 -T91-PLII-MVII-PCV92-MV92A/MV92B-V
14) Open fully the pipelines PLI (Single capacity process) and PLII at
their various manual valves.
15) Make sure the manual by-pass valve B92 around vessel T92 is
opened and the manual valves at the inlet MVI and outlet MV92 of
T92 are shut.
16) The pipeline PLII has two discharge manual valves, MV92A (globe
valve) and MV92B (gate valve). SHUT both the valves MV92A and
MV92B.
17) Check and adjust the pressure at AR91 is approximately at the
pressure indicated at AR91. Check MV91 is fully shut.
18) Slowly open MV91 and regulate it until the flow rate at the variable
area flow meter FI92 reads 35 Nm3/Hr
19) Check the pressure and flow rate setting:
a. Shut fully PCV91 from PIC91 in manual (M) mode with
MV=106.3%. Read the pressure at vessel T91 at the PV
reading of PIC91. If the pressure is about 22 – 27 psig, the
pressure is correctly set.
b. Open fully PCV91 from PIC91 in manual (M) mode with
MV=-6.3%. Read the pressure at vessel T91 at the PV
reading of PIC91. If the pressure is below 10 psig and the
flow rate at FI92 also reads 35 Nm3/Hr, the air flow rate is
correctly set.
c. Now the process air supply pressure and flow rate are set.
DO NOT readjust AR91 and MV91 hereafter.
CAMPUS : UniKL MICET EDITION: 1
LABORATORY: SECTION of 1
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT:GAS PRESSURE 2014
PROCESS CONTROL AMENDMENT
DATE:
5.2 ON/OFF PRESSURE CONTROL
It uses the ON/OFF pressure controller PIC92 to control at the High
pressure limit of PIC91.
1) Make sure that you have gone through the START-UP
procedures very carefully.
2) Start the chart drive of the recorder by pressing the `RCD'
pushbutton at the front of the recorder.
3) Shut fully PCV91 from PIC91 in manual (M) mode with
MV=106.3%. Read PV at PIC91, the pressure at vessel T91. The
pressure should be in the range of 22-27 psig.
4) Note the response of PT91 at the recorder PR91.
PCV92 opens when PT91 exceeds 21 psig and closes when PT91
drops below a fixed Dead Band (0.5 psig), i.e., 20.5 psig.
5) Try to repeat the ON/OFF action by opening and closing
PCV 91. This is done from PIC91 in manual (M) mode by
reducing the MV such that pressure PV drops below 20 psig.
Then shut PCV91 fully again with MV = 106.3%.
9) Transfer the controller to Auto (A) mode and wait for the
response to become almost stable.
CAMPUS : UniKL MICET EDITION: 1
LABORATORY: SECTION of 1
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT:GAS PRESSURE 2014
PROCESS CONTROL AMENDMENT
DATE:
10) Switch PIC91 to Manual (M) mode, decrease MV about 10%,
switch back to Auto (A) mode and observe the response for a
few minutes.
DO NOT FORGET TO MARK THE PID VALUES AND THE
SETPOINT ON THE CHART PAPER WHENEVER THE
VALUES ARE CHANGED. ALSO MARK ON THE CHART THE
BEGINNING OF EACH PART OF THE EXPERIMENT
11) If the response is slow to return to the set point SV = 15 psig,
reduce TI1 to 20 secs. and repeat the step (10) again.
12) Now set the PID controller with the second (II) trial values:
PB1 = 45%, TI1 = 30 secs, TD1 = 0 sec.
1) Make sure that pipelines PLI and PLII are opened throughout.
4) For two- capacity operation, vessels T91 and T92 are used.
• Shut the by-pass valve B92 around T92
• Open the manual valves at the inlet, MVI, and at the
outlet, MV92, of T92.
• Make sure the air flow path T91-PLI-T92-F192-PCV91-VP is
opened through MVI and MV92.
5) Switch P1C91 to Manual (M) mode.
6) Open PCV9I about 50% from PIC91 with MV = 50%.
7) Set the set point of P1C91 as SV = 18 psig.
8) Set the PID controller with the first (I) trial values:
PB1 = 70%, TI1 = 40 secs, TD1 = 0 sec.
9) Transfer the controller to Auto (A) mode and wait for the response
to become almost steady or continues to oscillate even after 3
cycles.
CAMPUS : UniKL MICET EDITION: 1
LABORATORY: SECTION of 1
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT:GAS PRESSURE 2014
PROCESS CONTROL AMENDMENT
DATE:
10) Switch PIC91 to Manual (M) mode, decrease its MV by about
10%, switch back to Auto (A) mode and observe the response till
it becomes almost steady or continues to oscillate even after 3
cycles.
DO NOT FORGET TO MARK THE PID VALUES AND THE
SETPOINT ON THE CHART PAPER WHENEVER THE VALUES
ARE CHANGED. ALSO MARK ON THE CHART THE BEGINNING
OF EACH PART OF THE EXPERIMENT.
12) Now set the PID controller with the second (II) trial values:
16) Try the third (III) trial values for the PID controller:
PB1 = 20%, TI1 = 30 secs, TD1 = 2 sec.
19) STOP the chart drive and retrieve the relevant portions of the
chart paper. Attach the chart paper along with the result
CAMPUS : UniKL MICET EDITION: 1
LABORATORY: SECTION of 1
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT:GAS PRESSURE 2014
PROCESS CONTROL AMENDMENT
DATE:
6.0 SHUTDOWN PROCEDURE
1. Switch the controller PIC91 to Manual(M) mode, and set the MV=100%
2. Stop Recording by push the recorder “RCD” button
3. Switch Off the main power supply
9.0 DISCUSSIONS
10.0 CONCLUSION
Conclusion is merely a summary of the important findings already reported in
the discussion section. It also relates to the objectives stated earlier.
CAMPUS : UniKL MICET EDITION: 1
LABORATORY: SECTION of 1
REVISION NO:
PROCESS TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT:GAS PRESSURE 2014
PROCESS CONTROL AMENDMENT
DATE:
11.0 SUGGESTIONS & RECOMMENDATIONS
Your ideas of suggestion & recommendation to improve the learning process for
this experiment or anything related to the experimental procedure etc.
12.0 REFERENCES
Minimum of at least 5 references (with 3 of them are paper/book/chapter(base)
CAMPUS : UniKL MICET EDITION: 1
LABORATORY: SECTION of 1
PROCESS CHEMICAL REVISION NO:
TECHNOLOGY
29 SEPT
EFFECTIVE DATE:
EXPERIMENT: LIQUID FLOW 2014
PROCESS CONTROL AMENDMENT
DATE: