Introduction To Powe Sysytem Analysis
Introduction To Powe Sysytem Analysis
UNIT I INTRODUCTION
Need for system planning and operational studies – basic components of a power
system.-Introduction to restructuring - Single line diagram – per phase and per unit
analysis – Generator - transformer – transmission line and load representation for
different power system studies.- Primitive network - construction of Y-bus using inspection
and singular transformation methods – z-bus.
Rotational Load:
Reactance diagram:
Static Loads are neglected.
Rotational Load:
[
Z BUS= Z 21 Z 22 Z 23
Z 31 Z 32 Z 33 ]
Z11 , Z 22 , Z 33=Diagonal Elements
Z12 , Z 13 , Z21 , Z 23 , Z31 , Z 32=Off −Diagonal Elements
The diagonal elements of bus impedance matrix are called driving point impedances of the
buses and off diagonal elements of bus impedance matrix are called transfer impedances of
the buses.
7. What is meant by percentage reactance? (MAY JUN
2013)
The reactances of generators, transformers and reactors are generally expressed in
percentage values to permit quick short circuit calculation.
Percentage reactance is defined as:
IX
% X= × 100
V
Where,
I = Full load current
V = Phase Voltage
X = Reactance in ohms per phase
Alternatively it can also be expressed in terms of KVA and KV
KVA
% X= X . 2
10 ( KV )
8. Draw the equivalent circuit of a 3 winding transformer. (NOV DEC 2012)
(MAY JUN 2013)
E=V + IZ
Z-steady state impedance
13. What are the advantages of per unit system? (APR
MAY 2011)
Per unit data representation yields valuable relative magnitude information.
Circuit analysis of systems containing transformers of various transformation ratios is
greatly simplified.
The p.u systems are ideal for the computerized analysis and simulation of complex
power system problems.
Manufacturers usually specify the impedance values of equivalent in per unit of the
equipment’s rating. If the any data is not available, it is easier to assume it’s per unit
value than its numerical value.
SIXTEEN MARKS
1. Using the method of bus building algorithm find the bus impedance matrix for the network
shown in fig.
(APR MAY
2015)
2. Draw the structure of an electrical power system and describe the components of the system
with typical values.
(APR MAY 2011)(NOV DEC
2014)
3. Obtain the per unit impedance diagram of the power system of fig shown below :
5. The single line diagram of a power system is shown in figure along with components data.
Determine the new per unit values and draw the reactance diagram. Assume 25 MVA, and
20KV as new base on generator G1 (MAY JUN 2014)
6. Describe the Zbus building algorithms in detail by using a three bus system. (MAY
JUN 2014)
7. A 90 MVA 11 KV 3 phase generator has a reactance of 25%. The generator supplies two
motors through transformer and transmission line as shown in figure. The transformer T1 is a
3 – phase transformer, 100 MVA, 10/132 KV, 6% reactance. The transformer T2 is composed
of 3 single phase units each rated, 300 MVA, 66110KV, with 5% reactance. The connection of
T1 & T2 are shown. The motors are rated at 50 MVA 10 KV and 20 % reactance. Taking the
generator rating as base, draw reactance diagram and indicate the reactance in per unit. The
reactance of line is 100 ohms.
(NOV DEC 2013)
8. Determine Ybus for the 3 - bus system shown in figure. Neglect the shunt capacitance of the
lines.(NOV DEC 2013)
9. For the system shown in figure, determine the generator voltage. Take a base of 100 MVA
and 210 KV in the transmission line.
11. Draw the reactance diagram using a base of 100 MVA, 220 KV in 50 ohm line.
Draw the network and find bus admittance matrix. (NOV DEC
2011)
14. Determine the Z bus for the system whose reactance diagram is shown in the Fig. where
the impedance is given in p.u
(NOV DEC 2011)
15. Explain the modeling of generator, load, transmission line and transformer for power flow,
short circuit and stability studies. (NOV DEC
2008) (NOV DEC 2012, 2007 reg)
UNIT II POWER FLOW ANALYSIS
Importance of power flow analysis in planning and operation of power systems -
statement of power flow problem - classification of buses - development of power flow
model in complex variables form - iterative solution using Gauss-Seidel method - Q-limit
check for voltage controlled buses – power flow model in polar form - iterative solution
using Newton-Raphson method.
TWO MARKS
1. Compare Gauss Seidal and Newton Raphson methods. (MAY JUN 2012)
(APR MAY 2015)
S.N Factor Gauss Seidal Newton Raphson
o
11. What are the different types of buses in a power system? What are the quantities
specified in each bus?
(NOV DEC 2011)
Types of bus Known Unknown
quantities quantities
Load or PQ bus P, Q V, δ
SIXTEEN MARKS
1. Fig shows the one line diagram of a simple three bus power system with generation at
buses 1 and 2. The voltage at bus 1 is V=1+j0.0 V per unit. Voltage magnitude at bus 2 is
fixed at 1.05 p.u with a real power generation of 400 MW. A load consisting of 500 MW and
400 MVAR is taken from bus 3. Line admittances are marked in per unit on a 100 MVA
base. For the hand calculation, line resistances and line charging succeptance are
neglected.
Using Newton-Raphson method, start with the initial estimates of
V 2 =1.05+ j0.0∧V 3 =1.05+ j 0.0 , and keeping|V 2|=1.05 pu, determine the phasor values V2
(0 ) (0 )
4. With a neat flow chart, explain the computational procedure for load flow solution using
Newton Raphson iterative method when the system contains all types of buses.
(NOV DEC 2010) (MAY JUN 2012) (APR MAY 2004) (APR MAY 2005) (NOV DEC
2004) (MAY JUNE 2013) (MAY JUN 2014) (NOV DEC 2014)
5. Describe the step by step procedure for load flow solution from GaussSeidal method, if PV
and PQ buses are present along with slack bus
(MAY JUNE 2014)
6. A three bus power system is shown in figure. The relevant per unit line admittance on
100MVA base are indicated on the diagram and bus data are given in table. Form Ybus and
determine the voltages at bus 2 and bus 3 after first iteration using Gauss Seidal method.
Take theacceleration factor a = 1.6 (NOV DEC 2013)
1 Slack 0 0 1.02 0
2 PQ 25 15 50 25
3 PV 0 0 60 30
1 Slack 0 0 1.02 0
2 PQ 25 15 50 25
3 PV 0 0 60 30
Assume that the bus 2 can supply any amount of reactive power. With aflat start, perform
the first iteration of power flow analysis using Newton-Raphson method.
(MAY JUNE 2013)
8. Derive load flow algorithm using Gauss – Seidal method with flow chart and discuss the
disadvantages of the method (NOV DEC 2009) (APR MAY 2011)
(MAY JUNE 2006) (MAY JUNE 2013)
9. The one line diagram of three bus power system is shown in given figure.
Bus 1: Slack bus, Especified = 1.05 ∠0
Bus 2: PV bus, Especified = 1.2 p.u, PG = 3 p.u
Bus 3: PQ bus, PL = 4 p.u, QL = 2 p.u.
Carry out one iteration of load flow solution by Gauss-Seidel method. Take Q limits of
generator 2 as 0 ≤ Q ≤ 4.
(NOV DEC 2012)(NOV DEC
2011)
10. With a neat flow chart explain the computational procedure for load flow solution
using fast decoupled method when the system contains all types of buses.
(NOV DEC 2010) (APR MAY 2011) (NOV DEC 2011) (MAY JUN 2011)
(NOV DEC 2011)
III FAULT ANALYSIS – BALANCED FAULTS
TWO MARKS
1. What for short circuit capacity (SCC) should be known at any bus. Write down the
expression for SCC.
(APR MAY 2015)
What is meant by fault level? (MAY
JUN 2013)
Define short circuit capacity. (MAY
JUN 2009)
Short circuit capacity or short circuit MVA or fault level at a bus is defined as the product of
the magnitude of the prefault bus voltage and the post fault current.
SCC=|V TH||I F|
2. What is the need for short circuit studies or fault analysis?
(NOV DEC 2011) (NOV DEC 2012) (NOV
DEC 2014)
Short circuit studies are essential in order to design or develop the protective schemes for
various parts of the system.To estimate the magnitude of fault current for the proper choice
of circuit breaker and protective relays.
3. What is symmetrical fault? (NOV DEC
2014)
State and explain symmetrical fault or balanced three phase fault.
This type of fault is defined as the simultaneous short circuit across all the three phases. It
occurs infrequently, but it is the most severe type of fault encountered. Because the
network is balanced, it is solved by per phase basis using Thevenin’s theorem or bus
impedance matrix or KVL, KCL laws.
4. Give the frequency of various faults occurrence in ascending order.
(MAY JUN 2014)
What is the order of severity and occurrence of different types of fault?
(NOV DEC 2013)
Types of fault Relative frequency of occurrence of
fault
1 Balanced currents in all the three Unbalanced currents in all the three
phases phases
4 It is the most severe fault and less It is highly prone to fault with less
occurrence fault severity
2. Explain the step by step procedure for systematic fault analysis using bus impedance
matrix.
(NOV DEC 2009) (NOV DEC 2010) (APR MAY 2011) (NOV DEC 2011) (NOV DEC
2012) (MAY JUNE 2013)(MAY JUNE 2014)
3. A 11KV, 100 MVA alternator having a sub-transient reactance of 0.25 p.u is supplying a 50
MVA motor having a sub-transient reactance of 0.2 p.u through a transmission line. The line
reactance is 0.05 p.u on a base of 100 MVA. The motor is drawing 40 MW at 0.8 pf leading
with a terminal voltage of 10.95 KV when a three phase fault occurs at the generator
terminal. Calculate the total current in generator and motor under fault condition.
(APR MAY 2011) (NOV DEC
2013)
4. Figure shows a generating station feeding a 132 KV system. Determine the total fault
current, fault level and fault current supplied by each alternator for a 3 - phase fault at the
receiving end bus. The line is 200 km long. Take a base of 100MVA, 11KV for LV side and
132 KV for HT side. (NOV DEC 2011) (NOV DEC 2013)
5. A synchronous generator and motor are rated 30 MVA, 13.2KV and both have subtransient
reactance of 20%. The line connecting them has reactance of 10% on the base of machine
ratings. The motor is drawing 20,000 kW at 0.8 pf leading and terminal voltage of 12.8 KV
when a symmetrical 3-¢ fault occurs at the motor terminals. Find the sub-transient current
in the generator, motor and fault by using interval voltages of the machines.(MAY JUNE
2013)
6. For the radial Network shown below, a three phase fault occurs at F. Determine the fault
current and the line voltage at 11KV bus under fault conditions.
(NOV DEC 2012)
(
Z BUS= j 0.08
0.04
0.07
0.15
0.06
0.09
0.06
0.13
0.05
0.09
0.05
0.12
)
In this system generators are connected to buses 1 and 2 and their sub transient
reactances were included when finding Zbus. If the prefault current is neglected, find the
subtransient current in p.u in the fault for a 3 phase fault at bus 4. Assume pre fault voltage
as 1 p.u if the sub transient reactance of generator in bus 2 is 0.2 p.u, find the sub transient
fault current supplied by the generator. (MAY JUN 2012)
9. Two synchronous motors are connected to the bus of large system through a short
transmission line shown in fig. the rating of the various components are:
Motor (each) : 1MVA,440 V, 0.1 p.u transient reactance
Line : 0.05Ω (reactance)
Large System : short circuit MVA at its bus at 440V is 8
When the motors are operating at 440V, calculate the short circuit current (symmetrical)
fed into a three phase fault at motor bus.
(APR MAY 2010)
UNIT IV FAULT ANALYSIS – UNBALANCED FAULTS
Introduction to symmetrical components – sequence impedances – sequence circuits of
synchronous machine, transformer and transmission lines - sequence networks analysis of
single line to ground, line to line and double line to ground faults using Thevenin’s
theorem and Z-bus matrix.
TWO MARKS
1. What are symmetrical components? (NOV DEC
2014)
What are the symmetrical components of a 3 phase system?
(NOV DEC 2012)
In a 3 phase system, the unbalanced vectors (either currents or voltage) can be resolved into
three balanced system of vectors. They are Positive sequence components Negative
sequence components and Zero sequence components. Unsymmetrical fault analysis can be
done by using symmetrical components.
2. What is sequence networks? (NOV DEC
2014)
The single phase equivalent circuit of a power system consists of impedances to current of
any one sequences is called sequence network
3. What are the features of zero sequence current? (MAY
JUN 2014)
Zero sequence currents can flow in star winding if there is a neutral connection, and
corresponding zero-sequence currents flow within the delta winding. However, no zero
sequence current enters or leaves the delta winding.
Zero-sequence currents cannot enter or leave either delta winding, al-though they can
circulate within the delta windings.
4. Write the symmetrical component currents of phase 'a' in terms of three phase
currents. (MAY JUN 2014)
Ia1 positive sequence current
Ia2 Negative sequence current
Ia0 Zero sequence current
5. What are the observations made from the analysis of various faults?
(NOV DEC 2013)
Single line to ground fault
All the three symmetrical components of current I a are equal
Ia
I a 0=I a 1=I a 2=
3
All the three sequence impedances are present in the system.
Line to line fault
Zero sequence current is zero.
I a 0=0
Therefore zero sequence impedance is absent in the system.
Double line to ground fault
Positive sequence voltage and negative sequence voltage is equal.
V a 1=V a 2
All the three sequence impedances are present in the system.
6. Write the boundary conditions for single line to ground fault. (APR MAY
2005) (NOV DEC 2013)
I b=0 ; I c =0 ; I a=I f
V a =Z f I a
7. Define negative sequence impedance. (NOV DEC 2011)
(MAY JUN 2013)
The Impedance offered by the network to the flow of negative sequence current is said to be
negative sequence impedance. It is denoted by Z 0
8. Draw the sequence networks for a delta delta connected transformer.(NOV DEC
2005) (NOV DEC 2012)
9. Name the fault in which all the three sequence components currents are equal and
in which positive and negative sequence currents together is equal to zero
sequence current. (MAY JUN 2012)
Single line to ground fault is the fault in which all the three sequence components
currents are equal
Double line to groundfault is the fault in which positive and negative sequence currents
together is equal to zero sequence current
10. Write the matrix notation of the operator ‘a’ which relates the phasors V a, Vb and
Vc with Va0, Va1, Va2
(MAY JUN 2012)
11. Name the fault which do not have zero sequence current flowing.
(NOV DEC 2011)
Line to line fault
12. What is sequence network? (APR MAY
2011)
The single phase equivalent circuit of power system consisting of impedances to current of
any one sequence only is called sequence network.
13. Write the symmetrical components of three phase system.
(APR MAY 2011)
positive sequence components
Negative sequence components.
Zero sequence components.
14. What is the significance of operator ‘a’ (NOV DEC
2007)
‘a’ is the operator that causes a counter clockwise rotation of 120 degree.
a=-0.5+0.866j= 1<120
a2=-0.5-0.866j= 1<240
a3=1=1<360
15. Draw the equivalent sequence network for a line to line bolted fault in a power
system. (MAY JUN 2007)
SIXTEEN MARKS
1. Explain about the concept of symmetrical components. (NOV DEC
2014)
2. A 25 MVA, 13.2 KV alternator with solidly grounded neutral has a subtransient reactance of
0.25 .p.u. The negative and zero sequence reactances are 0.35 and 0.01 p.u respectively. If
a double line-to-ground fault occurs at the terminals of the alternator, determine the fault
current and line-to-line voltages at the fault. (MAY JUN 2014)
3. Obtain the expression for fault current for a line to line fault taken place through an
impedance Zb in a power system.
(MAY JUN 2014)
4. Derive the expression for fault current in line to line fault on unloaded generator. Draw an
equivalent network showing the inter connection of networks to simulate line to line fault
(NOV DEC 2010) (APR MAY 2011) (NOV DEC 2011) (APR MAY 2010)
(NOV DEC 2013)
5. Figure shows a power system network. Draw zero sequence network for this system. The
system data is as under.
Generator G1 50 MVA 11 KV X0 = 0.08 pu
Transformer T1 50 MVA 11/220 KV X0 = 0.1 pu
Generator G2 30 MVA 11 KV X0 = 0.07 pu
Transformer T2 30 MVA 11/220 KV X0 = 0.09 pu
Zero sequence reactance of line is 555.6 ohms. Choose base MVA 50 andbase voltage
11KV for LT side and 220 KV for HT side.
(NOV DEC 2013)
6. Discuss in detail about the sequence impedances and networks of synchronous machines,
transmission lines transformers and loads.
(MAY JUN 2013)
7. A single line diagram of a power network is shown in Fig.
The system data is given in the table as below
Element Positive Negative Sequence Zero Sequence
Sequence Reactance Reactance
Reactance
Generator grounding reactance is 0.5 p.u. Draw sequence networks and calculate the fault
current for a line-to-line fault on phases b and c at point q. Assume 1.0 p.u prefault voltage
throughout. (MAY JUNE 2013)
8. Derive the expression for fault current in double line to ground fault on unloaded
generator. Draw an equivalent network showing the inter connection of networks to
simulate double line to ground fault
(APR MAY 2004) (NOV DEC 2009) (NOV DEC 2012) (MAY
JUNE 2006)
9. Derive the expression for fault current in single line to ground fault on unloaded generator.
Draw an equivalent network showing the inter connection of networks to simulate single
line to ground fault
(MAY JUN 2012) (APR MAY 2010) (APR MAY
2012)
10. A 30MVA, 11KVgenerator.has Z1 = Z2 = jO.2p.u. Z0 = j 0.05p.u. A line to ground fault
occurs on the generator terminals. Find the fault current and line to line voltages during
fault conditions. Assume that the generator neutral is solidly grounded and that the
generator is operating at no-load and at rated voltage at the occurrence of fault.
(NOV DEC 2011) (MAY JUN
2012)
11. A 50 MVA, 11KV three phase alternator was subjected to different types of faults. The
magnitude of the fault currents were.
Three phase fault :1870A
Line to Line fault : 2590A
Single Line to Ground fault : 4130A
The alternator neutral is solidly grounded. Find the p.u value of three sequence reactance
of the alternator. Neglected the resistance.
(MAY JUN 2012)
12. A 30 MVA, 11KV 3 phase synchronous generator has direct axis sub-transient reactance of
0.25 per unit. The negative and zero sequences reactance are, respectively, 0.35 and 0.1
per unit. The neutral of the generator is solidly grounded. Determine the sub transient
current in the generator and line-to-line for sub transient conditions when a single line-to-
ground fault occurs at the terminals of generator, assume that the generator is unloaded at
rated terminal when the fault occurs. (APR MAY 2005) (MAY
JUN 2012)
13. An alternator of negligible resistance, with solidly earthed neutral, having rated voltage at
no load condition is subjected to different types of fault at its terminals. The per unit values
of
Magnitudes of the fault currents are:
Three phase fault : 4.0 p.u
L-G fault : 4.2857 p.u
L-L fault : 2.8868 p.u
Calculate three sequence reactance (NOV DEC
2008)
14. A single line to ground fault occurs at bus 4 of the system shown in fig.
Draw sequence networks and compute fault currents
Gen 1 and 2 : 100MVA, 20KV, X’=X”=20%; X0=4%; Xn=5%
ω n 4.8541
frequency of oscillation f n= = =0.7726 Hz
2π 2π
5. Differentiate between voltage stability and rotor angle stability.
(NOV DEC 2013)
Voltage stability
Rotor angle stability is the ability of interconnected synchronous machines of a power
system to remain in synchronism.
Rotor angle stability
It is the ability of a power system to maintain steady acceptable voltages at all buses in
the system under normal operating conditions and after being subjected to a disturbance.
6. Define swing curve? What is the use of this curve? (NOV
DEC 2013)
The swing curve is the plot or graph between the power angle δ, and time, t.
Use:
It is usually plotted for a transient state to study the nature of variation in δ for a sudden large
disturbance. From the nature of variations of δ, the stability of a system for any disturbance
can be determined.
7. Define infinite bus in a power system. (NOV DEC 2012)
(MAY JUN 2013)
If the external power system is very large as compared to the system of any installation,
disturbances within the installation do not affect the voltage and frequency of the external
system. In such a situation, the external power source is known as an Infinite Bus.