Aeg Protect - Rcs Rec
Aeg Protect - Rcs Rec
>>
PERFECT IN FORM AND FUNCTION
Power Safety
Protect RCS Key Features
Protect RCS – key features The rectifiers are built as independent modules, optional equip-
ment like distribution boards, diode droppers etc. are installed in
• Standard system configurations - cost effective, short lead separate cubicle sections.
time solutions
• Customized systems - enhance the standard system by The cabinets are floor mounted and can be designed to meet
selecting from an extensive range of options special requirements. The batteries are mounted on free-standing
• All systems built with advanced GCAU - Generic Control and racks or in cabinets together with or separated from the rectifier.
Alarm Unit
• Communications system used to monitor and control the ‘’GCAU’’ control card
defined parameters locally or remotely. The main control card GCAU (Generic Control and Alarm Unit)
• Choice of several types of batteries: performs measurements, control charge process and provides a
䡩 Nickel-cadmium – vented or gas recombination wide range of alarm and monitoring options. The same card is
䡩 Lead acid – vented or gas recombination used in the single (SPRe) and the three phase (TPRe) systems.
• Advance Battery Management
• Parallel operation The GCAU card uses a fully digital control algorithm and incor-
• Simplified maintenance porates two micro controllers, using the latest micro controller
• High MTBF and low MTTR technology to ensure a high degree of safety and reliability.
䡩 Bespoke documentation; drawings, manuals The tasks of these micro controllers are:
䡩 Total solutions – including switchgear, load distribution 䡩 Process communication and monitoring
• International Service support – comprehensive 䡩 Regulation and synchronization
packages including;
• Product Services: Installation, Commissioning, Service
Contracts... Applications
• Site Services: Load testing, monitoring …
Designed to provide secure DC power for all Industrial applica-
tions; for Oil & Gas and Petrochemical Plants, Power Stations
Protect RCS Industrial rectifiers, and Substations, Water Treatment Plants, Manufacturing Plants,
Chargers & DC Systems Airports, Railways, etc
The Protect RCS DC System has been developed and designed • Navigational Aids
to provide high reliability power supply and battery charging • Emergency Lighting
capability. • Fire & Gas Detection Systems
• Fire Fighting
The Protect RCS DC System is a thyristor-controlled rectifier • Emergency Shutdown Systems
suitable for charging nickel-cadmium or lead-acid batteries while • Radio & Telecommunications
supplying DC loads. It can also be used without batteries as direct • Signaling
power supplies. • Telemetry
• Instrumentation & Process Control
The range of DC Systems is available in the three levels: • Gas Turbine Control
• Switchgear Tripping
• The first level consists of the Standard Rectifier with a compact • Motor Starting
set of alarms. • Lube-oil pump supply
• The second level offers a set of Basic Options, extensive func- • Power Generation, Transmission and Distribution
tions and alarms.
• The third level offers a full set of Extended Options, extensive
functions and alarms allowing customization of the systems to
comply with special customer requirements.
System display Monitoring software
An extensive human interface ensures that all the important The WINSPARC and WINSITE software (WINDOWS based) are the
parameters are accessible from the front panel. A large 16 applications designed for the local and remote supervision of the
characters by 2 lines LCD unit displays all the relative information control GCAU card in order to monitor and to configure the systems.
to the user. A three push button keyboard is used with 2 LEDs The software function allows visualizing on a PC screen system
(green and red) indicating the charger state. data such as alarms, measurements, modes, and history. The
The Display card is mounted on the front of the system and is remote commands can be sent to the system.
controlled by the GCAU card. It is a plug-in device and is connected The available types of communication are:
through two RJ 4-4 connectors with a 4-wire cable. All data and 䡩 Locally (via PC port COMx – RS232/RS485)
necessary power supply voltages are transferred over this cable. 䡩 Remotely (via Modem or Ethernet Network TCP/IP )
Batteries
AEG Power Solutions has considerable in-house knowledge in
battery technology and is able to offer expert advice on the
specifying, selection, operation and testing of batteries.
Our total system solutions include a wide range of products
using lead acid and nickel-cadmium batteries in vented and gas
recombination technologies. Batteries can be supplied on racks
or inside cabinets which match the chargers and can be mecha-
nically coupled to the charger cabinet if necessary.
Replacement batteries can be supplied and installed by our
Global Service Team.
Protect RCS: Standard System
Protect RCS
Protect RCS
INPUT
Protect RCS Single phase (SPRe) Single phase 230 Vac ± 10 % (220 V, 240 V)
Protect RCS Three Phase (TPRe) Three phase 400 Vac ± 10 % (380 V, 415 V)
Other voltages available as option
Exceptional variations + 15 / -20 % (functional)
Frequency 50 Hz or 60 Hz ± 6 %
OUTPUT
Nominal voltage (Udc) 24 V 48 V 110 V 220 V (Other voltages available as non-standard option)
Range of operating voltage Floating charge 75 % to 125 % of Udc Nominal
High rate charge 75 % to 135 % of Udc Nominal
Commissioning charge 75 % to 140 % of Udc Nominal
Static voltage regulation ± 0.5 % under the following conditions:
• at float charge
• 0-100 % DC load variation
• input voltage ± 10 %
• input frequency ± 6 %
• temperature from 0°C to 40°C
Dynamic voltage regulation Using standard filter and the battery connected
(capacity higher than 5 times I nom)
Load step Deviation
10-90 % –5 %
90 %-10 % +5 %
Current regulation 0–2 % of current limit
Long-term stability of UDC 0.15 % for 1000 hours
Temperature coefficient of UDC 0.18 % per °C
Charging characteristic Constant current / constant voltage (I/U as per IEC 478–1) during float charge
Input/Output isolation 2500 VAC between input/output and electrical earth
Insulation resistance > 200 M , 500 VDC
Ripple Max 2 % rms of nom. DC voltage, with a battery Ah capacity
of 5 times the charger nom rating, battery connected (see our filter options).
2.5 % rms typical (max 5 %) on rectifier output, battery not connected.
PROTECTION
• Polarity reversal of battery (blows battery fuse, optional)
• Soft-start function 0 to 100 %
• Short-circuits
• Limited to 100 % of rated current
• Internal DC fuse
• Non-volatile storage of system parameters and user setting
• Mains failure shutdown
• Rectifier failure shutdown
• High-voltage DC shutdown
• Thermal protection
EMC emissions Generic emission standards IEC/EN 61000-6-4 and generic immunity standards
IEC/EN 61000-6-2 available as standard option.
Safety According to IEC/EN 62040-1-2 standard
ENVIRONMENTAL
Ambient temperature Operating: 0°C to + 40°C
Derate from 40°C to 55°C by lowering the output current by 1.25% per °C.
Storage: -25°C to +70°C
Relative humidity Operation: from 20 % to 95 % non condensing.
Storage: from 15 % to 90 % (in original packaging).
Acoustic noise Typical 45-65 dB(A)
Altitude Up to 1000m, derate from 1000 to 4000m by lowering
the output current by 7 % per 1000 m.
Tropicalisation Suitable for ambient temperature and relative humidity specified above
and for ambient air free from dust and corrosive gases.
Protect RCS: Technical Data
Protect RCS – Single Phase Range (including systems with Basic Options)
Nominal Nominal Standard Systems & Basic Options Weight 2
DC output DC output Dimensions1 (approx)
Rectifier Voltage Current
Type V A Height (mm) Width (mm) Depth (mm) KG
24SPRe10 24 10 1200 600 821 85
24SPRe15 24 15 1200 600 821 95
24SPRe25 24 25 1200 600 821 105
24SPRe50 24 50 1200 600 821 160
24SPRe75 24 75 1200 600 821 180
24SPRe100 24 100 1200 600 821 195
48SPRe10 48 10 1200 600 821 95
48SPRe15 48 15 1200 600 821 100
48SPRe25 48 25 1200 600 821 145
48SPRe50 48 50 1200 600 821 200
48SPRe75 48 75 1600 600 821 295
110SPRe10 110 10 1200 600 821 110
110SPRe15 110 15 1200 600 821 145
110SPRe25 110 25 1200 600 821 190
110SPRe50 110 50 1200 600 821 345
Protect RCS – Three Phase Range (including systems with Basic Options)
24TPRe25 24 25 1200 600 821 145
24TPRe50 24 50 1200 600 821 185
24TPRe75 24 75 1200 600 821 250
24TPRe100 24 100 1200 600 821 285
24TPRe150 24 150 1600 600 821 305
24TPRe200 24 200 1600 600 821 345
24TPRe300 24 300 2000 600 821 * (4)
24TPRe400 24 400 2000 821
(2065 max)3 900 * (4)
24TPRe500 24 500 2000 821
(2065 max)3 900 * (4)
48TPRe25 48 25 1200 600 821 190
48TPRe50 48 50 1200 600 821 215
48TPRe75 48 75 1600 600 821 315
48TPRe100 48 100 1600 600 821 340
48TPRe150 48 150 1600 600 821 495
48TPRe200 48 200 1600 600 821 515
48TPRe300 48 300 2000 600 821 * (4)
48TPRe400 48 400 2000 821
(2065 max)3 900 * (4)
48TPRe500 48 500 2000 821
(2065 max)3 900 * (4)
110TPRe25 110 25 1200 600 821 215
110TPRe50 110 50 1600 600 821 365
110TPRe75 110 75 1600 600 821 495
110TPRe100 110 100 1600 600 821 520
110TPRe150 110 150 1600 600 821 585
110TPRe200 110 200 2000 821 770
(2065 max)3 900
110TPRe300 110 300 2000 821
(2065 max)3 900 * (4)
110TPRe400 110 400 2000 821 * (4)
(2065 max)3 900
110TPRe500 110 500 2080 1200 821 * (4)
1. Dimensions may vary for systems with Extended Options. 2. Weights may vary depending on selection of Basic Options and Extended Options. 3. Cabinet with additional fan cooling – top cover 65mm Height.
4. Weights on request. Please consult AEG Power Solutions for alternative systems.
Protect RCS: Technical Data
Protect RCS
Protect RCS – Single Phase Range (including systems with Basic Options)
Nominal Nominal Standard Systems + Basic Options Weight 2
DC output DC output Dimmensions 1 (approx)
Rectifer Voltage Current
Type V A Height (mm) Width (mm) Depth (mm) KG
220TPRe25 220 25 1600 600 821 250
220TPRe50 220 50 1600 600 821 390
220TPRe75 220 75 1600 600 821 550
220TPRe100 220 100 2000 900 821 570
220TPRe150 220 150 2000 900 821 620
220TPRe200 220 200 2000 900 821 830
220TPRe300 220 300 2000 900 821 * (4)
220TPRe400 220 400 2080 1200 821 * (4)
220TPRe500 220 500 2080 1200 821 * (4)
1. Dimensions may vary for systems with Extended Options. 2. Weights may vary depending on selection of Basic Options and Extended Options. 3. Cabinet with additional fan cooling – top cover 65mm Height.
4. Weights on request. Please consult AEG Power Solutions for alternative systems.
Advanced power supplies require advanced technical service and Product Services
support. Our customers know that they can count on AEG Refurbishment
Power Solutions specialists to deliver the right service and Consulting
support rapidly and efficiently. Load Bank & Capacity Testing
Installation & Commissioning
Transport Facility & equipment Management
Recycling Delivery Battery Monitoring
Installation
Spare Parts
Battery Replacement
Service In-house/Express Repair
Repair Training
Remote Monitoring
Power Quality Services
Equipment
Battery Customer start-up
Service Contracts - 24/7 Global Service Coverage
Service Maintenance/
service contracts service Corrective Maintenance
Design & Build - Turnkey Solutions