CS1140 Cerberus AlgoPilot Terminals Operating Instructions
CS1140 Cerberus AlgoPilot Terminals Operating Instructions
Operating instructions
EP7F
Introduction ...................................................................................................................... 13
General Remarks......................................................................................................................................13
State and Configuration Dependency.......................................................................................................14
Browsing Methods ....................................................................................................................................15
3
Fire & Security Products 11.2002
Siemens Building Technologies Group
System Functions.............................................................................................................70
How to SET DISPLAY CONTRAST ? ...................................................................................................70
How to SET BUZZER INTENSITY ? .....................................................................................................70
How to SET TIME & DATE ? ..................................................................................................................71
How to PERFORM A LED TEST ?........................................................................................................72
How to PERFORM A PRINTER TEST ? ..............................................................................................72
How to SWITCH PRINTER OFF / ON ?................................................................................................73
How to CHANGE PRINTER PAPER ? ..................................................................................................74
How to POLL ALARM COUNTER ? ......................................................................................................76
How to RESET ALARM COUNTER ? ...................................................................................................77
How to POLL EVENT MEMORY ? ........................................................................................................78
How to DELETE EVENT MEMORY ? ...................................................................................................80
Message Categories.......................................................................................................100
Message Categories Overview...............................................................................................................100
Alarm / Keys & Indicators .......................................................................................................................102
Alarm / Supplementary Information ........................................................................................................106
Alarm / Display in detail ..........................................................................................................................108
Alarm / CAC: Cerberus Alarm Concept ..................................................................................................110
Fault ........................................................................................................................................................112
Isolation...................................................................................................................................................112
Information ..............................................................................................................................................112
Service Functions...........................................................................................................113
Remote Transmission.............................................................................................................................113
Alarm devices .........................................................................................................................................114
Detector Test ..........................................................................................................................................115
Detector Parameter Sets ........................................................................................................................117
System Functions...........................................................................................................120
Printer .....................................................................................................................................................120
LED Test .................................................................................................................................................120
Time & Date ............................................................................................................................................120
4
Fire & Security Products 11.2002
Siemens Building Technologies Group
Miscellaneous................................................................................................................. 121
Terminology 'Area', 'Section' & 'Zone' ....................................................................................................121
Operation states 'manned' and 'unmanned' ...........................................................................................122
Timeouts .................................................................................................................................................124
5
Fire & Security Products 11.2002
Siemens Building Technologies Group
General Information i
General Information
About the The AlgoRex CS1140 is a high sophisticated fire detection system. The terminals B3Q660
product and B3Q680 serve as user interface to operate and to communicate with this system.
About this This document consists of the following sections. To each section a typical symbol is as-
documentation signed helping to keep overview and to see at a glance the current section on each page:
NOTE
☞ More information about this document can be found in the "Document Information" chap-
ter.
6
Fire & Security Products 11.2002
Siemens Building Technologies Group
General Information i
Important notes Before personnel begin work on the system they must have read and understood the related
operating instructions, in particular chapter “Safety Regulations“.
The consistent adherence to these instructions is a prerequisite for a safe application.
i Before they are delivered, products are tested to ensure they function correctly when used
properly. Siemens disclaims all liability for damage or injuries caused by the incorrect appli-
cation of the instructions or disregard of warnings of danger contained in the documentation.
This applies in particular to:
• Personal injuries or damage caused by improper use and incorrect use.
• Personal injuries or damage caused by disregarding safety instructions in the documenta-
tion or on the product.
• Personal injuries or damage caused by poor maintenance or a lack of maintenance.
Siemens Fire & Security Products provides the necessary training for these products. Infor-
mation about courses can be found in the Siemens Intranet or - if no access - please contact
your local Siemens representative.
7
Fire & Security Products 11.2002
Siemens Building Technologies Group
General Information i
Document Information
Purpose This document describes the operation of the AlgoRex CS1140 system.
Scope It contains information about the terminals B3Q660 and B3Q680, valid from software version
EP7F on.
Target group This product documentation and the work instructions are aimed at the following persons,
who have a particular function and have the corresponding training and qualification.
Training Siemens Fire & Security Products provides the necessary training for these products. Infor-
mation about courses can be found in the Siemens Intranet or - if no access - please contact
your local Siemens representative.
8
Fire & Security Products 11.2002
Siemens Building Technologies Group
General Information i
Terms, In this document these terms, abbreviations and conventions are used:
abbreviations
& conventions
Term Description
The Person Machine Interface of the AlgoRex system. It comprises
PMI the terminal hardware as well as the software functionality which al-
lows interaction between operator and the AlgoRex system.
Access level Defines the range of accessible functions.
Login Action necessary to get operating access.
Logout Action to disable operating access.
Passwords are intended to prevent operation by unauthorized per-
Password
sons. The password is asked during login.
Keyswitch Can be used instead of a password. (Optionally equipped)
Keys are the physical buttons located on the panel front. Keys are
Key always written in angle brackets,
e.g. <Acknowledge>, <3>, <✓ >.
A selectable entry in a menu.
Softkeys such as <Operate..> or <Full message> are printed in in-
verse bold characters. The softkeys are selected by pressing the as-
Softkey sociated key arranged to the left or to the right of the menu entries.
As there are real keys associated the angle brackets show the rela-
tionship to normal keys and help to distinguish from a display mes-
sage.
LED indicator The indicator lamps of the panel are called LEDs.
The Liquid Crystal Display (LCD) to display text messages and soft-
Display
keys is called 'display'.
Idle display Contents of the display if there is no message to be displayed.
Message Contents of the display if at least one message is present.
display
Allows access to operation of events and to access the main menu.
Primary menu
The primary menu is either the 'Idle display' or the 'Message display'.
Main menu Allows access to all possible functions of the fire detection system.
☞ Indicates references to other chapters or documents.
Document iden-
tification
Position Signification
Title page • System names
• Product type
• Purpose of the document
Last page bottom left • Document number consists of: Language, number, index
• Date of version
bottom right • Manual
• Register
Modification
index
Version Date Brief description
a 02.2002 Field test version
b 11.2002 First official version
9
Fire & Security Products 11.2002
Siemens Building Technologies Group
General Information i
Safety Regulations
Signal Words and Symbols
Introduction This chapter describes the danger levels and the relevant safety regulations applicable for
the use of the products.
☞ Please read the work instructions as well as the introductory chapters "Notes to the User"
and "Document Information" thoroughly before beginning any work.
Classification The danger level - that is, the severity and probability of danger - is indicated by the signal
and meaning of words listed below. Non-observance may lead to the consequences indicated:
signal words
Classification Meaning Consequences
May cause serious bodily in-
• DANGER Imminent danger! →
jury or danger to life!
May cause serious bodily in-
• WARNING Dangerous situation! →
jury or danger to life!
• CAUTION Possibly dangerous situation! → May cause light injuries!
May cause damage to the
product or to objects in the
• NOTE Possibly harmful situation! →
immediate vicinity of the
product!
Symbols and The symbols listed below indicate the nature and origin of the danger.
their meaning
General danger
Electrical voltage
10
Fire & Security Products 11.2002
Siemens Building Technologies Group
General Information i
Country- The products are developed and produced in compliance with the relevant international and
specific European safety standards. Should additional country-specific, local safety standards or
standards regulations concerning project planning, assembly, installation, operation and disposal of the
product apply in the place of operation, then these standards or regulations must also be
taken into account in addition to the safety regulations mentioned in the product documenta-
tion.
Electrical Any work on electrical installations may only be carried out by qualified electricians or in-
installations structed persons working under the guidance and supervision of a qualified electrician, in ac-
cordance with the electrotechnical regulations.
• Control units must be disconnected from the power supply during commissioning or
maintenance work.
• Terminals with an external voltage supply must be provided with a sign ”DANGER – Ex-
ternal voltage”.
• Mains leads to the control unit must be installed separately and provided with a clearly
marked fuse.
• Earthing must be carried out in compliance with local safety regulations.
• When work is carried out in explosion–hazardous areas, the appropriate safety precau-
tions must be taken.
Assembly, • If any tools or accessories such as ladders are required, safe and suitable devices must
installation, be used.
commissioning • Prevention of spurious tripping of the remote transmission must be assured.
and inspection • Always inform the fire brigade before testing the remote transmission.
work • The activation of fire control installations for test purposes must not cause damage to the
system or parts thereof.
• Fire control installations must only be activated after the test has been completed and the
system has been handed over to the customer.
• Third party systems or devices must only be activated in the presence of the responsible
person.
• When work on management stations and system terminals is performed, the safety regu-
lations of the connected sub–systems must be observed. This especially applies when
switching–off system components.
• In the case of extinguishing systems, always use the ”General installation instructions” as
a guideline. This guideline is available on request.
11
Fire & Security Products 11.2002
Siemens Building Technologies Group
General Information i
Modules and • Locally procured modules and spare parts must comply with the technical specifications
spare parts laid down by the manufacturer. This compliance is always ensured for original spare parts
supplied by us.
• Only use fuses with the specific fuse characteristics.
• Wrong battery types and improper battery exchange may introduce the danger of explo-
sion. Only use the specified battery type or an equivalent battery type recommended by
the manufacturer.
• Batteries require environmentally safe disposal. They must be handed in at the local col-
lecting points.
• Please take into account that the extinguishing agent cylinders are pressurized and must
be exchanged in compliance with the local safety regulations.
12
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Introduction
General Remarks
Purpose This section describes the procedures to handle spontaneous appearing events and how to
operate the full range of possible functions of this fire detection system.
Main focus It mainly deals with the question 'how' is something done. Therefore for all topics a brief step-
by-step instruction is provided.
Additional in- ☞ More information to understand this fire detection system in detail can be found in the
formation "Basic System Knowledge &" section beginning at page 81.
Before starting To get a better understanding on how to use these operating instructions please read the
topics "State and Configuration Dependency" and "Browsing Methods" on the following pa-
i ges.
13
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
What is the The menus depend on configuration, system state and access level, i.e. they may look
effect? slightly different from the figures in this manual.
Similarly some procedures depend on the actual system state and configuration.
and it changes to
<Zone -> ON> if the zone is switched OFF
Additionally it may even change to call a submenu if there are mixed states.
or
<All DETECTOR zones -> ON> if all zones are OFF
14
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Browsing Methods
Concept The AlgoRex system uses an object oriented operation concept, i.e. the available functional-
ity is determined by the features of the current object (e.g. a specific node in the logical or
physical tree).
You first have to specify the object which shall be handled. Then the available functionality
results from the selected object.
So you always have to select a specific node (this is called: you 'browse to a node') and then
you decide what has to be done with it.
1. You get to that specific 'detector zone' node. There you will have all functions available for
'detector zone' nodes (these functions differ from that of other nodes).
In this document the 'Tree browsing' method is used to set a specific state. To reset back to
i the original state, whenever possible the 'Direct access via message' method is used.
Tree browsing Browsing always starts on top level of the (inverse) tree and follows the branches down to
the desired node.
<Operate..>
▼
<Browse..>
▼
<Browse FIRE DETECTION..>
▼
<Select SECTION¯>
▼
<Select ZONE¯>
2. Now all available functions are displayed and the zone can be switched off by selecting
the softkeys <Zone -> OFF..> and <OFF>
15
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
This method can only be used if the required address information is known. It may be avail-
able on the display or written to the detectors or be known from floor plans.
The availability off address information on the display can be configured by the service engi-
neer
1. You get to the required direct access menu by using the following softkeys:
<Operate..>
▼
<Direct access..>
▼
<Enter LOGICAL ADDRESS (CSX)..>
2. Now you are prompted by the following message to enter the CSX number:
3. After having completed the entry, select softkey <Jump to> or press <✓ >. The selected
node and all available functions are displayed.
4. Now you can continue by selecting the softkeys <Zone -> OFF..> and <OFF>
Direct access Using this method always makes sense if a specific message of the abnormal state is visible
via message in one of the 4 message categories (Alarms, Faults, Isolation, Information).
Example A zone which is in the off state shall be switched on. This zone has generated an 'Isolation'
message:
1. Press key <Isolation> to select this message (eventually message scrolling may be re-
quired)
2. Then select softkey <Functions for sel. message..>: All available functions are displayed
3. Now the zone can be switched on by selecting the softkeys <ON/OFF functions..> and
<Zone -> ON>.
16
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
17
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Event Handling
A L A R M - what to do ?
ALARM
2 Fire brigade REQUESTED
01 AUTOM. FIRE ALARM
Total: 1
1
Main building / 1st floor
Room 104
02 AUTOM. FIRE ALARM
Main building / 1st floor
3
Acknowledge Intervention text Acknowledge
.
.
Alarm(s) by
pressing the Functions for
. <Acknowledge> key sel. message.. Reset
. Elements in ALARM Operate..
.
.
.
.
4 6
Alarms Faults Isolation Information
1 2 3
Alarm device
active
Alarm device
fault
Alarm device
off
Premises
manned
4 5 6
Remote alarm Remote transmission Remote alarm System
active fault off on
7 8 9
Alarm delay System Detector
off fault test mode Õ 0 ü
Step Action
1 Press <Acknowledge> ➊
2 Read top line of display ➋
IF top line reads
18
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
3 Poll
• intervention text ➌ (if available)
Emergency
IF 8 THEN
fire brigade is already informed • save people
• guide fire brigade
• fight the fire
IF 8 THEN
time count down runs immediately actuate nearest manual call
point
- or -
press <Alarm delay off> ➎
IF 8 THEN
no transmission to fire brigade call fire brigade by telephone
Minor incident
IF 8 THEN
fire brigade is already informed • try to stop the fire brigade
• press <Reset> ➏
→ The system reverts to 'Normal operation'
IF 8 THEN
time count down runs
immediately press <Reset> ➏
→ The system reverts to 'Normal operation'
IF 8 THEN
no transmission to fire brigade
press <Reset> ➏
→ The system reverts to 'Normal operation'
NOTES:
• Password entry is required to reset.
• It may be necessary to ventilate the room before reset is possible.
• Zones which cannot be reset may be temporarily switched off by pressing softkey
<Isolate detector zones in ALARM>
19
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
F A U L T - what to do ?
Step Action
NOTE:
Details for specific faults see below.
Defective FAULTS
01 Detector
Total: 1
Full message
Functions for
sel. message..
Operate..
Step Action
2 IF THEN
20
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
F A U L T - what to do ?, Continued
Full message
Functions for
sel. message..
Operate..
Step Action
2 IF THEN
there is any other defect Call your local service organization of Siemens
Building Technologies
Full message
Functions for
sel. message..
Operate..
To handle a fault caused by run out of printer paper follow these steps:
Step Action
1 Go to the printer
21
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
F A U L T - what to do ?, Continued
Full message
Functions for
sel. message..
Operate..
Step Action
1 IF THEN
Other faults For all other faults call your local service organization of Siemens Building Technologies
22
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Standard Procedures
Introduction • You can just start to operate. If access has not yet been granted, the login process auto-
matically starts.
• However it is also possible to get operating access before starting to operate.
• 'Getting operating access' is synonymous with 'logging in'.
INFORMATION Total: 1
01 Unmanned
ALARM Main building
. 5
.
.
.
1
3 Start operation
23
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
1 Insert key ➍
3 Start operation
NOTE:
The operating access remains while the key is left in the horizontal position.
Guest login Provides an easy access on access level 1 without having to enter a password:
3 Start operation
24
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
ALARM
. Acknowledge
.
. Reset
.
.
.
.
.
Precondition: Logout by <Õ> key can only be done on primary menu level. So if the system displays any
Returning to other menu, returning to the primary menu first is required.
the primary
menu To return to primary menu (from any menu, submenu or the main menu) follow these steps:
1 Press key <Õ> ➊ You get from any other menu immediately
to the primary menu.
"Press <X] to log out" is displayed.
Logout by To enforce an explicit logout (from primary menu level) follow these steps:
<Õ> key
NOTE:
Only possible if the key is not in horizontal position
2 Remove key ➋
25
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Operating If there is no operating access when starting to operate, the system asks to log in.
access
Which areas • Several organizationally autonomous systems can be operated via a common multi-area
are switched terminal. There may be areas with 'manned' state, other areas with 'unmanned' state.
over? • If there are such mixed states, the 'Premises manned' state indicator ➋ is flashing
• You can now either switch over just your own area or all areas from 'manned' to 'unman-
ned' or vice versa.
Switch over via To switch over from 'manned' to 'unmanned' (or vice versa) via function key follow these
function key steps:
1 Press key
<Premises manned> ➊
2 EITHER... OR...
(to switch own area) (to switch all areas)
2 1
Alarms Faults Isolation Information
26
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Switch over via To switch over from 'manned' to 'unmanned' (or vice versa) via menu follow these steps:
menu
NOTE:
Switching operating states 'manned' / 'unmanned' by menu only affects the selected area.
27
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
When does a ZONES equipped with automatic fire detectors or manual call points can be temporarily
zone have to be switched off (isolated).
switched OFF This is only necessary in exceptional situations, for example, while major construction is in
progress:
• ZONE with smoke detectors à if smoke or dust is produced by unusual work
• ZONE with heat detectors à if heat or steam is produced by unusual work
• ZONE with manual call point à if there is a possibility of inadvertent actuation
Operating If there is no operating access when starting to operate, the system asks to log in.
access
Switch OFF A zone which is switched OFF without time limit remains in the OFF state until it is switched
one single zone ON again.
(without time
limit) To switch OFF a zone without time limit follow these steps:
28
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Switch ON one The steps to switch ON a zone are independent of the method the zone has been switched
single zone OFF.
To switch ON a zone follow these steps:
3 Select softkey
<Functions for sel. message..>
29
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Operating If there is no operating access when starting to operate, the system asks to log in.
access
Switch OFF The time the zone remains switched OFF can be limited. After this time the zone is switched
one single zone on automatically.
with time limit To switch OFF a zone with time limit follow these steps:
30
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Extending the • If the time limit a zone is switched OFF is to short, it can be extended without switching
OFF state of a the zone on in between.
single zone • The old time limit is replaced by the new one. After that new time the zone is switched on
with time limit automatically.
To extend the OFF time of a zone with time limit follow these steps:
3 Select softkey
<Functions for sel. message..>
Switch ON ☞ Follow the procedure as described under "Switch ON one single zone" on page 29.
one single zone
Mixing different • It is possible to switch a zone OFF with time limit and then change it afterwards to OFF
OFF modes without time limit or vice versa.
• To do so just follow the switching OFF procedure while the specific zone is already in OFF
state and decide which OFF state should be chosen.
31
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Switching ☞ The procedure is similar to the one described for single zones in chapter
OFF/ON "How to SWITCH a single ZONE (ROOM) OFF / ON ?
with time limit (With Time Limit)" on page 30.
Switching per section with time limit is available for zones of type 'Automatic fire detector'
only.
Zone type For the following descriptions a zone type 'Automatic fire detector' has been assumed, but
the same procedure also applies for zones of type 'Manual call point'.
Operating If there is no operating access when starting to operate, the system asks to log in.
access
Switch OFF With this command all detector zones of a section can be switched OFF. To do so follow
all zones of a these steps:
section
32
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Switch ON With this command all detector zones of a section can be switched ON. To do so follow
all zones of a these steps:
section
3 Select softkey
<Functions for sel. message..>
NOTE:
If not all zones of that section are in the OFF state, follow these steps:
3 Select softkey
<Functions for sel. message..>
33
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Operating If there is no operating access when starting to operate, the system asks to log in.
access
7 Select softkey
<More functions..>
NOTE:
• If all elements of a ZONE are OFF, the corresponding zone is automatically isolated and
all element isolation messages are cancelled.
• In that case the reactivation is only possible on level ’ZONE’.
34
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
3 Select softkey
<Functions for sel. message..>
4 Select softkey
<More functions..>
3 Select softkey
<Functions for sel. message..>
4 Select softkey
<More functions..>
35
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Service Functions
Operating If there is no operating access when starting to operate, the system asks to log in.
access
Switch OFF The remote transmission of alarms of all assigned areas can be switched OFF/ON by a
remote alarm separate key.
by function key To switch off the remote transmission follow these steps:
Pressing key ➊ will immediately switch off the remote alarm off all assigned areas.
Switch ON To switch ON the remote transmission of alarms of all assigned areas follow these steps:
remote alarm
by function key
36
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Switch OFF There are three types of remote transmissions which can be switched off:
remote trans- • Remote transmission of fire alarms
missions by • Remote transmission of fault messages
menu • Remote transmission of other messages
To switch off the remote transmission of one single area follow these steps:
Switch ON re- To switch on the remote transmission of one single area follow these steps:
mote transmis-
sions by menu
37
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Operating If there is no operating access when starting to operate, the system asks to log in.
access
Switch OFF The alarm devices of all assigned areas can be switched OFF/ON by a separate key.
alarm devices To switch off the alarm devices follow these steps:
by function key
Pressing key ➊ will immediately switch off the alarm devices off all assigned areas.
Switch ON To switch ON the alarm devices of all assigned areas follow these steps:
alarm devices
by function key
2 1
Alarms Faults Isolation Information
38
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Switch OFF To switch off the alarm devices of one single area follow these steps:
alarm devices
by menu
Switch ON To switch on the alarm devices of one single area follow these steps:
alarm devices
by menu
39
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
What is this When calling this function the alarm devices will be activated for some seconds for testing
for? purposes.
Operating If there is no operating access when starting to operate, the system asks to log in.
access
40
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
41
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Some notes Testing detectors (or manual call points) is normally done on section level, but is also possi-
about mode ble on line or on zone level.
'Detector test'
It is not possible to set an element (an individual fire detector or manual call point) to 'De-
tector test'.
Sections and zones set to 'Detector test' are displayed spontaneously as a message in the
’Isolation’ category.
For what zones The command is available for zones with interactive, AnalogPLUS, MS9i, CBA and collective
is it available? devices.
How does it If a device is activated, its alarm indicator starts flashing for some seconds and a corre-
work? sponding message appears on the terminal during this time.
What means Per SECTION means all detector (or manual call point) zones within a SECTION.
'per SECTION'?
NOTE The same procedures for TEST and TEST OFF applies for manual call point zones
How to use this This chapter shows how to set on and off the mode 'Detector test'.
chapter ☞ For a description on how to do the actual testing see the following chapters:
• "How to TEST AUTOMATIC DETECTORS ?" on page 47
• "How to TEST MANUAL CALL POINTS ?" on page 48
Operating If there is no operating access when starting to operate, the system asks to log in.
access
42
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Set to mode To set all detector zones within a SECTION to 'Detector test' follow these steps:
'Detector test'
Step Action Result / Comments
2 Select softkey
<DETECTOR zone functions..>
Terminate To terminate test mode of all detector zones within a SECTION follow these steps:
mode
'Detector test'
Step Action Result / Comments
2 Select one of the detector zones to Use the display scroll keys
be switched back to 'Normal mode'
3 Select softkey
<Functions for sel. message..>
4 Select softkey
<Select SECTION>
5 Select softkey
<DETECTOR zone functions..>
43
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
What means This mode serves to test all zones of a specific detector line, i.e. all zones with devices which
'per LINE'? are physically connected to that specific line are set to test mode with one single command.
How does it It switches to test mode all corresponding zones, which are linked to a device on the se-
work? lected line.
Operating If there is no operating access when starting to operate, the system asks to log in.
access
44
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Set to mode To set all detector zones of a LINE to mode 'Detector test' follow these steps:
'Detector test'
Terminate To terminate test mode of all detector zones of a LINE follow these steps:
mode
'Detector test'
45
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Operating If there is no operating access when starting to operate, the system asks to log in.
access
Set to mode To set one single detector zone to 'Detector test' follow these steps:
'Detector test'
2 Select softkey
<TEST/RENOVATION/
INST.TEST funct...>
Terminate mode To terminate test mode of one single detector zone follow these steps:
'Detector test'
3 Select softkey
<Functions for sel. message..>
4 Select softkey
<TEST/RENOVATION/
INST.TEST funct...>
46
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Switching to Before testing can be done, the system has to be switched to the test mode.
test mode ☞ See the following chapters:
• "How to SET MODE 'DETECTOR TEST' per SECTION ?" on page 42
• "How to SET MODE 'DETECTOR TEST' per LINE ?" on page 44
• "How to SET MODE 'DETECTOR TEST' per ZONE ?" on page 46
Testing of This procedure describes the testing principle for automatic detectors.
automatic
detectors To test automatic detectors follow these steps:
NOTE:
After testing has been completed, the test mode has to be terminated.
☞ See the following chapters:
• "How to SET MODE 'DETECTOR TEST' per SECTION ?" on page 42
• "How to SET MODE 'DETECTOR TEST' per LINE ?" on page 44
• "How to SET MODE 'DETECTOR TEST' per ZONE ?" on page 46
47
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Switching to Before testing can be done, the system has to be switched to the test mode.
test mode ☞ See the following chapters:
• "How to SET MODE 'DETECTOR TEST' per SECTION ?" on page 42
• "How to SET MODE 'DETECTOR TEST' per LINE ?" on page 44
• "How to SET MODE 'DETECTOR TEST' per ZONE ?" on page 46
Testing manual This procedure describes the testing principle for manual call points of type DM1101,
call points of DM1131, DM1151 (type KAC).
type DM11x1
To test this type of manual call points follow these steps:
NOTE:
After testing has been completed, the test mode has to be terminated.
☞ See the following chapters:
• "How to SET MODE 'DETECTOR TEST' per SECTION ?" on page 42
• "How to SET MODE 'DETECTOR TEST' per LINE ?" on page 44
• "How to SET MODE 'DETECTOR TEST' per ZONE ?" on page 46
48
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Testing manual This procedure describes the testing principle for manual call points of type DM1103,
call points of DM1133, DM1153 (type ’indirect operation’).
type DM11x3
To test this type of manual call points follow these steps:
Testing manual This procedure describes the testing principle for manual call points of type DM1104,
call points of DM1134, DM1154 (type ’direct operation’).
type DM11x4
To test this type of manual call points follow these steps:
NOTE:
After testing has been completed, the test mode has to be terminated.
☞ See the following chapters:
• "How to SET MODE 'DETECTOR TEST' per SECTION ?" on page 42
• "How to SET MODE 'DETECTOR TEST' per LINE ?" on page 44
• "How to SET MODE 'DETECTOR TEST' per ZONE ?" on page 46
49
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
What is the The mode 'Installation test' allows to test the correct function of the whole fire detection sys-
mode 'Installa- tem including fire controls, acoustical alarm devices, etc. All functions remain enabled.
tion test' for ? Make sure that the remote transmission is switched off or the fire department is informed
about the test activities.
In mode ’Installation test’ interactive, AnalogPLUS and CBA devices respond faster (re-
sponse behavior as in mode 'Detector test').
After the test work has been completed immediately cancel the mode 'Installation test'.
Mode 'Installation test' is normally enabled and disabled on the level ’ZONE’ but also possi-
ble on the level ’SECTION’
The mode ’Installation test’ shall be carried out only by security staff and serves basically to
test the alarm organization and fire controls.
Operating If there is no operating access when starting to operate, the system asks to log in.
access
Set one single To switch one single detector zone to mode 'Installation test' follow these steps:
detector zone
to 'Installation
test'
2 Select softkey
<TEST/RENOVATION/INST.TEST
funct..>
50
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Set one single To switch one single detector zone back to 'Normal mode' follow these steps:
detector zone
back to 'Normal
mode'
3 Select softkey
<Functions for sel. message..>
4 Select softkey
<TEST/RENOVATION/INST.TEST
funct..>
Set all detector To set all detector zones to 'Installation test' follow these steps:
zones within a
SECTION to
'Installation
test'
2 Select softkey
<DETECTOR zone functions..>
51
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Set all detector To set all detector zones back to 'Normal mode' follow these steps:
zones within a
SECTION back
to 'Normal
mode'
2 Select one of the detector zones to Use the display scroll keys
be switched back to 'Normal mode'
4 Select softkey
<Select SECTION>
5 Select softkey
<TEST/RENOVATION/INST.TEST
funct..>
52
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
53
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
What is the Mode ’Renovation’ is a special feature of interactive DO and DOT detectors and only avail-
mode 'Renova- able on level ’ZONE’.
tion' for ?
In mode 'Renovation', interactive automatic detectors are much less sensitive. This may be
required while unusual work is in progress (e.g. during renovation of a building).
The fire detection system remains working, the remote transmission of alarm and fault mes-
sages is enabled.
Detectors in the mode ’Renovation’ are from the insurance and approval point of view out of
order. This is why the ’isolation’ message is generated.
Operating If there is no operating access when starting to operate, the system asks to log in.
access
2 Select softkey
<TEST/RENOVATION/INST.TEST
funct..>
54
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Set a detector To set a detector zone back to 'Normal mode' follow these steps:
zone back to
'Normal mode'
3 Select softkey
<Functions for sel. message..>
4 Select softkey
<TEST/RENOVATION/INST.TEST
funct..>
55
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
What can be Zones can be activated manually from any AlgoRex terminal.
done?
Which zones The following zones can be activated, but with different effect:
can be acti- • Detector zones
vated? • Control zones
Detector zones Each activation increases the danger level (depending on zone type):
Operating If there is no operating access when starting to operate, the system asks to log in.
access
56
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
3 Select softkey
<Functions for sel. message..>
Be aware of the fact that an activation of zones may lead to an alarm state which may re-
lease control zones, horns and remote transmissions!
57
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
What can be Elements can be activated manually from any AlgoRex terminal.
done?
Which ele- The following elements can be activated, but with different effect:
ments can be • Interactive detector element
activated? • AnalogPLUS detector element
• Digital element
• Control elements
Operating If there is no operating access when starting to operate, the system asks to log in.
access
2 Select softkey
<More functions..>
58
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
2 Select softkey
<More functions..>
2 Select softkey
<More functions..>
Be aware of the fact that an activation of digital elements may lead to an alarm state which
may release control zones, horns and remote transmissions!
59
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
2 Select softkey
<Functions for sel. message..>
4 Select softkey
<More functions..>
NOTE:
Reset is not possible unless the respective element has been deactivated.
To cancel the effect of an activation, the activation itself has to be cancelled first, not only the
i effect.
This is especially important with control elements
Example A command element is used to switch off all zones of a section and has been activated by
the 'Activate element' command.
The way to go back to the original state is not by switching on all zones of that section, but
by deactivating the active command element.
Otherwise the zones would switch on, but the command element would still remain active.
60
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
2 Select softkey
<More functions..>
Deactivation of To deactivate a Control element (with 'Information' message) follow these steps:
a Control ele-
ment (with
'Information'
message)
3 Select softkey
<Functions for sel. message..>
5 Select softkey
<More functions..>
61
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Deactivation of To deactivate a Control element (without 'Information' message) follow these steps:
a Control ele-
ment (without
'Information'
message)
2 Select softkey
<More functions..>
62
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
63
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
When does a Mainly in order to set the detector(s) temporarily to a less sensitive parameter set, while work
detector pa- is in progress (alternative to mode 'Renovation').
rameter set
have to be
changed?
What parameter ☞ A detailed list of all available parameter sets can be found in the section "Basic System
sets are avail- Knowledge &" in chapter "Detector Parameter Sets" on page 117.
able
• For interactive detectors only and only if this function has been enabled by the service en-
i gineer.
• Temporary change of parameter set shall only be done by the security staff
• Please note, that any temporary setting will be set back whenever the station is reset.
Operating If there is no operating access when starting to operate, the system asks to log in.
access
Changing the To set an other detector parameter set follow these steps:
parameter set
2 Select softkey
<Parameter set functions..>
3 Select softkey
<CHANGE parameter set>
64
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Reset to default To set back to default parameter set follow these steps:
parameter set
2 Select message
Parameter set changed
3 Select softkey
<Functions for sel. message..>
4 Select softkey
<Parameter set functions..>
NOTE:
'Parameter set -> DEFAULT' means setting back to the value, which was originally defined in
the system configuration
65
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Easy exchange With AlgoRex replacement of manual call points and DC modules is very easy. If the defec-
of manual call tive device has been found, the corresponding element can be set to the replace mode by
points and DC using the command 'Device replace mode -> ON'.
modules Then the operational personnel can change the faulty device.
Operating If there is no operating access when starting to operate, the system asks to log in.
access
Set Device The command is available on element level. A corresponding message is displayed on the
replace mode terminal. Only one element may be changed within one replace session.
-> ON The command ‘Device replace mode -> OFF’ or a reset of the station will end this mode.
To set a defective manual call point to replace mode follow these steps:
2 Select faulty manual call point Use the display scroll keys
3 Select softkey
<Functions for sel. message..>
4 Select softkey
<More functions..>
This command powers off the line corresponding to the selected element.
66
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Set Device The command is available on element level. It powers on the line corresponding to the se-
replace mode lected element. The corresponding message disappears.
-> OFF Additionally this command automatically sets all associated zones to detector test mode.
2 Select manual call point in 'replace Use the display scroll keys
mode'
3 Select softkey
<Functions for sel. message..>
4 Select softkey
<More functions..>
NOTE • After executing this command the message Change in hardware configuration appears.
• The new data will be merged at the station and the zone changes to test mode.
• After testing, the zone is set back to normal operation by using the 'Zone -> TEST OFF'
command.
• The message disappears after the service engineer has made an upload into AlgoWorks.
67
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
How is it done? To find out where exactly the break of an open line is, this function is very helpful. After this
command has been performed, the detector line is addressed just from one side. The termi-
nal will list all not seen devices from the actual direction. After using both commands the
service engineer can search in a smaller range and finally find the open line location and fix
it.
Switching back This command will terminate the stub line mode.
to normal mode The stub line mode will also be terminated by a reset of the station.
Operating If there is no operating access when starting to operate, the system asks to log in.
access
68
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
How to find the To detect the location of line break follow these steps:
break location
2 Select line with message open line Select message stub line forward
using the display scroll keys using the display scroll keys
9 You get fault messages of all You get fault messages of all
detectors behind the line break detectors before the line break
st nd
The line break lies between the detectors you got during the 1 and the 2 run.
How to go back To switch the line back to loop mode follow these steps:
to normal mode
3 Select softkey
<Functions for sel. message..>
69
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
System Functions
Operating If there is no operating access when starting to operate, the system asks to log in.
access
Operating If there is no operating access when starting to operate, the system asks to log in.
access
70
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Operating If there is no operating access when starting to operate, the system asks to log in.
access
Set time / date To adjust time and date follow these steps:
3 Select softkey
<More functions..>
4 Select softkey
<Set TIME and DATE>
5 Enter time 'hh:mm:ss' and date 'dd- Cursor points to value to be en-
mm-yy' using the numeric keys tered.
Cursor can be moved by softkey
<Next field>.
71
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Operating If there is no operating access when starting to operate, the system asks to log in.
access
<Operate..>
▼
<Browse..>
▼
<HARDWARE level..>
Operating If there is no operating access when starting to operate, the system asks to log in.
access
<Operate..>
▼
<Browse..>
▼
<HARDWARE level..>
2 Select softkey
<More functions..>
72
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Operating If there is no operating access when starting to operate, the system asks to log in.
access
<Operate..>
▼
<Browse..>
▼
<HARDWARE level..>
2 Select softkey
<More functions..>
<Operate..>
▼
<Browse..>
▼
<HARDWARE level..>
2 Select softkey
<More functions..>
73
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
74
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Paper feeding This picture shows how the printer paper is fed:
Print intensity If the print intensity is to low call your local service organization of Siemens Building Tech-
nologies
75
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Operating If there is no operating access when starting to operate, the system asks to log in.
access
Show number To poll the counter of fire alarms follow these steps:
of fire alarms
Show number To poll the counter of remote alarms follow these steps:
of remote
alarms
76
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Operating If there is no operating access when starting to operate, the system asks to log in.
access
Reset counter To reset the counter of fire alarms follow these steps:
of fire alarms
NOTE:
The number of fire alarms is immediately set to 0 without further inquiry
77
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
What is the • On AREA level only area specific messages are displayed. Independent of the section in
difference which the event memory is polled, always all area specific messages are displayed (i.e.
messages of all section of that specific area).
• On STATION level all messages from that specific station are displayed (i.e. section spe-
cific messages and section independent messages, such as logging in/out, messages
from power supply or from other function units).
Operating If there is no operating access when starting to operate, the system asks to log in.
access
Polling the To poll the event memory on AREA level, e.g. for section fire, follow these steps:
event memory
of an AREA
2 Select softkey
<Poll EVENT MEMORY..>
3 Select softkey
<ALL messages>
- or -
<ALARM messages>
- or -
<FAULT messages>
- or -
<ISOLATION messages>
- or -
<INFORMATION messages>
- or -
<TEST ALARM messages>
4 Adjust the FROM-TO range by en- Use the softkey <Next field> to
tering times/dates of interest move the cursor
- and -
Press <✓ > to start searching
78
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Polling the To poll the event memory on STATION level follow these steps:
event memory
of a STATION
2 Select softkey
<Poll EVENT MEMORY..>
3 Select softkey
<ALL messages>
- or -
<ALARM messages>
- or -
<FAULT messages>
- or -
<ISOLATION messages>
- or -
<INFORMATION messages>
- or -
<TEST ALARM messages>
4 Adjust the FROM-TO range by en- Use the softkey <Next field> to
tering times/dates of interest move the cursor
- and -
Press <✓ > to start searching
79
Fire & Security Products 11.2002
Siemens Building Technologies Group
Operating Instructions ➊➋➌
Operating If there is no operating access when starting to operate, the system asks to log in.
access
80
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Introduction
Purpose This section describes the main features of the detailed functionality of the AlgoPilot PMI.
Main focus The main focus in this section is to deliver background information to enable the operator to
understand the AlgoRex system concept.
What is the This section can be utilized for the training of operators or for self-study.
usage?
When may it be If only an extract of this document shall be used as brief operating instructions this section
omitted? may be omitted.
State and The menus depend on configuration, system state and access level, i.e. they may look
configuration slightly different from the figures in this manual.
dependency
Similarly some procedures depend on the actual system state and configuration.
81
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Introduction The AlgoPilot panel serves to display messages from the AlgoRex system and to operate it.
1
2
ALARM
4
. Acknowledge
.
. Reset
.
.
.
8 5
.
. 3
6
Alarms Faults Isolation Information
1 2 3
➊ Text display
with yellow illumination and associated keys. Presentation:
• yellow for all messages or during operator actions (automatically switched off when
not operated)
• dark, if no danger message is pending and no operator activity is in progress
➌ Display fields
• partially with function keys
• display the operating states of the fire detection system
➍ <Acknowledge> key
• to confirm that the operator has received a message
• message not acknowledged ➜ yellow LED is flashing
➎ <Reset> key
• to reset all pending alarms
• message acknowledged, but not reset ➜ yellow LED is flashing
82
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
➐ Keyswitch
• device for access control (optional for B3Q660)
Where do you All the panel elements for display and operation are described in specific chapters where
find a detailed each function is described in detail.
description?
However a little more detailed views of these elements will follow on the next pages.
Panel variants
Standard panel B3Q660 Nordic panel B3Q680
ALARM ALARM
. Acknowledge . Acknowledge
. .
. Reset . Reset
. .
. .
. .
. .
. .
Alarm device Alarm device Alarm device Premises 4 5 6 Alarm device Alarm device Alarm device Premises 4 5 6
active fault off manned active fault off manned
Remote alarm Remote transmission Remote alarm System Remote alarm Remote transmission Remote alarm System
active fault off on
7 8 9 active fault off on
7 8 9
Alarm delay System Detector Alarm delay System Detector
off fault test mode
Õ 0 ✓ off fault test mode
Õ 0 ✓
83
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Types of Visual As we have seen there are the following visual indicators:
Indicators • Display
• LEDs
Visual Indica- The different visual indicators can be found in the following figure:
tors
ALARM
. Acknowledge
.
. Reset
LEDs .
.
.
.
.
LEDs
84
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Types of • Danger managing operations must be easily accessible. Easy handling is also required for
Operation some frequently used functions.
They are called 'primary functions' and are accessed via 'primary menu' or by function
keys.
• Other operations of lower importance or lower frequency of occurrence need not have
such a subtle access. They are accessed via 'main menu'
Function Keys To operate the AlgoPilot panel a variety of function keys are provided. These keys allow di-
rect access to specific functions.
Numeric Used for the entry of numeric values such as passwords, or addresses.
Keypad The numeric keypad also includes the ok key (<✓ >) and the cancel key (<Õ>).
Keyswitch a somehow special access element is the keyswitch. However it is optional and therefore not
always equipped.
Operation The different operation elements can be found in the following figure.
Elements
ALARM
. Acknowledge
.
. Reset
.
.
.
.
.
Numeric keypad
Alarms Faults Isolation Information
1 2 3
Keyswitch
85
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Idle Display
Introduction The idle display is shown if the system is in normal operation state and if there is no mes-
sage to be displayed.
04-SEP-2002 10:35
Siemens AlgoRex
Fire Detection System
Version EP7F
Responsible
John Example / Phone 6789
Operate..
86
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Introduction • Many interactions between user and system take place via display and softkeys.
• The display serves not only to show system states, it also provides a menu which can be
operated via associated softkeys.
Operating If there is no operating access when starting to operate, the system asks to log in.
access
Example of The system gives the user the information about 2 pending alarms. At the same time the ap-
user interaction propriate menu is displayed.
via menu Via associated softkeys the user can
(softkeys) • Call the intervention text (➊)
• Display the functions for the selected message (➋)
- or -
• Change to the main menu (➌)
- or -
• Display the elements in alarm (➍)
3 Softkeys 3 Softkeys
(Menu selection keys) (Menu selection keys)
87
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Naming of The name of the softkey explains the functionality behind it. It may be a function which is
softkeys executed immediately, e.g. <LED TEST> or it may lead to a submenu, e.g. <HARDWARE
level..>, with another set of functions behind.
There are also some predefined navigation softkeys.
Softkey • Softkeys which are followed by 2 dots (..) signify that there is another menu behind.
presentation Example: <Operate..>, <HARDWARE level..>
• Softkeys without these dots are commands which are immediately executed.
Example: <LED TEST>, <Back to MAIN MENU>
Primary menu By default the primary menu is displayed. The softkeys vary depending on the state of the
system:
With message(s)
Without messages
Alarm message other message
88
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Main menu The main menu consists of up to 6 predefined softkeys. One of them is the navigation soft-
key <Escape>, which leads back to the primary menu. With the other 5 softkeys all available
functions of the system can be accessed.
Direct access..
Settings.. Browse..
Alarming.. Escape
Submenu Softkeys which are followed by 2 dots (..) lead to a submenu. As well as the primary or the
main menu a submenu can contain softkeys for executable functions or softkeys to access
others submenus.
Submenus denote a hierarchy. This leads to a menu tree.
Extended menu If there are too many functions on the same hierarchical level to be displayed, the menu may
be extended. This is not an extension like a submenu, for all softkeys still are on the same
hierarchical level.
State depend- The menu only shows allowed functions. It also considers the state of the actual part of the
ency system, e.g. zones.
Example:
THEN
The zones are switched immediately
with these commands
THEN
The zones are switched via
this submenu
89
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Menu Navigation
Introduction This chapter describes how to navigate on the different menu levels and how to change from
one level to another.
Operating If there is no operating access when starting to operate, the system asks to log in.
access
Navigation • You can change from primary menu to main menu and vice versa.
paths • From the main menu you can enter into submenus which may call other submenus.
• From a submenu you can return back either to the calling level or directly to the main
menu.
• Within extended menus you can switch back and forth.
• There are some predefined navigation softkeys.
Accessing To operate messages in the display, select the specific message by using the category se-
message spe- lection keys and the display scroll keys. Then select softkey <Functions for sel. mes-
cific functions sage..> to get the menu with all available functions for that specific message.
Example: As many submenus exist, it does not make sense, to list all possible submenus. But let's
have an example:
Entering a Via main menu we can enter submenu <Alarming..> and from there go to submenu <Alarm
submenu horns..>, where we have access to the following functions:
• <Alarm horn -> START>
• <Alarm horn -> TEST>
• <Alarm horn -> OFF>
Returning from The navigation softkeys to go back to the calling menu depend on the context. But at least
a submenu one navigation softkey (<Back> or <Back to MAIN MENU>) is included in a submenu.
Extended menu To switch back and forth within the hierarchical equal functions the softkeys
<More functions..> and <Previous functions..> are provided. This is comparable to scroll-
ing on a display.
90
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Predefined These softkeys have always the same functionality which is not depending on what level of
navigation the tree they are called.
softkeys
See table below.
The navigation to log in and out is treated in chapter "Login / Logout Navigation Overview"
on page 99.
91
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
User Category
What is it? There are several categories of users. Each category has its own privileges for operation.
Password
Keyswitch • Used to grant access to users possessing a key. So these users need not know a code.
• Access to different access levels is not possible.
• The keyswitch is optional, i.e. it is not always equipped.
92
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Access Level
Effect of ac- The range of accessible functions as well as the visible softkeys depend on the given access
cess levels level.
☞ see chapter "Function Lists 4" on page 125.
How to change There are two ways to change the access level:
access level • Password entry
• Actuating the keyswitch (if equipped)
• As a mixed form it is possible to actuate the keyswitch (if equipped) to get access level 2.1
e.g. and later to enter password to get access to a higher level.
When can ac- Changing of access level is only possible if the primary menu is selected.
cess levels be You can start to operate with one access level and then change to another.
changed
Assigning func- The range of accessible functions is defined for each access level by the service engineer.
tions to access
levels
93
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Starting to operate
Starting to op- • You can just start to operate. If access has not yet been granted, you are asked to log in.
erate This method is mainly used with password access.
- or -
Start
You decide to just trying You decide to first enter
to start to operate the password before
starting to operation
No Yes
Log in first?
No
Login
procedure
Continue
to operate
End
94
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Login
ALARM
. Acknowledge
.
. Reset
.
.
.
.
.
1
Logged out
Turn key to
horizontal
position
Logged in
NOTE:
The password entry procedure is described in detail below.
95
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Login, Continued
Start
Enter digits
<0..9>
Yes
Press key Wrong
<Õ> digit?
No
No
Password
completed?
Yes
Press key
<✓ >
- or -
select softkey
<ok>
End
96
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Logout
What is it? Logout sets the access level back to access level 1.
Logout by Operating is inhibited automatically if no key is pressed within a certain time (timeout = 1..10
timeout minutes or 0. Timeout = 0 means: no logout timeout. Timeout is set by the service engineer).
Of course there is no automatic logout if the key is in horizontal position.
Logout by Key- This picture shows how an explicit logout can be enforced (if the key is not in horizontal posi-
board tion).
<Back> <Õ>
<Escape> <Õ>
<Õ>
Logged out
97
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Logout, Continued
Logged in
Turn key
to vertical
position
Remove key
Logged out
98
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Goal To close the login / logout topic, this chapter shows an overview of all login and logout possi-
bilities.
Navigation Navigation during the login/logout phase is linked closely with menu operations. See follow-
paths ing diagram:
Logged IN Operate
Primary Menu Main Menu
Escape,
Õ
Logout Login to primary menu Change access level Login to main menu
99
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Message Categories
Introduction Messages are distinguished according to their nature and importance. They are thus divided
in categories.
Presentation on
the panel Alarms Faults Isolation Information
category category category category
1 2 3 4
If there are pending messages the associated LED of that category is lit up.
Characteristics The following table shows the characteristics of the different messages.
100
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
How to display • The different messages can be polled by pressing the appropriate key: ➊, ➋, ➌, or ➍.
messages • If several messages are pending, they can be scrolled with the display scroll keys.
NOTE Switching from one message category to another is always possible by pressing the corre-
sponding selection key. If a lower priority is selected, after a short timeout the system always
goes back to that message category with the highest priority.
☞ See chapter "Timeouts" on page 124.
Sample ISOLATION
01 Detector zone OFF
Total: 1
Functions for
sel. message..
Operate..
Functions for
sel. message..
Operate..
NOTE If in FAULT, ISOLATION and INFORMATION categories all messages can be displayed in
'full message' mode the softkeys <short message> and <full message> are not available.
101
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
How alarm Alarms are shown in the display and with specific LEDs.
messages are LEDs indicating alarm states are generally red.
displayed
ALARM 8
1 9
. Acknowledge
.
. Reset
.
.
.
. 10
.
3
5 Alarm device
active
Alarm device
fault
Alarm device
off
Premises
manned
4 5 6
Remote alarm Remote transmission Remote alarm System
6 active fault off on
7 8 9
Alarm delay System Detector
7 off fault test mode Õ 0 ✓
102
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Remote alarm
➏ LED 'Remote alarm active' lit up if alarm remote transmis-
active sion is active.
➍ Key <Alarms>
Alarms Pressing this key switches forth an back from the first (old-
est) to the last alarm.
If there are more alarms than can be displayed on one page
it switches forth and back the pages.
103
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
How to handle • If zone alarm messages are not resettable then a special dialogue is displayed which al-
non resettable lows to switch off directly all the concerned zones.
alarms • This dialogue is only displayed if the number of zone alarm messages which are not re-
settable does NOT exceed a certain number.
• This number of alarm messages can be programmed by the service engineer.
104
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
105
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Introduction More information about alarm messages can spontaneously be displayed or can be polled by
softkeys.
Plan number This is a reference number (e.g. room number) which can optionally be displayed.
Plan number
Logical address
Guidance text Guides the operator to do the correct actions in the given situation.
FIRE BRIGADE requested Total: 2
01 AUTOM.FIRE ALARM
Main building / 1st floor
Room 104
02 AUTOM.FIRE ALARM
Guidance text Main building / 1st floor
Corridor
Displays the
elements in alarm
106
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Intervention • The intervention text is an additional information to an alarm message and can optionally
text be programmed by the service engineer.
• 16 different intervention texts with each up to 6 lines can be programmed.
• It can be called by softkey. In addition to that it can be configured that the intervention text
is displayed spontaneously after acknowledging.
FIRE BRIGADE requested Total: 2
01 AUTOM.FIRE ALARM
Main building / 1st floor
Room 104
02 AUTOM.FIRE ALARM Menu selection
Main building / 1st floor key to display the
Corridor
interventionn text
107
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Sample alarm
nd
situation _2 Alarm message_
Zone 'Corridor'
Corridor
Room 101
Room 102
Room 103
Room 104
st
_1 Alarm message_
Zone 'Room 104'
Element information
108
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Guidance text Text which guides the operator to react correctly in an exceptional situation.
109
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
How does CAC When the system operates in 'Manned' mode, manual call points and automatic fire detec-
work? tors trigger different actions in the event of an alarm.
manned or
Alarm unmanned manned Operating mode
unmanned
event F
Local
alarm
<Acknowledge>
V1 pressed
running
'Emergency' 'Minor incident'
V1 = 0
<Alarm delay OFF>
- or -
F pressed V2 <Reset> pressed
running
V2 = 0
General
alarm
Remote Normal
alarm operation
Alarm ack- • This is a countdown time that is active for automatic detectors when the system operates
nowledgement in 'Manned' mode.
time 'V1' • Checks whether someone acknowledges the danger alarm message within the prepro-
grammed time.
• On expiration of this time the alarm is transmitted to the fire department.
• The remaining time is displayed in minutes and seconds.
Alarm investi- • This is a countdown time that is active for automatic detectors when the system operates
gation time 'V2' in 'Manned' mode.
• Limits the time for investigating the fire location to an individually programmed time.
• On expiration of this time the alarm is transmitted to the fire department.
• The remaining time is displayed in minutes and seconds.
• In case of minor incidents, an alarm must be reset before V2 expires to avoid unnecessary
alarm remote transmission.
110
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Dependencies Whether CAC applies or not depends on the operating mode and on the detector type:
111
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Fault
What is 'Fault' Abnormal system states e.g. caused by defective devices or installation.
Isolation
What is 'Isola- 'Isolation' denotes the state where one or several parts of the system are temporarily
tion' switched off.
Examples Some parts of the system which can temporarily be isolated: Zones, elements, horns, remote
transmissions, printers.
Isolating system parts disables their functionality. Isolation has to be used with extreme care.
i As soon as conditions have returned to normal, isolated system parts must be immediately
switched on again.
Information
112
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Service Functions
Remote Transmission
What is In the event of a FIRE ALARM the remote transmission calls the fire department.
'Remote trans- For FAULT there is normally a separate transmission path.
mission'?
Types of 'Re- There are three types of remote transmissions which can be switched off separately:
mote trans- • Remote transmission of fire alarms
mission' • Remote transmission of fault messages
• Remote transmission of other messages
How to switch All types of remote transmission can be switched off/on by menu.
off the 'Remote However for the remote transmission of fire alarms in addition to that a separate function
transmission'? key is provided.
LED and key The following LED and key are affected:
for alarm re- • Key <Remote alarm off> ➊ on the control panel performs switching over.
mote transmis- • LED ➋ indicates the 'OFF' state.
sion
Testing the The remote transmission must periodically be checked by activating a manual call point.
'Remote trans-
mission'
NOTE:
The fire department must be notified before the test is initiated.
113
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Alarm devices
LED and key to The following LED and key are affected:
switch off • Key <Alarm device off> ➊ on the control panel performs switching over.
alarm devices • LED ➋ indicates the 'OFF' state.
How to activate The alarm devices of a specific area can be activated by menu.
alarm devices? However in addition to that a separate function key is provided.
LED and key to The following LED and key are affected:
activate alarm • Key <Alarm device active> ➊ on the control panel performs switching over.
devices • LED ➋ indicates the 'active' state.
How to test The alarm devices can only be tested by menu (no separate function key provided).
alarm devices?
114
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Detector Test
What is the 'De- The mode 'Detector test' allows individual on-site function testing of automatic fire detectors
tector test' and manual call points without generating an alarm message.
mode for ?
Automatic fire Automatic fire detectors are actuated with a special detector tester.
detectors Interactive detectors are set to the special parameter set ’Test’ in order to achieve a fast ac-
tivation with the detector tester.
Manual call Manual call points are activated depending on the type:
points • From externally without breaking the glass pane or opening the housing.
• Simply by opening the door of the manual call point.
Test alarm Test alarm is the active state of automatic fire detectors or manual call points in 'Detector
test' mode. A test alarm does not generate a danger message in the control panel. That
means that neither acoustical alarm devices nor remote transmission or any other control
functions are activated.
Test alarms are recorded in the event memory and logged spontaneously, if a printer is con-
nected.
Recommenda- • Perform the function test periodically. The interval of this test is determined by the service
tions for detec- engineer.
tor test • Switch only the fire detectors of one SECTION at a time to 'Detector test', never the entire
building.
• For manual call points the function test needs to be performed only based on a spot-
check.
• Test automatic fire detectors and manual call points of the same room always separately.
• Do not set them to 'Detector test' simultaneously.
• After the test work has been completed immediately cancel the mode 'Detector test'.
Test timeout A timeout can be programmed per zone after which the zone switches back from operation
mode 'Test' to the previously selected mode.
☞ For more information about testing automatic detectors and manual call points see the
i following chapters:
• "How to TEST AUTOMATIC DETECTORS ?" on page 47
• "How to TEST MANUAL CALL POINTS ?" on page 48
115
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
116
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
What can be Interactive detector(s) can temporarily be set to a less sensitive parameter set, e.g. while
done? work is in progress (alternative to mode 'Renovation').
What is the • To simplify the comparison of smoke sensitivities between the parameter sets, we are
'Smoke Sensi- specifying an AlgoRex smoke sensitivity index.
tivity Index'? • Please note, that this index is a relative figure, where ’2’ means an increased sensitivity by
a factor of 2 (compared to the parameter set with index ’1’).
• Therefore the detector will alarm at half the smoke density if measured in the CEN smoke
tunnel according to EN54.
• An AlgoRex smoke sensitivity index of ’0’ means 'no alarm with smoke only'.
What is the Approximate response time when activating the detector with Siemens test gas in normal
'Response operating state (the above stated values in seconds cannot be compared with a real fire
Time'? situation)
☞ For details regarding ’detector parameter set’ call your local service organization of
i Siemens Building Technologies
117
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Response time
Available parameter sets
Smoke sensitivity index Mode Mode
and detector types
’manned’ ’unmanned’
DO: 2 90sec 90sec
APS005S DOT: 1 without heat influence
110sec 110sec
2 with max. heat influence
DO1151/52
DO: 2 60sec 30sec
APS006S DOT: 1 without heat influence
60sec 40sec
2.5 with max. heat influence
DO: 4 60sec 30sec
APS007S DOT: 2 without heat influence
60sec 40sec
5 with max. heat influence
DOT1151/52 DO: 4 90sec 90sec
APS009S DOT1151-Ex DOT: 2 without heat influence
110sec 110sec
4 with max. heat influence
1 without heat influence
APS015S 85sec 85sec
2 with max. heat influence
2 without heat influence
APS019S 85sec 85sec
4 with max. heat influence
4 without heat influence
APS081S 60sec 30sec
8 with max. heat influence
DOT1151/52 Similar as APS005S but with
APS082S
DOT1151-Ex adapted heat detection part
to fulfill also the Chinese
for China only
regulations for heat detectors
1.4 without heat influence
APS085S 75sec 45sec
4.3 with max. heat influence
20→30 increasing sensitivity with a
APS070SH very slowly developing 45sec 45sec
smouldering fire
APS071SH DO1153 20 45sec 45sec
APS072SH for 12 30sec 30sec
ASD-systems
APS073SH only 6 30sec 30sec
118
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
The detector DOTE1152 is a smoke detector according to EN54-7 with highest performance.
It is not a carbonmonoxide warning device and there will never be a carbonmonoxide warn-
ing displayed at the control unit.
no smoke
1 → 2 without heat influence 110 → 110 →
APS207SE response
2 → 5 with max. heat influence 60sec 40sec
(only heat)
no smoke
1 → 2 without heat influence 110 → 110 →
APS213SE response
2 → 5 with max. heat influence 60sec 40sec
(only heat)
DOTE1152 no smoke
2 → 4 without heat influence 40 →
APS216SE 60sec response
5 → 8 with max. heat influence 30sec
(only heat)
all parame-
ter sets for identical to DOT115x
DOT115x
119
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
System Functions
Printer
When does the • Normally the printer (if installed) operates in active stand-by.
printer have to • It is only switched off in special cases (for example to change the paper or during test and
be switched maintenance activities).
OFF? • The printer can be switched OFF and ON via the menu.
• The 'OFF' state is shown on the display.
LED Test
What is the For testing the correct functioning of all indicators (LEDs), the display and the alarm buzzer.
'LED test' used
for ? All visual and audible devices of the control panel are activated for a few seconds.
• Time and date are displayed during the time/date adjust procedure.
• It is also showed on the idle display.
120
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Miscellaneous
What is an It normally covers a whole building or part of a building and represents also the operating
'Area'? level. This is the logical designation for several, usually adjacent sections.
Sample area
AREA
Area 'Main building'
01 Main building
02 Factory
What is a It normally covers a floor or part of a floor in a building. This is the logical designation for
'Section'? several, usually adjacent zones.
Sample section
SECTION 'fire'
st
Section '1 floor' 01 Ground floor
02 First floor
03 Second floor
Select AREA
CALL POINT zone Select ZONE
functions..
DETECTOR zone Back to MAIN MENU
functions..
What is a It normally comprises one room of a building (with collective detectors => several rooms).
'Zone'? It is the logical designation of a detector group containing at least one detector.
Automatic fire detectors, manual call points and control outputs are always assigned to dif-
ferent ZONES.
For this reason we have
• zones comprising automatic fire detectors
• zones comprising manual call points
• zones comprising control in-/outputs
Sample zone
ZONES 'fire'
01 Room 103
02 Room 104
03 Room 105
Zone 'Room 104'
121
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
What does it The AlgoRex system can be configured to work differently depending on whether the person
mean? responsible is present or absent.
LED and key The following LED and key are affected:
1 2 ON = 'manned'
LED ➊
OFF = 'unmanned'
Premises
manned Key ➋ Performs manual switching over
For what sys- • The operating states 'manned' and 'unmanned' are relevant for systems in which the sig-
tems does this nals for automatic fire detectors and manual call points are processed differently, that
apply? means, the Cerberus Alarm Concept is activated.
• Additionally, interactive detectors can have a varying sensitivity depending on the operat-
ing states 'manned' and 'unmanned' and on their parameter set.
NOTE If several organizationally autonomous systems are operated via a common multi-area ter-
minal and not all areas are in the same state, the 'Premises manned' state indicator ➊ is
flashing.
☞ See also chapter "How to SWITCH PREMISES MANNED / UNMANNED ?" on page 26
in section "Operating Instructions ➊➋➌".
Automatic Automatic switching over from 'manned' to 'unmanned' (or vice versa) can be programmed
switchover by the service engineer.
Manual switch- The switchover from 'manned' to 'unmanned' (or vice versa) is also possible via the menu.
over via menu
122
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
indicator ➊
is ON 'manned' 'unmanned'
press key ➋
<Premises manned>
to switch over
If there is no opera-
ting access, then the
password query is
startet Password
entry
Confirmation query
is displayed
press key ➌
<✓ >
to confirm
Display shows the
new operating state
1 2
Alarms Faults Isolation Information
1 2 3
Alarm device
active
Alarm device
fault
Alarm device
off
Premises
manned
4 5 6
Remote alarm Remote transmission Remote alarm System
active fault off on
7 8 9
Alarm delay System Detector
off fault test mode Õ 0 ✓
NOTE:
• If there is only one single area switching is done immediately.
• If there are several areas the menu is called automatically and switching has to be done
via menu.
• Corresponding operator access level is required.
123
Fire & Security Products 11.2002
Siemens Building Technologies Group
Basic System Knowledge &
Timeouts
What types In AlgoRex on the terminal the following types of timeout are known:
exist? • Operation timeout
• Backlight timeout
• Logout timeout
• Result timeout
How is it A timeout is started with each manual operation. If the timeout is still running, it is restarted
triggered? with each following input.
Operation Defines the delay time the system waits after an operation before it changes back to display
timeout the current messages.
This timeout can be configured for operation with and without pending alarms.
Backlight Defines how long the display illumination remains on after a user input. This timeout can be
timeout configured per message category ('Danger', 'Fault', Isolation', 'Information').
Logout timeout Defines the delay time after an user input until the system performs an automatic logout.
Result timeout Defines how long the result of an operation (e.g. INFORMATION 'function unit') is shown on
the display.
How can the All these timeouts can be configured by the service engineer.
Timeouts be
configured?
124
Fire & Security Products 11.2002
Siemens Building Technologies Group
Function Lists 4
Function Lists 4
Access Level
1 2.1 2.2 3
➥ Area
➥ Switch to MANNED - ✔ ✔ ✔
➥ Switch to UNMANNED - ✔ ✔ ✔
➥ Switch ALL to MANNED - ✔ ✔ ✔
➥ Switch ALL to UNMANNED - ✔ ✔ ✔
➥ Poll EVENT MEMORY - - ✔ ✔
➥ ALL messages - - ✔ ✔
➥ ALARM messages - - ✔ ✔
➥ FAULT messages - - ✔ ✔
➥ ISOLATION messages - - ✔ ✔
➥ INFORMATION messages - - ✔ ✔
➥ TEST ALARM messages - - ✔ ✔
➥ Section
➥ DETECTOR zone functions - ✔ ✔ ✔
All DETECTOR zones -> OFF
➥ - ✔ ✔ ✔
(with/without time limit)
➥ All DETECTOR zones -> ON - ✔ ✔ ✔
➥ All DETECTOR zones -> TEST - ✔ ✔ ✔
➥ All DETECTOR zones -> TEST OFF - ✔ ✔ ✔
All DETECTOR zones -> INSTALLATION
➥ - ✔ ✔ ✔
TEST
All DETECTOR zones -> INSTALLATION
➥ - ✔ ✔ ✔
TEST OFF
125
Fire & Security Products 11.2002
Siemens Building Technologies Group
Function Lists 4
: Access Level
1 2.1 2.2 3
➥ Zone 'autom. detectors'
➥ Zone -> OFF (with/without time limit) - ✔ ✔ ✔
➥ Zone -> ON - ✔ ✔ ✔
➥ TEST/RENOVATION/INST.TEST functions - ✔ ✔ ✔
➥ Zone -> TEST - ✔ ✔ ✔
➥ Zone -> TEST OFF - ✔ ✔ ✔
➥ Zone -> INSTALLATION TEST - ✔ ✔ ✔
➥ Zone -> INSTALLATION TEST OFF - ✔ ✔ ✔
➥ Zone -> RENOVATION - ✔ ✔ ✔
➥ Zone -> RENOVATION OFF - ✔ ✔ ✔
➥ Activate FAULT TEST - ✔ ✔ ✔
➥ ACTIVATE zone - - - ✔
➥ ACTIVATE zone - - - ✔
➥ DEACTIVATE zone - - - ✔
126
Fire & Security Products 11.2002
Siemens Building Technologies Group
Function Lists 4
: Access Level
1 2.1 2.2 3
➥ Element 'interactive'
➥ Poll INFORMATION - ✔ ✔ ✔
➥ Element -> OFF - ✔ ✔ ✔
➥ Element -> ON - ✔ ✔ ✔
➥ Device replace mode -> ON - - ✔ ✔
➥ Device replace mode -> OFF - - ✔ ✔
➥ ACTIVATE element - - ✔ ✔
➥ DEACTIVATE element - - ✔ ✔
➥ Parameter set functions - - - -
➥ CHANGE parameter set - - - -
➥ Parameter set -> DEFAULT - - - -
➥ Element 'others'
➥ Poll INFORMATION - ✔ ✔ ✔
➥ Element -> OFF - ✔ ✔ ✔
➥ Element -> ON - ✔ ✔ ✔
➥ Device replace mode -> ON - - ✔ ✔
➥ Device replace mode -> OFF - - ✔ ✔
➥ ACTIVATE element - - ✔ ✔
➥ DEACTIVATE element - - ✔ ✔
➥ Control elements
➥ Poll INFORMATION - ✔ ✔ ✔
➥ Element -> OFF - ✔ ✔ ✔
➥ Element -> ON - ✔ ✔ ✔
➥ Device replace mode -> ON - - ✔ ✔
➥ Device replace mode -> OFF - - ✔ ✔
➥ ACTIVATE element - - ✔ ✔
➥ DEACTIVATE element - - ✔ ✔
127
Fire & Security Products 11.2002
Siemens Building Technologies Group
Function Lists 4
Browse EXTINGUISHING..
Access Level
1 2.1 2.2 3
➥ Area
See chapter "Browse FIRE DETECTION.."
➥
beginning on page 125
➥ Section
➥ Detector zone functions - ✔ ✔ ✔
See chapter "Browse FIRE DETECTION.."
➥
beginning on page 125
➥ Extinguishing functions - ✔ ✔ ✔
➥ Blocking functions - ✔ ✔ ✔
➥ BLOCKING autom. & man. exting. - ✔ ✔ ✔
➥ ENABLE autom. & man. exting. - ✔ ✔ ✔
➥ BLOCKING autom. exting. - ✔ ✔ ✔
➥ ENABLE autom. exting. - ✔ ✔ ✔
➥ Test functions - - - ✔
➥ Initiate TEST 'horn' - - - ✔
➥ Initiate TEST 'warning panel' - - - ✔
➥ Exting. control -> TEST - - - ✔
➥ Exting. control -> TEST OFF - - - ✔
128
Fire & Security Products 11.2002
Siemens Building Technologies Group
Function Lists 4
: Access Level
1 2.1 2.2 3
➥ Zone 'autom. detectors'
See chapter "Browse FIRE DETECTION.."
➥
beginning on page 125
➥ Element 'interactive'
See chapter "Browse FIRE DETECTION.."
➥
beginning on page 125
➥ Element 'others'
See chapter "Browse FIRE DETECTION.."
➥
beginning on page 125
➥ Control elements
See chapter "Browse FIRE DETECTION.."
➥
beginning on page 125
129
Fire & Security Products 11.2002
Siemens Building Technologies Group
Function Lists 4
Browse CONTROLS..
Access Level
1 2.1 2.2 3
➥ Area
See chapter "Browse FIRE DETECTION.."
➥
beginning on page 125
➥ Section
➥ All ZONES -> OFF - ✔ ✔ ✔
➥ All ZONES -> ON - ✔ ✔ ✔
➥ Zone
➥ Zone -> OFF (with/without time limit) - ✔ ✔ ✔
➥ Zone -> ON - ✔ ✔ ✔
➥ ACTIVATE zone - - - ✔
➥ DEACTIVATE zone - - - ✔
➥ Element 'digital'
See chapter "Browse FIRE DETECTION.."
➥
beginning on page 125
➥ Control elements
See chapter "Browse FIRE DETECTION.."
➥
beginning on page 125
130
Fire & Security Products 11.2002
Siemens Building Technologies Group
Function Lists 4
HARDWARE level..
Access Level
1 2.1 2.2 3
➥ Station 'CT11' / 'CI11'
➥ Poll INFORMATION - - ✔ ✔
➥ Printer -> OFF - - ✔ ✔
➥ Printer -> ON - - ✔ ✔
➥ Initiate PRINTER TEST - - ✔ ✔
➥ LED TEST ✔ ✔ ✔ ✔
➥ Delete EVENT MEMORY - - - ✔
➥ Poll EVENT MEMORY - ✔ ✔ ✔
➥ ALL messages - ✔ ✔ ✔
➥ ALARM messages - ✔ ✔ ✔
➥ FAULT messages - ✔ ✔ ✔
➥ ISOLATION messages - ✔ ✔ ✔
➥ INFORMATION messages - ✔ ✔ ✔
➥ TEST ALARM messages - ✔ ✔ ✔
➥ Station 'CC11'
➥ Poll INFORMATION - - ✔ ✔
➥ Printer -> OFF - - ✔ ✔
➥ Printer -> ON - - ✔ ✔
➥ Initiate PRINTER TEST - - ✔ ✔
➥ Delete EVENT MEMORY - - - ✔
➥ Poll EVENT MEMORY - ✔ ✔ ✔
➥ ALL messages - ✔ ✔ ✔
➥ ALARM messages - ✔ ✔ ✔
➥ FAULT messages - ✔ ✔ ✔
➥ ISOLATION messages - ✔ ✔ ✔
➥ INFORMATION messages - ✔ ✔ ✔
➥ TEST ALARM messages - ✔ ✔ ✔
:
131
Fire & Security Products 11.2002
Siemens Building Technologies Group
Function Lists 4
: Access Level
1 2.1 2.2 3
➥ FU 'DS11i line card' / 'DS11i line'
➥ Poll INFORMATION - ✔ ✔ ✔
➥ Re-configure D-Bus - - ✔ ✔
➥ Device read-in - - - ✔
➥ Localization by INSERTION - - - ✔
➥ Localization by ACTIVATION - - - ✔
➥ Detector line -> NORMAL MODE - - - ✔
➥ Detector line -> OFF - - - ✔
➥ Stub line forward - - - ✔
➥ Stub line backward - - - ✔
➥ Detector line -> TEST - - - ✔
➥ Detector line -> TEST OFF - - - ✔
➥ FU 'A+ line'
➥ Poll INFORMATION - ✔ ✔ ✔
➥ Re-configure D-Bus - - ✔ ✔
➥ Re-address D-Bus - - ✔ ✔
➥ Device read-in - - - ✔
➥ Localization by INSERTION - - - ✔
➥ Localization by ACTIVATION - - - ✔
➥ Detector line -> NORMAL MODE - - - ✔
➥ Detector line -> OFF - - - ✔
➥ Detector line -> TEST - - - ✔
➥ Detector line -> TEST OFF - - - ✔
132
Fire & Security Products 11.2002
Siemens Building Technologies Group
Function Lists 4
: Access Level
1 2.1 2.2 3
➥ FU 'CBA line card'
➥ Poll INFORMATION - ✔ ✔ ✔
➥ FU 'CBA line'
➥ Poll INFORMATION - ✔ ✔ ✔
➥ Re-configure D-Bus - - ✔ ✔
➥ Detector line -> OFF - - - ✔
➥ Detector line -> NORMAL MODE - - - ✔
➥ Detector line -> TEST - - - ✔
➥ Detector line -> TEST OFF - - - ✔
➥ FU 'Others'
➥ Poll INFORMATION - ✔ ✔ ✔
133
Fire & Security Products 11.2002
Siemens Building Technologies Group
Function Lists 4
Alarming..
Access Level
1 2.1 2.2 3
➥ Alarm horns
➥ Alarm horn -> ON - ✔ ✔ ✔
➥ Alarm horn -> OFF - ✔ ✔ ✔
➥ Alarm horn -> START - ✔ ✔ ✔
➥ Alarm horn -> STOP - ✔ ✔ ✔
➥ Alarm horn -> TEST - ✔ ✔ ✔
➥ Remote transmission
➥ REMOTE transm. 'fire' -> ON - ✔ ✔ ✔
➥ REMOTE transm. 'fire' -> OFF - ✔ ✔ ✔
➥ REMOTE transm. 'fault' -> ON - ✔ ✔ ✔
➥ REMOTE transm. 'fault' -> OFF - ✔ ✔ ✔
➥ REMOTE transm. 'other' -> ON - ✔ ✔ ✔
➥ REMOTE transm. 'other' -> OFF - ✔ ✔ ✔
➥ Alarm counters
➥ Poll counter 'REMOTE ALARMS' - ✔ ✔ ✔
➥ Poll counter 'FIRE ALARMS' - ✔ ✔ ✔
➥ Reset counter 'FIRE ALARMS' - - - ✔
134
Fire & Security Products 11.2002
Siemens Building Technologies Group
Function Lists 4
Direct Access..
Access Level
1 2.1 2.2 3
➥ Enter LOGICAL ADDRESS (CSX) - ✔ ✔ ✔
➥ Enter GROUP/ADDRESS - - - -
Settings..
Access Level
1 2.1 2.2 3
➥ Decrease display contrast - ✔ ✔ ✔
➥ Increase display contrast - ✔ ✔ ✔
➥ Decrease buzzer intensity - ✔ ✔ ✔
➥ Increase buzzer intensity - ✔ ✔ ✔
➥ Reconfigure C-Bus - - ✔ ✔
➥ Set TIME and DATE - - ✔ ✔
135
Fire & Security Products 11.2002
Siemens Building Technologies Group
Siemens Building Technologies AG
Alte Landstrasse 411
CH-8708 Männedorf
Tel. +41 1 - 922 61 11
Fax +41 1 - 922 64 50
www.cerberus.ch