SFP 1024
SFP 1024
SFP 1024
Northford, CT 06472
(203) 484-7161 Fax: (203) 484-7118
The SFP-1024/SFP-1024E
Fire Control Comm unicator
Communicator
Prog
Progrramming, Installation, Maintenance
and Oper ating Instr
Operating uction Man
Instruction ual
Manual
Document # 50475
7/22/99 Rev:
P/N 50475:D1
D
ECN 99-233
Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm Like all solid state electronic devices, this system may operate erratically or can
control panel. Disconnect all sources of power before servicing. Control unit and be damaged when subjected to lightning induced transients. Although no system is
associated equipment may be damaged by removing and/or inserting cards, completely immune from lightning transients and interferences, proper grounding will
modules, or interconnecting cables while the unit is energized. Do not attempt to reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to
install, service, or operate this unit until this manual is read and understood. an increased susceptibility to nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or encountered.
CAUTION - System Reacceptance Test after Software Changes: To ensure
proper system operation, this product must be tested in accordance with NFPA 72- Disconnect AC power and batteries prior to removing or inserting circuit boards.
1993 Chapter 7 after any programming operation or change in site-specific software. Failure to do so can damage circuits.
Reacceptance testing is required after any change, addition or deletion of system
components, or after any modification, repair or adjustment to system hardware or Remove all electronic assemblies prior to any drilling, filing, reaming, or punching
wiring. of the enclosure. When possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not interfere with battery,
All components, circuits, system operations, or software functions known to be transformer, and printed circuit board location.
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices that are Do not tighten screw terminals more than 9 in-lbs. Over tightening may damage
not directly affected by the change, up to a maximum of 50 devices, must also be threads, resulting in reduced terminal contact pressure and difficulty with screw
tested and proper system operation verified. terminal removal.
This system meets NFPA requirements for operation at 0-49O C/32-120 O F This system contains static-sensitive components. Always ground yourself with a
and at a relative humidity of 85% RH (non-condensing) at 30 O C/86 O F. proper wrist strap before handling any circuits so that static charges are removed
However, the useful life of the system's standby batteries and the electronic from the body. Use static suppressive packaging to protect electronic assemblies
components may be adversely affected by extreme temperature ranges and removed from the unit.
humidity. Therefore, it is recommended that this system and its peripherals be
installed in an environment with a nominal room temperature of 15-27O C/60-80O Follow the instructions in the installation, operating, and programming manuals.
F. These instructions must be followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability depend upon proper
Verify that wire sizes are adequate for all initiating and indicating device loops. installation.
Most devices cannot tolerate more than a 10% I.R. drop from the specified device
voltage.
An automatic fire alarm system - typically made up of smoke detectors, heat Audible warning devices such as bells may not alert people if these devices are
detectors, manual pull stations, audible warning devices, and a fire alarm control located on the other side of closed or partly open doors or are located on another
with remote notification capability can provide early warning of a developing fire. floor of a building.
Such a system, however, does not assure protection against property damage or
loss of life resulting from a fire. A fire alarm system will not operate without any electrical power. If AC power fails,
the system will operate from standby batteries only for a specified time.
Any fire alarm system may fail for a variety of reasons:
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For
Smoke detectors may not sense fire where smoke cannot reach the detectors such this reason, the rate-of-rise feature of each detector should be tested at least once
as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke per year by a qualified fire protection specialist.
detectors also may not sense a fire on another level or floor of a building. A second
floor detector, for example, may not sense a first floor or basement fire. Further- Equipment used in the system may not be technically compatible with the control.
more, all types of smoke detectors - both ionization and photoelectric types, have It is essential to use only equipment listed for service with your control panel.
sensing limitations. No type of smoke detector can sense every kind of fire caused
by carelessness and safety hazards like smoking in bed, violent explosions, Telephone lines needed to transmit alarm signals from a premise to a central
escaping gas, improper storage of flammable materials, overloaded electrical monitoring station may be out of service or temporarily disabled.
circuits, children playing with matches, or arson.
The most common cause of fire alarm malfunctions, however, is inadequate
IMPORTANT! Smoke detectors must be installed in the same room as the maintenance. All devices and system wiring should be tested and maintained by
control panel and in rooms used by the system for the connection of alarm professional fire alarm installers following written procedures supplied with each
transmission wiring, communications, signaling, and/or power. If detectors are device. System inspection and testing should be scheduled monthly or as required
not so located, a developing fire may damage the alarm system, crippling its by National and/or local fire codes. Adequate written records of all inspections should
ability to report a fire. be kept.
FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency Canadian Requirements
energy and if not installed and used in accordance with the instruction manual, may This digital apparatus does not exceed the Class A limits for radiation noise
cause interference to radio communications. It has been tested and found to comply emissions from digital apparatus set out in the Radio Interference Regulations of the
with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Canadian Department of Communications.
Rules, which is designed to provide reasonable protection against such interference
when operated in a commercial environment. Operation of this equipment in a Le present appareil numerique n'emet pas de bruits radioelectriques depassant les
residential area is likely to cause interference, in which case the user will be required limites applicables aux appareils numeriques de la classe A prescrites dans le
to correct the interference at his own expense. Reglement sur le brouillage radioelectrique edicte par le ministere des Communica-
tions du Canada.
2.0 Installation 19
2.1 General 19
2.2 Backbox Mounting 19
Figure 2-1: Cabinet Dimensions & Knockouts 20
Figure 2-2: Backbox and Battery Box 21
2.3 Operating Power 22
Figure 2-3: Operating Power Connections 22
Figure 2-4: Auxiliary Power Connections 23
2.4 Input Circuits 23
Figure 2-5: Style B Initiating Device Circuit Connect 24
2.5 Output Circuits 25
Figure 2-6: Notification Appliance Circuit Connections 25
Figure 2-7: Aux Relay and Relay Driver Terminals 25
2.6 Digital Communicator 26
Figure 2-8: Wiring Phone Jack 26
2.7 UL Power-limited Wiring Requirements 27
Figure 2-9: Typical Wiring for UL Power-limited 27
2.8 Optional Module Installation 28
Figure 2-10: Installation of CAC-10F Module 28
Figure 2-11: Wiring NACs and IDCs for Class A 28
Figure 2-12: Installation and Wiring of NAC-REM 29
Figure 2-13: Remote Printer Connections 30
Figure 2-14: LED-10IM Installation 31
Figure 2-15: Wiring LED-10IM to LED-10N 31
Figure 2-16: Wiring LED-10IM to ACM-8R 32
5.0 Servicing 76
5.1 Walk Test Mode 76
5.2 History Mode 77
5.3 Troubleshoot Mode 79
5.4 Lamp Test 80
Figure 5-1: Handset/Speaker Connection 80
5.5 Print Mode 81
5.6 Printer Output 81
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
The SFP-1024(E) COMPLIES WITH THE FOLLOWING NFPA STANDARDS:
NFPA 72-1993 National Fire Alarm Code for:
Central Station Signaling Systems (Automatic, Manual and Waterflow) Protected Premises Unit
Local Fire Alarm Systems
Remote Station Fire Alarm Systems
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction
Notifier Documents
Notifier Device Compatibility Document Document# 15378
AFM-16A Annunciator Document# 15207
FCPS-24 Field Charger/Power Supply Document# 50059
LDM Series Lamp Driver Modules Document# 15885
LED-10N Annunciator Document# 50581
ACM-8R Annunciator Control Relay Module Document# 15342
PK-1024 Manual Document# 50582
Description
iption
The SFP-1024 is a combination control panel and digital communicator all on one circuit board. It is a 10-zone panel,
which uses conventional input devices. The panel accepts waterflow devices, two-wire smoke detectors, four-wire
smoke detectors, pull stations and other normally-open contact devices. Outputs include two Notification Appliance
Circuits expandable to four, two programmable Form-A relays (option module with two Form-C relays can be
Product Descr
added), EIA-485 port to interface with remote annunciators and optional remote relay modules plus a printer port.
The integral communicator transmits system status (alarms, troubles, AC loss, others) to UL-listed Central Stations
via the public switched telephone network. The control panel has a built in programmer. It also supervises all wiring,
AC voltage, telephone line input voltage/current and battery level.
The control panel may be programmed or interrogated off site via the public switched telephone network. Any IBM
compatible personal computer with Windows™ 3.1 or greater, with a 1200 Baud Hayes™ compatible modem and
Notifier Upload/Download software P/N PK-1024, may serve as a Service Terminal. This allows downloading of any
portion or all of the program and upload of any portion or all of the program, history file, walktest data, current status
and system voltages. The SFP-1024E offers the same features as the SFP-1024 but allows connection to 220/240
VAC input.
Module
Notification
Appliance Circuits 10 Input
Programmable Zones
Description
24 VDC Relays
Power LED-10IM
Interface
iption
Module
NAC-REM Connector
Expander Module
Printer
Interface
Module
Connector
Four Character
7-Segment LED
Display
Keypad
PROM (U14)1
Optional
Transformer
Primary &
Secondary
Phone Lines
Holds up to 12 AH Batteries
Up to 60 Hrs. of Standby
Note:
1
Software for the Fire Control Communicator is located in a PROM inserted in the IC socket labeled U14. The
SFP-1024 and SFP-1024E each contain unique software. For specific panel software information refer to the SFP-
1024/SFP-1024E Field Software Change Procedure Document #50591.
Description
iption
SFP-1024E: 220/240 VAC, 50 Hz, 1.2 amps.
Wire size: minimum #14 AWG with 600V insulation
Battery (lead acid only) - J1
Product Descr
Maximum Charging Circuit: Normal Flat Charge—27.6V @ .8 amp
Maximum Charger Capacity: 17 Amp Hour battery (SFP-1024 cabinet holds max. 12
Amp Hour battery. Larger batteries require Notifier #BB-17 or other UL listed battery
cabinet).
Initiating Device Circuits TB5 and CAC-10F Option Module
Detector Zones 1 through 10
Power-limited Circuitry
Operation: All zones NFPA Style B - Convert to Style D using CAC-10F Class A
Converter Module.
Normal Operating Voltage: 24 VDC (ripple = 100 mV max)
Alarm Current: 15 mA
Short Circuit Current: 42 mA max.
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 4.7K, 1/2-Watt (part # 27072 UL listed)
Detector Loop Current is sufficient to ensure operation of one alarmed detector per zone.
Standby Current: 7.26 mA (includes ELR and 2 mA maximum detector current)
Smoke Detector Identifier A
Refer to Notifier Compatibility Chart for listed compatible devices.
Notification Appliance Circuits - TB4 & NAC-REM Option Module (TB2 & TB3)
Non-regulated special purpose power, Styles Y & Z supported
Power-limited circuitry
Operating Voltage Nominal 24 volts
Current for all external devices: 3.0 amps expandable to 6.0 amps
Current Limit: TB4 via electronic protection, NAC-REM option module (TB2 & TB3) via
PTC.
Max. signaling current/circuit: TB4 = 3.0 amps. NAC-REM = 1.5 amps.
End-of-line resistor: 4.7K, 1/2-Watt (part # 71252 UL listed) for Notification Appliance
Circuits
Refer to Notifier Compatibility Chart for listed compatible devices.
Form-A Relays - TB3
TB3 contact rating: 5.0 amps @ 30 VDC (resistive), 5.0 amps @ 125 VAC (resistive)
NAC-REM Form-C contact rating: 2.0 amps @ 30 VDC, 0.6 amps @ 125 VAC (resistive)
Four-wire Smoke Detector Power - TB2 Terminals 3 (+) & 4 (-)
Max. ripple voltage: 10 mVRMS Operating Voltage nominal 24 volts
Up to 500 mA is available for powering 4-wire smoke detectors.
Power-limited Circuitry. Recommended maximum Standby current is 50 mA1.
Refer to Notifier Compatibility Chart for compatible listed devices.
Nonresettable Regulated 24V Power - TB2 Terminals 1 (+) & 2 (-)
Max. ripple voltage: 10 mVRMS Operating Voltage nominal 24 volts
Total DC current available from this output is up to 500 mA.
Power-limited Circuitry. Recommended maximum Standby current is 150 mA 1.
Refer to Notifier Compatibility Chart for compatible listed devices.
Notes:
1) For power supply and battery calculations, refer to Appendix A.
2) Total current for nonresettable power, four-wire smoke power, and four Notifica-
tion Appliance Circuits must not exceed 6.0 amps. Total system current in excess
of 3.6 amps requires the XRM-24 (or XRM-24E for 220/240 VAC applications)
Transformer and 12 Amp Hour or 17 Amp Hour batteries.
SILENCE A
MODE B
Up Arrow (ACK) C
Down Arrow (ACK) D
1st EVENT E
ENTER/STORE F
Description
Displays
• Alarm - red LED
• Trouble - yellow LED
iption
Local Sounder - A piezo sounder provides separate and distinct sounds for alarm,
trouble, supervisory and critical process monitoring conditions.
Relays - Two dry Form-A relay contacts programmable for system alarm, system
trouble, system supervisory (standard and auto-resettable), standard and auto-
resettable process monitoring or communications failure are provided. Contacts are
rated 2 amps at 30 VDC resistive. Two additional Form-C relay contacts
programmable for alarm, trouble, standard and auto-resettable supervisory, standard
and auto-resettable process monitoring or communications fail are available using
the NAC-REM (NAC/Relay) option module. Contacts are rated 2 amps at 30 VDC
and 0.6 amps at 125 VAC resistive.
Printer Port - EIA-232 compatible, fully supervised and programmable for 2400,
4800 or 9600 Baud. Only one printer may be connected to the port. Consult the
factory for recommended printers.
Description
iption
32 AFM Series Annunciators or 32 LDM Series Annunciators or any combination of
the four devices totalling 32.
Product Descr
Telephone Lines - Fully supervised at all times, voltage is sensed to 4 volts and
current is sensed to 5 mA.
1.5 Digital Two modular phone jacks allow easy connection to telephone lines. Modular jacks
Communicator are labeled PH1 and PH2 for the Primary and Secondary phone lines. Telephone line
'Active' red LEDs are provided as well as a green 'Kissoff' LED. The integral digital
communicator provides the following functions:
• Line Seizure - takes control of the phone lines disconnecting any premises
phones.
• Listen for dial tone - 440 hertz tone typical in most networks.
• For tone burst or touchtone type formats: Discern proper 'Ack' and 'Kissoff'
tone(s) - The frequency and time duration of the tone(s) varies with the
transmission format. The control panel will adjust accordingly.
1.6 Components
Main Circuit Board The main circuit board contains the
system's CPU, power supply, other
primary components and wiring
interface connectors. Optional modules
plug in and are mounted to the main
circuit board. The main circuit board is
delivered pre-mounted in the cabinet.
Standard
Batteries The cabinet provides space for 12 Amp-Hour
batteries (for 17 Amp-Hour batteries use the listed
Notifier BB-17 battery box). Batteries must be ordered
separately.
CAC-10F Module
The CAC-10F Module can be used to convert the 10 Style B (Class B) Initiating
Device Circuits to 10 Style D (Class A) IDCs and the two Style Y (Class B)
Notification Appliance Circuits to two Style Z (Class A) NACs. The CAC-10F
module connects to J10 on the main circuit board. Refer to Figures 2-9 and 2-10.
NAC-REM Module
The NAC-REM (NAC/Relay) Module can be used to add two Style Z (Class A)
NACs and 2 Form-C relays. The module connects to J7 on the main circuit board.
Refer to Figure 2-12.
12 50475 Rev D1 9/22/99 P/N 50475:D1
1.8 Optional Dress Panel
Accessories A red dead-front dress panel (DP-1024) is available as an option (required for
Description
iption
Canadian installations). The dress panel restricts access to the system wiring while
allowing access to the membrane switch panel. Refer to Figure 1-1.
Battery Box
Product Descr
The Notifier BB-17 battery box may be
used to house two batteries greater than 12
AH to a maximum of 17 AH. The battery
box mounts directly below the main circuit
board in the cabinet (refer to Figure 2-2).
The BB-17 is gray and is provided with
knockouts.
The AFM Series Annunciators remotely display system status. The AFM/AEM-16AT
annunciators display zone alarm and trouble status. In addition, they provide remote
ACKNOWLEDGE, SILENCE, RESET and DRILL functions. The AFM Series
Anunciators require the use of the LED-10IM Interface Module. For more detailed
information, refer to the appropriate AFM Annunciator manual.
Description
AFM-16ATX
The Annunciator Fixed Module-16ATX contains 16 red alarm and 16
yellow trouble LEDs, a system trouble LED, an ON LINE/POWER
iption
AEM-16ATF
The Annunciator Expander Module-16ATF connects to the AFM-
16ATX and adds 16 sets of red alarm LEDs and yellow trouble LEDs. Up
to three AEM-16ATFs may be added to an AFM-16ATX but only one is
required.
Note: One AEM-16ATF is required with an AFM-16ATX to annunciate 10
zones of alarm and trouble as well as general system status provided
'8 point shift' function is not selected. Refer to Annunciator Manual
P/N 15390 for additional information.
AFM-16AT
The Annunciator Fixed Module-16AT contains 16 red alarm and 16
yellow trouble LEDs, a system trouble LED, an ON LINE/POWER
LED, and a local piezo sounder with switches for ACKNOWLEDGE,
SILENCE, RESET, and DRILL. The AFM-16AT is fixed at address '1'
and communication is via the EIA-485 data line.
AFM-16A
The Annunciator Fixed Module-16A has 16 red alarm LEDs. Multiple
annunciators may be used by setting all annunciators to Receive Only,
except the last AFM-16A in line. Each annunciator's address is internally FIRE ALARM ANNUNCIATOR
ALARM ZONE 1
fixed at '1', and communication is via the EIA-485 data line. The Local ALARM ZONE 2
ALARM ZONE 3
Silence/Acknowledge switch functions as local lamp test and silence for ALARM ZONE 4
ALARM ZONE 5
annunciator piezo. LEDs include On-Line and System Trouble indica- ALARM ZONE 6
ALARM ZONE 7
ALARM ZONE 8
tors. ALARM ZONE 9
ALARM ZONE 10
ALARM ZONE 11
ALARM ZONE 12
electrical box. Refer to the AFM-16A Manual for detailed information. ALARM ZONE 15
ALARM ZONE 16
PRESS
SYSTEM TROUBLE TO
SILENCE
ON LINE
Description
iption
The LDM Series Lamp Driver Modules, which consist of the LDM-32 master and
LDM-E32 expander modules, are used to provide an interface to a custom graphic
Product Descr
LED annunciator. The master module provides power and control for a maximum of
three expander modules (expander modules are not required when interfacing to the
SFP-1024). The LDM-32 and LDM-E32 have output connectors which are used to
drive lamps or LEDs and input connectors which are used for remote switch functions.
The LDM Series requires the use of the LED-10IM Interface Module. Refer to the
LDM Series Lamp Driver Modules Manual for a complete description.
The LDM-32
The Lamp Driver Module LDM-32 has 32 alarm
lamp/LED driver outputs which sink current to system
common (-) on activation. A single positive (+)
voltage is required to supply total operating power for
all lamps or LEDs when all drivers are activated. The
LDM-32 provides a separate driver for system trouble
and inputs for a local lamp test switch. A maximum
of 16 external control switches may be wired to the
LDM-32. DIP switch SW3 is used to enable or
disable the onboard piezo, enable remote switch
functions, select a flashing LED function for new
alarms and troubles, and other functions. Switch SW4
is used to configure the module to annunciate 32
alarms or 16 alarms and 16 troubles. A green ON-
LINE LED flashes to indicate ongoing communica-
tions with the host FACP. One LDM-32 supports up
to 3 LDM-E32 modules. The LDM-32 is supplied
with 4 standoffs and screws for mounting to a CHS-
4L chassis or custom backbox.
The FCPS-24 (FCPS-24E for 220/240 VAC applications) is a compact, remote power
supply and battery charger. This remote power supply consists of a filtered 24 VDC
output that may be configured to drive up to four Notification Appliance Circuits
[four Style Y (Class B) or two Style Z (Class A) and two Style Y (Class B)]. Alter-
nately, the four Notification Appliance Circuits may be used as auxiliary regulated
Description
Style Y/Style Z
Notification
Notification Appliance Circuit or
Appliance Circuit 24 VDC Output #1
Control Input #1
Style Y Notification
(from FACP)
Appliance Circuit or
24 VDC Output #2
Style Y/Style Z
Notification Appliance
Notification Circuit or 24 VDC
Appliance Circuit Output #3
Control Input #2
(from FACP) Style Y Notification
Appliance Circuit or
24 VDC Output #4
One of the most common applications for the FCPS-24(E) remote power supply
utilizes the NAC expander mode. In this application, one or two Notification Appli-
ance Circuits (NACs) are connected from the main FACP NAC output(s) to the
remote power supply Control Input circuits. When these Control Input circuits
activate (due to reverse polarity of the NAC output), the power supply will activate its
corresponding outputs. NAC Control Input #1 controls power supply output circuits
#1 and #2. NAC Control Input #2 controls output circuits #3 and #4.
During the inactive state, the remote power supply supervises its NAC field wiring for
short and open circuits. If a fault is detected, the supply will enter a trouble condition
and illuminate the corresponding NAC trouble LED (Output Circuits 1-4). However,
once the Notification Appliance Circuits are activated, the supervision is disabled and
the circuits are no longer supervised. Supervision of other power supply faults such
as low battery, Earth Fault, AC loss and battery charger failure will continue and may
be monitored via the independent trouble relay contact.
If a specific application requires that all four outputs activate at the same time, only
one NAC control input from the FACP is necessary. For this application, the Notifi-
cation Appliance Circuit from the FACP is wired into NAC Control Input #1 of the
remote supply and then a pair of wires are connected from NAC Control Output #1 to
NAC Control Input #2. Refer to the FCPS-24(E) Installation, Operation and Applica-
tion Manual for a complete description and examples of applications.
16 50475 Rev D1 9/22/99 P/N 50475:D1
1.9 Telephone 1.9.1 Telephone Circuitry:
Requirements Ringer Equivalence Number (REN) = 0.6B
Description
iption
Complies with FCC Part 68
and Warnings Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
Product Descr
The REN is used to determine the quantity of devices which may be connected to the
telephone line. Excessive REN's on the telephone line may result in the devices not
ringing in response to an incoming call. In most, but not all areas, the sum of the
REN's should not exceed five (5.0). To be certain of the number of devices that may
be connected to the line, as determined by the total REN's, contact the telephone
company to determine the maximum REN for the calling area.
Manufacturer : Notifier
12 Clintonville Rd.
Northford, CT 06472
If the control panel causes harm to the telephone network, the telephone company
reserves the right to temporarily discontinue service. Advance notification will be
provided except in cases when advance notice is not practical. In such cases,
notification will be provided as soon as possible. The opportunity will be given to
correct any problems and to file a complaint.
Two separate phone lines are required. Do not connect both telephone interfaces to
the same telephone line.
The control panel must be connected to the public switched telephone network
upstream of any private telephone system at the protected premises.
Description
An FCC compliant telephone cord must be used with this equipment. This
equipment is designed to be connected to the telephone network or premises wiring
using a compatible RJ31X male modular plug which is Part 68 compliant.
iption
Users should ensure for their own protection that the electrical ground connections
of the power utility, telephone lines and internal metallic water pipe system, if
present, are connected together. This precaution may be particularly important in
rural areas.
Caution: Users should not attempt to make such connections themselves, but should
contact the appropriate electric inspection authority, or electrician, as appropriate."
"The Load Number (LN) assigned to each terminal device denotes the percentage of
the total load to be connected to a telephone loop which is used by the device, to
prevent overloading. The termination on a loop may consist of any combination of
devices subject only to the requirement that the total of the Load Numbers of all the
devices does not exceed 100."
DOC Compliance - "This digital apparatus does not exceed the Class A limits for
radio noise emissions from digital apparatus set out in the Radio Interference
Regulations of the Canadian Department of Communications."
Installation
backbox. The key slots are located at the top
of the backbox and the two securing holes at
the bottom.
2.2 Backbox • Open the door and lift the door off the pin hinges.
Mounting • Remove the main PC board assembly by unscrewing the four screws in the
corners of the board. Set the board aside in a safe, clean place. Avoid static
discharge which may damage the board.
• Mark and predrill holes for the top two keyhole mounting bolts using the
dimensions shown.
• Install two upper fasteners in the wall with the screw heads protruding.
• Using the upper 'keyholes', mount the backbox over the two screws.
• Mark and drill the lower two holes.
• Mount backbox, install remaining fasteners and tighten.
• When the location is dry and free of construction dust, reinstall the main PC
board.
Bottom
Notes:
1) Mount the FACP cabinet to the wall.
2) Remove knockouts on bottom of FACP cabinet and top of BB-17.
3) Using conduit, hang BB-17 from FACP cabinet making sure there is at
least 1/2" of clearance between the two cabinets.
4) Anchor BB-17 to wall.
Installation
1 2 3 4
Figure 2-4: A uxiliar
Auxiliar
uxiliaryy Po w er Connections
Po
2.4 Input Circuits The control panel has 10 zone input circuits. The maximum loop resistance limit for
each is 100 ohms. All field wiring of each zone is supervised for opens and ground
faults. Both conditions are visually and audibly annunciated as well as
communicated to a Central Station.
Each zone is a Style B (Class B) Initiating Device Circuit (IDC) designed to accept
any Normally-Open contact device and conventional 2-wire, 24 volt smoke
detectors. Refer to Figure 2-5 for information on wiring Style B circuits. Use the
CAC-10F Option Module (refer to Figure 2-11) to convert all 10 circuits to Style D
(Class A). Each zone is power-limited to 7.26 mA in standby and 42 mA in alarm.
The zones may be programmed as shown below. The factory default is 2-wire smoke
detector for all zones.
• 2-wire Smoke Detector (factory default) • Reset
• Pull Station • Silence
• Normally-Open Contact Device(s) • Drill
• Supervisory • Acknowledge
• Supervisory, Auto-Resettable • Auto-resettable critical and
• Waterflow, silenceable noncritical process monitoring
• Waterflow, nonsilenceable • Critical and noncritical process
monitoring
Note: Process monitoring refers to circuits which do not specifically tie into
elements of the fire system as defined by NFPA codes. With the exception of
burglary functions, process monitoring circuits could be used to monitor any nonfire
functions such as water temperature, room temperature, door open/closed, gas
leakage, chemical leakage, etc.
50475 Rev D1 7/22/9 P/N 50475:D1
23
Process Monitoring may be accomplished for Local, Remote and Central Station
type services in the following ways:
• Local
When a critical process is detected, the relays (fail-safe) programmed to
transfer will deenergize. The ACM-8R Remote Relay Module can only be
used with noncritical process monitoring.
Installat ion
UL listed compatible 2--wire smoke detector UL listed compatible 2--wire smoke detector
Installation
for a listing of compatible Notification Appliances.
Standard Relays
The control panel provides two Form-A relays rated for 2.0 amps @ 30VDC
(resistive). Two Form-C relays can be added by installing the optional NAC-REM
(NAC/Relay) module.
The control panel's digital communicator is built into the main board. Connection
and wiring of two phone lines is required as shown below:
7 foot cables
(MCBL-7)
not supplied -
order separately
Power-limited
Circuit
Note that power-limited
wiring is connected to
Installation
terminal block below the Nonpower-limited Power-limited Circuits
installed circuit board Circuit
Power-limited
Circuit
AC Power
Install the two supplied metal standoffs in the holes (see Figure 2-10) on the main
circuit board. Carefully align the two connectors and press the CAC-10F module
securely into place. Make certain the pins are properly aligned to prevent bending or
breaking of any pins. Secure CAC-10F module to standoffs using the two supplied
Installat ion
screws. It is important that the supplied screw and washer be used to secure the
module to the metal standoff. This is necessary in order to help protect against
electrical transients.
Wire the Style Z (Class A) Notification Appliance Circuits (NACs) using TB4 of the
SFP-1024 and TB1of the CAC-10F module. Wire the Style D (Class A) Initiating
Device Circuits (IDCs) using TB5 of the SFP-1024 and TB2 of the CAC-10F
module. Make certain to observe polarity when connecting the devices to the
circuits. The B+ and A+ terminals must comprise the feed and return for the positive
side of a device and the B- and A- terminals must comprise the feed and return for
the negative side of a device. To configure any of the zones for Class B when the
CAC-10F is installed, simply wire to the B+ and B- inputs on TB5 of the main circuit
board and install the EOL resistor across the end of the circuit. Do not wire to the
corresponding A+ and A- terminals on TB2 of the CAC-10F module. Refer to
Figures 2-10 and 2-11.
Install the two supplied metal standoffs into the FACP main circuit board (see Figure
2-12). Ensure that the metal standoff is installed in the position indicated in the
illustration below. Carefully align the two connectors and press the NAC-REM
module securely into place. Make certain the pins are properly aligned to prevent
bending or breaking of any pins. It is important that the supplied screw and washer
Installation
be used to secure the module to the metal standoff. This is necessary in order to help
protect against electrical transients.
NAC #4
Metal Standoff
Installation
Installat ion
Remote printers require a separate external primary power. Also required is the
PRT-24 which includes the Printer Interface Module and a 6 foot interface cable
prewired to a DB25 connector. Connect the interface cable to the PRT-24 as shown
in Figure 2-13. Insert the two supplied standoffs into mounting holes near the J4
connector on the main board. Connect the Printer Interface board to J4 on the main
circuit board, press onto standoffs, and connect the attached cable to the serial EIA-
232 port on the printer. The printer may be placed a maximum of 50 feet from the
panel. Note that a ground fault may occur on the control panel when this connection
is made. For this reason, it is important that there be no preexisting ground fault on
the panel. For permanent printer connection, a ground fault is not allowed.
Printer Configuration
The PRT-24 is required. Also refer to the documentation supplied with your printer.
Set the printer’s options as listed in the table below. Baud rate is programmable to
2400, 4800 or 9600.
J1 located on back
of PRT-24 board
Install the two supplied standoffs into the FACP main circuit board. Ensure that the
metal standoff is installed in the position indicated in Figure 2-14. Carefully align
the two connectors and press the LED-10IM module securely into place. Make
certain the pins are properly aligned to prevent bending or breaking of any pins. It is
Installation
important that the supplied screw and washer be used to secure the module to the
metal standoff. This is necessary in order to help protect against electrical transients.
Metal Standoff
LED-10N Annunciator
- + EIA-485
7 6 5 4 3 2 1
Earth Ground
- 24 VDC
Earth + 24 VDC + 24 VDC
Ground
Shield LED-10IM
- 24 VDC
To assign the first eight relays of the first ACM-8R Relay Module to FACP IDCs 1-
8, set ACM-8R SW3 DIP switches 2 and 5 ON and 1, 3, 4, 6, 7 and 8 OFF.
To assign the first two relays of the second ACM-8R Relay Module to FACP IDCs 9
and 10, set ACM-8R SW3 DIP switches 3 and 5 ON and 1, 2, 4, 6, 7 and 8 OFF.
ACM-8R
NO
C
NC
To Next Device
SW4 SW3
Left Right
Decade Decade
Power-limited 24VDC
Switch Switch
LED-10IM
Figure 2-16: Wiring LED-10IM to ACM-8R
32 50475 Rev D1 9/22/99 P/N 50475:D1
LDM-32 Lamp Driver Module
The Lamp Driver Module is used to provide an interface to a custom graphic
annunciator. LDM-32 has 32 alarm lamp/LED driver outputs which sink current to
system common (-) on activation. A single positive (+) voltage is required to supply
total operating power for all lamps or LEDs when all drivers are activated. The
LDM-32 provides a separate driver for system trouble and inputs for a local lamp
test switch. A maximum of 16 external control switches may be wired to the LDM-
32. DIP Switch SW3 is used to enable or disable the onboard piezo, enable remote
switch functions, select a flashing LED function for new alarms and troubles, and
other functions. A green ON LINE LED flashes to indicate ongoing
communications with the host FACP. The LDM-32 is supplied with four standoffs
Installation
and screws for mounting to a CHS-4L chassis or custom backbox.
The LDM-32 is installed on the EIA-485 line using the LED-10IM Interface Module.
Communications wiring is supervised by the FACP. Power for module must be
power-limited.
To Next
Device
EIA-485
-
Power-limited
24 VDC Source LDM-32
LED-10IM
AFM-16A Annunciator
The Annunciator Fixed Module-16A has 16 red alarm LEDs. The annunciator
address is fixed at '1' and communication is via the EIA-485 line using the LED-
10IM Interface Module. The Local Silence/Acknowledge switch functions as local
Installat ion
lamp test and silence for annunciator piezo. LEDs include ON LINE/POWER and
System Trouble.
To Next Device
-
EIA-485
+
Power-limited
24 VDC Source
LED-10IM
Programming of the control panel is possible at any time except when an alarm
condition is present or during a fire drill.
The control panel has been designed for many different types of applications. After
examining your specific application, review the programming options and choose the
entries best suited for your system.
The control panel has a built-in intelligent programmer. All programming selections
are stored in nonvolatile Electrically-Erasable Programmable Read-Only Memory
(EEPROM). This ensures that the control panel will remember all entries made in
Progrr amming
programming mode even if both AC and battery power are removed. Invalid entries
cause a 'beep' from the onboard piezo sounder.
The user must program the primary and secondary phone numbers, account numbers
and 24 hour test report times for each Central Station account and the current time
and date. The control panel comes with factory chosen options/features already
Prog
programmed. Other options/features may be programmed if desired. If all factory
default settings are acceptable, programming is complete.
Successful entry into Program Mode from the keypad shuts off the fire protection and
places the panel into trouble. A 'system off normal' message is transmitted to the
central station. Programming via the PK-1024 upload/download software is
accomplished with the fire protection active/on.
Each option of the Program Mode is entered by keying in the program mode entry
7764
7764) and pressing the ENTER/STORE key.
code (7764
If an incorrect key is entered, reenter the proper 4-digit code before pressing the
[ENTER/STORE] key
___7
__77 Note that as you enter information into the
_776 control panel, the digits will scroll across the
7764 display from right to left
You are allowed a pause of up to 10 seconds in between each number while entering
the code. After pressing the [ENTER/STORE] key, the control panel will be in
Program Mode and display P__1 P__1, with the 1 flashing. If the [ENTER/STORE] key
is pressed, (1) Main Panel Options will be selected for programming. If (2) Event
Codes/Transmission Formats, (3) Option Module Selections or (4) Upload/Download
is keyed in and then the [ENTER/STORE] key pressed, the corresponding level will
50475 Rev D1 7/22/9 P/N 50475:D1
35
be selected for programming. You are allowed up to ten minutes of idle time at this
point before starting your programming, otherwise the control panel will go back to
Normal Mode. You also have a maximum of 10 minutes between any key stroke.
All entries made prior to the 10 minute time-out are valid and are stored.
Once in any of the four options of the Programming Mode, the control panel will:
• Blink the trouble LED.
• Activate the trouble relay.
• Disable the Notification Appliance Circuit(s).
• Disable the alarm relay.
• The display shows: 00_F
• Ignore all other keys other than those mentioned in this section.
• Continue to communicate any events not previously acknowledged at a
Central Station prior to entering Programming Mode.
While in any of the four levels of Programming Mode, the first two locations on the
Prog
Progrr amming
left of the display represent the memory address and the last location (farthest right)
represents the contents of the memory address. The first address displayed is shown
below:
00_F
(address)(data)
3.2 Switch The Function of each switch in program mode is shown below:
Functions
No function in Program Mode
Note: Location 56 is factory defaulted to = 0, Control Panel only. This keeps the
communicator off until location 56 is changed to: 1= panel/communicator. Once
location 56 is set to 1 and a valid phone number is entered, entry into the program
mode will cause transmission of the "System off Normal" report.
4 8 4 7 1 6 1 F F F F F F F F F
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 .
36 50475 Rev D1 9/22/99 P/N 50475:D1
Valid entries for both the primary and secondary phone numbers are 0 - F with the
numeric digits as dialed numbers and hex digits representing the following functions:
Progrr amming
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
Prog
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Contact ID, DTMF, 1400/2300 ACK
F: Future use
Note: Consult your Central Station for proper selection or consult our factory
representatives. For any format chosen, the control panel automatically programs all of
the event codes. See Tables 3-2 through 3-7.
Caution: Default entries for event codes (as shown in tables 3-2 through 3-7) are
programmed into memory each time address '16' is altered. Be certain to double check
entries after programming the zone functions, addresses 64 - 73. Program the format
first, then program the zone(s) function. Do not alter while the communicator is active.
Primary Central Station Number Account Code (17-20) Four locations at addresses
17-20 default to all '0's. Valid entries are (0-9 and A-F). The number of digits entered
must match the format selection. If programming '2, 3, 4, or 5' into address 16, enter 3
digits (location 20 is ignored). If programming '0, 1, 6, 7, 8, 9, A, B, C, D or E' into
address 16, enter 4 digits.
Primary Central Station Number 24/12/8/6 Hour Test Time Interval (25). The test
report sent to the Primary phone number may be sent every 6, 8, 12 or 24 hours. If the
message is to be sent every 24 hours, leave the factory default entry of zero. If other test
report times are needed, enter 1=12, 2=8 and 3=6.
50475 Rev D1 7/22/9 P/N 50475:D1
37
Secondary Central Station Phone Number (26-41). Programming is similar to program-
ming the primary phone number located at addresses 00 - 15. The defaults are also all 'F's.
F F F F F F F F F F F F F F F F
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 .
Note: Consult your Central Station for proper selection or consult our factory
representatives. For any format chosen, the control panel automatically programs all of
the event codes. See Tables 3-2 through 3-7.
Caution: Default entries for event codes (as shown in tables 3-2 through 3-7) are
programmed into memory each time address '42' is altered. Be certain to double check
entries after programming the zone functions, addresses 64 - 73. Program the format first,
then program the zone(s) function. Do not alter entry while the communicator is active.
Alarm Presignal Delay Timer (53-55) The alarm presignal timer is factory set to 120
Progrr amming
seconds (2 minutes), address 53=1, 54=2 and 55=0. The timer may be programmed from 0
to 179 seconds. Location 52 must be set to '1'.
Communicator/Fire Panel Selection (56) Leaving address 56 at '0' causes the control
panel to operate as a fire panel only. Selecting '1' will make it operate as a Fire panel/
Prog
communicator.
Backup Reporting (57) Leaving address 57 at '0' means that reports will be transmitted to
the secondary Central Station phone number only if attempts to communicate to the
primary Central Station phone number are unsuccessful. Programming a '1' causes all
reports to be transmitted to both the primary and secondary Central Station phone numbers.
Programming a '2' causes reports to go to the first available receiver.
Caution: Do not alter this entry while the communicator is active.
Touchtone/Rotary Select for Primary Phone(58) A '0' programmed in this address by the
factory triggers Touchtone dialing over the primary phone line. Select '1' for rotary dialing.
Make Break Ratio for Primary Phone (59) Use this address only if you have chosen '1'
for address 58. The make/break ratio is factory set to '0' which is 67/33, but may be
changed to '1' which is a 62/38 ratio.
Touchtone/Rotary Select for Secondary Phone (60) A '0' programmed in this address by
the factory triggers Touchtone dialing over the secondary phone line. Select '1' for rotary
dialing.
Make Break Ratio for Secondary Phone (61) Use this address only if you have chosen '1'
for address 60. The make/break ratio is factory set to '0' which is 67/33, but may be
changed to '1' which is a 62/38 ratio.
Zones 1-10 Function Selection (64-73) The ten zones on the control panel may be
programmed as shown in the following list. Program entries alter zone function, transmittal
priority and, as a result of altering the zone definition, the transmitted event code message
is automatically changed. Remote switch entries '9, A, B and C' cause the zone function to
be altered to match the FACP keypad entries. Initial closure (or shorting) of a switch
causes the switch function to occur. The switch must be returned to its normal position.
Progrr amming
silenceable; '6' for Waterflow, nonsilenceable; '7' for critical and noncritical process monitoring; '8'
for autoresettable process monitoring; '9' for remote reset switch; 'A' for remote silence switch; 'B'
for remote acknowledge switch; or 'C' for remote manual evacuate (drill) switch.
Prog
Factory default for zone 9 is '0', 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-
Open contact device; '3' for Supervisory; '4' for Supervisory, auto resettable; '5' for Waterflow,
silenceable; '6' for Waterflow, nonsilenceable; '7' for critical and noncritical process monitoring; '8'
for autoresettable process monitoring; '9' for remote reset switch; 'A' for remote silence switch; 'B'
for remote acknowledge switch; or 'C' for remote manual evacuate (drill) switch.
Note: Programming any zone to function as supervisory or supervisory auto-resettable will cause
the defaulted zone alarm event codes (note in Table 3-2) to be automatically changed. The
defaulted code of '1' is changed to '8' for formats 3+1 and 4+1 Standard and Expanded, 4+2
Expanded and 4+1 Express (refer to Tables 3-2 and 3-5). The defaulted codes of 11 through 1A
are changed to 81 through 8A accordingly for formats 4+2 Standard and 4+2 Express (refer to
Tables 3-3 and 3-6). Programming any zone to function as process monitoring (Zone Function
Selections 7 or 8) will cause the alarm event code to be automatically programmed as '0' or '00'
which disables the report. Be certain to reprogram the alarm event code for each process
monitoring zone. Restoral codes remain unchanged from factory defaults.
When using Contact ID Format, zone alarm and zone restoral event codes change automatically
as shown in Table 3-1. Be certain to reprogram alarm event codes when selecting process
monitoring functions. Zone fault and disable event codes may also be user reprogrammed (refer
to Appendix D).
1 Pull Station 11 5
A Silence N/A
B Acknowledge N/A
C Drill N/A
During the alarm verification period, access to other modes of operation is prevented.
ALARM VERIFICATION PERIOD
0 Sec. 6 Sec. 18 Sec. 120 Sec
CONFIRMATION TIME
Detector Zone Goes Into Alarm Alarm Ignored Control Panel Processes Alarm if Same Detector Zone is Still in Alarm
0 30 60 90 120
Different Detector Zone
Alarms Control Panel Immediately Processes Alarm
Progrr amming
monitoring auto-resettable.
Prog
local Authority Having Jurisdiction (AHJ) prior to altering this address.
Trouble Reminder (88) Factory default '0' disables the trouble reminder feature.
Selecting '1' will cause a reminding beep (after the Silence or Acknowledge switch is
pressed) every 15 seconds during an alarm and beep every two minutes during a
trouble condition. The beeps from the on board piezo sounder will occur until the
alarm or fault is cleared.
to be programmed.
Hours/Minutes
Select a digit then press [ENTER/STORE]
[ENTER/STORE]. The digit 2nd from the left will start
flashing. Select a digit then press [ENTER/STORE]
[ENTER/STORE]. Hours setting is complete.
With the digit 2nd from the right flashing, select a digit then press [ENTER/
STORE]
STORE]. The digit on the far right will start flashing. Select a digit then press
[ENTER/STORE]
[ENTER/STORE]. Minutes setting is complete. Note: If an invalid digit is selected
(i.e. 3 or higher for the first digit) the FACP piezo will beep and the digit will
continue to blink until a valid entry is made.
Year
After entering the last digit corresponding to minutes (far right digit) the display will
read 1996 with the digit 9, second from the right, flashing. Press [ENTER/STORE]
if acceptable or any digit. Entering a zero (0) will change the display to the year
2000. Repeat for digit to far right.
Month/Day
After the year is entered the display will show four digits representing the month and
day of the software release date. The month is represented by the two digits on the
left and the day by the two digits on the right. The digit on the far left will be
flashing. The month and day are set the same way as the hours and minutes. Once
the last digit corresponding to the day is entered, the display will show the contents
of address '00'. The real time clock/calendar keeps track of leap years automatically.
Note that the software for the SFP-1024 operates the internal clock based upon 60
Hz. The software for the SFP-1024E operates the internal clock based upon 50 Hz.
During Program Mode, if no key is pressed within 10 minutes, the panel will revert
to normal mode.
Each option of the Program Mode is entered by keying in the program mode entry
7764
7764) and pressing the ENTER/STORE key.
code (7764
If an incorrect key is entered, reenter the proper 4-digit code before pressing the
[ENTER/STORE] key.
You are allowed a pause of up to 10 seconds in between each number while entering
the code. After pressing the [ENTER/STORE] key, the control panel will be in
Program Mode and display P__1P__1, with the 1 flashing. Press 2 on the keypad and
then the [ENTER/STORE] key to select the Event Codes/Transmission Formats
Level for programming. You are allowed up to ten minutes of idle time at this point
before starting your programming, otherwise the control panel will go back to
Progrr amming
Normal Mode. You also have a maximum of 10 minutes between any key stroke.
All entries made prior to the 10 minute time-out are valid and are stored.
Prog
00_1
(address)(data)
The first three locations on the left of the display represent the memory address 00 of
the Format Chart previously selected in address 16 of the Main Panel Options section
of programming mode. The last location 1 (farthest right) represents the contents of
memory address (00) which is the format setting. The only value which can be
altered in the Format Charts is the setting which is the last digit to the right. To
change the value, key in the new digit.
Use the Up and Down Arrow keys to increment to the next address or decrement to
the previous address.
When desired changes have been completed, exit programming mode by pressing the
MODE key, followed by the four-digit code for an alternate mode and then the
[ENTER/STORE] key. To enter a different Programming Level, press MODE and
then press the [ENTER/STORE] key. The display will show P__2 with the '2'
flashing. Press the digit (1, 3 or 4) of the Programming Level to be accessed.
During Program Mode, if no key is pressed within 10 minutes, the panel will revert
to normal mode.
The Format Charts which may be selected in the Main Panel Options (Level 1)
section of the Programming Mode are shown on the following pages of this section.
Format charts for the Primary and Secondary Central Station Numbers are included.
Tab le 3-2: Ev
able ent Codes
Event Codes,, Pr imar
Primar
imaryy Centr al Station Number
Central
46 50475 Rev D1 9/22/99 P/N 50475:D1
Address Description Setting
61 Primary # Zone 1 Disabled Restore Code 5
62 Primary # Zone 2 Disabled Restore Code 5
63 Primary # Zone 3 Disabled Restore Code 5
64 Primary # Zone 4 Disabled Restore Code 5
65 Primary # Zone 5 Disabled Restore Code 5
66 Primary # Zone 6 Disabled Restore Code 5
67 Primary # Zone 7 Disabled Restore Code 5
68 Primary # Zone 8 Disabled Restore Code 5
69 Primary # Zone 9 Disabled Restore Code 5
70 Primary # Zone 10 Disabled Restore Code 5
71 Primary # Drill Restore Code 9
72 Primary # AC Fault Restore Code 9
73 Primary # Zone 1 Fault Restore Code D
74 Primary # Zone 2 Fault Restore Code D
75 Primary # Zone 3 Fault Restore Code D
76 Primary # Zone 4 Fault Restore Code D
77 Primary # Zone 5 Fault Restore Code D
Progrr amming
78 Primary # Zone 6 Fault Restore Code D
79 Primary # Zone 7 Fault Restore Code D
80 Primary # Zone 8 Fault Restore Code D
81 Primary # Zone 9 Fault Restore Code D
82 Primary # Zone 10 Fault Restore Code D
83 Primary # Earth Fault Restore Code A
84 Primary # Low Battery Fault Restore Code A
Prog
85 Primary # No Battery Fault Restore Code A
86 Primary # Telco Pri. Line Fault Restore Code A
87 Primary # Telco Sec. Line Fault Restore Code A
88 Primary # NAC #1 Fault Restore Code A
89 Primary # NAC #2 Fault Restore Code A
90 Primary # NAC #3 Fault Restore Code A
91 Primary # NAC #4 Fault Restore Code A
92 Primary # NAC #1 Disable Restore Code 5
93 Primary # NAC #2 Disable Restore Code 5
94 Primary # NAC #3 Disable Restore Code 5
95 Primary # NAC #4 Disable Restore Code 5
96 Primary # Comm Trouble Pri. # Restore Code A
97 Primary # Comm Trouble Sec. # Restore Code A
98 Primary # Printer Fault Restore Code A
99 Primary # Annunciator Fault Restore Code A
100 Primary # 485 Comm. Trouble Restore Code A
101 Primary # System Off Normal Restore Code A
102 Primary # System Test Report 9
103 Primary # System Abnormal Test Report F
104 Primary # Request for Up/Download 7
105 Primary # Successful Upload 7
106 Primary # Successful Download 7
107 Primary # Failed Up/Download 7
Tab le 3-2: Ev
able ent Codes
Event Codes,, Pr imar
Primar
imaryy Centr al Station Number (cont.)
Central
Tab le 3-3: Ev
able ent Codes
Event Codes,, Pr imar
Primar
imaryy Centr al Station Number
Central
48 50475 Rev D1 9/22/99 P/N 50475:D1
Address Description Settings
Progrr amming
158 - 159 Primary # Zone 7 Fault Restore Code D7
160 - 161 Primary # Zone 8 Fault Restore Code D8
162 - 163 Primary # Zone 9 Fault Restore Code D9
164 - 165 Primary # Zone 10 Fault Restore Code DA
166 - 167 Primary # Earth Fault Restore Code A1
168 - 169 Primary # Low Battery Fault Restore Code A2
170 - 171 Primary # No Battery Fault Restore Code A3
Prog
172 - 173 Primary # Telco Pri. Line Fault Restore Code A4
174 - 175 Primary # Telco Sec. Line Fault Restore Code A5
176 - 177 Primary # NAC #1 Fault Restore Code A6
178 - 179 Primary # NAC #2 Fault Restore Code A7
180 - 181 Primary # NAC #3 Fault Restore Code A8
182 - 183 Primary # NAC #4 Fault Restore Code A9
184 - 185 Primary # NAC #1 Disable Restore Code 5B
186 - 187 Primary # NAC #2 Disable Restore Code 5C
188 - 189 Primary # NAC #3 Disable Restore Code 5D
190 - 191 Primary # NAC #4 Disable Restore Code 5E
192 - 193 Primary # Comm Trouble Pri. # Restore Code AA
194 - 195 Primary # Comm Trouble Sec. # Restore Code AB
196 - 197 Primary # Printer Fault Restore Code AC
198 - 199 Primary # Annunciator Fault Restore Code AD
200 - 201 Primary # 485 Comm. Trouble Restore Code AE
202 - 203 Primary # System Off Normal Restore Code AF
204 - 205 Primary # System Test Report 99
206 - 207 Primary # System Abnormal Test Report 91
208 - 209 Primary # Request for Up/Download 71
210 - 211 Primary # Successful Upload 72
212 - 213 Primary # Successful Download 73
214 - 215 Primary # Failed Up/Download 74
Note: 1Zones programmed as supervisory alarm transmit as 81, 82, 83, 84, 85, 86, 87,
88, 89, 8A (instead of 11, 12, 13, 14, 15, 16, 17, 18, 19, 1A).
Tab le 3-3: Ev
able ent Codes
Event Codes,, Pr imar
Primar
imaryy Centr al Station Number (cont.)
Central
Progrr amming
228 Secondary # Zone 3 Disabled Code 4
229 Secondary # Zone 4 Disabled Code 4
230 Secondary # Zone 5 Disabled Code 4
231 Secondary # Zone 6 Disabled Code 4
232 Secondary # Zone 7 Disabled Code 4
233 Secondary # Zone 8 Disabled Code 4
234 Secondary # Zone 9 Disabled Code 4
Prog
235 Secondary # Zone 10 Disabled Code 4
236 Secondary # Drill Code 9
237 Secondary # AC Fault Code 9
238 Secondary # Zone 1 Fault Code F
239 Secondary # Zone 2 Fault Code F
240 Secondary # Zone 3 Fault Code F
241 Secondary # Zone 4 Fault Code F
242 Secondary # Zone 5 Fault Code F
243 Secondary # Zone 6 Fault Code F
244 Secondary # Zone 7 Fault Code F
245 Secondary # Zone 8 Fault Code F
246 Secondary # Zone 9 Fault Code F
247 Secondary # Zone 10 Fault Code F
248 Secondary # Earth Fault Code 6
249 Secondary # Low Battery Fault Code 6
250 Secondary # No Battery Fault Code 6
251 Secondary # Telco Pri. Line Fault Code 6
252 Secondary # Telco Sec. Line Fault Code 6
253 Secondary # NAC #1 Fault Code 6
254 Secondary # NAC #2 Fault Code 6
255 Secondary # NAC #3 Fault Code 6
256 Secondary # NAC #4 Fault Code 6
257 Secondary # NAC #1 Disable Code 4
258 Secondary # NAC #2 Disable Code 4
259 Secondary # NAC #3 Disable Code 4
260 Secondary # NAC #4 Disable Code 4
261 Secondary # Comm Trouble Pri. # Code 6
262 Secondary # Comm Trouble Sec. # Code 6
263 Secondary # Printer Fault Code 6
264 Secondary # Annunciator Fault Code 6
265 Secondary # 485 Comm. Trouble Code 6
266 Secondary # System Off Normal Code 6
267 Secondary # Zone 1 Alarm Restore Code E
268 Secondary # Zone 2 Alarm Restore Code E
269 Secondary # Zone 3 Alarm Restore Code E
270 Secondary # Zone 4 Alarm Restore Code E
271 Secondary # Zone 5 Alarm Restore Code E
272 Secondary # Zone 6 Alarm Restore Code E
273 Secondary # Zone 7 Alarm Restore Code E
274 Secondary # Zone 8 Alarm Restore Code E
275 Secondary # Zone 9 Alarm Restore Code E
276 Secondary # Zone 10 Alarm Restore Code E
Tab le 3-5: Ev
able ent Codes
Event Codes,, Secondar
Secondaryy Centr al Station Number
Central
50475 Rev D1 7/22/9 P/N 50475:D1
51
Address Description Setting
277 Secondary # Zone 1 Disabled Restore Code 5
278 Secondary # Zone 2 Disabled Restore Code 5
279 Secondary # Zone 3 Disabled Restore Code 5
280 Secondary # Zone 4 Disabled Restore Code 5
281 Secondary # Zone 5 Disabled Restore Code 5
282 Secondary # Zone 6 Disabled Restore Code 5
283 Secondary # Zone 7 Disabled Restore Code 5
284 Secondary # Zone 8 Disabled Restore Code 5
285 Secondary # Zone 9 Disabled Restore Code 5
286 Secondary # Zone 10 Disabled Restore Code 5
287 Secondary # Drill Restore Code 9
288 Secondary # AC Fault Restore Code 9
289 Secondary # Zone 1 Fault Restore Code D
290 Secondary # Zone 2 Fault Restore Code D
291 Secondary # Zone 3 Fault Restore Code D
292 Secondary # Zone 4 Fault Restore Code D
293 Secondary # Zone 5 Fault Restore Code D
294 Secondary # Zone 6 Fault Restore Code D
Prog
Progrr amming
Tab le 3-5: Ev
able ent Codes
Event Codes,, Secondar
Secondaryy Centr al Station Number (cont.)
Central
Progrr amming
242 - 243 Secondary # Zone 4 Disable Code 44
244 - 245 Secondary # Zone 5 Disable Code 45
246 - 247 Secondary # Zone 6 Disable Code 46
248 - 249 Secondary # Zone 7 Disable Code 47
250 - 251 Secondary # Zone 8 Disable Code 48
252 - 253 Secondary # Zone 9 Disable Code 49
254 - 255 Secondary # Zone 10 Disable Code 4A
Prog
256 - 257 Secondary # Drill Code 97
258 - 259 Secondary # AC Fault Code 92
260 - 261 Secondary # Zone 1 Fault Code F1
262 - 263 Secondary # Zone 2 Fault Code F2
264 - 265 Secondary # Zone 3 Fault Code F3
266 - 267 Secondary # Zone 4 Fault Code F4
268 - 269 Secondary # Zone 5 Fault Code F5
270 - 271 Secondary # Zone 6 Fault Code F6
272 - 273 Secondary # Zone 7 Fault Code F7
274 - 275 Secondary # Zone 8 Fault Code F8
276 - 277 Secondary # Zone 9 Fault Code F9
278 - 279 Secondary # Zone 10 Fault Code FA
280 - 281 Secondary # Earth Fault Code 61
282 - 283 Secondary # Low Battery Fault Code 62
284 - 285 Secondary # No Battery Fault Code 63
286 - 287 Secondary # Telco Pri. Line Fault Code 64
288 - 289 Secondary # Telco Sec. Line Fault Code 65
290 - 291 Secondary # NAC #1 Fault Code 66
292 - 293 Secondary # NAC #2 Fault Code 67
294 - 295 Secondary # NAC #3 Fault Code 68
296 - 297 Secondary # NAC #4 Fault Code 69
298 - 299 Secondary # NAC #1 Disable Code 4B
300 - 301 Secondary # NAC #2 Disable Code 4C
302 - 303 Secondary # NAC #3 Disable Code 4D
304 - 305 Secondary # NAC #4 Disable Code 4E
306 - 307 Secondary # Comm Trouble Pri. # Code 6A
308 - 309 Secondary # Comm Trouble Sec. # Code 6B
310 - 311 Secondary # Printer Fault Code 6C
312 - 313 Secondary # Annunciator Fault Code 6D
314 - 315 Secondary # 485 Comm. Trouble Code 6E
316 - 317 Secondary # System Off Normal Code 6F
318 - 319 Secondary # Zone 1 Alarm Restore Code E1
320 - 321 Secondary # Zone 2 Alarm Restore Code E2
322 - 323 Secondary # Zone 3 Alarm Restore Code E3
324 - 325 Secondary # Zone 4 Alarm Restore Code E4
326 - 327 Secondary # Zone 5 Alarm Restore Code E5
328 - 329 Secondary # Zone 6 Alarm Restore Code E6
330 - 331 Secondary # Zone 7 Alarm Restore Code E7
332 - 333 Secondary # Zone 8 Alarm Restore Code E8
334 - 335 Secondary # Zone 9 Alarm Restore Code E9
336 - 337 Secondary # Zone 10 Alarm Restore Code EA
Tab le 3-6: Ev
able ent Codes
Event Codes,, Secondar
Secondaryy Centr al Station Number
Central
50475 Rev D1 7/22/9 P/N 50475:D1
53
Address Description Setting
338 - 339 Secondary # Zone 1 Disable Restore Code 51
340 - 341 Secondary # Zone 2 Disable Restore Code 52
342 - 343 Secondary # Zone 3 Disable Restore Code 53
344 - 345 Secondary # Zone 4 Disable Restore Code 54
346 - 347 Secondary # Zone 5 Disable Restore Code 55
348 - 349 Secondary # Zone 6 Disable Restore Code 56
350 - 351 Secondary # Zone 7 Disable Restore Code 57
352 - 353 Secondary # Zone 8 Disable Restore Code 58
354 - 355 Secondary # Zone 9 Disable Restore Code 59
356 - 357 Secondary # Zone 10 Disable Restore Code 5A
358 - 359 Secondary # Drill Restore Code 98
360 - 361 Secondary # AC Fault Restore Code 93
362 - 363 Secondary # Zone 1 Fault Restore Code D1
364 - 365 Secondary # Zone 2 Fault Restore Code D2
366 - 367 Secondary # Zone 3 Fault Restore Code D3
368 - 369 Secondary # Zone 4 Fault Restore Code D4
370 - 371 Secondary # Zone 5 Fault Restore Code D5
372 - 373 Secondary # Zone 6 Fault Restore Code D6
Prog
Progrr amming
Note: 1Zones programmed as supervisory alarm transmit as 81, 82, 83, 84, 85, 86, 87,
88, 89, 8A.
Tab le 3-6: Ev
able ent Codes
Event Codes,, Secondar
Secondaryy Centr al Station Number (cont.)
Central
Progrr amming
246 - 248 Secondary # Zone 1 Disable Code 570 001
249 - 251 Secondary # Zone 2 Disable Code 570 002
252 - 254 Secondary # Zone 3 Disable Code 570 003
255 - 257 Secondary # Zone 4 Disable Code 570 004
258 - 260 Secondary # Zone 5 Disable Code 570 005
261 - 263 Secondary # Zone 6 Disable Code 570 006
264 - 266 Secondary # Zone 7 Disable Code 570 007
Prog
267 - 269 Secondary # Zone 8 Disable Code 570 008
270 - 272 Secondary # Zone 9 Disable Code 570 009
273 - 275 Secondary # Zone 10 Disable Code 570 010
276 - 278 Secondary # Drill Code 604 000
279 - 281 Secondary # AC Fault Code 301 000
282- 284 Secondary # Zone 1 Fault Code 380 001
285 - 287 Secondary # Zone 2 Fault Code 380 002
288 - 290 Secondary # Zone 3 Fault Code 380 003
291 - 293 Secondary # Zone 4 Fault Code 380 004
294 - 296 Secondary # Zone 5 Fault Code 380 005
297 - 299 Secondary # Zone 6 Fault Code 380 006
300 - 302 Secondary # Zone 7 Fault Code 380 007
303 - 305 Secondary # Zone 8 Fault Code 380 008
306 - 308 Secondary # Zone 9 Fault Code 380 009
309 - 311 Secondary # Zone 10 Fault Code 380 010
312 - 314 Secondary # Earth Fault Code 310 000
315 - 317 Secondary # Low Battery Fault Code 302 000
318 - 320 Secondary # No Battery Fault Code 311 000
321 - 323 Secondary # Telco Pri. Line Fault Code 351 000
324 - 326 Secondary # Telco Sec. Line Fault Code 352 000
327 - 329 Secondary # NAC #1 Fault Code 321 001
330 - 332 Secondary # NAC #2 Fault Code 322 002
333 - 335 Secondary # NAC #3 Fault Code 326 003
336 - 338 Secondary # NAC #4 Fault Code 327 004
339 - 341 Secondary # NAC #1 Disable Code 521 001
342 - 344 Secondary # NAC #2 Disable Code 522 002
345 - 347 Secondary # NAC #3 Disable Code 526 003
348 - 350 Secondary # NAC #4 Disable Code 527 004
351 - 353 Secondary # Comm Trouble Pri. # Code 354 001
354 - 356 Secondary # Comm Trouble Sec. # Code 354 002
357 - 359 Secondary # Printer Fault Code 336 000
360 - 362 Secondary # Annunciator Fault Code 330 001
363 - 365 Secondary # 485 Comm. Trouble Code 330 002
366 - 368 Secondary # System Off Normal Code 308 000
369 - 371 Secondary # System Test Message 602 000
372 - 374 Secondary # System Abnormal Test Message 608 000
375 - 377 Secondary # Upload/Download Request Code 411 000
378 - 380 Secondary # Upload Successful Code 416 000
381 - 383 Secondary # Download Successful Code 412 000
384 - 386 Secondary # Upload/Download Failed Code 413 000
Note: 1Refer to Table 3-1 for list of zone alarm event codes.
Tab le 3-7: Ev
able ent Codes
Event Codes,, Secondar
Secondaryy Centr al Station Number
Central
50475 Rev D1 7/22/9 P/N 50475:D1
55
3. Level Three - Option Module Selections
Each option of the Program Mode is entered by keying in the program mode entry
7764
7764) and pressing the ENTER/STORE key.
code (7764
If an incorrect key is entered, reenter the proper 4-digit code before pressing the
[ENTER/STORE] key.
You are allowed a pause of up to 10 seconds in between each number while entering
the code. After pressing the [ENTER/STORE] key, the control panel will be in
Program Mode and display P__1P__1, with the 1 flashing. Press 3 on the keypad and
then the [ENTER/STORE] key to choose the Option Module Selections. You are
allowed up to ten minutes of idle time at this point before starting your
Prog
Progrr amming
programming, otherwise the control panel will go back to Normal Mode. You also
have a maximum of 10 minutes between any key stroke. All entries made prior to
the 10 minute time-out are valid and are stored.
Upon entering the Option Modules Selections in programming mode, the following
will be displayed on the FACP Seven-Segment LED Display.
00_0
(address)(data)
The first two locations on the left of the display represent the memory address 00 of
the first Option Module (CAC-10F Converter Card). The last location 0 (farthest
right) represents the contents of memory address 00 which indicates that the card is
not installed. To install the card, press 1 on the keypad.
Use the Up and Down Arrow keys to increment to the next address or decrement to
the previous address.
When desired changes have been completed, exit programming mode by pressing the
MODE key, followed by the four-digit code for an alternate mode and then the
[ENTER/STORE] key. To enter a different Programming Level, press MODE and
then press the [ENTER/STORE] key. The display will show P__3 with the '3'
flashing. Press the digit (1, 2 or 4) of the Programming Level to be accessed.
During Program Mode, if no key is pressed within 10 minutes, the panel will revert
to normal mode.
Devices which may be connected to the EIA-485 port include LDM graphic
annunciators, AFM LED type annunciators, LED-10N LED type annunciators and
ACM-8R relay modules. Included on the LDM, LED-10N and ACM-8R are
switches which select an address from 01 to 32. For each device added or connected
to the EIA-485 port via the LED-10IM select an address on each, with the exception
of the ACM-8R (refer to the applications section of the ACM-8R Manual P/N
50362). Addresses must be sequential with no gaps allowed. For example, if 13
devices are connected to the EIA-485 port, the maximum monitored address value
entered into locations 02-03 must be 02 = '1' and 03 = '3'. If 25 devices are
connected to the EIA-485 port, the maximum monitored address entered into
locations 02-03 must be 02 = '2' and 03 = '5'.
Progrr amming
All devices connected to the EIA-485 are fully supervised by the FACP. Note that
AFM series annunciators occupy address '01'. The address of the AFM series cannot
be altered. When using AFM series devices with LDMs, LED-10Ns and ACM-8Rs,
be certain that none of the other devices are set to address '01'. Factory default
entry is 02 = 0 and 03 = 1.
Prog
Printer Installed (04)
The factory default entry of '0' in address 04 informs the FACP that a printer is not
connected to the panel. This entry must be changed to '1' if a printer is connected.
The PRT-24 printer interface module must be installed on J4 of the SFP-1024 main
circuit board before a printer can be installed.
following lengths of time (requires prior approval of local AHJ), enter '1' for 5
minutes; '2' for 10 minutes; '3' for 15 minutes; '4' for 20 minutes; '5' for 25 minutes;
or '6' for 30 minutes.
The non-Canadian supervisory function will turn on the red zone alarm LED for any
type of zone function. The blink rate at the annunciators is 1 second ON/ 1 second
OFF for fire alarm, ½ second ON/ ½ second OFF for supervisory alarm and ¼
second ON/ ¼ second OFF for process monitored alarm. The default entry is '0' for
non-Canadian supervisory annunciation; enter '1' for Canadian Supervisory
Annunciation.
Note: UL and ULC require slide-in labels on all annunciators to be clearly marked
as to the function of each zone.
Progrr amming
Caution: When selecting this function, be aware that ACM-8R relays programmed
for alarm will not activate for supervisory alarms.
Prog
4. Level Four - Upload/Download Option
Each option of the Program Mode is entered by keying in the program mode entry
7764
7764) and pressing the ENTER/STORE key.
code (7764
If an incorrect key is entered, reenter the proper 4-digit code before pressing the
[ENTER/STORE] key.
You are allowed a pause of up to 10 seconds in between each number while entering
the code. After pressing the [ENTER/STORE] key, the control panel will be in
Program Mode and display P__1P__1, with the 1 flashing. Press 4 on the keypad and
then the [ENTER/STORE] key to choose the Upload/Download Option. You are
allowed up to ten minutes of idle time at this point before starting your
programming, otherwise the control panel will go back to Normal Mode. You also
have a maximum of 10 minutes between any key stroke. All entries made prior to
the 10 minute time-out are valid and are stored.
The first two locations on the left of the display represent the memory address 00
00.
The last location 0 (farthest right) represents the contents of memory address 00
which is the first digit of the Panel Identification Number. To change the Panel ID
Number, key in the first of the four digits for the ID. Increment to the next address
and key in the second number. Continue until all digits are programmed.
Use the Up and Down Arrow keys to increment to the next address or decrement to
the previous address.
During Program Mode, if no key is pressed within 10 minutes, the panel will revert
to normal mode.
The SFP-1024 can be programmed remotely from a PC using a modem and the
telephone line. Information can also be retrieved from the FACP with the same
method. The Upload/Download Option allows an operator to set the necessary
parameters to allow the uploading and downloading of data between the FACP and
PC.
Progrr amming
5. Def ault Pr
Default Proo g r amming
To return all program entries in all four levels to their factory original settings,
perform the following steps only when the system is idle in Normal standby
Prog
condition:
Press the MODE key followed by the four digit code 3337 and press the ENTER/
STORE key.
☛ 3337 DEF
DEFault P rogramming) on a Touch-Tone® phone
spells DEFP (DEF
If an incorrect key is entered, reenter the proper 4-digit code before pressing the
[ENTER/STORE] key.
Within five seconds, repeat this entry by again pressing the MODE key followed by
the four digit code 3337 and pressing the [ENTER/STORE] key. The display will
read 3337 while the E2 nonvolatile memory (storage area for all programming
options) is being reprogrammed with the original default settings. When
reprogramming is complete, the display will be blank.
Figure 4-1: Ne
Neww and Old Ke ypad/Displa
Ke y
ypad/Display
Normal Mode The SFP-1024 has several modes of operation including: Normal, Program, Walk
Test, Troubleshoot, History, Lamp Test, Print and Upload/Download. There are
also four function modes: Drill, Zone Enable/Disable, NAC Enable/Disable and
Default Programming. Upon initial power up, the system will be in Normal Mode.
This section discusses operation of the control panel in the Normal Mode.
4.1 Switches Below is a description of the system function switches in Normal Mode:
RESET The System Reset Switches reset the system and any smoke detectors. Reset
switches may be located on the FACP key pad (illustrated above), any of the 10
zones programmed as a remote reset switch, remotely on any of the LED-10N
annunciators, the LDM graphic annunciators, or the AFM series annunciators. If any
of the System Reset Switches are pressed, the control panel will:
Any alarm, supervisory or trouble condition that exists after a system reset, will
resound the system, reactivating normal system activity. Upon release of a System
Reset Switch, the FACP display will read rES_ for six seconds.
SILENCE Silence switches may be located on the FACP key pad (illustrated above), any of the
10 zones programmed as a remote silence switch, remotely located on any of the
LED-10N annunciators, the LDM graphic annunciators, or the AFM series
62 50475 Rev D1 9/22/99 P/N 50475:D1
annunciators. The Silence Switch performs the same functions as the System
Acknowledge Switch, in addition, if any of the System Silence Switches are pressed:
• The silenceable Notification Appliance Circuits will be turned OFF.
• The main circuit board silence LED will be turned ON.
• The SILn message will be displayed (where n = NAC #).
• The system piezo sounders will be shut OFF.
• 'NAC #N Silenced' message will be stored in the History file.
• 'NAC #N Silenced' message will be sent to the printer
ACKNOWLEDGE/STEP Acknowledge/Step switches (Up/Down arrow keys) are located on newer model FACP
keypads (see Figure 4-1), remotely located on any of the LED-10N annunciators, the
LDM graphic annunciators, or the AFM series annunciators and an option exists that
allows any of the 10 zones to be programmed to function as a remote acknowledge
switch.
Operating Instructions
The Acknowledge/Step switch silences the system piezo sounders and changes all
flashing system LEDs to steady. An acknowledge message is sent to the printer and
history files. The Step function permits scrolling through multiple stored events during
normal, history and walktest modes.
When more than one event exists, the first press of the Acknowledge/Step switch silences
the system piezo sounders and changes all flashing system LEDs to steady. The second
press of the switch stops the scrolling and holds the event on the display for five seconds.
Subsequent pressing of the switch 'steps' through each active event. The Acknowledge
Switch must be pressed within 15 seconds to prevent NACs from turning on if alarm
presignal is selected. For additional information on alarm presignal, refer to
Programming Section 3.0.
DRILL Drill switches may be located on any of the 10 zones programmed as a remote drill
switch, remotely on any of the LED-10N annunciators, the LDM graphic annunciators, or
the AFM series annunciators. To perform a drill from any of these switches, the Drill
switch must be pressed and held for two seconds (time to prevent accidental activation).
The SFP-1024 turns on all NACs and turns off the system silence LEDs. The message
shown on the display is dril
dril. The drill message is sent to the printer and history files.
The system silence keys will silence all silenceable NACs during a fire drill.
To perform a drill from the FACP, press the MODE key followed by the code 3745 then
press [ENTER/STORE]
[ENTER/STORE]. The display will read dril dril. The alarm relay is not activated.
There is an option to transmit the fire drill report code to the Central Station. During a
fire drill, the SILENCE key will silence all silenceable NACs and the RESET key
restores the panel to normal. All zones remain active during a fire drill.
MODE Pressing the Mode Switch followed by a valid 4-digit numerical code and [ENTER/
STORE] selects one of the six modes of operation.
☛ To enter normal mode from any other mode press MODE then
6676 [ENTER/STORE]
[ENTER/STORE]. 6676 spells NORM on a Touch-Tone® phone.
1st EVENT This switch along with the Up Arrow and Down Arrow keys, is used to display any
presently active alarm and/or fault conditions present in the system. Press the 1st Event
switch at any time to display the first event (alarm and/or trouble) that occurred.
UP ARROW (ACK) Use the Up Arrow key to view other events (newer), that have occurred and are
active - not cleared yet. It also acknowledges the event by silencing the local piezo.
[ENTER/STORE] See individual mode descriptions in other sections of this manual. In Normal Mode,
this key is used after pressing the MODE key followed by a four digit mode code
then the [ENTER/STORE] key.
4.2 Displays Four 7-segment red LED characters provide visual annunciation of status, events and
messages. A list of messages that may appear on the display in normal mode is
shown below:
d__1 Zone 1 Disabled F__9 Trouble Zone 9
d__2 Zone 2 Disabled F_10 Trouble Zone 10
d__3 Zone 3 Disabled F_85 Annunciator Bus Fault
d__4 Zone 4 Disabled F__A Annunciator Fault
d__5 Zone 5 Disabled F__E Earth Fault
Operating Instructions
System Trouble
Trouble—This yellow LED blinks to indicate that a fault or abnormal
condition exists and that the fire alarm system may be inoperative. It turns on steady
when a system silence or acknowledge switch is pressed.
AC Power On On—A green LED that remains on while the A.C. power supply is within
correct limits. If this indicator fails to light under normal conditions, service the
system immediately.
Supervisory
Supervisory—A yellow LED that blinks to indicate the need for action in
connection with the supervision or maintenance of sprinklers, extinguishing systems
or other protective systems.
System Silence
Silence—A yellow LED that turns on to indicate that an Alarm or Trouble
condition exists in the system, but Notification Appliance Circuits (if programmed as
Operating Instructions
silenceable) and local piezo have been silenced.
Kiss-Off —A green LED that blinks when a Central Station has acknowledged
receipt of each transmitted message or when a portion of up or downloaded data has
been accepted from a Service Terminal.
Kissoff LED
Secondary
Line
All alarm and system trouble conditions are annunciated on the control panel's display.
The control panel will maintain an 'active event list' which will consist of all alarms,
supervisory alarms and system troubles currently active, and not cleared, requiring
immediate service. When the system is cleared and restored to normal, the display will
be blank. All alarms and troubles are stored in a history file and may be recalled at
any time.
Higher priority events take precedence over lower priority events. Display and
reporting of System Status is done on a priority basis. Priorities are, from highest to
lowest:
1. Alarms
2. Supervisory Alarms
Operating Instructions
3. System Troubles
4. Process Monitoring Alarms
If the events to be displayed consist of alarms and disabled zones only, (no troubles),
the control panel will scroll them on the display. As each new alarm occurs, it will be
displayed immediately on the display for five seconds. After this five second period,
the display will scroll all alarms in the system. Pressing the 1st Event key or one of the
'ACK' keys will stop the scrolling. The 1st Event key will also cause the display to
show the First alarm that occurred after the panel was last reset, cleared of all active
events and placed into normal mode. Operation of the Up and Down arrow keys will
display all remaining events in sequence.
If events to be displayed include system troubles, only one event is displayed at a time
and there is no scrolling. The event displayed is the highest priority. Pressing the 1st
Event key will cause the display of the first event that occurred after the panel was last
reset, cleared of all active events and placed into normal mode. Operation of the Up
and Down arrow keys will display all remaining events in order of their occurrences.
Note that when any zone is programmed as a supervisory or process monitored zone, it
will not be processed in the same manner as a conventional alarm zone. See
Supervisory Condition and Process Monitored Alarm later in this section.
66 50475 Rev D1 9/22/99 P/N 50475:D1
4.3.2 Fire Alarm Restoral
The control panel returns to normal after all alarms have been cleared and a system
reset switch has been pressed (pull stations reset, smoke detectors reset and no
smoke is present, waterflow has stopped). The control panel will perform the
following upon restoral of all active alarms:
Operating Instructions
Program zones for Supervisory in applications where a waterflow sensing device has
been employed and the wiring to the waterflow valve and/or a tamper switch is to be
monitored. If the tamper switch has been activated (Normally Open contacts close),
a supervisory alarm condition will occur.
Possible trouble messages that may appear on the display are as follows:
Operating Instructions
• Clear the 4-character display.
• Communicate the alarm restoral code programmed for the activated zone.
• Store the alarm restoral message in the History file.
• Turn off the piezo sounder.
• Turn off appropriate zone relay output (ACM-8R).
• Turn off any system relays (main circuit board) programmed for process alarm
activation.
• Output alarm restoral message to printer.
• Terminate upload or download communications.
• Turn off all remote annunciator zone alarm LEDs.
Note: For any zone programmed for autoresettable process monitored alarm, the reset
key does not need to be pressed to clear the zone.
To disable a zone, press the MODE key once, (the display will go blank) you then
have 10 seconds to start entering the code 3472
3472. Next press the [ENTER/STORE]
key.
The zone disable message will remain on the display until the zone is reenabled. To
reenable a zone, press the MODE key once, (the display will go blank) you then
have 10 seconds to start entering the code 3622
3622. Next, press the [ENTER/STORE]
key.
☛ 3622 spells ENAB on a Touch-Tone® phone
A flashing upper case E will appear on the left of the display. Next, press the zone
number to be enabled. The number will appear on the far right display character.
Press [ENTER/STORE]
[ENTER/STORE]. The zone is reenabled. Note that the trouble relay is
restored to normal and the FACP trouble LED is off and all system annunciator zone
trouble LEDs are off.
The NAC/bell disable feature may be used to disable any of the four main panel
NAC/bell circuits. While in Normal Mode, NACs may be disabled if they are
normal, in trouble or alarmed.
To disable an NAC/bell, press the MODE key once, (the display will go blank).
You then have 10 seconds to start entering the code 3472
3472. Next, press the [ENTER/
STORE] key.
A flashing lower case d will appear on the far left of the display. Next, press the b
key followed by the NAC number to be disabled. The b and the NAC number will
appear on the far right display characters. Press [ENTER/STORE]
[ENTER/STORE]. The NAC is
disabled. All system annunciators will show general trouble status and the main
panel display will show the NAC disabled message, turn on the system trouble LED
and activate relays programmed for system trouble.
The NAC disable message will remain on the display until the circuit is reenabled.
To reenable an NAC, press the MODE key once (the display will go blank). You
then have 10 seconds to start entering the code 3622
3622. Next, press the [ENTER/
STORE] key.
A flashing upper case E will appear on the left of the display. Next, press the b key
followed by the NAC number to be enabled. The b and the NAC number will
appear on the far right display characters. Press [ENTER/STORE]
[ENTER/STORE]. The NAC is
reenabled. Note that relays programmed as trouble are restored to normal and the
FACP trouble LED is off and all system annunciator general trouble LEDs are off.
4.4 Central Station The control panel transmits zone and system status reports to Central Stations via the
Communications public switched telephone network. Two supervised telephone line connections are
made to interface the control panel to the telephone lines. Two 7-foot telephone
cords P/N MCBL-7 may be used for this purpose.
The control panel supervises both telephone lines for proper voltage. A delay of two
minutes will occur before a fault in either phone line connection is reported as a
trouble. When a fault is detected, an audible trouble signal will sound, the yellow
trouble LED will blink, the 4 character display will show either 'no 1' or 'no 2'
(depending upon which telephone line has the fault. 'no 1' = Primary Line, 'no 2' =
Secondary Line) and the trouble condition will be reported to a Central Station over
the remaining good phone line.
The control panel comes with line seizure capability provided for both the primary
and secondary telephone line interfaces. Any time that the control panel needs to
make a call to a Central Station, line seizure will disconnect any local premises
Operating Instructions
phones sharing the same telephone line.
All transmissions to Central Stations will be sent over the Primary Central Station
phone line. In the event of noisy phone lines, transmissions will be sent over the
backup Secondary phone line.
Two phone numbers must be programmed, the Primary Central Station phone
number and the Secondary Central Station phone number. There are three options
for transmission to the central station:
1. All messages are always sent to the primary central station phone number
with the secondary central station phone number for emergency backup
purposes only.
2. All reports are sent to both central station phone numbers.
3. Reports are sent to the first available central station phone number only.
The SFP-1024 meets NFPA 72 National Fire Code reporting requirements for: (a)
the type of signal (b) condition and (c) location of the reporting premises. The
general priority reporting structure is:
The control panel is capable of reporting detailed messages depending upon the
format in use. Table 4-1 shows the reporting structure for all formats.
System Trouble Restore SSS(S) RTS SSS(S) RTS SSSS RTSRTS2 SSSS RTSY
RTSRTSRTS(RTS) Y
Zone Disable SSS(S) DZ SSS(S) DZ SSSS RDZRDZ2 SSSS DZZ
DZDZDZ(DZ) Z
Zone Disable Restore SSS(S) RDZ SSS(S) RDZ SSSS RDZRDZ2 SSSS RDZZ
RDZRDZRDZ(RDZ) Z
Bell Disable SSS(S) DB SSS(S) DB SSSS DBDB2 SSSS DBDB2
Bell Disable Restore SSS(S) RB SSS(S) RB SSSS RBRB2 SSSS RBRB2
Low Battery SSS(S) L SSS(S) L SSSS LL2 SSSS LL2
Low Battery Restore SSS(S) RL SSS(S) RL SSSS RLRL2 SSSS RLRL2
No Battery SSS(S) N SSS(S) N SSSS NN2 SSSS NN2
No Battery Restore SSS(S) RN SSS(S) RN SSSS RNRN2 SSSS RNRN2
AC Loss SSS(S) P SSS(S) P SSSS PP2 SSSS PP2
AC Loss Restore SSS(S) RP SSS(S) RP SSSS RPRP2 SSSS RPRP2
Fire Drill SSS(S) Fd SSS(S) Fd SSSS FdFd2 SSSS FdFd2
Fire Drill Restore SSS(S) RFd SSS(S) RFd SSSS RFdRFd2 SSSS RFdRFd2
Supervisory Condition SSS(S) V SSS(S) V SSSS VV2 SSSS VZ
VVV(V) Z
Supervisory Condition SSS(S) RV SSS(S) RV SSSS RVRV2 SSSS RVZ
Restore RVRVRV(RV) Z
Test Report SSS(S) X SSS(S) X SSSS XX2 SSSS XX2
Up or Download SSS(S) UD SSS(S) UD SSS UDUD2 SSS UDUD2
Refer to Table 4-2 for an explanation of each letter code in Table 4-1.
Refer to Table 4-3 for a list of compatible receivers.
Operating Instructions
L = Low Battery (1st digit)
L2 = Low Battery (2nd digit)
RL = Low Battery Restore (1st digit)
RL2 = Low Battery Restore (2nd digit)
N = No Battery (1st digit)
N2 = No Battery (2nd digit)
RN = No Battery Restore (1st digit)
RN2 = No Battery Restore (2nd digit)
P = AC Loss (1st digit)
P2 = AC Loss (2nd digit)
RP = AC Loss Restore (1st digit)
RP2 = AC Loss Restore ( 2nd digit)
FD = Fire Drill (1st digit)
FD2 = Fire Drill (2nd digit)
RFD = Fire Drill Restore (1st digit)
RFD2 = Fire Drill Restore (2nd digit)
V = Supervisory Condition (1st digit)
V2 = Supervisory Condition (2nd digit)
RV = Supervisory Condition Restore (1st digit)
RV2 = Supervisory Condition Restore (2nd digit)
X = Test Report (1st digit)
X2 = Test Report (2nd digit)
Y = A Trouble Corresponding to The Following:
1 = Earth Fault
2 = Not Used
3 = Not Used
4 = Telco Primary Line Fault
5 = Telco Secondary Line Fault
6 = NAC #1 Fault
7 = NAC #2 Fault
8 = NAC #3 Fault
9 = NAC #4 Fault
A = Communication Failure to Primary Number
B = Communication Failure to Secondary Number
C = Printer Fault
D = Annunciator Fault
E = 485 Communication Failure
F = System Off Normal
UD = Upload/download 1st digit
UD2 = Upload/download 2nd digit
Note
Note: For Expanded Reporting, the control panel automatically adds the digit
corresponding to the zone number, and the second digit corresponding to any
system trouble condition. Only the first digit is programmable.
Communication Trouble
Printer Trouble
Annunciator Trouble
EIA-485 Fault
System off Normal
Process Monitoring Alarm
4: Restoral Reports
Zone Alarm
Supervisory
Zone(s) Enabled
Fire Drill
AC
Zone Fault
Earth
Battery
Telephone Line
Notification Appliance Circuits
Communication
Printer
Annunciator
EIA-485
System off Normal
Process Monitoring Restored
5: System Test (Lowest Priority)
Red LEDs are provided on the control panel circuit board to identify which
telephone line is activated. Also a green LED (labeled 'Kissoff') will turn on
whenever the control panel has successfully transmitted reports to the Central
Station. The 'Kissoff' LED may turn on several times during communications with a
Central Station.
Osborne Hoffman
6000/6500 (5)
Models 1 & 2
Silent Knight
CS-4000 (3)
Surguard
3000R (7)
Radionics
MLR-2 (9)
CP220FB
Sescoa
Ademco
685 (1)
Format #
9000
FBI
(Addresses 16 & 42)
ITI
0 4+1 Ademco Express ✔ ✔ ✔
1 4+2 Ademco Express ✔ ✔ ✔
✔(8) ✔ ✔
2 3+1/Standard/1800/2300 ✔ ✔ (2) ✔ ✔ (4) ✔ ✔
✔(5,6) ✔ ✔
3 3+1/Expanded/1800/2300 ✔ ✔ (2) ✔ ✔ (4) ✔ ✔ ✔
4 3+1/Standard/1900/1400 ✔ ✔ (2) ✔ (4) ✔ ✔ ✔
Operating Instructions
5 3+1/Expanded/1900/1400 ✔ ✔ (2) ✔ (4) ✔ ✔ ✔
6 4+1/Standard/1800/2300 ✔ ✔ (2) ✔ ✔ (4) ✔ ✔ (5) ✔ ✔
7 4+1/Expanded/1800/2300 ✔ ✔ (2) ✔ (4) ✔ ✔ ✔
8 4+1/Standard/1900/1400 ✔ ✔ (2) ✔ (4) ✔ ✔ ✔
9 4+1/Expanded/1900/1400 ✔ ✔ (2) ✔ (4) ✔ ✔ ✔
A 4+2/Standard/1800/2300 ✔ ✔ (2) ✔ ✔ (4) ✔ ✔ (5) ✔ ✔
B 4+2/Expanded/1800/2300 ✔ ✔ (2) ✔ (4) ✔ ✔ ✔
C 4+2/Standard/1900/1400 ✔ ✔ (2) ✔ (4) ✔ ✔ ✔
D 4+2/Expanded/1900/1400 ✔ ✔ (2) ✔ (4) ✔ ✔ ✔
E Ademco Contact ID ✔ ✔ ✔ ✔
For an audible walktest, the first initiating device activated on a zone will cause the
Notification Appliance Circuits to turn on for four seconds. Subsequent device
activations on the same zone will cause the Notification Appliance Circuits to turn
on for one second. Any smoke detectors that are activated will be reset. Zonal faults
(open circuits) will cause the appliance circuit to remain on steadily. Prior to entering
Walk Test Mode, check to be certain that all system faults have been cleared.
Note: Trouble relays will be activated while the control panel is in this mode.
Placing the control panel into walk test mode will only be possible if the system has
no active alarms.
Pressing the MODE key followed by the 4-digit code 9255 [ENTER/STORE]
will place the control panel into Walk Test Mode.
An S will be displayed on the left most character and a flashing 0 on the far right
Ser
Servicing
character. For audible walktest, press the [ENTER/STORE] key. For silent
walktest, press the 1 key followed by the [ENTER/STORE] key.
vicing
During Walk Test Mode, zonal activity is displayed in real time as it occurs. At the
end of Walk Testing the system, the display will show the last event that occurred.
To view all events stored during Walk Test, use the Up Arrow, Down Arrow and 1st
Event keys. The Down Arrow key moves the Walk Test list to show older - previous
events. The Up Arrow key moves the Walk Test list to show newer - most recent
events. Pressing the 1st Event key at any time will cause the display of the first event
stored upon initial entry into Walk Test Mode. While in Walk Test Mode, the control
panel will store up to 256 events in the Walk Test File for later recall and display.
Zone disable mode may be used while in Walktest mode. Should a faulty device
require repair, the zone may be disabled while the repair is performed. This allows
the user to return the system to Normal mode enabling all other zones. This also
prevents triggering of a false alarm.
To return the control panel to normal mode, press the mode key, the numbers 6676
and the [ENTER/STORE] key. To go to any other mode, press the MODE key
followed by the appropriate four digit code. To go from silent walktest to audible
walktest (or vice versa), press the MODE key followed by the [ENTER/STORE]
key. S__0 or S__1 will appear in the display. Simply alter the '0' or '1' entry then
press the [ENTER/STORE] key. Any delay between key entries greater than 10
seconds causes the control panel to remain in Walk Test Mode.
The control panel will automatically revert back to Normal Mode if no system
activity has occurred for 60 minutes. This would include pressing any keys or
activity on any zone. Exiting Walk Test mode leaves the Walk Test file in memory
such that it may be printed in Print Mode. Subsequent entries into Walk Test mode
delete the Walk test file.
Note: Remote site upload or download is possible when the system is in Walk Test
mode.
5.2 History Mode All Normal Mode events are stored in a History File list for future recall. Recall is
Servicing
vicing
possible via the 4-character display or via an optional printer. See the following page
for a list and description of each event displayed.
The History File list is a first-in first-out (FIFO) buffer. Only the most recent events
Ser
may be called up from memory. Old events will be overwritten i.e., pushed out of the
FIFO.
The number of stored events is 256. The History File is kept in E2 memory. Complete
power loss will not erase the list.
Pressing the MODE key followed by 4478 [ENTER/STORE] places the control
panel into History Mode. This will not occur if there are any active alarm conditions
present. The fire protection remains active in History mode. If an alarm occurs, the
panel will automatically exit History mode. The event displayed, is the most recent
event.
☛ 4478 spells HIST on a Touch-Tone® phone.
• Display all events as they occurred since the last time the History File list was
cleared. The most recent event will be displayed first.
• Ignore all other keys other than those mentioned in this section.
• Continue to communicate any events not previously acknowledged at the
Central Station prior to entering History Mode.
The Down Arrow key moves the History File to show older-previous events. The Up
Arrow key moves the History file to show newer-most recent events.
50475 Rev D1 7/22/9 P/N 50475:D1
77
Shown below is the list of messages as they will appear on the display:
To erase the list from E2 memory, press the SILENCE key twice before exiting the History Mode. A lack of keyboard
activity for a period of 10 minutes will cause the control panel to return to normal mode. If a printer is connected to
the panel, the history file will be printed upon successful entry into History Mode and a list of the most recent 256
events, time and date stamped, will print out.
Note: Remote site upload or download is possible when the system is in History mode.
The UP Arrow key, Down Arrow key and 1st EVENT keys do not function in
this mode.
Servicing
vicing
Readings will vary proportionately depending upon system load and AC line voltage.
A C Line Pressing A [ENTER/STORE] displays the AC input voltage as shown below. The
following lists the AC line voltage range. The AC ON indicator will turn off when the
Ser
AC line voltage drops below the Low Line threshold, and the trouble LED will turn on.
Batter
Batteryy Pressing B [ENTER STORE] will display the Battery Voltage. Shown below are the
critical battery threshold conditions:
Telephone Lines Pressing C for touchtone dialing or D for rotary dialing, followed by [ENTER/
STORE] causes seizure of the Primary phone line which in turn lights the red LED
signifying Primary phone line active. After a delay of three seconds, the control
panel goes off hook to acquire a dial tone.
The secondary phone line may be tested by pressing the E key for touchtone dialing
or the F key for rotary dialing and then following the same procedure used for the
primary phone line.
Note: Remote site upload or download is not possible while testing the phone lines in
this portion of Troubleshoot mode.
NA
NACC 1, 2, 3 & 4 Pressing B1 followed by [ENTER/STORE] displays the voltage on NAC #1.
Pressing B2 followed by [ENTER/STORE] displays the voltage on NAC #2.
Pressing B3 followed by [ENTER/STORE] displays the voltage on NAC #3.
Pressing B4 followed by [ENTER/STORE] displays the voltage on NAC #4.
NAC voltage readings are nominally -2.32 volts when an EOL resistor of correct
value is in place. A reading of 0.00 volts appears for shorts, -4.50 volts for opens.
Intermediate readings are also available.
Resettab le P
Resettable o w er
Po Pressing the RESET key followed by [ENTER/STORE] displays the resettable 24
volt power. Resettable 24 volt power must read 24 volts + or - 10%.
Ser
Servicing
5.4 Lamp Test To perform a Lamp Test, press MODE then 5267 followed by [ENTER/STORE]
[ENTER/STORE].
This will test all system LEDs on the FACP. The LEDs will stay on for five seconds,
then the control panel will return to normal mode.
vicing
Selecting Printer Mode by pressing the MODE key followed by 7746 then [ENTER/
STORE] will cause the display to read Prn and the following to be printed:
The fire protection remains active while in print mode. Remote site upload or
download is allowed while in Print mode. An alarm on any zone will take priority
causing the panel to exit print mode.
5.6 Printer Output This section illustrates sample printouts for various panel modes.
Servicing
vicing
Zone 1 2-Wire Smoke Detector Active 06-26-1996 14:15:24
Zone 2 Pull Station Active 06-26-1996 14:15:29
Zone 3 N.O. Contact Device Active 06-26-1996 14:15:34
Zone 4 Supervisory Active 06-26-1996 14:15:37
Ser
Zone 5 Waterflow, Silenceable Active 06-26-1996 14:15:45
Zone 6 Process Monitoring Active 06-26-1996 14:15:49
System Silenced 06-26-1996 14:15:53
NAC 1 Silence 06-26-1996 14:15:56
NAC 2 Silence 06-26-1996 14:15:59
Zone 1 Alarm Cleared 06-26-1996 14:16:03
Low Battery Detected 06-26-1996 14:16:09
Normal Battery 06-26-1996 14:16:15
Loss of AC Power 06-26-1996 14:16:19
AC Power Restore 06-26-1996 14:16:42
Drill Mode Entered 06-26-1996 14:16:51
System Reset 06-26-1996 14:17:25
Drill Mode Cleared 06-26-1996 14:17:33
1. Print out all programmed data via print mode or manually view
programmed entries and compare to intended program data.
Upload/Download
wnload
2. Test all affected panel operations.
3. Immediately correct any problems found.
6.1 Do wnloading
Downloading Any time that the control panel is downloaded, whether initiated at the jobsite or
While the control panel is communicating with the Service Terminal, the panel's
green Modem LED and one of the red Line Seize LEDs will remain on steady. At
the conclusion of a successful download transaction, the green Kissoff LED will
come on steady for one second. Upon termination of communication, the green
Modem LED will turn off and the red Line Seize LED will turn off.
ü Download with callback - The Service Terminal calls the control panel. The
control panel answers the call, confirms the calling party then hangs up. The
Service Terminal then waits for a callback from the control panel. After the
control panel calls the Central Station and successfully reports that a request for
downloading has been received, the control panel calls the Service Terminal
back. Upon secret code verification, data transfers occur. When the data
transfers are completed and the Service Terminal disconnects from the control
panel, the panel calls the Central Station back to confirm either successful or
nonsuccessful results.
ü Download with callback disabled - The Service Terminal calls the control
panel. No hangup sequence occurs. Data transfers proceed.
Remote Site Upload/Do
Note: Callback enable/disable is controlled by the master user at the Service Terminal
on a per call basis.
With program address location 56 set to '1' in Program Mode Level 1, anytime a
download with callback is initiated, the control panel will first either contact the primary
Central Station or contact both the primary and secondary Central Stations or contact
the first available Central Station Phone Number to report a 'request for up/download'
Upload/Download
message (depending upon the program entry in Program Level 4 address location 42).
Once the request is 'Kissed-off' by the Central Station(s), the control panel will then call
the appropriate Service Terminal and begin the downloading process.
With program address location 56 set to '1' in Program Mode Level 1, anytime a
download with callback disabled is initiated, the control panel and the Service Terminal
will communicate and transfer data without first contacting a Central Station. When the
wnload
data transfers are completed and the control panel disconnects from the Service
Terminal, the panel will call the Central Station and report:
To prevent the 'request for up/download' message(s) from being reported to the Central
Station(s), make certain to leave address 56 = 0 or disable all upload/download reports
back to both Central Stations. Refer to Tables 3-2 through 3-7 for additional
information.
84 50475 Rev D1 9/22/99 P/N 50475:D1
During the downloading process, the fire protection remains active
active.. Should a
system trouble or alarm condition occur, the control panel immediately terminates
downloading and processes the trouble or alarm locally and transmits the
information to the Central Station(s).
6.1.1 Security Remote site upload and download with the control panel has been carefully designed
Features to include key security features to insure proper functionality. The key features are
listed and explained below.
Upon successful connection (i.e. secret code verified and callback complete, if
applicable), if no communication occurs within two minutes, the panel will
disconnect the call.
Upload/Download
wnload
The panel identification number will be used in the future to identify the panel to the
Service Terminal (when the panel calls the Service Terminal) automatically.
Calls initiated at the FACP must be coordinated at the Service Terminal manually.
Error Checking
As each block of data is received by the control panel, it is checked for accuracy. If
an error is detected, the block is retransmitted until correct, up to a maximum of four
times. If the Secret Code is not verified and four errors occur, the call is
disconnected and the report that the upload/download was not successful is called to
the Central Station(s).
6.2 Do wnloading
Downloading Before initiating the Download procedure, make certain that the control panel is: (1)
Initiated at in Normal mode, (2) Central Station communications are off or Main Panel Options
programming location 56 = 0, and (3) the communicator is in the standby state; red
Control P anel
Panel
Line Seize LEDs are off, green Modem and Kissoff LEDs are off.
Place the control panel into Program mode and program one or both of the Service
Terminal phone numbers. It is also advisable at this time to coordinate this call with
the Service Terminal operator to allow the Service Terminal operator to easily identify
the incoming call.
Exit the Program mode and return the panel to Normal mode. Press the Mode key
followed by the 4-digit code 3696 [ENTER/STORE]
[ENTER/STORE].
The display to the far left will flash the letter 'S'. Press the digit '1' for Service
Terminal phone #1 or '2' for Service Terminal #2, followed by [ENTER/STORE]
[ENTER/STORE].
The control panel will now call the appropriate Service Terminal phone number. With
the Service Terminal set up with the correct download customer file and operating in
the communications window, the downloading process may begin.
Once the called Service Terminal accepts the incoming call (control panel) and verifies
the secret code, the downloading process is allowed to continue. Downloading
Remote Site Upload/Do
progresses until all programmed information has been successfully loaded into the
control panel. Communication terminates upon the Service Terminal hanging up or
upon the FACP hanging up after a two minute timeout following completion of data
transfer.
6.3 Do wnloading
Downloading Before initiating the Download procedure, make certain that the communicator is in
Initiated at a the standby state; red Line Seize LEDs are off, green Modem and Kissoff LEDs are off.
Ser vice
Service
Upload/Download
Once an incoming call is accepted/answered by the control panel, the panel will:
Ter minal
erminal
1. Establish basic modem connection
2. Verify secret code
3. Verify callback vs. no callback request from the Service Terminal. If callback
is requested then perform steps 4 through 10, if no callback is requested then
perform steps 9 and 10 only
wnload
Uploading is possible at any time provided the following conditions are true:
Once an incoming call is accepted/answered by the control panel, the panel will:
Upload/Download
wnload
panel will proceed to the next step
7. Return call to Service Terminal
8. Verify secret code
9. Begin uploading
Use the Total Standby and Alarm Load Currents calculated in Tables A-2A and A-2B for the following battery
calculation.
Add Standby and Alarm Load for Required Ampere Hour Battery = ______________
Note:
1) 12 Ampere Hour battery can be located in the Backbox.
2) 17 Ampere Hour batteries require the BB-17 Battery box.
Appendices
The SFP-1024 provides regulated power for operating the fire alarm control panel, operating external devices, and
operating the standby battery. The power for operating external devices is limited. Use Table A-2A (standby or
non-alarm) and Table A-2B (alarm) to determine if external loading is within the capabilities of the power supply.
Concerning 4-wire smoke detectors: Be sure to power detectors from TB2, Terminals 3 and 4.
Total
# of Current
Device Type Current
Devices (Amps)
(Amps)
Main Circuit Board 1 X 0.138 = 0.138
LED-10IM (1 max.) X 0.017 =
PRT-24 (1 max.) X 0 = 0
CAC-10F (1 max.) X 0.004 =
NAC-REM (1 max.) X 0.002 =
2-wire Detector
[ ] X [ ]1 =
Heads
4-wire Detector
[ ] X [ ]1 =
Heads
Power Supervision
[ ] X 0.025 =
Relays
Current Draw from3
TB2 (nonalarm) =
Appendices
Note:
1) Refer to the Device Compatibility Document for 2-wire smoke detector standby current.
2) Must use compatible listed Power Supervision Relay.
3) The total standby current must include both the resettable (TB2 Terminals 3 & 4) and nonresettable
(TB2 Terminals 1 & 2) power. Caution must be taken to ensure that current drawn from these outputs
during alarm does not exceed maximum ratings specified (see Table a-2B).
Total
# of Current
Device Type Current
Devices (Amps)
(Amps)
Notes:
1) Current limitations of terminals:
• TB2, Terminals 1 and 2 = 0.500 amp, regulated filtered, 24VDC +/- 5%, 120HZ ripple @ 10 mV RMS.
Nonresettable Power (100 Hz ripple if SFP-1024E).
Appendices
• TB2, Terminals 3 and 4 = 0.500 amp, regulated filtered, 24VDC +/- 5%, 120HZ ripple @ 10 mV RMS.
Resettable Power (100 Hz ripple if SFP-1024E).
4) The current shown represents one zone on the Main Circuit Board in alarm. For all ten zones in alarm, the
current draw increases to 0.590 amps with communicator off and 0.610 amps with communicator on.
5) Current limitation of terminal TB4 circuits is 3 amps per Notification Appliance Circuit.
6) Current limitation of NAC-REM module circuits is 1.5 amps per Notification Appliance Circuit.
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
Addresses 00 to 15 store the Primary Central Station Phone Number. Enter 'F' to represent the end of the number.
❑ ❑ ❑ ❑ Primary Central Station 24-Hour Test Time. Enter military time (i.e. 1400 for 2 pm).
21 22 23 24
❑ Primary Number Test Time Interval. Enter '0' for 24-hour; '1' - 12-hour; '2' - 8-hour; '3' for 6-hour.
25
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
Addresses 26-41 store the Secondary Central Station Phone Number. Enter 'F' to represent the end of the
number.
❑ ❑ ❑ ❑ Secondary Central Station 24-Hour Test Time. Enter military time (i.e. 1400 for 2 pm).
47 48 49 50
❑ Secondary Central Station Number Test Time Interval. Enter '0' for 24-hour; '1' - 12-hour; '2' - 8-hour; '3'
51
for 6-hour.
❑ Alarm Presignal. Enter '0' to disable; '1' to enable.
52
❑ ❑ ❑ Alarm Presignal Delay Time. Enter 0-179 additional seconds (default = 120 seconds).
53 54 55
❑ Communicator/ Fire Panel Selection. Enter '0' for fire panel only; '1' for fire panel/communicator opera-
56
tion.
❑ 57
Backup Reporting. Enter '0' to report to secondary phone # as backup only; '1' to report to both primary
and secondary phone number for all reports/messages; '2' reports go to first available receiver.
❑ Touchtone/Rotary Select for Primary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.
Appendices
58
❑ 59
Make/Brake Ratio for Primary Phone. Enter '0' for 67/33; '1' for 62/38.
❑ 60
Touchtone/Rotary Select for Secondary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.
❑ 61
Make/Brake Ratio for Secondary Phone. Enter '0' for 67/33; '1' for 62/38.
❑ 62
Future use.
❑ 63
Future use.
❑ Alarm Verification. Enter '0' for no verification; '1' for verification of all 2- wire smoke zones.
76
❑ AC Loss Delay. Enter '0' for 6 hours; '1' for 7 hours; '2' for 8 hours; '3' for 9 hours; '4' for 10 hours; '5'
77
for 11 hours; '6' for 12 hours; '7' for 15 hours; '8' for 16 hours; '9' for 17 hours; 'A' for 18 hours; 'B' for 19
hours; 'C' for 20 hours; 'D' for 21 hours; 'E' for 22 hours; 'F' for 23 hours.
❑ 78
Programmable Relay #1 Definition. Enter '0' for alarm; '1' for supervisory; '2' for supervisory auto-
resettable; '3' for trouble; '4' for comm. fail; '5' for process monitoring; '6' for process monitoring auto-
resettable.
❑ 79
Programmable Relay #2 Definition. Enter '0' for alarm; '1' for supervisory; '2' for supervisory auto-
resettable; '3' for trouble; '4' for comm. fail; '5' for process monitoring; '6' for process monitoring auto-
resettable.
❑ 80
Notification Appliance Circuit #1 Selection: Enter '0' for enabled (silenceable); '1' for enable (nonsi-
lenceable); '2' to disable.
❑ 81
Silence Inhibit NAC #1. Enter '0' for no silence inhibit; '1' to inhibit silencing of NAC #1 for one minute.
❑ 82
Auto Silence NAC #1. Enter '0' for no auto silence; '1' for 5 minutes; '2' for 10 minutes; '3' for 15
minutes; '4' for 20 minutes; '5' for 25 minutes; '6' for 30 minutes.
❑ 83
Coding NAC #1. Enter '0' for steady; '1' for March Time (120 ppm); '2' for California (10 seconds on, 5
seconds off); '3' for Temporal (0.5 on, 0.5 off, 0.5 on, 0.5 off, 0.5 on, 1.5 off).
❑ 84
Notification Appliance Circuit #2 Selection: Enter '0' for enabled (silenceable); '1' for enable (nonsi-
lenceable); '2' to disable.
❑ 85
Silence Inhibit NAC #2. Enter '0' for no silence inhibit; '1' to inhibit silencing of NAC #2 for one minute.
❑ 86
Auto Silence NAC #2. Enter '0' for no auto silence; '1' for 5 minutes; '2' for 10 minutes; '3' for 15 min-
utes; '4' for 20 minutes; '5' for 25 minutes; '6' for 30 minutes.
❑ 87
Coding NAC #2. Enter '0' for steady; '1' for March Time (120 ppm); '2' for California (10 seconds on, 5
seconds off); '3' for Temporal (0.5 on, 0.5 off, 0.5 on, 0.5 off, 0.5 on, 1.5 off).
Appendices
❑ 88
Trouble Reminder. Enter '0' to disable; '1' to enable.
❑
F ❑
F ❑
F ❑
F
00
❑
F ❑
F
01
❑
F ❑
F ❑
F
02
❑
F ❑
F ❑
F ❑
03
F ❑
F ❑
F ❑
F
04 05 06 07 08 09 10 11 12 13 14 15
Addresses 00 to 15 store the Primary Central Station Phone Number. Enter 'F' to represent the end of the number.
❑
E Primary Central Station Comm Format: ('E' for Ademco Contact ID Format).
16
❑
0 ❑
0 ❑
17
0
18
❑
0
19
Primary Central Station Account Code.
20
❑
0 ❑
0 ❑
21
0
22
❑
0
23
Primary Central Station 24-Hour Test Time. 0000 = 12:00 midnight.
24
❑
0 Primary Central Station Number Test Time Interval. '0' for 24-hour.
25
❑
F ❑
F
26
❑
F
27
❑
F
28
❑F
29
❑F ❑ F
30
❑
F
31
❑
F
32
❑F
33
❑F
34
❑F ❑
35
F ❑
F
36
❑
F ❑
F
37 38 39 40 41
Addresses 26-41 store the Secondary C. S. Phone Number. Enter 'F' to represent the end of the number.
❑
E Secondary Central Station Comm Format: ('E' for Ademco Contact ID Format).
42
❑
0 ❑0
43
❑0
44
❑0
45
Secondary Central Station Account Code.
46
❑
0 ❑0
47
❑0
48
❑0
49
Secondary Central Station 24-Hour Test Time. 0000 = 12:00 midnight.
50
❑
0 Secondary Central Station Number Test Time Interval. '0' for 24-hour.
51
❑
0 Alarm Presignal. 0 for no alarm presignal.
52
❑
1 ❑
2 ❑
53
0
54
Alarm Presignal Delay Time. 120 second alarm presignal delay.
55
❑
0 Communicator/ Fire Panel Selection. 0 for panel only operation.
56
❑
0 Backup Reporting. '0' to report to secondary Central Station phone # as backup only.
57
❑
0 Touchtone/Rotary Select for Primary Phone. '0' for touchtone dialing.
58
❑
0 Make/Brake Ratio for Primary Phone. Enter '0' for 67/33.
59
❑
0 Touchtone/Rotary Select for Secondary Phone. '0' for touchtone dialing.
60
❑
0 Make/Brake Ratio for Secondary Phone. Enter '0' for 67/33.
Appendices
61
❑
0 Future use. Leave default of '0'.
62
❑
0 Future use. Leave default of '0'.
63
❑
0 Zone 1 Function Select. '0' for 2-wire smoke detectors.
64
❑
0 Zone 2 Function Select. '0' for 2-wire smoke detectors.
65
❑
0 Zone 3 Function Select. '0' for 2-wire smoke detectors.
66
❑
0 Zone 4 Function Select. '0' for 2-wire smoke detectors.
67
❑
0 Zone 5 Function Select. '0' for 2-wire smoke detectors.
68
❑
0 Zone 7 Function Select. '0' for 2-wire smoke detectors.
70
❑
0 Zone 8 Function Select. '0' for 2-wire smoke detectors.
71
❑
0 Zone 9 Function Select. '0' for 2-wire smoke detectors.
72
❑
0 Zone 10 Function Select. '0' for 2-wire smoke detectors.
73
❑
0 ❑
0
74
Waterflow Retard Timer. '00' for no delay.
75
❑
0 Alarm Verification. '0' = no alarm verification.
76
❑
0 AC Loss Delay. '0' for 6 hours.
77
❑
0 Programmable Relay #1 Definition. '0' for alarm.
78
❑
3 Programmable Relay #2 Definition. '3' for trouble.
79
❑
0 Notification Appliance Circuit #1 Selection: '0' for enabled (silenceable).
80
❑
0 Silence Inhibit NAC #1. '0' for no silence inhibit.
81
❑
0 Auto Silence NAC #1. '0' for no auto silence.
82
❑
0 Coding NAC #1. '0' for steady, no coding.
83
❑
0 Notification Appliance Circuit #2 Selection: '0' for enabled (silenceable).
84
❑
0 Silence Inhibit NAC #2. '0' for no silence inhibit.
85
❑
0 Auto Silence NAC #2. '0' for no auto silence.
86
❑
0 Coding NAC #2. '0' for steady, no coding.
87
❑
0 Trouble Reminder. '0', no trouble reminder.
88
Appendices
4+2 Standar
Standardd and 4+2 Expr ess F
Express or
For ma
orma ts Pr
mats imar
Primar
imaryy Centr al Sta
Central tion
Station
❑ 0
❑
1
❑
2
❑ 3
❑ 4
❑ 5
❑ 6
❑ 7
❑ 8
❑
9
❑
10
❑
11
❑
12
❑ 13
❑
14
❑
15
❑ 16
❑ 17
❑ 18
❑ 19
❑ 20
❑ 21
❑
22
❑
23
❑
24
❑
25
❑ 26
❑
27
❑
28
❑ 29
❑ 30
❑ 31
❑ 32
❑ 33
❑ 34
❑
35
❑
36
❑
37
❑
38
❑ 39
❑
40
❑
41
❑ 42
❑ 43
❑ 44
❑ 45
❑ 46
❑ 47
❑
48
❑
49
❑
50
❑
51
❑ 52
❑
53
❑
54
❑ 55
❑ 56
❑ 57
❑ 58
❑ 59
❑ 60
❑
61
❑
62
❑
63
❑
64
❑ 65
❑
66
❑
67
❑ 68
❑ 69
❑ 70
❑ 71
❑ 72
❑ 73
❑
74
❑
75
❑
76
❑
77
❑ 78
❑
79
❑
80
❑ 81
❑ 82
❑ 83
❑ 84
❑ 85
❑ 86
❑
87
❑
88
❑
89
❑
90
❑ 91
❑
92
❑
93
❑ 94
❑ 95
❑ 96
❑ 97
❑ 98
❑ 99
❑
100
❑
101
❑
102
❑
103
❑ 104
❑
105
❑
106
❑ 107
❑ 108
❑ 109
❑ 110
❑ 111
❑ 112
❑
113
❑
114
❑
115
❑
116
❑ 117
❑
118
❑
119
❑ 120
❑ 121
❑ 122
❑ 123
❑ 124
❑ 125
❑
126
❑
127
❑
128
❑
129
❑ 130
❑
131
❑
132
❑ 133
❑ 134
❑ 135
❑ 136
❑ 137
❑ 138
❑
139
❑
140
❑
141
❑
142
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
Appendices
143 144 145 146 147 148 149 150 151 152 153 154 155
❑ 156
❑
157
❑
158
❑ 159
❑ 160
❑ 161
❑ 162
❑ 163
❑ 164
❑
165
❑
166
❑
167
❑
168
❑ 169
❑
170
❑
171
❑ 172
❑ 173
❑ 174
❑ 175
❑ 176
❑ 177
❑
178
❑
179
❑
180
❑
181
❑ 182
❑
183
❑
184
❑ 185
❑ 186
❑ 187
❑ 188
❑ 189
❑ 190
❑
191
❑
192
❑
193
❑
194
❑ 195
❑
196
❑
197
❑ 199
❑ 199
❑ 200
❑ 201
❑ 202
❑ 203
❑
204
❑
205
❑
206
❑
207
❑ 208
❑
209
❑
210
❑ 211
❑ 212
❑ 213
❑ 214
❑ 215
❑
216
❑
217
❑
218
❑
219
❑
220
❑
221
❑ 222
❑ 223
❑ 224
❑
225
❑
226
❑
227
❑
228
❑
229
❑
230
❑
231
❑
232
❑
233
❑
234
❑ 235
❑ 236
❑ 237
❑
238
❑
239
❑
240
❑
241
❑
242
❑
243
❑
244
❑
245
❑
246
❑247
❑ 248
❑ 249
❑ 250
❑
251
❑
252
❑
253
❑
254
❑
255
❑
256
❑
257
❑
258
❑
259
❑260
❑ 261
❑ 262
❑ 263
❑
264
❑
265
❑
266
❑
267
❑
268
❑
269
❑
270
❑
271
❑
272
❑273
❑ 274
❑ 275
❑ 276
❑
277
❑
278
❑
279
❑
280
❑
281
❑
282
❑
283
❑
284
❑
285
❑286
❑ 287
❑ 288
❑ 289
❑
290
❑
291
❑
292
❑
293
❑
294
❑
295
❑
296
❑
297
❑
298
❑299
❑ 300
❑ 301
❑ 302
❑
303
❑
304
❑
305
❑
306
❑
307
❑
308
❑
309
❑
310
❑
311
❑312
❑ 313
❑ 314
❑ 315
❑
316
❑
317
❑
318
❑
319
❑
320
❑
321
❑
322
❑
323
❑
324
❑325
❑ 326
❑ 327
❑ 328
❑
329
❑
330
❑
331
❑
332
❑
333
❑
334
❑
335
❑
336
❑
337
❑338
❑ 339
❑ 340
❑ 341
❑
342
❑
343
❑
344
❑
345
❑
346
❑
347
❑
348
❑
349
❑
350
❑351
❑ 352
❑ 353
❑ 354
❑
355
❑
356
❑
357
❑
358
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
Appendices
359 360 361 362 363 364 365 366 367 368 369 370 371
❑
372
❑
373
❑
374
❑
375
❑
376
❑377
❑ 378
❑ 379
❑ 380
❑
381
❑
382
❑
383
❑
384
❑
385
❑
386
❑
387
❑
388
❑
389
❑390
❑ 391
❑ 392
❑ 393
❑
394
❑
395
❑
396
❑
397
❑
398
❑
399
❑
400
❑
401
❑
402
❑403
❑ 404
❑ 405
❑ 406
❑
407
❑
408
❑
409
❑
410
❑
411
❑
412
❑
413
❑
414
❑
415
❑416
❑ 417
❑ 418
❑ 419
❑
420
❑
421
❑
422
❑
423
❑
424
❑
425
❑
426
❑
427
❑
428
❑429
❑ 430
❑ 431
Ev ent Codes/T
Event Codes/Trr ansmission F or
For ma
matt Pr
orma Proo g r amming Ref er
Refer ence Sheet F
erence ac-
Fac-
tory Defaults
4+2 Standar
Standardd and 4+2 Expr ess F
Express or
For ma
orma
mats ts Pr imar
Primar
imaryy Centr al Sta
Central tion
Station
❑
1
0
❑
1
1
❑
1
2
❑
2
3
❑
1
4
❑3
5
❑
1
6
❑
4
7
❑
1
8
❑
5
9
❑
1
10
❑
6
11
❑
1
12
❑
7
13
❑
1
14
❑
8
15
❑
1
16
❑
9
17
❑1
18
❑
A
19
❑
4
20
❑
1
21
❑
4
22
❑
2
23
❑
4
24
❑
3
25
❑
4
26
❑
4
27
❑
4
28
❑
5
29
❑
4
30
❑6
31
❑
4
32
❑
7
33
❑
4
34
❑
8
35
❑
4
36
❑
9
37
❑
4
38
❑
A
39
❑
9
40
❑
7
41
❑
9
42
❑
2
43
❑F 44
❑
1
45
❑
F
46
❑
2
47
❑
F
48
❑
3
49
❑
F
50
❑
4
51
❑
F
52
❑
5
53
❑
F
54
❑
6
55
❑
F
56
❑7 57
❑
F
58
❑
8
59
❑
F
60
❑
9
61
❑
F
62
❑
A
63
❑
6
64
❑
1
65
❑
6
66
❑
2
67
❑
6
68
❑
3
69
❑6 70
❑
4
71
❑
6
72
❑
5
73
❑
6
74
❑
6
75
❑
6
76
❑
7
77
❑
6
78
❑
8
79
❑
6
80
❑
9
81
❑
4
82
❑B 83
❑
4
84
❑
C
85
❑
4
86
❑
D
87
❑
4
88
❑
E
89
❑
6
90
❑
A
91
❑
6
92
❑
B
93
❑
6
94
❑
C
95
❑6 96
❑
D
97
❑
6
98
❑
E
99
❑
6
100
❑
F
101
❑
E
102
❑
1
103
❑
E
104
❑
2
105
❑
E
106
❑
3
107
❑
E
108
❑4 109
❑
E
110
❑
5
111
❑
E
112
❑
6
113
❑
E
114
❑
7
115
❑
E
116
❑
8
117
❑
E
118
❑
9
119
❑
E
120
❑
A
121
❑5 122
❑
1
123
❑
5
124
❑
2
125
❑
5
126
❑
3
127
❑
5
128
❑
4
129
❑
5
130
❑
5
131
❑
5
132
❑
6
133
❑
5
134
❑7 135
❑
5
136
❑
8
137
❑
5
138
❑
9
139
❑
5
140
❑
A
141
❑
9
142
❑
8
❑
9
❑
3
❑
D
❑
1
❑D ❑
2
❑
D
❑
3
❑
D
❑
4
❑
D
❑
5
Appendices
143 144 145 146 147 148 149 150 151 152 153 154 155
❑
D
156
❑
6
157
❑
D
158
❑
7
159
❑
D
160
❑8 161
❑
D
162
❑
9
163
❑
D
164
❑
A
165
❑
A
166
❑
1
167
❑
A
168
❑
2
169
❑
A
170
❑
3
171
❑
A
172
❑
4
173
❑A 174
❑
5
175
❑
A
176
❑
6
177
❑
A
178
❑
7
179
❑
A
180
❑
8
181
❑
A
182
❑
9
183
❑
5
184
❑
B
185
❑
5
186
❑C 187
❑
5
188
❑
D
189
❑
5
190
❑
E
191
❑
A
192
❑
A
193
❑
A
194
❑
B
195
❑
A
196
❑
C
197
❑
A
198
❑
D
199
❑A 200
❑
E
201
❑
A
202
❑
F
203
❑
9
204
❑
9
205
❑
9
206
❑
1
207
❑
7
208
❑
1
209
❑
7
210
❑
2
211
❑
7
212
❑3 213
❑
7
214
❑
4
215
❑
1
216
❑
1
217
❑
1
218
❑
2
219
❑
1
220
❑
3
221
❑
1
222
❑
4
223
❑
1
224
❑5
225
❑
1
226
❑
6
227
❑
1
228
❑
7
229
❑
1
230
❑
8
231
❑
1
232
❑
9
233
❑
1
234
❑
A
235
❑
4
236
❑
1
237
❑4
238
❑
2
239
❑
4
240
❑
3
241
❑
4
242
❑
4
243
❑
4
244
❑
5
245
❑
4
246
❑
6
247
❑
4
248
❑
7
249
❑
4
250
❑8
251
❑
4
252
❑
9
253
❑
4
254
❑
A
255
❑
9
256
❑
7
257
❑
9
258
❑
2
259
❑
F
260
❑
1
261
❑
F
262
❑
2
263
❑F
264
❑
3
265
❑
F
266
❑
4
267
❑
F
268
❑
5
269
❑
F
270
❑
6
271
❑
F
272
❑
7
273
❑
F
274
❑
8
275
❑
F
276
❑9
277
❑
F
278
❑
A
279
❑
6
280
❑
1
281
❑
6
282
❑
2
283
❑
6
284
❑
3
285
❑
6
286
❑
4
287
❑
6
288
❑
5
289
❑6
290
❑
6
291
❑
6
292
❑
7
293
❑
6
294
❑
8
295
❑
6
296
❑
9
297
❑
4
298
❑
B
299
❑
4
300
❑
C
301
❑
4
302
❑D
303
❑
4
304
❑
E
305
❑
6
306
❑
A
307
❑
6
308
❑
B
309
❑
6
310
❑
C
311
❑
6
312
❑
D
313
❑
6
314
❑
E
315
❑6
316
❑
F
317
❑
E
318
❑
1
319
❑
E
320
❑
2
321
❑
E
322
❑
3
323
❑
E
324
❑
4
325
❑
E
326
❑
5
327
❑
E
328
❑6
329
❑
E
330
❑
7
331
❑
E
332
❑
8
333
❑
E
334
❑
9
335
❑
E
336
❑
A
337
❑
5
338
❑
1
339
❑
5
340
❑
2
341
❑5
342
❑
3
343
❑
5
344
❑
4
345
❑
5
346
❑
5
347
❑
5
348
❑
6
349
❑
5
350
❑
7
351
❑
5
352
❑
8
353
❑
5
354
❑9
355
❑
5
356
❑
A
357
❑
9
358
❑
8
359
❑
9
360
❑
3
361
❑
D
362
❑
1
363
❑
D
364
❑
2
365
❑
D
366
❑
3
367
❑D
368
❑
4
369
❑
D
370
❑
5
371
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
Appendices
D 6 D 7 D 8 D 9 D A A 1 A
372 373 374 375 376 377 378 379 380 381 382 383 384
❑
2
385
❑
A
386
❑
3
387
❑
A
388
❑
4
389
❑
A
390
❑
5
391
❑
A
392
❑
6
393
❑A
394
❑
7
395
❑
A
396
❑
8
397
❑
A
398
❑
9
399
❑
5
400
❑
B
401
❑
5
402
❑
C
403
❑
5
404
❑
D
405
❑
5
406
❑E
407
❑
A
408
❑
A
409
❑
A
410
❑
B
411
❑
A
412
❑
C
413
❑
A
414
❑
D
415
❑
A
416
❑
E
417
❑
A
418
❑
F
419
❑9
420
❑
9
421
❑
9
422
❑
1
423
❑
7
424
❑
1
425
❑
7
426
❑
2
427
❑
7
428
❑
3
429
❑
7
430
❑
4
431
Ev ent Codes/T
Event Codes/Trr ansmission F or
For ma
matt Pr
orma Proo g r amming Sheets ffor
or
All 3+1, All 4+1 and 4+2 Expanded F or
For
ormama
matsts Pr imar
imary
Primar y Centr al Sta
Central tion
Station
❑ 0
❑ 1
❑
2
❑ 3
❑ 4
❑ 5
❑ 6
❑ 7
❑ 8
❑
9
❑
10
❑
11
❑
12
❑ 13
❑ 14
❑
15
❑ 16
❑ 17
❑ 18
❑ 19
❑ 20
❑ 21
❑
22
❑
23
❑
24
❑
25
❑ 26
❑ 27
❑
28
❑ 29
❑ 30
❑ 31
❑ 32
❑ 33
❑ 34
❑
35
❑
36
❑
37
❑
38
❑ 39
❑ 40
❑
41
❑ 42
❑ 43
❑ 44
❑ 45
❑ 46
❑ 47
❑
48
❑
49
❑
50
❑
51
❑ 52
❑ 53
❑
54
❑ 55
❑ 56
❑ 57
❑ 58
❑ 59
❑ 60
❑
61
❑
62
❑
63
❑
64
❑ 65
❑ 66
❑
67
❑ 68
❑ 69
❑ 70
❑ 71
❑ 72
❑ 73
❑
74
❑
75
❑
76
❑
77
❑ 78
❑ 79
❑
80
❑ 81
❑ 82
❑ 83
❑ 84
❑ 85
❑ 86
❑
87
❑
88
❑
89
❑
90
❑ 91
❑ 92
❑
93
❑ 94
❑ 95
❑ 96
❑ 97
❑ 98
❑ 99
❑
100
❑
101
❑
102
❑
103
❑ 104
❑ 105
❑
106
❑ 107
Ev ent Codes/T
Event Codes/Trr ansmission F
--- or
For ma
matt Pr
orma Proo g r amming Sheets fforor
All 3+1, All 4+1 and 4+2 Expanded F or
For ma
orma ts Pr
mats imar
Primar
imaryy Centr al Sta
Central tion
Station
❑ 216
❑ 217
❑
218
❑ 219
❑ 220
❑ 221
❑ 222
❑ 223
❑ 224
❑
225
❑
226
❑
227
❑
228
❑ 229
❑ 230
❑
231
❑ 232
❑ 233
❑ 234
❑ 235
❑ 236
❑ 237
❑
238
❑
239
❑
240
❑
241
❑ 242
❑ 243
❑
244
❑ 245
❑ 246
❑ 247
❑ 248
❑ 249
❑ 250
❑
251
❑
252
❑
253
❑
254
Appendices
❑ 255
❑ 256
❑
257
❑ 258
❑ 259
❑ 260
❑ 261
❑ 262
❑ 263
❑
264
❑
265
❑
266
❑
267
❑ 268
❑ 269
❑
270
❑ 271
❑ 272
❑ 273
❑ 274
❑ 275
❑ 276
❑
277
❑
278
❑
279
❑
280
❑ 281
❑ 282
❑
283
❑ 284
❑ 285
❑ 286
❑ 287
❑ 288
❑ 289
❑
290
❑
291
❑
292
❑
293
❑ 294
❑ 295
❑
296
❑ 297
❑ 298
❑ 299
❑ 300
❑ 301
❑ 302
❑
303
❑
304
❑
305
❑
306
❑ 307
❑ 308
❑
309
❑ 310
❑ 311
❑ 312
❑ 313
❑ 314
❑ 315
❑
316
❑
317
❑
318
❑
319
❑ 320
❑ 321
❑
322
❑ 323
100 50475 Rev D1 9/22/99 P/N 50475:D1
--- To enter Programming Mode Level 2, press Mode: 7 7 6 4, '2', Enter
Ev ent Codes/F
Event or
Codes/For ma
matt Pr
orma Proo g r amming Ref er
Refer ence Sheet F
erence actor
Factor
actoryy Def aults
Defaults
All 3+1, All 4+1 and 4+2 Expanded F or
For
ormama ts Pr
mats imar
Primar
imaryy Centr
Centralal Sta tion
Station
❑
1
0
❑
1
1
❑
1
2
❑
1
3
❑
1
4
❑1
5
❑
1
6
❑
1
7
❑
1
8
❑
1
9
❑
4
10
❑
4
11
❑
4
12
❑
4
13
❑
4
14
❑
4
15
❑
4
16
❑
4
17
❑4
18
❑
4
19
❑
9
20
❑
9
21
❑
F
22
❑
F
23
❑
F
24
❑
F
25
❑
F
26
❑
F
27
❑
F
28
❑
F
29
❑
F
30
❑F
31
❑
6
32
❑
6
33
❑
6
34
❑
6
35
❑
6
36
❑
6
37
❑
6
38
❑
6
39
❑
6
40
❑
4
41
❑
4
42
❑
4
43
❑4 44
❑
6
45
❑
6
46
❑
6
47
❑
6
48
❑
6
49
❑
6
50
❑
E
51
❑
E
52
❑
E
53
❑
E
54
❑
E
55
❑
E
56
❑E 57
❑
E
58
❑
E
59
❑
E
60
❑
5
61
❑
5
62
❑
5
63
❑
5
64
❑
5
65
❑
5
66
❑
5
67
❑
5
68
❑
5
69
❑5 70
❑
9
71
❑
9
72
❑
D
73
❑
D
74
❑
D
75
❑
D
76
❑
D
77
❑
D
78
❑
D
79
❑
D
80
❑
D
81
❑
D
82
❑A 83
❑
A
84
❑
A
85
❑
A
86
❑
A
87
❑
A
88
❑
A
89
❑
A
90
❑
A
91
❑
5
92
❑
5
93
❑
5
94
❑
5
95
❑A 96
❑
A
97
❑
A
98
❑
A
99
❑
A
100
❑
A
101
❑
9
102
❑
F
103
❑
7
104
❑
7
105
❑
7
106
❑
7
107
Ev ent Codes/F
Event or
Codes/For ma
matt Pr
orma Proo g r amming Ref er
Refer ence Sheet F
erence actor
Factor
actoryy Def aults
Defaults
All 3+1, All 4+1 and 4+2 Expanded F or
For ma
orma
matsts Secondar
Secondaryy Centr
Centralal Sta tion
Station
❑
1
216
❑
1
217
❑
1
218
❑
1
219
❑
1
220
❑
1
221
❑
1
222
❑
1
223
❑
1
224
❑
1
225
❑
4
226
❑
4
227
❑
4
228
❑
4
229
❑
4
230
❑
4
231
❑
4
232
❑
4
233
❑
4
234
❑
4
235
❑
9
236
❑
9
237
❑
F
238
❑
F
239
❑
F
240
❑
F
241
❑
F
❑
F
❑
F
❑
F
❑
F
❑
F
❑
6
❑
6
❑
6
❑
6
❑
6
❑
6
❑
6
Appendices
242 243 244 245 246 247 248 249 250 251 252 253 254
❑
6
255
❑
6
256
❑
4
257
❑
4
258
❑
4
259
❑
4
260
❑
6
261
❑
6
262
❑
6
263
❑
6
264
❑
6
265
❑
6
266
❑
E
267
❑
E
268
❑
E
269
❑
E
270
❑
E
271
❑
E
272
❑
E
273
❑
E
274
❑
E
275
❑
E
276
❑
5
277
❑
5
278
❑
5
279
❑
5
280
❑
5
281
❑
5
282
❑
5
283
❑
5
284
❑
5
285
❑
5
286
❑
9
287
❑
9
288
❑
D
289
❑
D
290
❑
D
291
❑
D
292
❑
D
293
❑
D
294
❑
D
295
❑
D
296
❑
D
297
❑
D
298
❑
A
299
❑
A
300
❑
A
301
❑
A
302
❑
A
303
❑
A
304
❑
A
305
❑
A
306
❑
A
307
❑
5
308
❑
5
309
❑
5
310
❑
5
311
❑
A
312
❑
A
313
❑
A
314
❑
A
315
❑
A
316
❑
A
317
❑
9
318
❑
F
319
❑
7
320
❑
7
321
❑
7
322
❑
7
323
101
50475 Rev D1 7/22/9 P/N 50475:D1
--- To enter Programming Mode Level 2, press Mode: 7 7 6 4, '2', Enter
Ev ent Codes/T
Event Codes/Trr ansmission F or
For ma
matt Pr
orma Proo g r amming Sheets ffor
or
Ademco Contact ID Primary Central Station
❑ 0
❑1
❑
2
❑ 3
❑ 4
❑ 5
❑ 6
❑ 7
❑ 8
❑
9
❑
10
❑
11
❑
12
❑ 13
❑14
❑
15
❑ 16
❑ 17
❑ 18
❑ 19
❑ 20
❑ 21
❑
22
❑
23
❑
24
❑
25
❑ 26
❑27
❑
28
❑ 29
❑ 30
❑ 31
❑ 32
❑ 33
❑ 34
❑
35
❑
36
❑
37
❑
38
❑ 39
❑40
❑
41
❑ 42
❑ 43
❑ 44
❑ 45
❑ 46
❑ 47
❑
48
❑
49
❑
50
❑
51
❑ 52
❑53
❑
54
❑ 55
❑ 56
❑ 57
❑ 58
❑ 59
❑ 60
❑
61
❑
62
❑
63
❑
64
❑ 65
❑66
❑
67
❑ 68
❑ 69
❑ 70
❑ 71
❑ 72
❑ 73
❑
74
❑
75
❑
76
❑
77
❑ 78
❑79
❑
80
❑ 81
❑ 82
❑ 83
❑ 84
❑ 85
❑ 86
❑
87
❑
88
❑
89
❑
90
❑ 91
❑92
❑
93
❑ 94
❑ 95
❑ 96
❑ 97
❑ 98
❑ 99
❑
100
❑
101
❑
102
❑
103
❑ 104
❑105
❑
106
❑ 107
❑ 108
❑ 109
❑ 110
❑ 111
❑ 112
❑
113
❑
114
❑
115
❑
116
❑ 117
❑118
❑
119
❑ 120
❑ 121
❑ 122
❑ 123
❑ 124
❑ 125
❑
126
❑
127
❑
128
❑
129
❑ 130
❑131
❑
132
❑ 133
❑ 134
❑ 135
❑ 136
❑ 137
❑ 138
❑
139
❑
140
❑
141
❑
142
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
Appendices
143 144 145 146 147 148 149 150 151 152 153 154 155
❑ 156
❑157
❑
158
❑ 159
❑ 160
❑ 161
❑ 162
❑ 163
❑ 164
❑
165
❑
166
❑
167
❑
168
❑ 169
❑170
❑
216
❑217
❑
218
❑
219
❑
220
❑
221
❑ 222
❑ 223
❑ 224
❑
225
❑
226
❑
227
❑
228
❑
229
❑230
❑
231
❑
232
❑
233
❑
234
❑ 235
❑ 236
❑ 237
❑
238
❑
239
❑
240
❑
241
❑
242
❑243
❑
244
❑
245
❑
246
❑
247
❑ 248
❑ 249
❑ 250
❑
251
❑
252
❑
253
❑
254
❑
255
❑256
❑
257
❑
258
❑
259
❑
260
❑ 261
❑ 262
❑ 263
❑
264
❑
265
❑
266
❑
267
❑
268
❑269
❑
270
❑
271
❑
272
❑
273
❑ 274
❑ 275
❑ 276
❑
277
❑
278
❑
279
❑
280
❑
281
❑282
❑
283
❑
284
❑
285
❑
286
❑ 287
❑ 288
❑ 289
❑
290
❑
291
❑
292
❑
293
❑
294
❑295
❑
296
❑
297
❑
298
❑
299
❑ 300
❑ 301
❑ 302
❑
303
❑
304
❑
305
❑
306
❑
307
❑308
❑
309
❑
310
❑
311
❑
312
❑ 313
❑ 314
❑ 315
❑
316
❑
317
❑
318
❑
319
❑
320
❑321
❑
322
❑
323
❑
324
❑
325
❑ 326
❑ 327
❑ 328
❑
329
❑
330
❑
331
❑
332
❑
333
❑334
❑
335
❑
336
❑
337
❑
338
❑ 339
❑ 340
❑ 341
❑
342
❑
343
❑
344
❑
345
❑
346
❑347
❑
348
❑
349
❑
350
❑
351
❑ 352
❑ 353
❑ 354
❑
355
❑
356
❑
357
❑
358
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
Appendices
359 360 361 362 363 364 365 366 367 368 369 370 371
❑
372
❑373
❑
374
❑
375
❑
376
❑
377
❑ 378
❑ 379
❑ 380
❑
381
❑
382
❑
383
❑
384
❑
385
❑386
Ev ent Codes/T
Event Codes/Trr ansmission F or
For ma
matt Pr
orma Proo g r amming Ref er
Refer ence Sheet F
erence ac-
Fac-
tory Defaults
Ademco Contact ID Primary Central Station
❑
1
0
❑
1
1
❑
1
2
❑
1
3
❑
1
4
❑1
5
❑
1
6
❑
1
7
❑
1
8
❑
1
9
❑
1
10
❑
1
11
❑
1
12
❑
1
13
❑
1
14
❑
1
15
❑
1
16
❑
1
17
❑1
18
❑
1
19
❑
1
20
❑
1
21
❑
1
22
❑
1
23
❑
1
24
❑
1
25
❑
1
26
❑
1
27
❑
1
28
❑
1
29
❑
5
30
❑7
31
❑
0
32
❑
5
33
❑
7
34
❑
0
35
❑
5
36
❑
7
37
❑
0
38
❑
5
39
❑
7
40
❑
0
41
❑
5
42
❑
7
43
❑0 44
❑
5
45
❑
7
46
❑
0
47
❑
5
48
❑
7
49
❑
0
50
❑
5
51
❑
7
52
❑
0
53
❑
5
54
❑
7
55
❑
0
56
❑5 57
❑
7
58
❑
0
59
❑
6
60
❑
0
61
❑
4
62
❑
3
63
❑
0
64
❑
1
65
❑
3
66
❑
8
67
❑
0
68
❑
3
69
❑8 70
❑
0
71
❑
3
72
❑
8
73
❑
0
74
❑
3
75
❑
8
76
❑
0
77
❑
3
78
❑
8
79
❑
0
80
❑
3
81
❑
8
82
❑0 83
❑
3
84
❑
8
85
❑
0
86
❑
3
87
❑
8
88
❑
0
89
❑
3
90
❑
8
91
❑
0
92
❑
3
93
❑
8
94
❑
0
95
❑3 96
❑
1
97
❑
0
98
❑
3
99
❑
0
100
❑
2
101
❑
3
102
❑
1
103
❑
1
104
❑
3
105
❑
5
106
❑
1
107
❑
3
108
❑5 109
❑
2
110
❑
3
111
❑
2
112
❑
1
113
❑
3
114
❑
2
115
❑
2
116
❑
3
117
❑
2
118
❑
6
119
❑
3
120
❑
2
121
❑7 122
❑
5
123
❑
2
124
❑
1
125
❑
5
126
❑
2
127
❑
2
128
❑
5
129
❑
2
130
❑
6
131
❑
5
132
❑
2
133
❑
7
134
❑3 135
❑
5
136
❑
4
137
❑
3
138
❑
5
139
❑
4
140
❑
3
141
❑
3
142
❑
6
❑
3
❑
3
❑
0
❑
3
❑3 ❑
0
❑
3
❑
0
❑
8
❑
6
❑
0
❑
2
Appendices
143 144 145 146 147 148 149 150 151 152 153 154 155
❑
6
156
❑
0
157
❑
8
158
❑
4
159
❑
1
160
❑1 161
❑
4
162
❑
1
163
❑
6
164
❑
4
165
❑
1
166
❑
2
167
❑
4
168
❑
1
169
❑
3
170
❑
1
216
❑
1
217
❑
1
218
❑
1
219
❑
1
220
❑1
221
❑
1
222
❑
1
223
❑1
224
❑
1
225
❑
1
226
❑
1
227
❑
1
228
❑
1
229
❑
1
230
❑
1
231
❑
1
232
❑
1
233
❑1
234
❑
1
235
❑
1
236
❑1 237
❑
1
238
❑
1
239
❑
1
240
❑
1
241
❑
1
242
❑
1
243
❑
1
244
❑
1
245
❑
5
246
❑7247
❑
0
248
❑
5
249
❑7
250
❑
0
251
❑
5
252
❑
7
253
❑
0
254
❑
5
255
❑
7
256
❑
0
257
❑
5
258
❑
7
259
❑0260
❑
5
261
❑
7
262
❑0
263
❑
5
264
❑
7
265
❑
0
266
❑
5
267
❑
7
268
❑
0
269
❑
5
270
❑
7
271
❑
0
272
❑5273
❑
7
274
❑
0
275
❑6
276
❑
0
277
❑
4
278
❑
3
279
❑
0
280
❑
1
281
❑
3
282
❑
8
283
❑
0
284
❑
3
285
❑8286
❑
0
287
❑
3
288
❑8
289
❑
0
290
❑
3
291
❑
8
292
❑
0
293
❑
3
294
❑
8
295
❑
0
296
❑
3
297
❑
8
298
❑0299
❑
3
300
❑
8
301
❑0
302
❑
3
303
❑
8
304
❑
0
305
❑
3
306
❑
8
307
❑
0
308
❑
3
309
❑
8
310
❑
0
311
❑3312
❑
1
313
❑
0
314
❑3
315
❑
0
316
❑
2
317
❑
3
318
❑
1
319
❑
1
320
❑
3
321
❑
5
322
❑
1
323
❑
3
324
❑5325
❑
2
326
❑
3
327
❑2
328
❑
1
329
❑
3
330
❑
2
331
❑
2
332
❑
3
333
❑
2
334
❑
6
335
❑
3
336
❑
2
337
❑7338
❑
5
339
❑
2
340
❑1
341
❑
5
342
❑
2
343
❑
2
344
❑
5
345
❑
2
346
❑
6
347
❑
5
348
❑
2
349
❑
7
350
❑3351
❑
5
352
❑
4
353
❑3
354
❑
5
355
❑
4
356
❑
3
357
❑
3
358
❑ ❑ ❑ ❑ ❑ ❑3 ❑ ❑ ❑ ❑ ❑ ❑ ❑
Appendices
6 3 3 0 3 0 3 0 8 6 0 2
359 360 361 362 363 364 365 366 367 368 369 370 371
❑
6
372
❑
0
373
❑
8
374
❑
4
375
❑
1
376
❑1377
❑
4
378
❑
1
379
❑6
380
❑
4
381
❑
1
382
❑
2
383
❑
4
384
❑
1
385
❑
3
386
where
Notes:
1) GG Group Number is fixed at '00' and cannot be changed.
2) CCC Zone Number is transmitted as '001' for zone one up to '010' for zone 10.
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble reports in
the Ademco Contact ID Reporting Structure follows:
Notes:
1) 18
18, which is used in the reporting structure to identify the transmission as Contact ID, is not printed
out in the alarm and trouble report.
2) Q , which is the Event Qualifier for the reporting structure, is printed out in the report as an E for New
Event or R for New Restore.
EVENT MESSAGE
Medical Alarms - 100
100 Medical EMERG - Personal Emergency - #
101 Pendant transmitter EMERG - Personal Emergency - #
102 Fail to report in EMERG - Fail to Check-in - #
Appendices
Panic Alarms - 120
120 Panic Alarm PANIC - Panic - #
121 Duress PANIC - Duress
122 Silent PANIC - Silent Panic - #
123 Audible PANIC - Audible Panic - #
Appendices
384 RF transmitter low battery TROUBLE - RF Sensor Batt. - #
Open/Close - 400
400 Open/Close OPENING CLOSING
401 Open/Close by user OPENING - User # CLOSING - User #
402 Group Open/Close OPENING - Group User # CLOSING - Group User #
403 Automatic Open/Close OPENING - Automatic CLOSING - Automatic
404 Late Open/Close OPENING - Late CLOSING - Late
405 Deferred Open/Close Opening not used Closing not used
406 Cancel OPENING - Cancel Closing not used
407 Remote arm/disarm OPENING - Remote CLOSING - Remote
408 Quick arm Opening not applicable CLOSING - Quick Arm
409 Keyswitch Open/Close OPENING - Keyswitch CLOSING - Keyswitch
Bypasses - 570
570 Zone bypass BYPASS - Zone Bypass - #
571 Fire bypass BYPASS - Fire Bypass - #
572 24 hour zone bypass BYPASS - 24 Hour Bypass - #
573 Burglar bypass BYPASS - Burg. Bypass - #
574 Group bypass BYPASS - Group Bypass
Test.Misc. - 600
601 Manual trigger test TEST - Manually Triggered Restore not applicable
Appendices
❑0
CAC-10F Class A Converter Card installed. Factory default is '0' for card not installed; enter '1' for
card installed.
❑1
LED-10IM EIA-485 Interface Module installed. Factory default is '0' for no module installed; enter '1' for
module installed.
❑ ❑
2 3
Annunciator or ACM-8R maximum monitored address on EIA-485 line. Factory default is address
2 = 0, address 3 = 1. Enter the two digit address set on the switches of the annunciator or ACM-8R
Remote Relay module with the highest (maximum) address.
❑4
Printer installed. Factory default is '0' for printer not installed; enter '1' for printer installed (requires
PRT-24 printer interface module).
❑5
Printer Baud Rate. Factory default is '0' for 2400 Baud; enter '1' for 4800 Baud; '2' for 9600 Baud.
❑6
NAC/Relay Option Module installed. Factory default is '0' for no module installed; enter '1' for module
installed.
❑7
Programmable Relay #3 Definition. This selection determines the panel condition which will cause
Relay #3 to activate. Factory default is '1' for supervisory; enter '0' for alarm; '2' for supervisory auto-
resettable; '3' for trouble; '4' for communication fail; '5' for process monitoring; '6' for auto-resettable
process monitoring.
❑8
Programmable Relay #4 Definition. This selection determines the panel condition which will cause
Relay #4 to activate. Factory default is '4' for communication fail; enter '0' for alarm; '1' for supervisory;
'2' for supervisory auto-resettable; '3' for trouble; '5' for process monitoring; '6' for auto-resettable
process monitoring.
❑9
NAC #3 Type Selection. Factory default is '0' for NAC #3 enabled (silenceable); enter '1' for enabled
(nonsilenceable); '2' to disabled.
❑10
NAC #3 Silence Inhibit. Factory default is '0' for no silence inhibit; enter '1' to inhibit silencing of NAC
#3 for one minute after an alarm.
❑11
NAC #3 Autosilence feature which silences signals after a selected period. Factory default is '0' for no
Appendices
autosilence for NAC #3; enter '1' for 5 mins.; '2' for 10 mins.; '3' for 15 mins.; '4' for 20 mins.; '5' for 25
mins.; '6' for 30 mins.
❑12
NAC #3 Signal Coding. Factory default is '0' for steady (no coding); '1' for March Time code (120
PPM); '2' for California Time code (10 secs. on, 5 secs. off); '3' for Temporal Time code (0.5 secs. on,
0.5 secs. off, 0.5 secs. on, 0.5 secs. off, 0.5 secs. on, 1.5 secs. off).
❑
0
0
CAC-10F Class A Converter Card not installed.
❑
0 EIA-485 annunciator or ACM-8R not installed.
1
❑
0 ❑
1 Maximum annunciator or ACM-8R address on EIA-485 line.
2 3
❑
0 Printer not installed.
4
❑
0
5
Printer Baud Rate. ('0' = 2400 Baud).
❑
0 NAC/Relay Option Module not installed.
6
❑
1 Programmable Relay #3 Definition. ('1' = supervisory).
7
❑
4 Programmable Relay #4 Definition. ('4' = communication fail).
8
❑
0 NAC #3 Type Selection. ('0' for NAC #3 enabled, silenceable).
9
❑
0 NAC #3 Silence Inhibit. ('0' = no silence inhibit).
10
❑
0 NAC #3 Autosilence feature which silences signals after a selected period. ('0' = no autosilence for
11
NAC #3).
❑
0
12
NAC #3 Signal Coding. ('0' = steady, no coding).
❑
0
13
NAC #4 Type Selection. ('0' = NAC #4 enabled, silenceable)
❑
0
14
NAC #4 Silence Inhibit. ('0' = no silence inhibit).
❑
0
15
NAC #4 Autosilence feature which silences signals after a selected period. ('0' = no autosilence for
NAC #4).
❑
0
16
NAC #4 Signal Coding. ('0' for steady, no coding).
❑
0
17
Non-Canadian Supervisory Annunciation.
Appendices
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Service Terminal # 1 Phone Number. Addresses 4-19 store the phone number of Service Terminal #1. Enter
'F' to represent the end of the number.
❑ ❑20 21
Ring Count on Primary Phone Line. Enter number of rings prior to panel answering call. Valid
entries are 0 - 25 (0 = no answer). Factory default is 25.
❑ FAX/Answer Machine, Primary Phone Line. Enter '0' for no sharing of phone line; '1' for sharing.
22
❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38
Service Terminal # 2 Phone Number. Addresses 23 - 38 store the phone number of Service Terminal #2.
Enter 'F' to represent the end of the number.
❑ ❑39 40
Ring Count on Secondary Phone Line. Enter number of rings prior to panel answering call. Valid
entries are 0 - 25 (0 = no answer). Factory default is 25.
❑ 41
FAX/Answer Machine, Secondary Phone Line. Enter '0' for no sharing of phone line; '1' for sharing.
❑ 42
Upload/Download Backup Reporting. Enter '0' for Upload/Download reports to go to the Secondary
Central Station Phone Number on backup only; '1' for Upload/Download reports to always go to the
Secondary; '2' for upload/download reports to go to the first available Central Station phone number.
Appendices
❑
0 ❑
0 ❑
0
0 ❑
0 Panel Identification Number.
1 2 3
❑
F ❑
F ❑
4
F ❑
F ❑
5
F ❑ F ❑
6
F ❑ F ❑
7
F ❑ F ❑
8
F ❑
F ❑
F ❑
F
9
❑
F ❑
F
10 11 12 13 14 15 16 17 18 19
Addresses 4-19 store the phone number of Service Terminal #1. Enter 'F' to represent the end of the number.
❑
2 ❑
5
20
Ring Count on Primary Phone Line.
21
❑
0 FAX/Answer Machine, Primary Phone Line. (0' = no sharing of phone line).
22
❑
F ❑
F
23
❑
F ❑
F
24
❑F ❑F
25
❑
F ❑
26
F ❑F
27
❑
F ❑F
28
❑F
29
❑F
30
❑
F ❑
31
F ❑
F
32 33 34 35 36 37 38
Addresses 23 - 38 store the phone number of Service Terminal #2. Enter 'F' to represent the end of the
number.
❑
2 ❑
5
39
Ring Count on Secondary Phone Line.
40
❑
0 FAX/Answer Machine, Secondary Phone Line. ('0' = no sharing of phone line).
41
❑
0 Upload/Download Backup Reporting. ('0' = Upload/Download reports to go to the Secondary
42
Appendices
CIRCUIT TYPE CIRCUIT FUNCTION WIRE TYPE AND RECOMMENDED WIRE GUAGE
LIMITATIONS MAX DISTANCE
(FEET)
Initiating Device Connects to Initiating Untwisted, unshielded wire 10,000 12AWG Belden 9583 WPW999
Circuit Devices (Do not exceed 100 ohms) 8,000 14AWG Belden 9581 WPW995
(power-limited) 4,875 16AWG Belden 9575 WPW991
3,225 18AWG Belden 9574 WPW975
24 VDC Connects to No more than 1.2 volt drop Distance limitation 12-18 AWG
Regulated annunciators and allowed from supply source set by 1.2 volt
Resettable, other accessories to end of any branch maximum line drop
Nonresettable
(power-limited)
Appendices
OPERATION MODES
OPERATION
9255 (WALK) Enters Walktest Mode May select silent or audible walktest function.
Fire protection is off.
4478 (HIST) View History File Use display or printer to view History File.
Fire protection is on.
8768 (TROU) Activates internal system voltmeter for Fire protection is off while voltmeter function
troubleshooting and diagnosing problems is enabled.
7746 (PRIN) Sends status, history file, walktest file, Fire protection is on. Requires PRT-24
troubleshoot voltages and entire option module.
programming selections to printer
5267 (LAMP) Turns on all LEDs on the main PCB and all Fire protection is on.
system annunciators for 5 seconds
3696 (DOWN) Allows for downloading the entire program Must have service terminal ready. Fire
file to the panel protection remains on.
FUNCTION MODES
Appendices
CODE ACTIVITY NOTES
3472 (DISA) Allows disabling of any input zone or NAC May only disable one NAC or zone at a time.
Places system into trouble.
3622 (ENAB) Allows enabling (return to normal) of any zone May only enable one NAC or zone at a time.
or NAC
3745 (DRIL) Performs drill function by turning on all NAC Transmission of drill function to central
outputs station is defaulted to ON.
3337 (DEFP) Reprograms all entries for Program Levels 1 Entry of code must be performed two times
through 4 to the original factory default in rapid succession as a safety feature. Use
settings. caution when using this feature.
NO TIFIER® warrants its products to be free from defects in materials and workmanship
NOTIFIER
for eighteen (18) months from the date of manufacture, under normal use and service.
Products are date stamped at time of manufacture. The sole and exclusive obligation
of NO TIFIER® is to repair or replace, at its option, free of charge for parts and labor,
NOTIFIER
any part which is defective in materials or workmanship under normal use and service.
For products not under NO TIFIER® manufacturing date-stamp control, the warranty
NOTIFIER
is eighteen (18) months from date of original purchase by NO TIFIER®'s distributor
NOTIFIER
unless the installation instructions or catalog sets forth a shorter period, in which
case the shorter period shall apply. This warranty is void if the product is altered,
repaired or serviced by anyone other than NO TIFIER® or its authorized distributors or
NOTIFIER
if there is a failure to maintain the products and systems in which they operate in a
proper and workable manner. In case of defect, secure a Return Material Authorization
form from our customer service department. Return product, transportation prepaid,
to NO TIFIER®, One Fire-Lite Place, Northford, Connecticut 06472-1653.
NOTIFIER
This writing constitutes the only warranty made by NO TIFIER® with respect to its
NOTIFIER
®
NO TIFIER
products. NOTIFIER does not represent that its products will prevent any loss by
fire or otherwise, or that its products will in all cases provide the protection for which
they are installed or intended. Buyer acknowledges that NO TIFIER® is not an insurer
NOTIFIER
and assumes no risk for loss or damages or the cost of any inconvenience,
transportation, damage, misuse, abuse, accident or similar incident.
This warranty replaces all previous warranties and is the only warranty made by
NO TIFIER®. No increase or alteration, written or verbal, of the obligation of this warranty
NOTIFIER
is authorized.