Sesi-Tspl-Opn-Sop-Btg-002 (FDF)
Sesi-Tspl-Opn-Sop-Btg-002 (FDF)
Sesi-Tspl-Opn-Sop-Btg-002 (FDF)
Table of Content
1 PURPOSE.......................................................................................................................3
2 SCOPE............................................................................................................................3
3 INPUT............................................................................................................................3
4 OUTPUT........................................................................................................................3
5 RESPONSIBILITY.............................................................................................................3
6 SYSTEM DESCRIPTION....................................................................................................3
7 EQUIPMENT DETAILS.....................................................................................................3
7.1 TECHNICAL SPECIFICATIONS OF FD FAN:................................................................................ 3
7.2 MOTOR SPECIFICATION:..................................................................................................... 4
7.3 FDF PERFORMANCE SPECIFICATION:........................................................................................4
7.4 OIL SYSTEM MAIN TECHNICAL SPECIFICATION............................................................................5
8 ELECTRICAL FEEDER DETAILS..........................................................................................5
9 ABBREVIATION..............................................................................................................6
10 STARTING PROCEDURE...................................................................................................6
10.1 PRESTART-UP CHECKS:.......................................................................................................6
10.2 TAKING FIRST FAN IN SERVICE:............................................................................................9
10.3 TAKING SECOND FAN IN SERVICE:........................................................................................9
11 SHUTDOWN PROCEDURE.............................................................................................10
12 ISOLATION PROCEDURE WITH CHECK LIST....................................................................10
13 NORMALIZATION PROCEDURE WITH CHECK LIST..........................................................10
NORMALIZATION CHECK LIST: REFER ANNEXURE-2.............................................................11
14 REFERENCE..................................................................................................................11
15 RECORD.......................................................................................................................11
16 SAFETY MEASURES.......................................................................................................11
17 ENVIRONMENT............................................................................................................11
1 PURPOSE
This procedure is intended to provide guidance and instructions for carrying out
start up and shut down of FD fan A & B during plant start-up .
2 Scope
This procedure is applicable to FD fan A & B located at boiler area of 3x660MW.
3 Input
Air, Power
4 Output
Secondary Air to Furnace
5 Responsibility
Boiler Field Engineer, Boiler Desk Engineer, Shift In-charge
6 System Description
The function of FD fan is to supply secondary air to furnace for efficient coal / oil
combustion in furnace. There are 2 FD fans (2x60% capacity). The fan is of axial
flow type and having blade pitch control system for air flow regulation. Blade
pitch is controlled by high pressure oil. Oil skid contains 2 HP pumps. Oil cooler
&filter are located in the return path of blade pitch control. There is provision of
SCAPH to improve the air temp of APH inlet during cold start-up and to minimise
chance of cold end corrosion. Fan bearings are cooled by bath oil cooling
system. Motor has anti friction bearings.
7 Equipment Details
7.1 Technical specifications of FD Fan:
SNO Project Unit Numerical value
1.
Fan model ASN 2880/ 1800
2.
Design flow M3/h 993600
3.
Regulator Type Moving blade adjustment
4.
Number of impellers stage 1
5.
Each blade number sheet 30
6.
Adjusting range of blade Degree 10-55
7.
First critical speed of fan r/min 1287
8.
Fan bearing type Rolling bearing
9.
Bearing lubrication way Oil bath lubrication
10.
Lubrication oil brand N46 turbine oil
11.
Bearing cooling water t/h no
12.
Bearing cooling way Natural cooling
SCAPH
Heat transfer area 395m2
9 Abbreviation
9.1. APH- Air pre-Heater
9.2. UOM- Unit of Measures
9.3. SADC- Secondary air Damper Control
9.4. OCW- Open circuit Cooling water
9.5. HP- High Pressure
9.6. LP- Low Pressure
10 Starting Procedure
Start permissive:
ID fan running.
FD fan has no protection stop.
FD fan stopped.
FD fan discharge damper closed.
Inlet moving blades closed (0%).
Sec air damper at APH outlet opened.
Other FD fan running or other fan outlet damper and sec air damper at APH
outlet opened with moving blades opened.
Lube oil pressure normal.
Lube oil tank level normal.
Fan/Motor bearing temperature not high
Modification Proposal Issue 01 Rev 0 Page 6 of 13
Document Control No SESI-TSPL-OPN-SOP-BTG-002 Date 22.09.2010
Prepared By. Reviewed By Approved by
TALWANDI SABO POWER LIMITED,
3 x 660MW POWER PLANT, MANSA.
SOP for Forced Draught Fan (FD Fan)
Protections:
Both ID fans tripped.
When both streams are in service, FD trips on corresponding ID fan trip.
FD fan running, 60secs and discharge damper closed.
Control oil pressure very low<0.8 Mpa. (LOGIC OFF).
Fan bearing vibration-H>4.6 mm/s, HH>7.1 mm/s, FDF trips when (X is H & Y
is HH) OR (Y is H & X is HH),delay 5 secs.
Fan bearing temperature very high>95 deg C (213 logic).
Motor bearing temperature very high>85 deg C.
Motor winding temperature very high>l25 deg C (3/6 logic)
Furnace pressure HHH after MFT >4.5 kpa , both FD fans trip.
10.3.4 Make blade pitch of both fan equal by parallel operation. After
getting desired condition of furnace draft & excess air. Put both
fan pitch control in auto and put master in AUTO.
10.3.5 If there is any considerable deviation between loadings of both
fans, give between pitch controls of fans to keep the fan's
current almost equal.
11 Shutdown Procedure
11.1. Take two mills out of service from five mill operation and keep the boiler
on operation by ensuring flame stability. Reduce the boiler load to 50%.
11.2. Take secondary air master control in manual.
11.3. Reduce gradually blade pitch of FD fan which is to be stopped and
increase blade pitch of other FD fan which is to be kept in service.
While executing this step watch on secondary air flow, secondary air
box inlet pressure, furnace to secondary air box differential pressure fan
header pressure and furnace draft and flame stability.
11.4. Reduce blade pitch to minimum gradually.
11.5. Check the current and vibration of running fan and get ensure for its
stability.
11.6. Stop the fan.
11.7. Ensure discharge damper closes in auto.
11.8. Stop oil pump after 2 hrs. After stopping fan if no reverse rotation is
observed
14 Reference
14.1. SEPCO FD Fan Manual
14.2. SEPCO Boiler O&M Manual
15 Record
15.1. Boiler Desk Operator Log Book
15.2. Boiler Field Operator Log Book
16 Safety Measures
16.1. Ensure WE's are worn. Ensure adequate lighting near the work place.
16.2. Ensure orderly execution of the entire activities with respect to
mechanical and electrical system.
16.3. Always wear Safety shoes, helmet and earplug.
16.4. While racking in and racking out the electrical breaker, wear mask Suit
and rubber gloves.
16.5. Before releasing the equipment for offline permit, ensure that the
equipment is electrically and mechanically isolated. Check FD fan Motor
body has two earthing strips.
16.6. Check before starting of Motor, Motor coupling has coupling guard.
17 Environment
17.1. While starting/stopping and during running of the equipment, check for
any kind of leakage/spillage, water leakage and for any abnormal sound
17.2. If any oil Leakage/Spillage is there, try to avoid the same spilling on the
ground by adopting temporary measures. Then inform to maintenance
department for arresting the problem online or offline depending upon
the condition. As a preventive measure avoid the spillage/leakage of oil,
maintenance team will be checking thoroughly the looseness of joints,
and healthiness of oil seals during preventive maintenance.
17.3. If any water leakage is there, inform to maintenance department for
arresting either on line or offline depending on the condition.
Modification Proposal Issue 01 Rev 0 Page 12 of 13
Document Control No SESI-TSPL-OPN-SOP-BTG-002 Date 22.09.2010
Prepared By. Reviewed By Approved by
TALWANDI SABO POWER LIMITED,
3 x 660MW POWER PLANT, MANSA.
SOP for Forced Draught Fan (FD Fan)