STRENGTH CALCULATION
Tank Identification : 0
Tank Size
Diameter Of Tank. D : 59.06 ( Ft ) 18,000 ( mm )
Radius Of Tank R : 29.53 (Ft) 9,000 (mm)
Height Of Tank. H : 32.81 ( Ft ) 10,000 ( mm )
Pumping Rates :
IN : 10,676 ( m3 / h )
OUT : 10,676 ( m3 / h )
Insulation : 0 mm NO
Shell Plate thickness are calculated By One-Foot Method in Accordance With……API 650
390×tb
W= = 0 in = 0 mm
√H.G
W = 20 in ( per API - 650 Section 3 . 5 . 2 )
1.6666666667 59.06 0 0.0 0.000
= 35215 lb
15847 Kg
Sheet No. :
Ac = p x r x c = 2,748.58 ft 2
p = design load
= snow load + live load + insulation + roof plates + P ( external )
= 42.89 psf
= 0.298 psi
2× π × R = 29.53 pieces
N min =
l
Nmin must be a multiple of 10, therefore Nmin = ### pieces
Actual Numbers of Rafter = 26
1
t= + Ca = ### in
√( 2× Sd
p )
t min = 0.1875 + CA ( per API - 650 or API - 620 )
= 0.25 in
t min = 0.2962 in
Sheet :
RAFTER DESIGN
l = MRS x 12
= 354.33 in
Where : q= 4.76
q
T2 = W 3 Cot Qo = 54548.45 lb
θ π
θi = x = 0.12 rad
2 180
θ
T2. R β= ( deg ) = 6.92 deg
M max=
2 [ 1 1
− =
sin β θ i ] 4332.26 lb-in 2
6. M
σ M= = 5868.76 psi < 19800 psi
h. t 2
4. Compressive Hoop Load 6. Radial Shear force :
T2 T2
226273.24 lb V max= 27274.22 lb
T max= = =
2 . Sin . β 2
5. Compresive Hoop Stress 7. Radial Shear stress :
T max V max
σC = = 25543.73 psi τ= = 3078.96 psi
ht ht
Compressive Hoop Stress is Fail Radial Shear Stress is Satisfactory
Wr = 12.4992 lb / ft ( input for tabel structure )
Job No. 0 Item No. 0 Code
= 34,888 lb
= 27,911 lb ( corroded )
1 pt ×OD
Xw= (
3 24 )
= 0.82 ft
ID
Rc = = 354 in
2
1
2 = 5.46 in
Wc=0 . 6×[ Rc . ( t −ca ) ]
Rc = 4,267 in
R 2=
sin θ
Rc
R 2=
sin θ
1
2 = 8.49 in
Wc=0 . 3× [ R 2 . ( t −ca ) ]
2
OD × ( P−8 t )
A min= = -2.64 in2.
30800×tan θ
Sheet No :
of Top Angle
Sheet No. :
SEISMIC MOMENT
Ms = Seimic moment
Ms = Z x I x ( C1 x Ws x Xs + C1 x Wr x Ht + C1 x W1 x X1 + C2 x W2 x X2 )
Xs = 16.404199
C1 x Ws x Xs = 0.578 x 0 x16.4042 = 0
C1 x Wr x Ht = 0.578 x 327463 x 33 = 6209772
C1 x W1 x X1 = 0.578 x 1789437 x 11.93 = 1.2E+07
C2 x W2 x X2 = 0.340 x 3317801 x 17.34 = 2E+07
Ms = Z x I x ( C1 x Ws x Xs + C1 x Wr x Ht + C1 x W1 x X1 + C2 x W2 x X2 )
= 7623992.9 ft-lb
wl = 7.9 x ( tb - ca ) x sqrt ( Sy x G x H )
= -528.35919 lb/ft
1 .273 . M
b=Wt+ = 2839.3 lb/ft max. longitudinal compressive force
D2
GHD2 / t2 = ###
Fa = 10 6 x t / D = 3175 psi
1 .273 . M
b=Wt+ = 2839.3 lb/ft max. longitudinal compressive force
D2
GHD2 / t2 = ###
Fa = 10 6 x t / D = 3175 psi
WIND MOMENT
w=0.2833×t× (π 4)×((12.OD)+3)
2
= ### ft
t ( insulation)
As=H × OD + ( 6 )
= ### ft2.
π
W =W (shell )+W (roof )− P× ×144×OD
4
2
[ ]
= ### lb
where :
W shell = 15444
W roof = 44484
4 Mwind W
bt wind
D.N N
= #DIV/0! lb
ANCHOR BOLTS :
Material : A-307
( Seismic Load ) :
btseis = #DIV/0! lb
( Wind Load ) :
bt = #DIV/0! lb
( Uplift ) :
bt = #DIV/0! lb
( Bolt Calculations ) :
Exclusive of Corrosion ,
Nominal Bolt Diameter Req'd = 0.202 " ( from ANSI B1.1 )
Including Corrosion ,
Nominal Bolt Diameter Req'd = 0.2645 " ( from ANSI B1.1 )
Dia bolt = 0.3125 " ( from ANSI B1.1 )
Sheet No. :
ME = 28800000 28800000
= 1.0
t = 3 P D / 2 A E + Ca + tq
= 0.065 in
EMERGENCY VENTING
Qe = x1 * x2 * Qe
= 6184 CFM