Control Manual 30RB - RQ - LR 1
Control Manual 30RB - RQ - LR 1
Pro-Dialog Control
A B C
R
1 - SAFETY CONSIDERATIONS................................................................................................................................................ 3
1.1 - General....................................................................................................................................................................................... 3
1.2 - Avoid electrocution................................................................................................................................................................... 3
2 - GENERAL DESCRIPTION..................................................................................................................................................... 3
2.1 - General....................................................................................................................................................................................... 3
2.2 - Abbreviations used................................................................................................................................................................... 3
3 - HARDWARE DESCRIPTION................................................................................................................................................ 4
3.1 - General....................................................................................................................................................................................... 4
3.2 - Electrical supply to boards....................................................................................................................................................... 4
3.3 - Light emitting diodes on boards.............................................................................................................................................. 4
3.4 - The sensors................................................................................................................................................................................. 4
3.5 - The controls................................................................................................................................................................................ 5
3.6 - Connections at the user’s terminal block............................................................................................................................... 5
4 - SETTING UP PRO-DIALOG PLUS CONTROL................................................................................................................ 7
4.1 - User interface general features................................................................................................................................................ 7
4.2 - Unit start/stop control.............................................................................................................................................................. 8
4.3 - Menus......................................................................................................................................................................................... 9
5 - PRO-DIALOG PLUS CONTROL OPERATION............................................................................................................. 28
5.1 - Start/stop control..................................................................................................................................................................... 28
5.2 - Heating/cooling/standby operation....................................................................................................................................... 28
5.3 - Evaporator water pump control............................................................................................................................................ 29
5.4 - Control interlock contact....................................................................................................................................................... 29
5.5 - Evaporator antifreeze protection.......................................................................................................................................... 29
5.6 - Control point........................................................................................................................................................................... 29
5.7 - Demand limit........................................................................................................................................................................... 31
5.8 - Night mode............................................................................................................................................................................... 31
5.9 - Capacity control...................................................................................................................................................................... 31
5.10 - Head pressure control.......................................................................................................................................................... 31
5.11 - Defrost function.................................................................................................................................................................... 31
5.12 - Additional electric heater stage control............................................................................................................................. 31
5.13 - Control of a boiler................................................................................................................................................................. 31
5.14 - Master/slave assembly.......................................................................................................................................................... 31
5.15 - Optional heat reclaim module............................................................................................................................................. 32
5.16 - Free-cooling option............................................................................................................................................................... 32
6 - DIAGNOSTICS - TROUBLESHOOTING.......................................................................................................................... 33
6.1 - General..................................................................................................................................................................................... 33
6.2 - Displaying alarms.................................................................................................................................................................... 33
6.3 - Resetting alarms...................................................................................................................................................................... 33
6.4 - Alarm codes............................................................................................................................................................................. 34
GENERAL LEGEND
Each of the following drawings is replaced in the whole document by the corresponding explanation:
Start/stop button
Return key
Down arrow
Up arrow
DELTA T. Example: temperature difference between entering and leaving heat exchanger temperatures
Means character is flashing
The cover graphics are solely for illustration and forms no part of any offer for sale or any sale contract. The manufacturer
reserves the right to change the design at any time without notice.
2
1 - SAFETY CONSIDERATIONS 2 - GENERAL DESCRIPTION
Installation, start-up and servicing of equipment can be Pro-Dialog is a system for controlling single-, dual- or triple-
hazardous if certain factors particular to the installation are circuit 30RB air-cooled liquid chillers or 30RQ air-to-water
not considered: operating pressures, presence of electrical heat pumps. Pro-Dialog controls compressor start-up needed
components and voltages and the installation site (elevated to maintain the desired heat exchanger entering or leaving
plinths and built-up up structures). Only properly qualified water temperature. In cooling mode it controls the operation
installation engineers and highly qualified installers and of the fans to maintain the correct condensing pressure in
technicians, fully trained for the product, are authorised to each circuit. For heat pump units it controls and optimises
install and start-up the equipment safely. During all servicing the defrost cycles of each circuit in order to minimize the
operations all instructions and recommendations which heating capacity reduction. Safety devices are constantly
appear in the installation and service instructions for the monitored by Pro-Dialog to ensure their safe operation.
product, as well as on tags and labels fixed to the equipment Pro-Dialog also gives access to a Quick Test program
and components and accompanying parts supplied sepa- covering all inputs and outputs.
rately, must be read, understood and followed.
• Apply all standard safety codes and practices. All Pro-Dialog Plus controls can work in accordance with
• Wear safety glasses and gloves. three independent modes:
• Use the proper tools to move heavy objects. Move • Local mode: the machine is controlled by commands
units carefully and set them down gently. from the user interface.
• Remote mode: the machine is controlled by remote
1.2 - Avoid electrocution contacts (volt-free contacts).
• CCN mode: the machine is controlled by commands
Only personnel qualified in accordance with IEC (Inter- from the Carrier Comfort Network (CCN). In this
national Electrotechnical Commission) recommendations case, a data communication cable is used to connect
may be permitted access to electrical components. It is the unit to the CCN communication bus.
particularly recommended that all sources of electricity to
the unit be shut off before any work is begun. Shut off the The operating mode must be chosen with the Start/Stop
main power supply at the main circuit breaker or isolator. button described in section 4.2.1. When the Pro-Dialog
Plus system operates autonomously (Local or Remote
IMPORTANT: This equipment uses and emits electro- mode) it retains all of its own control capabilities but does
magnetic signals. Tests have shown that the equipment not offer any of the features of the CCN network.
conforms to all applicable codes with respect to electro-
magnetic compatibility. 2.2 - Abbreviations used
RISK OF ELECTROCUTION: Even when the main In this manual, the refrigeration circuits are called circuit
circuit breaker or isolator is switched off, certain circuits A, circuit B and circuit C. The compressors in circuit A are
may still be energised, since they may be connected to a labelled A1, A2, A3 and A4. Those in circuit B are B1, B2,
separate power source. B3 and B4 and those in circuit C are C1, C2, C3 and C4.
RISK OF BURNS: Electrical currents cause components The following abbreviations are used frequently:
to get hot either temporarily or permanently. Handle CCN : Carrier Comfort Network
power cable, electrical cables and conduits, terminal box CCn : Operating type: CCN
covers and motor frames with great care. LED : Light Emitting Diode
LEN : Sensor Bus (internal communication bus linking
Fan start-up: the basic board to the slave boards)
ATTENTION: In accordance with the operating LOFF : Operating type: Local Off
conditions the fans can be cleaned periodically. A fan can L-On : Operating type: Local On mode
start at any time, even if the unit has been shut down. L-Sc : Operating type: Local On following a time schedule
MASt : Operating type: master unit (master/slave assembly)
rEM : Operating type: by remote contacts
SCT : Saturated Condensing Temperature
SST : Saturated Suction Temperature
EXV : Electronic Expansion Valve
3
3 - HARDWARE DESCRIPTION 3.2 - Electrical supply to boards
3.1 - General All boards are supplied from a common 24 V a.c. supply
referred to earth.
Figure 1 - control board
CAUTION: Maintain the correct polarity when connecting
1 2 3 the power supply to the boards, otherwise the boards may
4
1 be damaged.
4
3.5 - The controls 3.6 - Connections at the user’s terminal block
Boiler
This relay output authorises start/stop of a boiler.
Cooling units
Description Connector/ Terminal Board Remarks
channel
Evaporator pump 1 control J2A / CH19 PD5-BASE The control can regulate one or two evaporator pumps, and automatically change over
between the two pumps.
Evaporator pump 2 control J2A / CH20 PD5-BASE The control can regulate one or two evaporator pumps, and automatically change over
between the two pumps.
Evaporator heater control J2B / CH21 PD5-BASE This (and the pipe heater for units without pumps) protects the evaporator against frost.
Alarm relay output J3 / CH24 PD5-BASE Indicates alarms.
Alert relay output J3 / CH25 PD5-BASE Indicates alerts.
Operation or ready-to-start relay J3 / CH26 PD5-BASE Indicates if the unit is ready to start or operates.
output
Contact 1: J4 / CH11 32-33 PD5-BASE This contact is used for unit start/stop. It is only taken into account if the unit is under
Start/stop remote operation control (rEM).
Contact 2: J4 / CH12 65-66 PD5-BASE This contact is only taken into account if the unit is under remote operation control (rEM).
Setpoint selection
Contact 3: J4 / CH13 63-64 PD5-BASE See the description of these contacts in sections 3.6.5 and 3.6.6.
Demand limit selection 1
Contact 3 bis: CH9 NRCP2-BASE This contact is only present if the energy management option is used.
Demand limit selection 2
User safety loop input J4 / CH15a 34-35 PD5-BASE This contact is mounted in series with the water flow control contact. It can be used for
any customer safety loop that requires that the unit is stopped, if it is open. If it is unused
this contact must be bridged.
Contact 4: J4 / CH14 PD5-BASE This contact is used to select the heat reclaim mode.This contact is only used, if the heat
Heat reclaim selection reclaim option is used (not compatible with the free cooling option).
Contact 4: J4 / CH14 PD5-BASE If this contact is closed, it is used to prevent operation of the free cooling mode. It is only
Free cooling prevention taken into account, if the unit is under remote operation control (rEM). This contact is only
used if the free cooling option is used (incompatible with the heat reclaim option).
Contact 5: J5C / CH18 PD5-BASE If this contact is open, the pump is controlled and an alarm has tripped.
Pump operation status
Connection to CCN J12 PD5-BASE An RS-485 bus is used for connection to the CCN.
- Pin 1: signal +
- Pin 2: ground
- Pin 3: signal -
Critical alarm relay output J2C / CH23 PD5-BASE Output allows disconnecting the general unit power supply, if a contactor is stuck and
there is an increased risk of the unit being damaged.
5
Heat pump units
Description Connector/ Terminal Board Remarks
channel
Evaporator pump 1 control J2A / CH19 PD5-BASE The control can regulate one or two evaporator pumps, and automatically change over
between the two pumps.
Evaporator pump 2 control J2A / CH20 PD5-BASE The control can regulate one or two evaporator pumps, and automatically change over
between the two pumps.
Evaporator heater control J2B / CH21 PD5-BASE This (and the pipe heater for units without pumps) protects the evaporator against frost.
4-way valve A control J2C/ CH22 PD5-BASE The control regulates the 4-way valve during heat/cool changeover or during defrost
cycles.
4-way valve B control J2C/ CH23 PD5-BASE The control regulates the 4-way valve during heat/cool changeover or during defrost
cycles.
Alarm relay output J3 / CH24 PD5-BASE Indicates alarms.
Alert relay output J3 / CH25 PD5-BASE Indicates alerts.
Operation or ready-to-start relay J3 / CH26 PD5-BASE Indicates if the unit is ready to start or operates.
output
Contact 1: J4 / CH11 32-33 PD5-BASE This contact is used for unit start/stop. It is only taken into account if the unit is under
Start/stop remote operation control (rEM).
Contact 2: J4 / CH12 65-66 PD5-BASE This contact is only taken into account if the unit is under remote operation control (rEM).
Setpoint selection
Contact 3: J4 / CH13 63-64 PD5-BASE See the description of these contacts in sections 3.6.5 and 3.6.6.
Demand limit selection 1
Contact 3 bis: CH9 NRCP2-BASE This contact is only present if the energy management option is used.
Demand limit selection 2
User safety loop input J4 / CH15a 34-35 PD5-BASE This contact is mounted in series with the water flow control contact. It can be used for
any customer safety loop that requires that the unit is stopped, if it is open. If it is unused
this contact must be bridged.
Contact 4: J5B / CH17 PD5-BASE This contact is used for heating/cooling mode selection. It is only taken into account if the
Heating/cooling selection unit is under remote operation control (rEM).
Contact 5: J5C / CH18 PD5-BASE If this contact is open, the pump is controlled and an alarm has tripped.
Pump operation status
Connection to CCN J12 PD5-BASE An RS-485 bus is used for connection to the CCN.
- Pin 1: signal +
- Pin 2: ground
- Pin 3: signal -
Critical alarm relay output J2C / CH22 NRCP2-BASE Output allows disconnecting the general unit power supply, if a contactor is stuck and
there is an increased risk of the unit being damaged (available if the energy management
option is used).
6
4 - SETTING UP PRO-DIALOG PLUS CONTROL
A B A B
R
A B
A B
Main interface
A
It gives access to all Pro-Dialog Plus data and operating
B
functions. It consists of:
C
• A two-digit display showing the number of the item
selected.
• A four-digit display showing the contents of the item
selected.
• LEDs and buttons for unit start/stop, menu selection,
Menu block menu item selection and value adjustment.
Main interface
Button Name Description
Menu Permits the selection of a main menu. Each main menu is represented by an icon. The icon is lit if active.
Up arrow Permits scrolling through the menu items (in the two-digit display). If the modification mode is active this button authorises increase of the
value of any parameter.
Down arrow Permits scrolling through the menu items (in the two-digit display). If the modification mode is active this button authorises decrease of the
value of any parameter.
Enter Gives access to the modification mode, validates a modification or displays expanded item description.
Start/stop Authorises start or stop of the chiller in local mode or modification of its operating type.
SETPOINTS menu Displays the unit setpoints and enables them to be modified.
INPUTS menu Displays the status of the unit digital and analogue inputs.
OUTPUTS/TESTS menu Displays the status of the unit outputs and enables them to be tested.
OPERATING LOG menu Displays the operating times and number of starts for the unit and the compressors.
7
The summary interface (right hand section) includes a mimic 4.2 - Unit start/stop control
diagram of the unit, together with push-buttons and LEDs.
It gives quick access to the main operating parameters of 4.2.1 - Description
the unit. The unit start/stop can be controlled by one of the following
methods:
Summary interface LEDs • Locally on the actual unit (Local control type)
LED Indication when lit • By remote control with the aid of user contacts (remote
Green LED:
The unit is authorised to start or is already running control type)
A Red LED: • By CCN control with the aid of the CCN (CCN control
- Lit: circuit A or unit shut down by alarm type)
- Flashing: circuit A or unit running with alarm present
B Red LED:
- Lit: circuit B or unit shut down by alarm The main interface includes a Start/Stop button which can
- Flashing: circuit B or unit running with alarm present
be used to stop or start the unit in the local operating type
C Red LED:
- Lit: circuit C or unit shut down by alarm or to select the remote or CCN operating type.
- Flashing: circuit C or unit running with alarm present
Green LED:
The evaporator pump is running.
The available operating types are described in the following
Yellow LEDs: table.
From top to bottom - start/stop status of compressor A1, A2, A3 and A4
or B1, B2, B3 and B4 or C1, C2, C3 and C4. Flashing LED indicates that
the circuit is in the protection or defrost mode (A, B or C). The following operating types can be selected using the
Green LED: Start/Stop button:
The unit operates in heating mode.
Green LED:
Operating types
The unit operates in cooling mode.
4-digit Description
display
Summary interface push buttons (dual-circuit)
LOFF Local Off. The unit is halted in local mode.
Button Display
L-On Local On. The unit is in local control mode and is authorised to start.
Blue button: evaporator leaving or entering water temperature in °C
Gray button: outdoor air temperature in °C L-Sc* Local On - timer control. The unit is in local control mode. It is
authorised to start if the period is occupied. If the timer program for
Control point (setpoint + reset) in °C unit operation is unoccupied, the unit remains shut down until the
period becomes occupied.
CCN CCN. The unit is controlled by CCN commands.
Press 1: circuit A/B discharge pressure in kPa rEM Remote. The unit is controlled by remote control contacts.
(1) Press 2: circuit A/B saturated condensing temperature in °C MAST* Master Unit. The unit runs as a master in a two unit lead/lag
arrange-ment. This is displayed if the unit is configured for master/
Press 1: circuit A/B suction pressure in kPa
slave control.
(1) Press 2: circuit A/B saturated suction temperature in °C
* Displayed if the configuration requires it.
Press 1: compressor A1/B1 operating hours in h/10 or h/100 Section 5.1 gives a more detailed description of the commands to start/stop
(1) Press 2: compressor A2/B2 operating hours in h/10 or h/100 the unit, analysed by operating type.
Press 3: compressor A3/B3 operating hours in h/10 or h/100
Press 4: compressor A4/B4 operating hours in h/10 or h/100
(1) There is a separate button for each of the two circuits. 4.2.2 - Stopping the unit in local mode
The unit can be stopped in local mode at any time by
Summary interface push buttons (triple-circuit) pressing the Start/Stop button.
Button Display
Blue button: evaporator leaving or entering water temperature in °C To stop the unit
Gray button: outdoor air temperature in °C
Button Action 2-digit display 4-digit display
Control point (setpoint + reset) in °C Press the Start/Stop button for C LOFF
less than 4 seconds (one short
press is enough).
Press 1: circuit A/B/C discharge pressure in kPa If the button is released, the unit t LOFF
(1) Press 2: circuit A/B/C saturated condensing temperature in °C stops without the need for further
action.
Press 1: circuit A/B/C suction pressure in kPa
(1) Press 2: circuit A/B/C saturated suction temperature in °C
4.2.3 - Starting unit and selecting an operating type
Press 1: compressor A1/B1/C1 operating hours in h/10 or h/100
(1) Press 2: compressor A2/B2/C2 operating hours in h/10 or h/100 The unit can be started in local mode, or unit operating
Press 3: compressor A3/B3/C3 operating hours in h/10 or h/100 type can be changed at any time using the Start/Stop
Press 4: compressor A4/B4/C4 operating hours in h/10 or h/100
button. In the example that follows, the unit is stopped
Press 1: Selects circuit A to display information
A (only on triple-circuit units) (LOFF) and the user wants to start the unit in local mode.
Press 1: Selects circuit B to display information
B
A (only on triple-circuit units)
Press 1: Selects circuit C to display information
C
A (only on triple-circuit units)
(1) There is a common button for the three circuits; for circuit selection press one
of the three last buttons described above.
8
Start-up with the previously used operating type when the unit is stopped The following example shows how to access item 3 in the
in local mode (loff)
Pressures menu.
Button Action 2-digit 4-digit
display display
The unit is in local stop mode. The previously LOFF Selecting a menu item
used operating type is local on (L-ON) Operation Press Menu LED Item number
button 2-digit display
Press the Start/Stop button for 4 seconds (one L-On
short press-down is sufficient). L-ON Press the MENU button until 0
illuminates immediately. “C” flashes in the the LED marked PRESSURE
2-digit display to show that the controller is lights.
awaiting confirmation. 0
Press the Enter button to confirm the operating L-On
type. “t” is displayed in the 2-digit display to
Press one of the Arrow buttons 1
indicate the operating type selected. If the
until the two-digit display shows
Enter button is not pressed soon enough, the
3 (item number 3).
controller will cancel the change and remain in
2
the stop mode.
9
4.3.4 - Expand display
Pressing the Enter button causes a 23 character text expan-
sion to be scrolled across the four-digit display. All user
menus provide an expansion of the current displayed
parameters. If the expansion is complete the four-digit
display reverts to item value. This function can be inhibited
through the User Configuration menu.
Press one of the Arrow buttons until the two-digit display shows 1 (item number 1- cooling setpoint 2). 1 6.0
The value for setpoint 2 is displayed in the four-digit display (6.0°C in this example).
Press the Enter button for more than 2 seconds to enable the value associated with item 1 to be 6.0
modified. The Setpoint menu LED and the two-digit display flash indicating that modification mode is 1
active.
Keep pressing the Down Arrow button until the value 5.7 is displayed in the four-digit display. The 5.9
Setpoint menu LED and the two-digit display keep flashing. 1
1 5.8
1 5.7
Press the Enter button again to validate the change. The new setpoint is 5.7°C.The Setpoint menu 1 5.7
LED and the two-digit display stop flashing, indicating that modification mode no longer applies.
10
MAIN MENUS
INFORMATIONS
INFORMATION TEMPERATURES
TEMPERATURES PRESSION S
PRESSURES CONSIGNES
SETPOINTS ENTREES
INPUTS SORTIES
OUTPUTS CONFIGURATION
CONFIGURATION ALARMES
ALARMS HISTORIQUE ALARMES
ALARM HISTORY ALARMES
RUNTIME
SUB-MENUS
SUB-SUB-MENUS
USER
USER 11 USER
USER 22 TIME & DATE
TIME & DATE SCHEDULE
SCHEDULE 11 SCHEDULE
SCHEDULE 22 HOLIDAY
HOLIDAYS BROADCAST SERVICE
SERVICE11 SERVICE2
SERVICE 2 MASTER/SLAVE
MASTER/SLAVE HSM
HSM
HOLIDAY 16
11
12
ITEM STATUS TEMP PRESSURES SETPOINTS INPUTS OUTPUTS CONFIG ALARMS ALARMS HISTORY RUNTIMES
0 Default display Evaporator water Discharge Cooling setpoint 1 Contact 1: on/off/heating/ Output 1 SUB-MENU: User Number of active Historic alarm code 1** SUB-MENU:
entering temp. pressure circuit A cooling Configuration (USEr) alarms/resets** Runtimes 1
1 Mode Evaporator water Suction pressure Cooling setpoint 2 Contact 2: setpoint selection Output 2 SUB-MENU: Service Active alarm code 1** Historic alarm code 2** SUB-MENU:
leaving temp. circuit A Configuration Runtimes 2
(SErviCE)
2 Chiller occupied mode* Outdoor temperature Discharge Ice storage setpoint* Contact 4: heating/cooling [1]* - SUB-MENU: Factory Active alarm code 2** Historic alarm code 3** SUB-MENU:
pressure circuit B* Configuration Runtimes 3
(FACtorY)
3 Minutes left Heat reclaim entering Suction pressure Heating setpoint 1* Contact 4: heat reclaim [2]* - - Active alarm code 3** Historic alarm code 4** SUB-MENU:
water temp.* circuit B* OR free cooling prevention [2] Maintenance
4 Cooling/heating Heat reclaim leaving Discharge Heating setpoint 2* User safety loop input status - - Active alarm code 4** Historic alarm code 5** -
selection* water temp.* pressure circuit C*
5 Cooling/heating status* Saturated discharge Suction pressure Auto changeover Water pump operation - - Active alarm code 5** Historic alarm code 6** -
temperature circuit A circuit C* threshold (cooling mode)* contact status*
6 Heat reclaim selection* Saturated suction Vacuum pressure, Auto changeover Control box thermostat - - - Historic alarm code 7** -
temp. circuit A circuit A* threshold (heating mode)*
7 Total capacity in % Suction temperature, Vacuum pressure, Heat reclaim mode input Contact 3: demand limit - - - Historic alarm code 8** -
circuit A circuit B* setpoint* selection 1*
8 Capacity circuit A in % Superheat, circuit A - Heat reclaim mode input Contact 3 bis: demand limit - - - Historic alarm code 9** -
dead band* selection 2*
9 Capacity circuit B in % Saturated discharge - Setpoint demand Ice storage remote contact* - - - Historic alarm code 10** -
temp. circuit B limitation 1*
10 Capacity circuit C in Saturated discharge - Setpoint demand Remote unit contact, - - - Historic alarm code 11** -
%* temp. circuit B limitation 2* continued occupied mode*
11 Present demand limit Suction temperature, - Setpoint demand User safety loop input* - - - Historic alarm code 12** -
in % circuit B limitation 3*
Menu tree structure
12 Present lag limit in %* Superheat, circuit B - Ramp loading* Demand limit control - - - Historic alarm code 13** -
limitation value*
13 Setpoint in local Saturated discharge - Cooling - zero reset Setpoint reset value* - - - Historic alarm code 14** -
control temp. circuit C* threshold*
14 Setpoint occupied Saturated discharge - Cooling - full reset Ambient temperature value* - - - Historic alarm code 15** -
mode temp. circuit C* threshold*
15 Active setpoint Suction temperature, - Cooling - full reset value* Subcooling liquid - - - Historic alarm code 16** -
circuit C* temperature, circuit A*
16 Control point Superheat, circuit C* - Heating - zero reset Subcooling liquid - - - Historic alarm code 17** -
threshold* temperature, circuit B*
17 Controlled water Defrost temperature, - Heating - full reset Subcooling temperature, - - - Historic alarm code 18** -
temperature circuit A* threshold* circuit A*
18 Indicator, heat recovery Defrost temperature, - Heating - full reset value* Subcooling temperature, - - - Historic alarm code 19** -
in progress, circuit A* circuit B* circuit B*
19 Indicator, heat recovery System water - - - - - - Historic alarm code 20** -
in progress, circuit B* temperature*
Legend
* Displayed if the configuration requires it 1 For heat pump units
** Displayed if the alarm exists 2 For cooling only units
- Not in use
4.3.5 - Description of the Information menu
3: Unit status
OFF - Off: Unit is stopped and not authorised to start.
rEADY - Ready: Unit is authorised to start
dELAY - Delay: Unit is in delay at start-up. This delay is active after the unit has been switched on. The delay can be configured in the
- User Configuration menu
StOPPing - Stopping: Unit is currently stopping
running - On: Unit is running or authorised to start
triPout - Fault shutdown
OvErridE - Limit: The operating conditions do not allow total unit operation
dEFrOSt - Defrost: One circuit is in defrost mode
FrEEcOOl Free cooling: The unit operates in free cooling mode
- 6: Alarm mode
ALArM - Alarm: Unit is totally stopped because of failure
ALErt Alert: Unit is in failure but not completely stopped
7: Master/Slave status
MAStEr - Master: The master/slave control is active and the unit is the master
SLAvE - Slave: The master/slave control is active and the unit is the slave
Texts 4 and 5 are not displayed if the unit is in Local off mode or if the unit is in remote control mode and contact 1 is open
1 [1] nn Active mode codes. Each active mode is displayed in turn. This Item is masked when nil. Pressing the enter button when a mode
- code is displayed causes a character text expansion to be scrolled accross the four-digit display. See the description in the
following table
2 [2] This item indicates the current unit occupied/unoccupied mode.
occu - Occupied
unoc Unoccupied
Forc The value is displayed in turn with ‘Forc’ when the unit is in CCN control and if this variable if forced through CCN.
3 nn.n minutes Start-up delay. This item indicates the minutes left before the unit can be started. This delay at start-up is always active after the
unit has been switched on. The delay can be configured in the User Configuration 1 menu.
4 [2] Heating/cooling on selection: This item is accessible in read/write, if the unit is in local control mode.
HEAt - Heating mode selection
COOL - Cooling mode selection
Auto - Automatic heating/cooling mode changeover selection. Only displayed if the auto changeover function is selected (User
- Configuration 1 menu).
5 [2] Heating/cooling mode. This item indicates whether the unit is in cooling or heating. Displayed if the unit controls a boiler.
HEAt - Heating
COOL - Cooling
StbY - Standby: Unit is in auto cooling/heating changeover mode, and is in standby.
both - Both: The unit operates in cooling (compressors) and heating (boiler). Only with HSM operation.
Forc - The value is displayed in turn with ‘Forc’ when the unit is in CCN control and if this variable if forced through CCN.
6 [2] Yes - Heat reclaim mode selection. Only displayed if the unit is a chiller and the heat reclaim option is used. The value is displayed in
No turn with ‘Forc’ when the unit is in CCN control and if this variable if forced through CCN.
Forc
6 [2] Yes - Free cooling prevention status. Only shown if the unit is a chiller and if the free cooling option is available. The value is displayed
No in turn with “Forc”, when the unit is in CCN control and if this variable is forced through CCN.
Forc
7 nnn % Total active capacity of unit. It is the percentage of compressor capacity used by the unit.
8 nnn % Total active capacity of circuit A. It is the percentage of compressor capacity used by on circuit A.
9 [2] nnn % Total active capacity of circuit B. It is the percentage of compressor capacity used by on circuit B. Dual-circuit units only.
10 [2] nnn % Total active capacity of circuit C. It is the percentage of compressor capacity used by on circuit C. Triple-circuit units only.
11 nnn % Present demand limit. This is the authorised operating capacity of the unit. See section 5.7.
Forc The value is displayed in turn with ‘Forc’ when the unit is in CCN control and if this variable if forced through CCN.
12 [2] nnn % Present lag chiller demand limit. Displayed when the master/slave control is selected.
13 [2] Setpoint select in local mode. This point is read/write accessible. Displayed only when the unit is LOFF, L-On or L-Sc operating type.
SP-1 - SP-1 = cooling/heating setpoint 1
SP-2 SP-2 = cooling/heating setpoint 2
AUtO AUtO = active setpoint depends on schedule 2 (setpoint selection schedule). See section 5.6.1 & 4.3.11.6.
13
Information menu (3) continued
Item Format Units Description
14 [2] Setpoint occupied mode.
occu - Occupied: cooling setpoint 1 is active
unoc Unoccupied: cooling setpoint 2 is active
Forc The value shall be displayed in turn with ‘Forc’ when the unit is in CCN control and if this variable if forced through CCN.
15 ±nn.n °C Active setpoint. This is the current cooling/heating setpoint: cooling/heating setpoints 1, 2 or ice storage setpoint.
16 Control point. This is the setpoint used by the controller to adjust the temperature of the leaving or entering water (according to
configuration).
±nn.n °C Control point = active setpoint + reset. See section 5.6
Forc The value is displayed in turn with ‘Forc’ when the unit is in CCN control and if this variable if forced through CCN.
17 ±nn.n °C Controlled water temperature. Water temperature that the unit tries to maintain at the control point.
18 n Heat reclaim sequence indicator, circuit A (option).
19 n Heat reclaim sequence indicator, circuit B (option).
[1] This item is masked when nil.
[2] This item is displayed in certain unit configurations only.
14
4.3.6 - Description of the Temperatures menu
15
4.3.8 - Description of the Setpoints menu
16
4.3.9 - Description of the Inputs menu
17
4.3.10 - Description of the Outputs/Tests menu
4.3.10.1 - General
This menu displays the status of the controller outputs.
Moreover, when the machine is fully stopped (LOFF) the
outputs can be activated for manual tests (the access to the
tests is password controlled).
18
Outputs status & Tests menu (continued)
Item Format Units Description
10 0 to 6 Fan status, circuit C. Permits selection of the fan to be tested.
tESt 1 = fan C1
2 = fan C2
3 = fan C3
4 = fan C4
5 = fan C5
6 = fan C6
11 b1b2b3b4 Alarm status
tESt b1 = alarm relay
b2 = alert relay
b3 = general alarm relay (present if energy management option is used)
b4 = critical alarm relay output. Caution: If this output is connected, its activation will disconnect the general unit power
supply.
12 nnn % EXV A position
tESt 0% = EXV closed; 100% = EXV open
In test mode this permits selection of the required position.
13 nnn % EXV B position
tESt 0% = EXV closed; 100% = EXV open
In test mode this permits selection of the required position.
14 nnn % EXV C position
tESt 0% = EXV closed; 100% = EXV open
In test mode this permits selection of the required position.
15 nnn % Fan speed, circuit A. Only displayed if a variable speed controller is selected in circuit A.
tESt In test mode, this permits selection of the required speed.
16 nnn % Fan speed, circuit B. Only displayed if a variable speed controller is selected in circuit B.
tESt In test mode, this permits selection of the required speed.
17 nnn % Fan speed, circuit C. Only displayed if a variable speed controller is selected in circuit C.
tESt In test mode, this permits selection of the required speed.
18 - Evaporator water pump #1 command status. Not displayed if the unit does not control a pump.
On On: pump is running
Stop Stop: pump is stopped
tESt Forc: this item is displayed only when the unit is stopped locally (LOFF). selecting this item authorises turning on the
FAIL pump with no delay and for an unlimited length of time. The pump will remain on until any button of the user interface is
Good pressed: it is then immediately stopped. If the unit is in CCN control, then the pump status is displayed in turn with “Forc” if
Forc the pump status if forced through CCN.
During the test phase, power to the pump is switched on for 10 seconds only. When the test is completed the following is
displayed:
- Fail: displayed if the test has failed because the pump was not started
- Good: displayed if the test was successful
19 On - Evaporator water pump #2 command status. Not displayed if the unit does not control a secondary pump.
OFF On: pump is running
tESt Stop: pump is stopped
FAIL Forc: this item is displayed only when the unit is stopped locally (LOFF). selecting this item authorises turning on the
Good pump with no delay and for an unlimited length of time. The pump will remain on until any button of the user interface is
Forc pressed: it is then immediately stopped. If the unit is in CCN control, then the pump status is displayed in turn with “Forc” if
the pump status if forced through CCN.
During the test phase, ...as above
19
Submenu outputs 2 (selection) (continued)
Item Format Units Description
8 On Boiler operating status.
OFF On: operating
tESt OFF: stopped
9 b1b2 b3 Free cooling 3-way valve status (only displayed when the free cooling option is selected).
b1 = 3-way valves, circuit A
b2 = 3-way valves, circuit B
b3 = 3-way valves, circuit C
0 corresponds to a closed valve (cooling position) and 1 corresponds to an open valve (free cooling position)
10 b1b2 b3 Free cooling refrigerant pump status (only displayed when the free cooling option is selected).
tESt b1 = pump, circuit A
b2 = pump, circuit B
b3 = pump, circuit C
11 nn.n Unit capacity 0-10 V signal value (10 V = 100 %). Only displayed if the energy management option is selected.
tESt
12 b1b2 Chiller operating status
b1 = ready (ready-to-start or in operation)
b2 = in operation
13 YES/no Used for local interface test only. Lights or flashes all LEDs and blocks, so as to check that they are working properly.
20
Sub-menu user configuration
Item User 1 User 2 Date Schedule 1 Schedule 2 Holidays Broadcast
[USER1] [USER2] [dAtE] [ScHEduLE 1MEnu] [ScHEduLE 2 MEnu] [HOLidAy MEnu] [BrodCASt]
0 Return to previous menu Return to previous menu Return to previousReturn to previous Return to previous Return to previous menu Return to previous
menu menu menu menu
1 Selection of lead circuit Periodic pump start-up Hour SUB-MENU: SUB-MENU: SUB-MENU: Broadcast
Period 1 [PErIod 1] Period 1 [PErIod 1] Holidays 1 [HOLidAy 1] acknowledger selection
2 Load sequence selection Night mode - start hour Day of the week SUB-MENU: SUB-MENU: SUB-MENU: Broadcast activation
Period 2 [PErIod 2] Period 2 [PErIod 2] Holidays 2 [HOLidAy 2]
3 Ramp selection Night mode - end hour Day and month SUB-MENU: SUB-MENU: SUB-MENU: Outdoor temperature
Period 3 [PErIod 3] Period 3 [PErIod 3] Holidays 3 [HOLidAy 3] broadcast bus
4 Start-up delay Night mode maximum Year SUB-MENU: SUB-MENU: SUB-MENU: Outdoor temperature
demand Period 4 [PErIod 4] Period 4 [PErIod 4] Holidays 4 [HOLidAy 4] broadcast element
5 Water pump selection Number clock 1 Summertime SUB-MENU: SUB-MENU: SUB-MENU:
activation Period 5 [PErIod 5] Period 5 [PErIod 5] Holidays 5 [HOLidAy 5]
6 Water pump changover Number clock 2 Summertime start SUB-MENU: SUB-MENU: SUB-MENU:
delay month Period 6 [PErIod 6] Period 6 [PErIod 6] Holidays 6 [HOLidAy 6]
7 Pump shutdown in standby CCN element number Summertime start SUB-MENU: SUB-MENU: SUB-MENU:
mode day of the week Period 7 [PErIod 7] Period 7 [PErIod 7] Holidays 7 [HOLidAy 7]
8 Verification of the water flow CCN bus number Summertime start SUB-MENU: SUB-MENU: SUB-MENU:
rate if the pump has stopped week of the month Period 8 [PErIod 8] Period 8 [PErIod 8] Holidays 8 [HOLidAy 8]
9 Setpoint reset selection, Interface text language Summertime end SUB-MENU:
cooling mode month Holidays 9 [HOLidAy 9]
10 Setpoint reset selection, Extended display Summertime end SUB-MENU:
heating mode selection day of the week Holidays 10 [HOLidAy 10]
11 Automatic heating/cooling Password for all user Summertime end SUB-MENU:
changeover selection configurations week of the month Holidays 11 [HOLidAy 11]
12 Demand limit selection Software version number SUB-MENU:
Holidays 12 [HOLidAy 12]
13 Maximum demand limit Boiler activation SUB-MENU:
current value temperature threshold Holidays 13 [HOLidAy 13]
14 Minimum demand limit Ice storage mode SUB-MENU:
current value authorisation Holidays 14 [HOLidAy 14]
15 Electric heating stage Free cooling authorisation SUB-MENU:
operation threshold temperature limit (max.) Holidays 15 [HOLidAy 15]
16 Electric heating stage Authorisation of pre-cooling SUB-MENU:
operation schedule by free cooling Holidays 16 [HOLidAy 16]
17 Electric heating safety stage Maximum duration of full
threshold load operation in free
cooling
18 Quick start-up, electric
heater stages in defrost mode
...
...
HOLIDAY 15
HOLIDAY 16
21
4.3.11.3 - Description of the User 1 Configuration sub-menu
22
4.3.11.4 - Description of the User 2 Configuration sub-menu
23
4.3.11.5 - Description of Date and Time configuration sub-menu
24
Typical timer program: ATTENTION: The broadcast function must be activated
to utilise the holiday schedule, even if the unit is running
Time MON TUE WES THU FRI SAT SUN HOL
in stand-alone mode (not connected to CCN). See section
0 P1
4.3.11.8.
1 P1
2 P1
3 Holiday period X configuration sub-menus (X = 1 to 16)
Item Format Comments
4
0 HoLidAy X Sub-menu When selected this item authorises a return to
5
the configuration menu.
6
1 0 to 12 Start month of public holiday period
7 P2 P2 P3 P4 P4 P5 0 = period not in use
8 P2 P2 P3 P4 P4 P5 1 = January, 2 = February, etc.
9 P2 P2 P3 P4 P4 P5 2 0 to 31 Start day of public holiday period. 0 period
10 P2 P2 P3 P4 P4 P5 not in use.
11 P2 P2 P3 P4 P4 P5 3 0 to 99 days Duration of the public holiday period in days.
12 P2 P2 P3 P4 P4 Typical programming for public holidays:
A public holiday period lasting 1 day on 20th May, for instance, is configured as
13 P2 P2 P3 P4 P4
MON: Monday follows: start month = 5, start day = 20, duration = 1
14 P2 P2 P3 P4 P4 A public holiday period lasting 2 day on 25th May, for instance, is configured as
TUE: Tuesday
15 P2 P2 P3 P4 P4
WED: Wednesday follows: start month = 5, start day = 25, duration = 2
16 P2 P2 P3 P4 P4 THU: Thursday
17 P2 P2 P3 FRI: Friday 4.3.11.8 - Description of the Broadcast sub-menu
18 P3 SAT: Saturday
19 P3 SUN: Sunday
(broAdCASt)
20 P3 P6 HOL: Public holidays The controller provides a broadcast configuration menu
21 which you can use to configure the unit to be the CCN’s
22 Occupied
Unoccupied
broadcaster, responsible for transmitting the time, outdoor
23
temperature, and holiday flags to all system elements.
Warning: if the unit operates in standalone mode (not CCN connected) this choice must be set to Yes if the holiday function is used (see
section 4.3.11.6) or if you want to configure the daylight saving time function.
2 0/1/2 This item permits activation or deactivation of the broadcast mode.
0 = the controller is not the broadcaster, and it is not useful to configure another selection in this table.
1 = broadcasts time, date, holidays and the outside temperature.
2 = for chillers only. Summertime and holidays are not taken into consideration without broadcasting the information on the bus.
3 nnn OAT Broadcaster bus number: it is the bus number of the system that has the outside air temperature sensor connected to it.
4 nnn OAT Broadcaster element number: it is the element number of the system element that has the outside air temperature sensor connected
to it.
25
4.3.12 - Description of the Alarms menu 4.3.14.1 - Description of the Runtimes 1 menu
This menu is used to display and reset up to 5 active alarms.
It also permits alarm reset. If no alarm is active this menu Runtimes menu [1]
is not accessible. Item Format Units Comments
0 RuntiME 1 menu - When selected this item authorises
return to the previous menu
Alarms menu 1 nnnn | M 10 | M100 hrs/10 or 100 Unit operating hours*
Item Format Comments 2 nnnn | M 10 | M100 hrs/10 or 100 Compressor A1 operating hours*
0 [1] X ALArM X alarms are active 3 [1] nnnn | M 10 | M100 hrs/10 or 100 Compressor A2 operating hours*
rESEt ALArM Reset of alarms is requested. 4 [1] nnnn | M 10 | M100 hrs/10 or 100 Compressor A3 operating hours*
5 [1] nnnn | M 10 | M100 hrs/10 or 100 Compressor A4 operating hours*
To reset all active alarms, continuously press the
6 nnnn | M 10 | M100 hrs/10 or 100 Compressor B1 operating hours*
Enter key. ‘rESET ALArM’ is then displayed.
Press the select key again: all alarms are reset. 7 nnnn | M 10 | M100 hrs/10 or 100 Compressor B2 operating hours*
1 [1] Alarm code text Current alarm code 1** 8 [1] nnnn | M 10 | M100 hrs/10 or 100 Compressor B3 operating hours*
2 [1] Alarm code text Current alarm code 2** 9 [1] nnnn | M 10 | M100 hrs/10 or 100 Compressor B4 operating hours*
3 [1] Alarm code text Current alarm code 3** 10 - | M 10 | M100 -/10 or 100 Machine starts*
4 [1] Alarm code text Current alarm code 4** 11 - | M 10 | M100 -/10 or 100 Compressor A1 starts*
5 [1] Alarm code text Current alarm code 5** 12 [1] - | M 10 | M100 -/10 or 100 Compressor A2 starts*
[1] This item is masked when nil 13 [1] - | M 10 | M100 -/10 or 100 Compressor A3 starts*
* See section “Alarm codes” 14 [1] - | M 10 | M100 -/10 or 100 Compressor A4 starts*
** Pressing the Enter key when alarm code is displayed causes the following 15 - | M 10 | M100 -/10 or 100 Compressor B1 starts*
message to be scrolled: 16 - | M 10 | M100 -/10 or 100 Compressor B2 starts*
“time of alarm” “date of alarm” “full CCN alarm message” 17 [1] - | M 10 | M100 -/10 or 100 Compressor B3 starts*
- “time of alarm”: xxhmm 18 [1] - | M 10 | M100 -/10 or 100 Compressor B4 starts*
- “date”: dd-mm
[1] This item is masked when not used
- “full CCN alarm message”: up to 64 characters
NOTES
* Certain values are divided by 10 or by 100, so that number of hours or
4.3.13 - Description of the Alarms History menu start-ups of less then 10 are displayed as 0.
Alarms History menu When the value is divided by 10 or by 100 it is displayed in turn with “M 10” or
“M100”.
Item Format Comments
0 [1] Alarm code text* Alarm history code 1**
1 [1] Alarm code text* Alarm history code 2** 4.3.14.2 - Description of Runtimes 2 menu
2 [1] Alarm code text* Alarm history code 3**
3 [1] Alarm code text* Alarm history code 4**
Runtimes menu [1]
4 [1] Alarm code text* Alarm history code 5**
Item Format Units Comments
5 [1] Alarm code text* Alarm history code 6**
0 RuntiME 2 menu - When selected this item
6 [1] Alarm code text* Alarm history code 7**
authorises return to the previous
7 [1] Alarm code text* Alarm history code 8** menu
8 [1] Alarm code text* Alarm history code 9** 1 [1] nnnn | M 10 | M100 hrs/10 or 100 Pump 1 operating hours*
9 [1] Alarm code text* Alarm history code 10** 2 [1] nnnn | M 10 | M100 hrs/10 or 100 Pump 2 operating hours*
10 [1] Alarm code text* Alarm history code 11** 3 [1] nnnn | M 10 | M100 hrs/10 or 100 Heat reclaim condenser pump
.... .... .... operating hours
19 [1] Alarm code text* Alarm history code 20** 4 nnnn - Compressor starts for compressor
[1] This item is masked when nil with most starts during the last
* See section “Alarm codes” hour
** Pressing the Enter key when alarm code is displayed causes the following 5 nnnn - 24 hours average number of
message to be scrolled: starts/hour, compressor
“time of alarm” “date of alarm” “full CCN alarm message” 6 [1] nnnn | M 10 | M100 hrs/10 or 100 Compressor C1 operating hours
- “time of alarm”: xxhmm
7 [1] nnnn | M 10 | M100 hrs/10 or 100 Compressor C2 operating hours
- “date”: dd-mm
- “full CCN alarm message”: up to 64 characters 8 [1] nnnn | M 10 | M100 hrs/10 or 100 Compressor C3 operating hours
9 [1] nnnn | M 10 | M100 hrs/10 or 100 Compressor C4 operating hours
10 [1] nnnn | M 10 | M100 -/10 or 100 Compressor C1 starts
4.3.14 - Description of the Runtime menu 11 [1] nnnn | M 10 | M100 -/10 or 100 Compressor C2 starts
12 [1] nnnn | M 10 | M100 -/10 or 100 Compressor C3 starts
13 [1] nnnn | M 10 | M100 -/10 or 100 Compressor C4 starts
RUNTIMES 14 [1] nnnn | M 10 | M100 -/10 or 100 No. of defrost cycles, circuit A
15 [1] nnnn | M 10 | M100 -/10 or 100 No. of defrost cycles, circuit B
16 [1] nnnn | M 10 | M100 -/10 or 100 Free cooling refrigerant pump
operating hours, circuit A
17 [1] nnnn | M 10 | M100 -/10 or 100 Free cooling refrigerant pump
operating hours, circuit B
RUNTIMES 1 RUNTIMES 2 RUNTIMES 3 MAINTENANCE
[runtiMES 1] [runtiMES 2] [runtiMES 3] [MAintEnAnCE] 18 [1] nnnn | M 10 | M100 -/10 or 100 Free cooling refrigerant pump
operating hours, circuit C
[1] This item is masked when not used
26
4.3.14.3 - Description of the Runtimes 3 menu 4.3.14.4 - Maintenance menu description
To be active, the maintenance function must be preset in
Runtimes menu the Service configuration.
Item Format Units Comments
0 RuntiME 3 menu - When selected this item
authorises return to the Item Format Description
previous menu 0 MAintEnAnCE MEnu When selected this item authorises return to the
1 nnnn | M 10 | M100 hrs/10 or 100 Fan A1 operating hours previous menu.
2 nnnn | M 10 | M100 hrs/10 or 100 Fan A2 operating hours 1 [1] 0 to 6 Deletes the maintenance alerts.
3 [1] nnnn | M 10 | M100 hrs/10 or 100 Fan A3 operating hours 2 [1] YES/no Refrigerant control.
4 [1] nnnn | M 10 | M100 hrs/10 or 100 Fan A4 operating hours 3 [1] YES/no Water loop rate to low
5 [1] nnnn | M 10 | M100 hrs/10 or 100 Fan A5 operating hours 4 [1] nnnn Next primary pump maintenance operation in
nnn days. If the number of days = 0, the delay
6 [1] nnnn | M 10 | M100 hrs/10 or 100 Fan A6 operating hours
before maintenance has elapsed.
7 nnnn | M 10 | M100 hrs/10 or 100 Fan B1 operating hours
5 [1] nnnn Next secondary pump maintenance operation in
8 nnnn | M 10 | M100 hrs/10 or 100 Fan B2 operating hours nnn days. If the number of days = 0, the delay
9 [1] nnnn | M 10 | M100 hrs/10 or 100 Fan B3 operating hours before maintenance has elapsed.
10 [1] nnnn | M 10 | M100 hrs/10 or 100 Fan B4 operating hours 6 [1] nnnn Next maintenance operation on the heat reclaim
11 [1] nnnn | M 10 | M100 hrs/10 or 100 Fan B5 operating hours condenser pump. If the number of days = 0, the
12 [1] nnnn | M 10 | M100 hrs/10 or 100 Fan B6 operating hours delay before maintenance has elapsed.
13 [1] nnnn | M 10 | M100 hrs/10 or 100 Fan C1 operating hours 7 [1] nnnn Next water filter maintenance operation in nnn
14 [1] nnnn | M 10 | M100 hrs/10 or 100 Fan C2 operating hours days. If the number of days = 0, the delay before
15 [1] nnnn | M 10 | M100 hrs/10 or 100 Fan C3 operating hours maintenance has elapsed.
16 [1] nnnn | M 10 | M100 hrs/10 or 100 Fan C4 operating hours [1] This item is masked when not used.
17 [1] nnnn | M 10 | M100 hrs/10 or 100 Fan C5 operating hours
18 [1] nnnn | M 10 | M100 hrs/10 or 100 Fan C6 operating hours
[1] This item is masked when not used
27
5 - PRO-DIALOG PLUS CONTROL OPERATION • Start/Stop schedule: occupied or unoccupied status of
the unit as determined by the chiller start/stop program
5.1 - Start/stop control (Schedule #1).
• Master control type. This parameter is used when the
The table below summarises the unit control type and stop unit is the master unit in a two chiller lead/lag arrange-
or go status with regard to the following parameters. ment. The master control type determines whether the
• Operating type: this is selected using the start/stop unit is to be controlled locally, remotely or through
button on the front of the user interface. CCN (this parameter is a Service configuration).
• Remote start/stop contacts: these contacts are used • CCN emergency shutdown: if this CCN command is
when the unit is in remote operating type (rEM). See activated, it shuts the unit down whatever the active
sections 3.6.2 and 3.6.3. operating type.
• CHIL_S_S: this network command relates to the chiller • General alarm: the unit is totally stopped due to failure.
start/stop when the unit is in CCN control (CCn).
Variable forced to disable: the unit is halted. Variable
forced to Enable: the unit runs in accordance with
schedule 1.
* This threshold does not apply to cooling only units that do not control a boiler.
In automatic mode the outdoor temperature determines
the heating/cooling/standby changeover based on the two
threshold values configured by the user (see Setpoint menu
for cooling and heating mode changeover thresholds). If the
unit is in standby it does not cool or heat, and no compressor
can be activated. The diagram below summarises the
operating principle in automatic mode.
28
5.2.2 - Heating/cooling/auto selection • Remote heating/cooling contacts: these contacts are
The table below summarises the unit heating/cooling only active if the unit is under remote control. See
operation, based on the following parameters: sections 3.6.2 and 3.6.3.
• Control type: indicates whether the unit operates in • HC_SEL: this network command permits heating/
local, remote or CCN mode. See section 5.1. cooling/auto control, if the unit is in CCN operating
• Unit on/off status: indicates whether the unit is shut mode.
down (not authorised to start) or in operation (or • Outdoor temperature: determines the operation, if
authorised to start). the unit is in automatic heating/cooling/standby
• Heating/cooling/auto selection in local mode: changeover mode.
operating mode selected via the user interface. See
Information menu.
Parameter status
On/off status Control type Heating/cooling selection Remote heating/ HC_SEL Outdoor temperature Operating mode
in local mode cooling contacts
Off - - - - - Cooling
On Local Cooling - - - Cooling
On Local Heating - - - Heating
On Local Auto - - > Cooling threshold Cooling
On Local Auto - - < Heating threshold Heating*
On Local Auto - - Between cooling and heating thresholds Standby
On Remote - Cooling mode - - Cooling
On Remote - Heating mode - - Heating
On Remote - Auto mode - > Cooling threshold Cooling
On Remote - Auto mode - < Heating threshold Heating*
On Remote - Auto mode - Between cooling and heating thresholds Standby
On CCN - - Cooling - Cooling
On CCN - - Heating - Heating
On CCN - - Auto > Cooling threshold Cooling
On CCN - - Auto < Heating threshold Heating*
On CCN - - Auto Between cooling and heating thresholds Standby
* Does not apply to cooling only units that do not control a boiler.
The unit can control one or two evaporator water pumps. This contact checks the status of a loop (water flow switch
The evaporator water pump is turned on when this option and customer safety loop, see section 3.6). It prevents the
is configured (see User configuration) and when the unit is unit from starting if it is open when the delay at start-up has
in one of the on modes described above or in delay mode. expired. This open contact leads to an alarm shut-down, if
Since the minimum value for the delay at start-up is 1 minute the unit is running.
(configurable between 1 and 15 minutes), the pump will run
for at least one minute before the first compressor starts. 5.5 - Evaporator antifreeze protection
The pump is kept running for 20 seconds after the unit goes to
stop mode. The pump keeps working when the unit switches The heater for the evaporator and water pump (for units
from heating to cooling mode or vice-versa. It is turned off with a pump) can be energised to protect the evaporator, if
if the unit is shut down due to an alarm unless the fault is a it can be damaged by freezing, when the unit is shut down
frost protection error. The pump can be started in particular for a long time at low outdoor temperature.
operating conditions when the evaporator heater is active (see
section 5.5). See section 5.14 for the particular evaporator NOTE: Evaporator heater control parameters can be
pump control for the follower unit (master/slave assembly). modified, using the Service configuration.
If two pumps are controlled and the reversing function has 5.6 - Control point
been selected (see User 1 configuration), the control tries to
limit the pump run time delta to the configured pump change- The control point represents the water temperature that
over delay. If this delay has elapsed, the pump reversing the unit must produce. The inlet water is controlled by
function is activated, when the unit is running. During the default, but the outlet water can also be controlled
reversing function both pumps run together for two seconds. (requires a Service configuration modification).
If a pump has failed and a secondary pump is available, the Control point = active setpoint + reset
unit is stopped and started again with this pump.
5.6.1 - Active setpoint
The control provides a means to automatically start the Two setpoints can be selected as active in cooling mode and
pump each day at 14.00 hours for 2 seconds when the unit two in heating mode. Usually, the second cooling setpoint
is off. If the unit is fitted with two pumps, the first pump is is used for unoccupied periods. The second setpoint in
started on odd days and the second pump is started on heating mode is used for unoccupied periods.
even days. Starting the pump periodically for few seconds
increases the life-time of the pump bearings and the
tightness of the pump seal.
29
Depending on the current operations, the active setpoint The following tables summarise the possible selections
can be selected by choosing the item in the Information depending on the control types (local, remote or CCN)
menu, with the user’s volt-free contacts, with network and the following parameters:
commands or with the setpoint timer program (schedule 2). • Setpoint select in local control: item #13 of the Infor-
mation menu permits selection of the active setpoint,
if the unit is in local operating type.
• Heating/cooling operating mode.
• Control contacts 2: status of control contact 2.
• Schedule 2 status: schedule for setpoint selection.
% Building load
30
5.7 - Demand limit 5.11 - Defrost function
The demand limit is used to restrict the unit power consump- Defrost is activated, when the unit is in heating mode, in
tion. The Pro-Dialog control system allows limitation of order to reduce frost build-up on the air heat exchanger.
the unit capacity, using one of two methods: The defrost cycle can only be applied to one circuit at a
• by means of user-controlled volt-free contacts. The time. During the defrost cycle the fans of that circuit are
units without energy management option only have one stopped, and the four-way refrigerant valve is reversed,
demand limit level (only one contact: control contact 3). forcing the circuit to cooling mode. The fan can temporarily
The units equipped with energy management option be restarted during the defrost cycle. The defrost cycle is
permit three demand limit levels (2 contacts). The unit fully automatic and does not require any setting.
capacity can never exceed the limit setpoint activated
by these contacts. The limit setpoints can be modified 5.12 - Additional electric heater stage control
in the setpoint menu.
• by means of a 4-20 mA input type on the energy manage- The heat pump units can control up to four additional
ment board. The limit is now based on a linear interpo- electric heating stages.
lation from 0 to 100%, based on the input signal. The
demand limit in night mode is selectable (if the value The electric heating stages are activated to complement the
is below the one controlled by the external signal). heating capacity when the following conditions are satisfied:
• The unit uses 100% of the available heating capacity,
5.8 - Night mode or the unit is limited in its operation by a protection
mode (low suction temperature, hot gas or defrost
The night period is defined (see User configuration) by a sequence in progress protection), and in all cases
start time and an end time that are the same for each day cannot satisfy the heating load.
of the week. During the night period, the number of fans • The outdoor temperature is below a configured threshold
operating can be reduced, and the unit capacity may be (see User 1 configuration).
limited (but a minimum capacity value can be configured). • The unit demand limit is not active.
5.9 - Capacity control The user may configure the last available electric heating
stages as a safety stage. In this case, the safety stage is only
This function adjusts the number of active compressors to activated in addition to the other stages if there is a machine
keep the heat exchanger water temperature at its setpoint. fault, preventing the use of the heating capacity. The other
The precision with which this is achieved depends on the electric heating stages will continue to operate as described
capacity of the water loop, the flow rate, the load, and the above.
number of stages available on the unit. The control system
continuously takes account of the temperature error with 5.13 - Control of a boiler
respect to the setpoint, as well as the rate of change in this
error and the difference between entering and leaving NOTE: The control of the electric heating stages or of a
water temperatures, in order to determine the optimum boiler is not authorised for slave units.
moment at which to add or withdraw a capacity stage. If the
same compressor undergoes too many starts (per hour) or The unit can control the start-up of a boiler, if it is in heating
runs below one minute each time it is started this automa- mode. When the boiler is operating, the unit water pump is
tically brings about reduction of compressor starts, which stopped.
makes leaving water temperature control less precise. In
addition, the high pressure, low pressure or defrost unloading A heat pump unit and a boiler cannot operate together. In
functions can also affect the temperature control accuracy. this case the boiler output is activated in the following
Compressors are started and stopped in a sequence designed conditions:
to equalise the number of start-ups (value weighted by • The unit is in heating mode, but a fault prevents the
their operating time). use of the heat pump capacity.
• The unit is in heating mode, but works at a very low
5.10 - Head pressure control outdoor temperature, making the heat pump capacity
insufficient. The outdoor air temperature threshold
The head pressure is controlled by a maximum of six fans. for use of the boiler is fixed at -10°C, but this value
As an option, a variable-speed controller can control one or can be adjusted in the User 1 menu.
all of the fans. The head pressure is independently controlled
for each circuit, based on the saturated condensing tempe- 5.14 - Master/slave assembly
rature value.
Two PRO-DIALOG Plus units can be linked to produce a
Fan start-up: master/slave assembly. The two machines are interconnected
ATTENTION: The fans can be started periodically (for over the CCN bus. All parameters required for the master/
cleaning), even if the unit is switched off. slave function must be configured through the Service
configuration menu. Master/slave operation requires the
connection of a temperature probe at the common manifold
on each machine, if the heat exchanger leaving water
temperature is controlled.
31
The master/slave assembly can operate with constant or 5.15 - Optional heat reclaim module
variable flow. In the case of variable flow each machine
must control its own water pump and automatically shut This option requires the installation of an additional board.
down the pump, if the cooling capacity is zero. For constant
flow operation the pumps for each unit are continuously This board allows control of:
operating, if the system is operating. The master unit can • A heat reclaim condenser pump,
control a common pump that will be activated, when the • A heat reclaim condenser heater,
system is started. In this case the slave unit pump is not used. • Two solenoid valves to shut off the heat reclaim coil
(one for each circuit),
All control commands to the master/slave assembly (start/ • Two solenoid drain valves for the heat reclaim coil
stop, setpoint, heating/cooling operation, load shedding, (one for each circuit),
etc.) are handled by the unit which is configured as the • Two solenoid valves to shut off the water condenser
master, and must therefore only be applied to the master (one for each circuit),
unit. They will be transmitted automatically to the slave • Two solenoid drain valves for the water condenser
unit. The master unit can be controlled locally, remotely or (one for each circuit).
by CCN com-mands. Therefore to start up the assembly,
simply validate the Master operating type (MASt) on the Selecting the heat reclaim mode can be done with either
master unit. If the Master has been configured for remote the local interface or remotely with the (recl_sw) contact or
control then use the remote volt-free contacts for unit by CCN.
start/stop. The slave unit must stay in CCN operating type
continuously. To stop the master/slave assembly, select The heat reclaim function is active when: the heat reclaim
Local Off (LOFF) on the master unit or use the remote entering water temperature is lower than the heat reclaim
volt-free contacts if the unit has been configured for setpoint, minus half of the heat reclaim dead band.
remote control.
The heat reclaim function is not active when: the heat
One of the functions of the master unit (depending on its reclaim entering water temperature is higher than the heat
configuration) may be the designation, whether the master reclaim setpoint, plus half of the heat reclaim dead band.
or slave is to be the lead machine or the follower. The roles
of lead machine and follower will be reversed when the In the dead band the function remains in its active mode.
differ-ence in running hours between the two units exceeds The default value of the dead band is 4.4 K. This value can
a con-figurable value, ensuring that the running times of be modified by Carrier Service.
the two units are automatically equalised. The changeover
between lead machine and follower may take place when Changeover procedure from cooling to heat reclaim mode:
the assembly is started up, or even whilst running. The • Start-up of the condenser pump.
running time balancing function is not active if it has not • Verification of the condenser flow switch control
been configured: in this case the lead machine is always the contact. If this remains open after one minute of
master unit. condenser pump operation, the circuit remains in
cooling mode and an alarm will be activated.
The lead machine will always be started first. When the • As soon as the saturated condensing temperature
lead machine is at its full available capacity, start-up delay reaches 30°C, the pumpdown sequence is activated.
(configurable) is initialised on the follower. When this • Pumpdown: opening of the condenser water inlet
delay has expired, and if the error on the control point is valve and closing of the air condenser air valves 3
greater than 1.7°C, the follower unit is authorised to start seconds later.
and the pump is activated. The follower will automatically • After one minute or when the subcooling value is
use the master unit active setpoint. The lead machine will be above -10°C the heat reclaim function is effective.
held at its full available capacity for as long as the active
capacity on the follower is not zero. When the follower 5.16 - Free-cooling option
unit receives a command to stop, its evaporator water
pump is turned off with 20 seconds delay. The direct-expansion free-cooling principle is to circulate
the liquid refrigerant with a pump and to condense it to a
In the event of a communication fault between the two lower temperature at the condenser when the outside
units, each shall return to an autonomous operating mode temperature is low (below the setpoint). The performance
until the fault is cleared. If the master unit is halted due to achieved is huge, as only a pump and fans are activated.
an alarm, the slave unit is authorised to start without prior
conditions. This option requires the installation of an additional board
for each circuit. These boards allow control of:
ATTENTION: For heat pumps operating in master/slave • a three-way compressor shut-off valve
mode and with leaving water temperature control the first • a refrigerant pump.
AUX2 fan board must be replaced by the AUX1 board
and connected to a common temperature sensor. The following sensors are connected to each board:
• a pump suction pressure sensor
• a pump discharge pressure sensor
• a potentiometer to copy the position of the three-way
valve.
32
The prevention or authorisation of free cooling mode 6 - DIAGNOSTICS - TROUBLESHOOTING
operation can be controlled by the local interface or
remotely by customer contact 4 or by the CCN network. 6.1 - General
If pre-cooling is prohibited, free cooling starts if: The Pro-Dialog Plus control system has many fault tracing
• the outside temperature is lower than the aid functions. The local interface and its various menus
programmed threshold value (USER2 menu, item 15) give access to all unit operating conditions. If an operating
• the difference between outside temperature and fault is detected, an alarm is activated and an alarm code is
control point is higher than the minimum operating stored in the Alarm menu.
threshold value (4°C)
6.2 - Displaying alarms
If pre-cooling is authorised, free cooling starts if:
• the outside temperature is lower than the programmed The alarm LEDs on the summary interface (see section
threshold value (USER2 menu, item 15) 4.1) give a quick display of the status of each circuit and
• the difference between outside temperature and leaving the unit as a whole.
water temperature is higher than the minimum • A flashing LED shows that the circuit is operating but
operating threshold value (4°C) there is an alarm.
• A steady LED shows that the circuit has been shut
To stop the free cooling, a hysteresis of 0.5 K has been applied down due to a fault.
to these temperatures. When free cooling is stopped, a new
session is prohibited for one hour. The Alarm menu on the main interface displays up to 5
fault codes that are active on the unit.
Free cooling change-over procedure:
• The compressors stop (if the unit was operating) 6.3 - Resetting alarms
• The high/low pressure is equalised by opening the EXV
• The three-way valve receives the command to open When the cause of the alarm has been corrected the alarm
can be reset, depending on the type, either automatically on
Procedure to start up one circuit in free cooling: return to normal, or manually when action has been taken
• Wait for the complete opening of the three-way valve on the unit. Alarms can be reset even if the unit is running.
• Draw a vacuum and transfer the residual compressor
charge to the free-cooling circuit by starting up a This means that an alarm can be reset without stopping the
compressor (“pump-down”), machine. In the event of a power supply interrupt, the unit
• Start up the fans restarts automatically without the need for an external
• Cycle the pump (rotation for 10 seconds, shut-down command. However, any faults active when the supply is
for 4 seconds) interrupted are saved and may in certain cases prevent a
• Verify that a differential pressure is established at the circuit or a unit from restarting.
pump terminals.
A manual reset must be run from the main interface using
During free cooling operation all fans are activated except the following procedure:
when the differential between the outside temperature and
the leaving water temperature reaches a certain threshold Reset of active alarms
value. In this case only half of the fans are energised. Operation Item number Item value Press Menu
2-digit 4-digit button LED
display display
Expansion valve (EXV) control is based on the difference Hold down the MENU 0
button until the LED for
between the outside temperature and the leaving water alarms lights. The 4-digit
temperature to prevent disengaging or cavitation of the display shows the number
refrigerant pump. of active alarms (2 in this 0 2 ALArM
example).
Press the Enter button until 0 rESEt ALArM
The same pump stability logic can activate a pump-down “rESEt ALARrM” is shown
in the 4-digit display.
cycle, based on the pressure level detected in the compressors
at shut-down (up to three times in a free-cooling cycle) to
make the full refrigerant charge in the free-cooling circuit Press the Enter button 0 Good then,
again to validate the reset. 2 AL then,
available. “Good” is displayed for 2 no ALArM
seconds then, “2 ALArM”
and then, “no ALArM”.
33
6.4 - Alarm codes
The following list gives a complete description of each alarm code and its possible cause.
34
Alarm code descriptions (continued)
Alarm code Alarm description Reset type Probable cause Action taken by the control
Process faults
P-01 Water heat exchanger frost protection Automatic if the same alarm has Water flow rate to low or Unit is shut down
not tripped during the last 24 defective thermistor
hours, otherwise manual
P-05 Low suction temperature, circuit A Automatic when the temperature Pressure sensor defective, Circuit is shut down
returns to normal, and if this alarm EXV blocked or low
has not appeared during the last refrigerant charge
24 hours, otherwise manual
P-06 Low suction temperature, circuit B As above As above As above
P-07 Low suction temperature, circuit C As above As above As above
P-08 High superheat, circuit A As above As above As above
If free-cooling option is
used: 3-way valve position
incorrect
P-09 High superheat, circuit B As above As above As above
P-10 High superheat, circuit C As above As above As above
P-11 Low superheat, circuit A As above As above As above
If free-cooling option is
used: 3-way valve position
incorrect
P-12 Low superheat, circuit B As above As above As above
P-13 Low superheat, circuit C As above As above As above
P-14 Water flow control and customer interlock fault Automatic if the unit is in manual Evaporator pump defect or Unit is shut down
shut-down status, otherwise water flow switch fault
manual
P-15 Condenser water flow controller fault Manual Sensor defective The heat reclaim mode is stopped
P-16 Compressor A1 not started or no pressure increase Manual Connection problem Compressor is shut down
P-17 Compressor A2 not started or no pressure increase Manual Connection problem As above
P-18 Compressor A3 not started or no pressure increase Manual Connection problem As above
P-19 Compressor A4 not started or no pressure increase Manual Connection problem As above
P-20 Compressor B1 not started or no pressure increase Manual Connection problem As above
P-21 Compressor B2 not started or no pressure increase Manual Connection problem As above
P-22 Compressor B3 not started or no pressure increase Manual Connection problem As above
P-23 Compressor B4 not started or no pressure increase Manual Connection problem As above
P-24 Compressor C1 not started or no pressure increase Manual Connection problem As above
P-25 Compressor C2 not started or no pressure increase Manual Connection problem As above
P-26 Compressor C3 not started or no pressure increase Manual Connection problem As above
P-27 Compressor C4 not started or no pressure increase Manual Connection problem As above
P-28 Control box thermostat or phase reversal detected Automatic when the contact closes Control box badly Unit is shut down
again ventilated or poor
electrical connection
P-29 Communication loss with the System Manager Automatic when communication is CCN installation bus Unit goes into autonomous mode
re-established defective
P-30 Communicaiton loss between master and slave Automatic when communication is CCN installation bus As above
re-established defective
MC-nn Master chiller No. 1 configuration error at nn Automatic when the master Master/slave configuration Master/slave mode is stopped
configuration returns to normal or error
when the unit is no longer in
master/slave mode
FC-n0 No factory configuration Automatic when the configuration The unit size has not been Unit is shut down
is entered configured
FC-01 Illegal factory configuration number Manual The unit size has been As above
configured with the wrong
value
P-31 CCN emergency stop Manual Network command As above
P-32 Fault water pump 1 Manual Pump overheating or poor Unit is completely stopped if there is
pump connection no emergency pump
P-33 Fault water pump 2 Manual Pump overheating or poor As above
pump connection
P-34 Reclaim operation failure, circuit A Manual Sensor defective or low The heat reclaim mode of the circuit
condenser water flow rate is stopped
P-35 Reclaim operation failure, circuit B Manual Sensor defective or low As above
condenser water flow rate
P-37 Repeated high pressure unloading, circuit A Automatic Transducer defective or None
ventilation circuit fault
P-38 Repeated high pressure unloading, circuit B Automatic As above As above
P-39 Repeated high pressure unloading, circuit C Automatic As above As above
P-40 Repeated low suction temperature unloading in Manual Pressure sensor defective Circuit is shut down
heating mode, circuit A or refrigerant charge too
low
P-41 Repeated low suction temperature unloading in Manual As above As above
heating mode, circuit B
P-42 Repeated low suction temperature unloading, Manual As above As above
circuit C
P-43 Heat exchanger temperature too low, less than Automatic when the temperature Operating compressor The unit cannot start
10°C, prevents unit start-up detected returns to normal or protection out of range or
when the mode returns to cooling pressure sensor fault
35
Alarm code descriptions
Alarm code Alarm description Reset type Probable cause Action taken by the control
Process faults (cont’d)
P-91 Position of the free cooling 3-way valve Manual The valve has not reached Unit is shut down
incorrect for circuit A the expected position in the
time assigned
P-92 Position of the free cooling 3-way valve As above As above As above
incorrect for circuit B
P-93 Position of the free cooling 3-way valve As above As above As above
incorrect for circuit C
P-94 Operating fault in free cooling, circuit A Automatic, if the unit switches The refrigerant pump has The free cooling mode of the circuit is
back to normal cooling mode not correctly started or has stopped
cavitated
P-95 Operating fault in free cooling, circuit B As above As above As above
P-96 Operating fault in free cooling, circuit C As above As above As above
P-97 Reversed entering/leaving water sensors Manual Sensor defective, sensors Unit is stopped
reversed
CT-01 Fault, contactor stuck, circuit A Manual A compressor contactor is Ventilation and EXV control are maintained.
stuck, the compressor A second critical fault can result in the shut
cannot shut down down of the ventilation, closure of the EXV
and destruction of the compressor
CT-02 Fault, contactor stuck, circuit B As above As above As above
CT-03 Fault, contactor stuck, circuit C As above As above As above
V0-xx Fault, variable speed controller, circuit A Manual or automatic Speed controller fault or The circuit continues to operate, the speed
alert controller slows down the motor. The circuit
shuts down
V1-xx Fault, variable speed controller, circuit B As above As above As above
V2-xx Fault, variable speed controller, circuit C As above As above As above
Maintenance alarms
A1-01 Maintenance alert, service number nn Manual The preventive maintenance
date has passed
Compressor faults
A1-01 Fault, compressor A1 N°1 See compressor alarm subcode
A1-nn Fault, compressor A1 N°nn See compressor alarm subcode
A2-01 Fault, compressor A2 N°1 See compressor alarm subcode
A2-nn Fault, compressor A2 N°nn See compressor alarm subcode
A3-01 Fault, compressor A3 N°1 See compressor alarm subcode
A3-nn Fault, compressor A3 N°nn See compressor alarm subcode
A4-01 Fault, compressor A4 N°1 See compressor alarm subcode
A4-nn Fault, compressor A4 N°nn See compressor alarm subcode
B1-01 Fault, compressor B1 N°1 See compressor alarm subcode
B1-nn Fault, compressor B1 N°nn See compressor alarm subcode
B2-01 Fault, compressor B2 N°1 See compressor alarm subcode
B2-nn Fault, compressor B2 N°nn See compressor alarm subcode
B3-01 Fault, compressor B3 N°1 See compressor alarm subcode
B3-nn Fault, compressor B3 N°nn See compressor alarm subcode
B4-01 Fault, compressor B4 N°1 See compressor alarm subcode
B4-nn Fault, compressor B4 N°nn See compressor alarm subcode
C1-01 Fault, compressor C1 N°1 See compressor alarm subcode
C1-nn Fault, compressor C1 N°nn See compressor alarm subcode
C2-01 Fault, compressor C2 N°1 See compressor alarm subcode
C2-nn Fault, compressor C2 N°nn See compressor alarm subcode
C3-01 Fault, compressor C3 N°1 See compressor alarm subcode
C3-nn Fault, compressor C3 N°nn See compressor alarm subcode
C4-01 Fault, compressor C4 N°1 See compressor alarm subcode
C4-nn Fault, compressor C4 N°nn See compressor alarm subcode
Process faults
XX-01* Compressor B1 motor temperature too high Manual Motor fault, wiring The compressor is shut down
XX-02* Compressor B1 crankcase heater fault Manual Crankcase heater defective, As above
wiring fault
XX-03* Compressor B1 high pressure switch fault Manual Condenser flow rate too low, As above
condenser valve blocked, fan
circuit fault, condenser air or
water entering temperature
too high
XX-04* PTC temperature probe Manual Probe defective As above
Compressor motor B1 out of range
XX-05 Compressor board power supply is Automatic Unstable system voltage, Compressor is shut down
disconnected system power supply
unavailable
XX-06 Compressor board and contactor power Automatic Unstable system voltage, Compressor is shut down to avoid damage
supply drop system power supply to the contactors
unavailable
* XX-04 = A1 to A4, B1 to B4 and C1 to C4