P499VBS 401C
P499VBS 401C
P499VBS 401C
Product/Technical Bulletin
Code No. LIT-12011190
Part No. 24-7664-2659, Rev. —
Issued December 11, 2006
FIG:P499dimen
P499 Electronic Pressure Transducers provide several
output options:
Red Wire = SUPPLY
5/16
• 0.5 to 4.5 VDC ratiometric Black Wire = COMMON Maximum
White Wire = OUTPUT (8)
• 0 to 10 VDC
• 4 to 20 mA
o
Insert 1/4 in. SAE 45 Flare Internal Thread
Pressure connections are available in two standard Plug (7/16-20 UNF) with Depressor (Style 47)
styles:
Product Code Number1 Length 3. Perform a leak test on fittings and connections
before putting the system into operation.
WHA-PKD3-200C 6-1/2 ft (2.0 m)
WHA-PKD3-400C 13 ft (4.0 m) Wiring
WHA-PKD3-600C 19-5/8 ft (6.0 m) CAUTION: Risk of Electric Shock.
Disconnect power supply before making
1. Wire harnesses for P399 transducers and
P499 transducers are interchangeable. ! electrical connections to avoid electrical
shock.
Mounting Follow the wiring guidelines given to avoid causing
The P499 transducer mounts directly to most damage to the transducer and improper equipment
refrigeration equipment pressure tap ports. operation:
CAUTION: Risk of Property Damage. • Ensure wiring conforms to the National Electrical
Mount the pressure control separately Code and local regulations.
! from the electrical cabinet and seal all • Do not apply more than the maximum supply
electrical piping to prevent ammonia from voltage to the transducer. See Technical
migrating to the electrical components. Specifications .
Where there may be exposure to
ammonia, use only ammonia compatible • Do not extend the wiring harness leads more than
control modules and pressure 250 ft (76 m). Use 22 AWG, 3-wire, shielded cable
connections. System shutdown due to to extend wiring harness leads.
improper adjustment may cause property • Do not run low-voltage cable in conduit or wiring
damage. troughs with high-voltage wires.
IMPORTANT: When installing the • Ensure that the shielded cable is terminated
P499 transducers, observe all regulations governing according to code and the control’s instruction
the handling and containment of hazardous or sheets.
regulated materials (refrigerants or lubricants). Checkout
IMPORTANT: Locate pressure tap points on the IMPORTANT: The P499 transducer is a precision
top side of the refrigerant lines to reduce risk of sensing device and testing accuracy is typically
equipment damage or malfunction caused by beyond the capability of field diagnostic tools.
accumulation of oil, liquids, or sediment in the
pressure chamber. Before applying power, check all wiring connections.
After applying power, operate controlled equipment
under normal conditions and use a reliable set of
pressure gauges to verify that the transducer and the
associated control are operating properly.
FIG:idl_10V
pressure. The output voltage varies from 10% to 90%
Vo= Ideal Output Voltage
of the supply voltage, providing a 0.5 to 4.5 VDC
P = Measured Pressure
(nominal) signal. Px = Full Range Pressure of Sensor
To verify that the transducer is working properly: Figure 4: Ideal Voltage Calculation for
1. With the transducer in place and the controlled 0 to 10 VDC Transducers
system pressure stabilized, measure the pressure
at the transducer with an accurate and reliable
3. Measure the voltage between the transducer
gauge. Use this in Step 3 as the measured
OUTPUT (white wire) and COMMON (black wire)
pressure, P.
with a multimeter set to measure DC voltage. This
2. Measure the voltage between SUPPLY (red wire) is the measured output voltage.
and COMMON (black wire). Use this in Step 3 as
the measured supply voltage, Vs. 4. Compare the ideal output voltage (Step 2) and the
measured output voltage (Step 3). If the measured
3. Use the equation in Figure 3 to calculate the ideal output voltage differs greatly from the ideal output
output voltage for the ratiometric transducers. voltage, replace the transducer.
Note: It is normal for the transducer reading to differ
Vo = Vs [0.1 + 0.8 ( P )] VDC somewhat from pressure gauge readings due to
voltmeter and gauge tolerances, and other factors.
Vo= Ideal Output Voltage
Vs= Measured Supply Voltage 4 to 20 mA Versions
FIG:idl_rtmtrc
P = Measured Pressure
Px = Full Range Pressure of Sensor To verify that the transducer is working properly:
1. With the transducer in place and the controlled
Figure 3: Ideal Voltage Calculation for
system pressure stabilized, measure the pressure
0.5 to 4.5 VDC Ratiometric Transducers
at the transducer with an accurate and reliable
gauge. Use this in Step 2 as the measured
4. Measure the voltage between the transducer pressure, P.
OUTPUT (white wire) and COMMON (black wire) 2. Use the equation in Figure 5 to calculate the ideal
with a multimeter set to measure DC voltage. This output current for the 4 to 20 mA transducers.
is the measured output voltage.
5. Compare the ideal output voltage (Step 3) and the I = 4 + 16 ( P ) mA
FIG:idl_mA
P499
Electrical Connection
A AMP (compatible with 174357-2 and 174358-7 connectors)
C Cable - Unshielded
H Hirschmann Form C with mating cable socket (DIN43650)
J Hirschmann Form A without mating cable socket (DIN43650)
P Packard
S Cable - Shielded
Pressure Connection
A 1/8”-27 NPT External Thread (Style 49)
B 1/4” SAE 45o Flare External Thread
o
C 1/4” SAE 45 Flare Internal Thread (7/16-20 UNF) with Depressor (Style 47)
D 1/4”-18 NPT External Thread
FIG:ordr_mtrx
Table 4: Standard 0 to 10 VDC P499 Transducer Models with Packard Electrical Connections
Product Code Pressure Fitting Pressure Range1 Individual or Kit2
Number
P499VAP-101C 1/8”-27 NPT External Thread (Style 49) 0 to 100 psi Individual
(0 to 6.9 bar)
P499VAP-101K Kit
P499VAP-105C 0 to 500 psi Individual
(0 to 34.5 bar)
P499VAP-105K Kit
P499VAP-107C 0 to 750 psi Individual
(0 to 51.7 bar)
P499VAP-107K Kit
P499VCP-101C 1/4 in. SAE 45° Flare Internal Thread 0 to 100 psi Individual
(7/16-20 UNF) with Depressor (Style 47) (0 to 6.9 bar)
P499VCP-101K Kit
P499VCP-105C 0 to 500 psi Individual
(0 to 34.5 bar)
P499VCP-105K Kit
P499VCP-107C 0 to 750 psi Individual
(0 to 51.7 bar)
P499VCP-107K Kit
Controls Group .
507 E. Michigan Street All marks herein are the marks of their respective owners.
Milwaukee, WI 53202 © 2006 Johnson Controls, Inc.