SFP 1024

Download as pdf or txt
Download as pdf or txt
You are on page 1of 120

One Fire-Lite Place

Northford, CT 06472
(203) 484-7161 Fax: (203) 484-7118

The SFP-1024/SFP-1024E
Fire Control Comm unicator
Communicator
Prog
Progrramming, Installation, Maintenance
and Oper ating Instr
Operating uction Man
Instruction ual
Manual

Document # 50475
7/22/99 Rev:
P/N 50475:D1
D
ECN 99-233
Installation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability:

WARNING - Several different sources of power can be connected to the fire alarm Like all solid state electronic devices, this system may operate erratically or can
control panel. Disconnect all sources of power before servicing. Control unit and be damaged when subjected to lightning induced transients. Although no system is
associated equipment may be damaged by removing and/or inserting cards, completely immune from lightning transients and interferences, proper grounding will
modules, or interconnecting cables while the unit is energized. Do not attempt to reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to
install, service, or operate this unit until this manual is read and understood. an increased susceptibility to nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or encountered.
CAUTION - System Reacceptance Test after Software Changes: To ensure
proper system operation, this product must be tested in accordance with NFPA 72- Disconnect AC power and batteries prior to removing or inserting circuit boards.
1993 Chapter 7 after any programming operation or change in site-specific software. Failure to do so can damage circuits.
Reacceptance testing is required after any change, addition or deletion of system
components, or after any modification, repair or adjustment to system hardware or Remove all electronic assemblies prior to any drilling, filing, reaming, or punching
wiring. of the enclosure. When possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not interfere with battery,
All components, circuits, system operations, or software functions known to be transformer, and printed circuit board location.
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices that are Do not tighten screw terminals more than 9 in-lbs. Over tightening may damage
not directly affected by the change, up to a maximum of 50 devices, must also be threads, resulting in reduced terminal contact pressure and difficulty with screw
tested and proper system operation verified. terminal removal.

This system meets NFPA requirements for operation at 0-49O C/32-120 O F This system contains static-sensitive components. Always ground yourself with a
and at a relative humidity of 85% RH (non-condensing) at 30 O C/86 O F. proper wrist strap before handling any circuits so that static charges are removed
However, the useful life of the system's standby batteries and the electronic from the body. Use static suppressive packaging to protect electronic assemblies
components may be adversely affected by extreme temperature ranges and removed from the unit.
humidity. Therefore, it is recommended that this system and its peripherals be
installed in an environment with a nominal room temperature of 15-27O C/60-80O Follow the instructions in the installation, operating, and programming manuals.
F. These instructions must be followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability depend upon proper
Verify that wire sizes are adequate for all initiating and indicating device loops. installation.
Most devices cannot tolerate more than a 10% I.R. drop from the specified device
voltage.

While installing a fire alarm system may make lower insurance


Fire Alarm System Limitations rates possible, it is not a substitute for fire insurance!

An automatic fire alarm system - typically made up of smoke detectors, heat Audible warning devices such as bells may not alert people if these devices are
detectors, manual pull stations, audible warning devices, and a fire alarm control located on the other side of closed or partly open doors or are located on another
with remote notification capability can provide early warning of a developing fire. floor of a building.
Such a system, however, does not assure protection against property damage or
loss of life resulting from a fire. A fire alarm system will not operate without any electrical power. If AC power fails,
the system will operate from standby batteries only for a specified time.
Any fire alarm system may fail for a variety of reasons:
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For
Smoke detectors may not sense fire where smoke cannot reach the detectors such this reason, the rate-of-rise feature of each detector should be tested at least once
as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke per year by a qualified fire protection specialist.
detectors also may not sense a fire on another level or floor of a building. A second
floor detector, for example, may not sense a first floor or basement fire. Further- Equipment used in the system may not be technically compatible with the control.
more, all types of smoke detectors - both ionization and photoelectric types, have It is essential to use only equipment listed for service with your control panel.
sensing limitations. No type of smoke detector can sense every kind of fire caused
by carelessness and safety hazards like smoking in bed, violent explosions, Telephone lines needed to transmit alarm signals from a premise to a central
escaping gas, improper storage of flammable materials, overloaded electrical monitoring station may be out of service or temporarily disabled.
circuits, children playing with matches, or arson.
The most common cause of fire alarm malfunctions, however, is inadequate
IMPORTANT! Smoke detectors must be installed in the same room as the maintenance. All devices and system wiring should be tested and maintained by
control panel and in rooms used by the system for the connection of alarm professional fire alarm installers following written procedures supplied with each
transmission wiring, communications, signaling, and/or power. If detectors are device. System inspection and testing should be scheduled monthly or as required
not so located, a developing fire may damage the alarm system, crippling its by National and/or local fire codes. Adequate written records of all inspections should
ability to report a fire. be kept.

FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency Canadian Requirements
energy and if not installed and used in accordance with the instruction manual, may This digital apparatus does not exceed the Class A limits for radiation noise
cause interference to radio communications. It has been tested and found to comply emissions from digital apparatus set out in the Radio Interference Regulations of the
with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Canadian Department of Communications.
Rules, which is designed to provide reasonable protection against such interference
when operated in a commercial environment. Operation of this equipment in a Le present appareil numerique n'emet pas de bruits radioelectriques depassant les
residential area is likely to cause interference, in which case the user will be required limites applicables aux appareils numeriques de la classe A prescrites dans le
to correct the interference at his own expense. Reglement sur le brouillage radioelectrique edicte par le ministere des Communica-
tions du Canada.

Technical Publishing Document PRECAULG.PM6 12/31/96


NFPA Standards, UL Documents 5

1.0 Product Description 7


1.1 Product Features 7
Figure 1-1: Optional DP-1024 7
Figure 1-2: SFP-1024 Panel 8
1.2 Specifications 9
1.3 Controls and Indicators 10
Table of Contents
1.4 Circuits 10
1.5 Digital Communicator 11
1.6 Components 11
1.7 Optional Modules 12
1.8 Optional Accessories 13
1.9 Telephone Requirements and Warnings 17

2.0 Installation 19
2.1 General 19
2.2 Backbox Mounting 19
Figure 2-1: Cabinet Dimensions & Knockouts 20
Figure 2-2: Backbox and Battery Box 21
2.3 Operating Power 22
Figure 2-3: Operating Power Connections 22
Figure 2-4: Auxiliary Power Connections 23
2.4 Input Circuits 23
Figure 2-5: Style B Initiating Device Circuit Connect 24
2.5 Output Circuits 25
Figure 2-6: Notification Appliance Circuit Connections 25
Figure 2-7: Aux Relay and Relay Driver Terminals 25
2.6 Digital Communicator 26
Figure 2-8: Wiring Phone Jack 26
2.7 UL Power-limited Wiring Requirements 27
Figure 2-9: Typical Wiring for UL Power-limited 27
2.8 Optional Module Installation 28
Figure 2-10: Installation of CAC-10F Module 28
Figure 2-11: Wiring NACs and IDCs for Class A 28
Figure 2-12: Installation and Wiring of NAC-REM 29
Figure 2-13: Remote Printer Connections 30
Figure 2-14: LED-10IM Installation 31
Figure 2-15: Wiring LED-10IM to LED-10N 31
Figure 2-16: Wiring LED-10IM to ACM-8R 32

3.0 Programming Instructions 35


3.1 Entering Program Mode 35
3.2 Switch Functions 36
Figure 3-1: Control Panel Keypad 36
3.3 Program Options 36
Table 3-1: Event Code Changes for Contact ID 42
Figure 3-2: Verification Timing Diagram 42
Table 3-2: Event Codes, Primary C. S. Number 46
Table 3-3: Event Codes, Primary C. S. Number 48
Table 3-4: Event Codes, Primary C. S. Number 50
Table 3-5: Event Codes, Secondary C. S. Number 51
Table 3-6: Event Codes, Secondary C. S. Number 53
Table 3-7: Event Codes, Secondary C. S. Number 55
50475 Rev D1 7/22/9 P/N 50475:D1
3
4.0 Operating Instructions 62
4.1 Switches 62
4.2 Displays 64
Figure 4-1: Phone Connectors & LEDs 65
4.3 Operation 66
4.3.1: Alarm Response 66
4.3.2: Alarm Restoral 67
4.3.3: System Supervisory Condition Response 67
Table of Contents
4.3.4: System Supervisory Restoral Response 67
4.3.5: Trouble Condition Response 68
4.3.6: Trouble Condition Restoral 68
4.3.7: Process Monitored Alarm Response 69
4.3.8: Process Monitored Alarm Restoral 69
4.3.9: OFF Normal Reporting 69
4.3.10: Zone Disable/Enable 69
4.3.11: NAC (bell) Disable/Enable 70
4.3.12: Fire Drill 70
4.4 Central Station Communications 71
Table 4-1: Format Selection Addresses (16+42) 72
Table 4-2: Format Selection Address Explanation 73
Table 4-3: Compatible UL Listed Receivers 75

5.0 Servicing 76
5.1 Walk Test Mode 76
5.2 History Mode 77
5.3 Troubleshoot Mode 79
5.4 Lamp Test 80
Figure 5-1: Handset/Speaker Connection 80
5.5 Print Mode 81
5.6 Printer Output 81

6.0 Remote Site Upload/Download 83


6.1 Downloading Program: General 83
6.1.1 Security Features 85
6.2 Downloading Initiated at Control Panel 86
6.3 Downloading Initiated at Service Terminal 86
6.4 Uploading Initiated at Service Terminal 87
6.5 Simultaneous Data Transfers 87

Appendix A: Battery Calculations 88


Appendix B: Main Panel Option Program Sheets 91
Appendix C: Format Charts Program Sheets 96
Appendix D: Ademco Contact ID Event Codes 106
Appendix E: Option Module Program Sheets 111
Appendix F: Upload/Download Program Sheets 114
Appendix G: Wire Requirements 116
Appendix H: Operation and Function Modes 117

4 50475 Rev D1 9/22/99 P/N 50475:D1


This control panel has been designed to comply with standards set forth by the following
regulatory agencies:
• Underwriters Laboratories Standard UL 864
• NFPA 72-1993 National Fire Alarm Code
• CAN/ULC - S527-M87 Standard for Control Units for Fire Alarm Systems

Before proceeding, the installer should be familiar with the following documents.

NFPA Standards
The SFP-1024(E) COMPLIES WITH THE FOLLOWING NFPA STANDARDS:
NFPA 72-1993 National Fire Alarm Code for:
Central Station Signaling Systems (Automatic, Manual and Waterflow) Protected Premises Unit
Local Fire Alarm Systems
Remote Station Fire Alarm Systems

Underwriters Laboratories Documents:


UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers—Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
CAN/ULC - S524-M91 Standard for Installation of Fire Alarm Systems

Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction

Notifier Documents
Notifier Device Compatibility Document Document# 15378
AFM-16A Annunciator Document# 15207
FCPS-24 Field Charger/Power Supply Document# 50059
LDM Series Lamp Driver Modules Document# 15885
LED-10N Annunciator Document# 50581
ACM-8R Annunciator Control Relay Module Document# 15342
PK-1024 Manual Document# 50582

50475 Rev D1 7/22/9 P/N 50475:D1


5
6 50475 Rev D1 9/22/99 P/N 50475:D1
1.0 Product Descr iption
Description

Description
iption
The SFP-1024 is a combination control panel and digital communicator all on one circuit board. It is a 10-zone panel,
which uses conventional input devices. The panel accepts waterflow devices, two-wire smoke detectors, four-wire
smoke detectors, pull stations and other normally-open contact devices. Outputs include two Notification Appliance
Circuits expandable to four, two programmable Form-A relays (option module with two Form-C relays can be

Product Descr
added), EIA-485 port to interface with remote annunciators and optional remote relay modules plus a printer port.

The integral communicator transmits system status (alarms, troubles, AC loss, others) to UL-listed Central Stations
via the public switched telephone network. The control panel has a built in programmer. It also supervises all wiring,
AC voltage, telephone line input voltage/current and battery level.

The control panel may be programmed or interrogated off site via the public switched telephone network. Any IBM
compatible personal computer with Windows™ 3.1 or greater, with a 1200 Baud Hayes™ compatible modem and
Notifier Upload/Download software P/N PK-1024, may serve as a Service Terminal. This allows downloading of any
portion or all of the program and upload of any portion or all of the program, history file, walktest data, current status
and system voltages. The SFP-1024E offers the same features as the SFP-1024 but allows connection to 220/240
VAC input.

1.1 Product Features


• Selectable as Local Fire Panel or Fire Panel/Communicator
• Programmable Zone ID: 2-Wire Smoke; Pull Station;
Normally-Open Contact; Supervisory; Supervisory-
Auto-resettable; Waterflow (silenceable); Waterflow
(nonsilenceable), Remote Switch for Reset, Silence,
Acknowledge and Drill, Standard and Auto-reset
Critical and Noncritical Process Monitoring
• 10 Style B (Class B) Initiating Device Circuits (IDCs)
• Two NFPA Style Y (Class B) Notification
Appliance Circuits (NACs)
• CAC-10F Option Module to convert all 10 IDCs to
Style D (Class A) and convert two Style Y
(Class B) NACs to Style Z (Class A)
• 6.6 amps of system power
• 6.0 amps of NAC power Figure 1-1: Optional DP-1024
• Remote Relay Option Module (ACM-8R) providing (dress panel coverplate)
one 5 amp relay per zone.
• Built-in Programmer • History File with 256 Event Storage
• Built-in Voltmeter • Silence Inhibit per Notification Appliance Circuit
• Telephone Line Active LED Indicators • Auto-Silence per Notification Appliance Circuit
• Communication Confirmation (Kissoff) LED • Touchtone/Rotary Dialing per telephone line
• Disable report by event • Programmable Make/Break Ratio
• Programmable Event Codes • Fuseless
• 24 Volt Operation • Printer Interface Module (PRT-24)
• Real Time Clock and Calendar • NAC-REM Option Module adds two Form-C
• Trouble Reminder relays and two Style Z (Class A) NACs.
• Alarm Verification • Print Real-time System Status
• Interfaces with Notifier annunciators (requires • Print History, Walktest Files, Program
LED-10IM Option Module) Contents, and Troubleshoot mode voltages
ü LED-10N Remote Annunciator provides one red • PK-1024 Upload/Download Software Kit.
alarm and one yellow trouble LED per zone. • Number of dial attempts (5 min, 10 max)
Mounts to a standard 3-gang electrical box • Programmable Zone Delay (waterflow only)
ü LDM-32 Graphic Annunciator • Low AC Voltage Sense
ü AFM Series LED Annunciators • One Man silent or audible Walk Test
• Small Size 16.900" x 14.500" x 4.625" • Optional Dead Front cover (DP-1024)
Note: Unless otherwise specified, the term SFP-1024 shall be used in this manual to refer to both the
SFP-1024 and the SFP-1024E Fire Control Communicators.
50475 Rev D1 7/22/9 P/N 50475:D1
7
Class A Converter
Product Descr

Module
Notification
Appliance Circuits 10 Input
Programmable Zones
Description

24 VDC Relays
Power LED-10IM
Interface
iption

Module
NAC-REM Connector
Expander Module
Printer
Interface
Module
Connector
Four Character
7-Segment LED
Display
Keypad
PROM (U14)1

Optional
Transformer
Primary &
Secondary
Phone Lines

Holds up to 12 AH Batteries
Up to 60 Hrs. of Standby

Note:
1
Software for the Fire Control Communicator is located in a PROM inserted in the IC socket labeled U14. The
SFP-1024 and SFP-1024E each contain unique software. For specific panel software information refer to the SFP-
1024/SFP-1024E Field Software Change Procedure Document #50591.

Figure 1-2: SFP-1024 Panel


Panel

8 50475 Rev D1 9/22/99 P/N 50475:D1


1.2 Specifications AC Power - TB1
SFP-1024: 120 VAC, 60 Hz, 2.3 amps

Description
iption
SFP-1024E: 220/240 VAC, 50 Hz, 1.2 amps.
Wire size: minimum #14 AWG with 600V insulation
Battery (lead acid only) - J1

Product Descr
Maximum Charging Circuit: Normal Flat Charge—27.6V @ .8 amp
Maximum Charger Capacity: 17 Amp Hour battery (SFP-1024 cabinet holds max. 12
Amp Hour battery. Larger batteries require Notifier #BB-17 or other UL listed battery
cabinet).
Initiating Device Circuits TB5 and CAC-10F Option Module
Detector Zones 1 through 10
Power-limited Circuitry
Operation: All zones NFPA Style B - Convert to Style D using CAC-10F Class A
Converter Module.
Normal Operating Voltage: 24 VDC (ripple = 100 mV max)
Alarm Current: 15 mA
Short Circuit Current: 42 mA max.
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 4.7K, 1/2-Watt (part # 27072 UL listed)
Detector Loop Current is sufficient to ensure operation of one alarmed detector per zone.
Standby Current: 7.26 mA (includes ELR and 2 mA maximum detector current)
Smoke Detector Identifier A
Refer to Notifier Compatibility Chart for listed compatible devices.
Notification Appliance Circuits - TB4 & NAC-REM Option Module (TB2 & TB3)
Non-regulated special purpose power, Styles Y & Z supported
Power-limited circuitry
Operating Voltage Nominal 24 volts
Current for all external devices: 3.0 amps expandable to 6.0 amps
Current Limit: TB4 via electronic protection, NAC-REM option module (TB2 & TB3) via
PTC.
Max. signaling current/circuit: TB4 = 3.0 amps. NAC-REM = 1.5 amps.
End-of-line resistor: 4.7K, 1/2-Watt (part # 71252 UL listed) for Notification Appliance
Circuits
Refer to Notifier Compatibility Chart for listed compatible devices.
Form-A Relays - TB3
TB3 contact rating: 5.0 amps @ 30 VDC (resistive), 5.0 amps @ 125 VAC (resistive)
NAC-REM Form-C contact rating: 2.0 amps @ 30 VDC, 0.6 amps @ 125 VAC (resistive)
Four-wire Smoke Detector Power - TB2 Terminals 3 (+) & 4 (-)
Max. ripple voltage: 10 mVRMS Operating Voltage nominal 24 volts
Up to 500 mA is available for powering 4-wire smoke detectors.
Power-limited Circuitry. Recommended maximum Standby current is 50 mA1.
Refer to Notifier Compatibility Chart for compatible listed devices.
Nonresettable Regulated 24V Power - TB2 Terminals 1 (+) & 2 (-)
Max. ripple voltage: 10 mVRMS Operating Voltage nominal 24 volts
Total DC current available from this output is up to 500 mA.
Power-limited Circuitry. Recommended maximum Standby current is 150 mA 1.
Refer to Notifier Compatibility Chart for compatible listed devices.
Notes:
1) For power supply and battery calculations, refer to Appendix A.
2) Total current for nonresettable power, four-wire smoke power, and four Notifica-
tion Appliance Circuits must not exceed 6.0 amps. Total system current in excess
of 3.6 amps requires the XRM-24 (or XRM-24E for 220/240 VAC applications)
Transformer and 12 Amp Hour or 17 Amp Hour batteries.

50475 Rev D1 7/22/9 P/N 50475:D1


9
1.3 Controls and Front Panel Switches
Indicators RESET Digits 0-9
Product Descr

SILENCE A
MODE B
Up Arrow (ACK) C
Down Arrow (ACK) D
1st EVENT E
ENTER/STORE F
Description

Displays
• Alarm - red LED
• Trouble - yellow LED
iption

• Supervisory - yellow LED


• AC Power - green LED
• Four, Seven Segment Displays - red
• Primary Phone Line Active - red LED
• Secondary Phone Line Active - red LED
• 'Kissoff' Signal from Central Station - green LED
• Silence - yellow LED
• Modem - green LED

Local Sounder - A piezo sounder provides separate and distinct sounds for alarm,
trouble, supervisory and critical process monitoring conditions.

1.4 Circuits Input Circuits


Ten input circuits provide Style B (Class B) configuration standard and may be
converted to Style D (Class A) by installing the CAC-10F module. Input circuits
may be used as standard fire control panel zones, remote input switches
(Acknowledge, Silence, Drill, Reset) or as standard or auto-resettable critical and
noncritical process monitoring. All ten Initiating Device Circuits accept Normally-
Open contact devices and two-wire smoke detectors.
Output Circuits
• 24 Volt Resettable Power Output 500 mA
• 24 Volt Nonresettable Power Output 500 mA
• Primary Telephone Line
• Secondary Telephone Line
• 24 Volt Battery Charger (up to 17 AH batteries)
• Printer Port
• EIA-485 Port (interfaces to LED-10N Annunciator, AFM Series and LDM Graphic
Series Annunciators and ACM-8R Remote Relay Module)

Notification Appliance Circuits - Two Notification Appliance Circuits Style Y


(Class B) configurable for Style Z (Class A) using the CAC-10F option module.

Relays - Two dry Form-A relay contacts programmable for system alarm, system
trouble, system supervisory (standard and auto-resettable), standard and auto-
resettable process monitoring or communications failure are provided. Contacts are
rated 2 amps at 30 VDC resistive. Two additional Form-C relay contacts
programmable for alarm, trouble, standard and auto-resettable supervisory, standard
and auto-resettable process monitoring or communications fail are available using
the NAC-REM (NAC/Relay) option module. Contacts are rated 2 amps at 30 VDC
and 0.6 amps at 125 VAC resistive.

Printer Port - EIA-232 compatible, fully supervised and programmable for 2400,
4800 or 9600 Baud. Only one printer may be connected to the port. Consult the
factory for recommended printers.

10 50475 Rev D1 9/22/99 P/N 50475:D1


EIA-485 Port - EIA-485 compatible port on the LED-10IM option module supports
up to 32 LED-10N Remote Annunciators or 32 sets of ACM-8R Relay Modules or

Description
iption
32 AFM Series Annunciators or 32 LDM Series Annunciators or any combination of
the four devices totalling 32.

Product Descr
Telephone Lines - Fully supervised at all times, voltage is sensed to 4 volts and
current is sensed to 5 mA.

Battery Charger - Will charge up to 17 AH batteries. The SFP-1024 cabinet holds a


maximum of 12 AH batteries. The Notifier BB-17 is required to hold 17 AH
batteries. The charger is rated for 850 mA maximum current.

1.5 Digital Two modular phone jacks allow easy connection to telephone lines. Modular jacks
Communicator are labeled PH1 and PH2 for the Primary and Secondary phone lines. Telephone line
'Active' red LEDs are provided as well as a green 'Kissoff' LED. The integral digital
communicator provides the following functions:

• Line Seizure - takes control of the phone lines disconnecting any premises
phones.

• Off/On Hook - perform on and off-hook status to the phone network.

• Listen for dial tone - 440 hertz tone typical in most networks.

• Dialing the Central Station(s) number - default is Touch-Tone®,


programmable to rotary.

• For tone burst or touchtone type formats: Discern proper 'Ack' and 'Kissoff'
tone(s) - The frequency and time duration of the tone(s) varies with the
transmission format. The control panel will adjust accordingly.

• Communicate in the following formats:


✓12 Tone Burst Types: 20 pps
(3+1, 4+1, 4+2, 3+1 Exp., 4+1 Exp., 4+2 Exp.)
✓ 3 Touchtone Types:
4 + 1 Ademco Express
4 + 2 Ademco Express
Ademco Contact ID
See Table 4-3 for list of compatible receivers.

1.6 Components
Main Circuit Board The main circuit board contains the
system's CPU, power supply, other
primary components and wiring
interface connectors. Optional modules
plug in and are mounted to the main
circuit board. The main circuit board is
delivered pre-mounted in the cabinet.

50475 Rev D1 7/22/9 P/N 50475:D1


11
Cabinet
Product Descr

The cabinet is gray with an attractive navy blue front


overlay. The backbox measures 16.900" x 14.500" x 4.625"
and provides space for two batteries (up to 12 Amp-Hours).
Also available is an optional dress panel, DP-1024, which
mounts inside the cabinet.
Description
iption

Transformer Two 100VA transformers are provided standard with


Standard
Assembly the panel.

Standard
Batteries The cabinet provides space for 12 Amp-Hour
batteries (for 17 Amp-Hour batteries use the listed
Notifier BB-17 battery box). Batteries must be ordered
separately.

1.7 Optional Modules LED-10IM


The LED-10IM Interface Module provides an EIA-485 port to support the LED-
10N Remote Annunciator, LDM Series Annunciator, AFM Series Annunciator and
ACM-8R Relay Modules. EIA-485 wiring is supervised for open circuits by this
module. The LED-10IM mounts to connector J6 in the upper right corner of the
main board. See Figure 2-14.

ACM-8R Relay Module


The ACM-8R option module provides 8 Form-C relays rated at 5 amps each. The
Relay Module connects to the EIA-485 port off of the LED-10IM option module.
Relays are assigned to each of the 10 Initiating Device Circuits. Refer to Figure 2-
16 for additional information.

Printer Interface Module-PRT-24


The Printer Interface Module may be used to connect a printer to the control panel
for the purpose of printing a history report, walktest file, troubleshoot report,
program entries or current system status. Printers require separate external primary
power. Connect the PRT-24 module (with cable) to the serial EIA-232 port on the
printer. The module mounts to the J4 connector on the main circuit board. Note: An
EDP listed printer must be used if printer will be permanently attached. See Figure
2-13. Baud rate is programmable (refer to Option Module Selections in Section
3.3).

CAC-10F Module
The CAC-10F Module can be used to convert the 10 Style B (Class B) Initiating
Device Circuits to 10 Style D (Class A) IDCs and the two Style Y (Class B)
Notification Appliance Circuits to two Style Z (Class A) NACs. The CAC-10F
module connects to J10 on the main circuit board. Refer to Figures 2-9 and 2-10.

NAC-REM Module
The NAC-REM (NAC/Relay) Module can be used to add two Style Z (Class A)
NACs and 2 Form-C relays. The module connects to J7 on the main circuit board.
Refer to Figure 2-12.
12 50475 Rev D1 9/22/99 P/N 50475:D1
1.8 Optional Dress Panel
Accessories A red dead-front dress panel (DP-1024) is available as an option (required for

Description
iption
Canadian installations). The dress panel restricts access to the system wiring while
allowing access to the membrane switch panel. Refer to Figure 1-1.

Battery Box

Product Descr
The Notifier BB-17 battery box may be
used to house two batteries greater than 12
AH to a maximum of 17 AH. The battery
box mounts directly below the main circuit
board in the cabinet (refer to Figure 2-2).
The BB-17 is gray and is provided with
knockouts.

Program Kit - PK-1024


This kit includes three 3 1/2" diskettes plus Instruction Manual P/N 50582. When
the software is loaded into an IBM compatible computer, it creates an off-line
Service Terminal that allows any SFP-1024 panel to be uploaded or downloaded
over standard telephone lines.

LED Zone Type - LED-10N Annunciator


The LED-10N is a 10 zone LED annunciator which mounts on a standard 3-gang box
and provides LED indication of the following:

Alarm Zone 1 (red) Trouble Zone 1 (yellow) AC Power (green)


Alarm Zone 2 (red) Trouble Zone 2 (yellow) Alarm (red)
Alarm Zone 3 (red) Trouble Zone 3 (yellow) Trouble (yellow)
Alarm Zone 4 (red) Trouble Zone 4 (yellow) Supervisory (yellow)
Alarm Zone 5 (red) Trouble Zone 5 (yellow) Alarm Silence (yellow)
Alarm Zone 6 (red) Trouble Zone 6 (yellow)
Alarm Zone 7 (red) Trouble Zone 7 (yellow)
Alarm Zone 8 (red) Trouble Zone 8 (yellow)
Alarm Zone 9 (red) Trouble Zone 9 (yellow)
Alarm Zone 10 (red) Trouble Zone 10 (yellow)

A local trouble sounder and


switches for remote
Acknowledge, Silence, Drill and
Reset are also provided. Wiring is
inherently supervised by the
FACP. Slide-in paper labels
permit an easy change of zone
information. Dip switches allow
the enabling and disabling of the
local piezo sounder (with approval
of local AHJ), enabling and
disabling of the mechanical
keyswitch which may be used to
prevent unauthorized use of the function switches and selection of annunciator
receive/transmit mode. See Figure 2-15. Note: The LED-10N Remote Annunciator
requires the use of the LED-10IM Interface Module.

50475 Rev D1 7/22/9 P/N 50475:D1


13
Accessories: LED Zone Type - AFM Series Annunciators
Product Descr

The AFM Series Annunciators remotely display system status. The AFM/AEM-16AT
annunciators display zone alarm and trouble status. In addition, they provide remote
ACKNOWLEDGE, SILENCE, RESET and DRILL functions. The AFM Series
Anunciators require the use of the LED-10IM Interface Module. For more detailed
information, refer to the appropriate AFM Annunciator manual.
Description

AFM-16ATX
The Annunciator Fixed Module-16ATX contains 16 red alarm and 16
yellow trouble LEDs, a system trouble LED, an ON LINE/POWER
iption

LED, and a local piezo sounder with switches for ACKNOWLEDGE,


SILENCE, RESET, and DRILL. The AFM-16ATX is fixed at
address '1' and will accept up to 3 AEM-16ATF Expanders.

The AFM-16ATX can be mounted in a Notifier ABS or ABF series


backbox. Refer to the AFM-16ATX Manual for detailed information.
Note: Only one AFM-16ATX is required to annunciate 10 zones of
alarm and trouble, provided '8 point shift' function is selected. Refer
to Annunciator Manual P/N 15390 for additional information.

AEM-16ATF
The Annunciator Expander Module-16ATF connects to the AFM-
16ATX and adds 16 sets of red alarm LEDs and yellow trouble LEDs. Up
to three AEM-16ATFs may be added to an AFM-16ATX but only one is
required.
Note: One AEM-16ATF is required with an AFM-16ATX to annunciate 10
zones of alarm and trouble as well as general system status provided
'8 point shift' function is not selected. Refer to Annunciator Manual
P/N 15390 for additional information.

AFM-16AT
The Annunciator Fixed Module-16AT contains 16 red alarm and 16
yellow trouble LEDs, a system trouble LED, an ON LINE/POWER
LED, and a local piezo sounder with switches for ACKNOWLEDGE,
SILENCE, RESET, and DRILL. The AFM-16AT is fixed at address '1'
and communication is via the EIA-485 data line.

The AFM-16AT can be mounted in a Notifier ABS or ABF series


backbox. Refer to the AFM-16AT Manual for detailed information.

AFM-16A
The Annunciator Fixed Module-16A has 16 red alarm LEDs. Multiple
annunciators may be used by setting all annunciators to Receive Only,
except the last AFM-16A in line. Each annunciator's address is internally FIRE ALARM ANNUNCIATOR

ALARM ZONE 1

fixed at '1', and communication is via the EIA-485 data line. The Local ALARM ZONE 2
ALARM ZONE 3

Silence/Acknowledge switch functions as local lamp test and silence for ALARM ZONE 4
ALARM ZONE 5

annunciator piezo. LEDs include On-Line and System Trouble indica- ALARM ZONE 6
ALARM ZONE 7
ALARM ZONE 8
tors. ALARM ZONE 9
ALARM ZONE 10
ALARM ZONE 11
ALARM ZONE 12

The AFM-16A Annunciator can be mounted in a standard 4-gang ALARM ZONE 13


ALARM ZONE 14

electrical box. Refer to the AFM-16A Manual for detailed information. ALARM ZONE 15
ALARM ZONE 16

PRESS
SYSTEM TROUBLE TO
SILENCE

ON LINE

14 50475 Rev D1 9/22/99 P/N 50475:D1


Graphic Annunciator Driver - LDM Series Lamp Driver Modules
(refer to Appendix for detailed wiring requirements)

Description
iption
The LDM Series Lamp Driver Modules, which consist of the LDM-32 master and
LDM-E32 expander modules, are used to provide an interface to a custom graphic

Product Descr
LED annunciator. The master module provides power and control for a maximum of
three expander modules (expander modules are not required when interfacing to the
SFP-1024). The LDM-32 and LDM-E32 have output connectors which are used to
drive lamps or LEDs and input connectors which are used for remote switch functions.
The LDM Series requires the use of the LED-10IM Interface Module. Refer to the
LDM Series Lamp Driver Modules Manual for a complete description.

The LDM-32
The Lamp Driver Module LDM-32 has 32 alarm
lamp/LED driver outputs which sink current to system
common (-) on activation. A single positive (+)
voltage is required to supply total operating power for
all lamps or LEDs when all drivers are activated. The
LDM-32 provides a separate driver for system trouble
and inputs for a local lamp test switch. A maximum
of 16 external control switches may be wired to the
LDM-32. DIP switch SW3 is used to enable or
disable the onboard piezo, enable remote switch
functions, select a flashing LED function for new
alarms and troubles, and other functions. Switch SW4
is used to configure the module to annunciate 32
alarms or 16 alarms and 16 troubles. A green ON-
LINE LED flashes to indicate ongoing communica-
tions with the host FACP. One LDM-32 supports up
to 3 LDM-E32 modules. The LDM-32 is supplied
with 4 standoffs and screws for mounting to a CHS-
4L chassis or custom backbox.

50475 Rev D1 7/22/9 P/N 50475:D1


15
System Power Expansion - FCPS-24(E) Remote Power Supply
Product Descr

The FCPS-24 (FCPS-24E for 220/240 VAC applications) is a compact, remote power
supply and battery charger. This remote power supply consists of a filtered 24 VDC
output that may be configured to drive up to four Notification Appliance Circuits
[four Style Y (Class B) or two Style Z (Class A) and two Style Y (Class B)]. Alter-
nately, the four Notification Appliance Circuits may be used as auxiliary regulated
Description

power configured for resettable or nonresettable operation.

The FCPS-24(E) may be used in a number of different applications. It may be used as


a remotely-mounted power supply and battery charger powering up to four, coded or
iption

non-coded, Notification Appliance Circuits. Alternately, any or all of these circuits


may be used as 24 VDC output circuits capable of powering four-wire smoke detec-
tors or any device that requires filtered power. These circuits may be configured as
resettable or nonresettable outputs to expand FACP auxiliary system power.

Style Y/Style Z
Notification
Notification Appliance Circuit or
Appliance Circuit 24 VDC Output #1
Control Input #1
Style Y Notification
(from FACP)
Appliance Circuit or
24 VDC Output #2

Style Y/Style Z
Notification Appliance
Notification Circuit or 24 VDC
Appliance Circuit Output #3
Control Input #2
(from FACP) Style Y Notification
Appliance Circuit or
24 VDC Output #4

AC Power Battery Charger

Specific FCPS Trouble


Application Contact Output
Power

One of the most common applications for the FCPS-24(E) remote power supply
utilizes the NAC expander mode. In this application, one or two Notification Appli-
ance Circuits (NACs) are connected from the main FACP NAC output(s) to the
remote power supply Control Input circuits. When these Control Input circuits
activate (due to reverse polarity of the NAC output), the power supply will activate its
corresponding outputs. NAC Control Input #1 controls power supply output circuits
#1 and #2. NAC Control Input #2 controls output circuits #3 and #4.

During the inactive state, the remote power supply supervises its NAC field wiring for
short and open circuits. If a fault is detected, the supply will enter a trouble condition
and illuminate the corresponding NAC trouble LED (Output Circuits 1-4). However,
once the Notification Appliance Circuits are activated, the supervision is disabled and
the circuits are no longer supervised. Supervision of other power supply faults such
as low battery, Earth Fault, AC loss and battery charger failure will continue and may
be monitored via the independent trouble relay contact.

If a specific application requires that all four outputs activate at the same time, only
one NAC control input from the FACP is necessary. For this application, the Notifi-
cation Appliance Circuit from the FACP is wired into NAC Control Input #1 of the
remote supply and then a pair of wires are connected from NAC Control Output #1 to
NAC Control Input #2. Refer to the FCPS-24(E) Installation, Operation and Applica-
tion Manual for a complete description and examples of applications.
16 50475 Rev D1 9/22/99 P/N 50475:D1
1.9 Telephone 1.9.1 Telephone Circuitry:
Requirements Ringer Equivalence Number (REN) = 0.6B

Description
iption
Complies with FCC Part 68
and Warnings Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes

Product Descr
The REN is used to determine the quantity of devices which may be connected to the
telephone line. Excessive REN's on the telephone line may result in the devices not
ringing in response to an incoming call. In most, but not all areas, the sum of the
REN's should not exceed five (5.0). To be certain of the number of devices that may
be connected to the line, as determined by the total REN's, contact the telephone
company to determine the maximum REN for the calling area.

1.9.2 Digital Communicator:


Before connecting the control panel to the public switched telephone network, the
installation of two RJ31X jacks is necessary. The following information is provided
if required by the local telephone company :

Manufacturer : Notifier
12 Clintonville Rd.
Northford, CT 06472

Product Model Number: SFP-1024


FCC Registration Number: 1W6USA-74525-AL-E
Ringer Equivalence: 0.6B

1.9.3 Telephone Company Rights and Warnings:

The telephone company under certain circumstances may temporarily discontinue


services and/or make changes in its facilities, services, equipment or procedures
which may affect the operation of this control panel. However, the telephone
company is required to give advance notice of such changes or interruptions.

If the control panel causes harm to the telephone network, the telephone company
reserves the right to temporarily discontinue service. Advance notification will be
provided except in cases when advance notice is not practical. In such cases,
notification will be provided as soon as possible. The opportunity will be given to
correct any problems and to file a complaint.

DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START,


OR PARTY LINE SERVICES.

50475 Rev D1 7/22/9 P/N 50475:D1


17
When the control panel activates, premise phones will be disconnected.
Product Descr

Two separate phone lines are required. Do not connect both telephone interfaces to
the same telephone line.

The control panel must be connected to the public switched telephone network
upstream of any private telephone system at the protected premises.
Description

An FCC compliant telephone cord must be used with this equipment. This
equipment is designed to be connected to the telephone network or premises wiring
using a compatible RJ31X male modular plug which is Part 68 compliant.
iption

1.9.4 For Canadian Applications

The following is excerpted from CP-01 Issue 5:


"NOTICE: The Canadian Department of Communications label identifies certified
equipment. This certification means that the equipment meets certain
telecommunications network protective, operational and safety requirements. The
Department does not guarantee the equipment will operate to the user's satisfaction.

Before installing this equipment, users should ensure that it is permissible to be


connected to the facilities of the local telecommunications company. The
equipment must also be installed using an acceptable method of connection. In
some cases, the company's inside wiring associated with a single line individual
service may be extended by means of a certified connector assembly (telephone
extension cord). The customer should be aware that compliance with the above
conditions may not prevent degradation of service in some situations.

Repairs to certified equipment should be made by an authorized Canadian


maintenance facility designated by the supplier. Any repairs or alterations made by
the user to this equipment, or equipment malfunctions, may give the
telecommunications company cause to request the user to disconnect the equipment.

Users should ensure for their own protection that the electrical ground connections
of the power utility, telephone lines and internal metallic water pipe system, if
present, are connected together. This precaution may be particularly important in
rural areas.

Caution: Users should not attempt to make such connections themselves, but should
contact the appropriate electric inspection authority, or electrician, as appropriate."

"The Load Number (LN) assigned to each terminal device denotes the percentage of
the total load to be connected to a telephone loop which is used by the device, to
prevent overloading. The termination on a loop may consist of any combination of
devices subject only to the requirement that the total of the Load Numbers of all the
devices does not exceed 100."

DOC Compliance - "This digital apparatus does not exceed the Class A limits for
radio noise emissions from digital apparatus set out in the Radio Interference
Regulations of the Canadian Department of Communications."

IC Registration Number: 21325785A


Load Number: 2

18 50475 Rev D1 9/22/99 P/N 50475:D1


2.0 Installation
2.1 General Mounting Options
The cabinet may be either semi-flush or surface
mounted. The door is removable during the
installation period by opening and lifting off the
hinges.

The cabinet mounts using two key slots and two


additional 0.250" diameter holes located in the

Installation
backbox. The key slots are located at the top
of the backbox and the two securing holes at
the bottom.

Carefully unpack the system and check for


shipping damage. Mount the cabinet in a
clean, dry, vibration-free area where extreme
temperatures are not encountered. The area
should be readily accessible with sufficient
room to easily install and maintain the panel.
Locate the top of the cabinet approximately
five feet above the floor with the hinge
mounting on the left. Determine the number of conductors required for the devices
to be installed. Sufficient knockouts are provided for wiring convenience. Select the
appropriate knockout(s) and pull the required conductors into the box. Note that
there are no knockouts on the left (hinged) side of the cabinet. All wiring should be
in accordance with the National and/or Local codes for fire alarm systems.

2.2 Backbox • Open the door and lift the door off the pin hinges.
Mounting • Remove the main PC board assembly by unscrewing the four screws in the
corners of the board. Set the board aside in a safe, clean place. Avoid static
discharge which may damage the board.
• Mark and predrill holes for the top two keyhole mounting bolts using the
dimensions shown.
• Install two upper fasteners in the wall with the screw heads protruding.
• Using the upper 'keyholes', mount the backbox over the two screws.
• Mark and drill the lower two holes.
• Mount backbox, install remaining fasteners and tighten.
• When the location is dry and free of construction dust, reinstall the main PC
board.

50475 Rev D1 7/22/9 P/N 50475:D1


19
Top
Installat ion

Left Side Right Side

Bottom

Draw wires through the respective knockout locations.

Figure 2-1: Cabinet Dimensions & Knockout Locations


20 50475 Rev D1 9/22/99 P/N 50475:D1
Installation

Notes:
1) Mount the FACP cabinet to the wall.
2) Remove knockouts on bottom of FACP cabinet and top of BB-17.
3) Using conduit, hang BB-17 from FACP cabinet making sure there is at
least 1/2" of clearance between the two cabinets.
4) Anchor BB-17 to wall.

Figure 2-2: FA CP Bac


FA kbo
Backbo
kboxx and Batter
Batteryy Box
Box
50475 Rev D1 7/22/9 P/N 50475:D1
21
2.3 Operating CAUTION: Several different sources of power can be connected to this panel.
Power Disconnect all sources of power before servicing. The panel and associated equipment
may be damaged by removing and/or inserting cards, modules, or interconnecting
cables while this unit is energized.

Primary Power Source (AC) and Earth Ground Connections


AC power connections are made inside the control panel cabinet. The primary power
source for the SFP-1024 is 120 VAC, 60 Hz, 2.3 amps and for the SFP-1024E is 220/
240 VAC, 50 Hz, 1.2 amps. Run a pair of wires (with ground conductor) from the
protected premises main breaker box to TB1 of the main circuit board. As per the
National Electric Code, use 14 AWG (1.6 mm O.D.) or heavier gauge wire with 600V
Installat ion

insulation. No other equipment may be connected to this circuit. In addition, this


circuit must be provided with overcurrent protection and may not contain any power
disconnect devices. A separate Earth Ground connection must be made to ensure
proper panel operation and lightning and transient protection. Connect the Earth
Ground wire (minimum 14 AWG) to one of the transformer mounting studs. Note: Do
not use conduit for the Earth Ground connection since this does not provide reliable
protection.

Secondary Power Source (Batteries)


Observe polarity when connecting the battery. Connect the battery cable to J1 on the
main circuit board using the plug-in connector and cable provided. The battery charger
is current limited and capable of recharging sealed lead acid type batteries. The charger
shuts off when the system is in alarm or if the battery voltage drops too low (below
17.4 VDC). See Appendix A for calculation of the correct battery rating. CAUTION:
Battery contains sulfuric acid which can cause severe burns to the skin and eyes, and
can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or
eyes with water for 15 minutes and seek immediate medical attention.
Connect Earth Ground Wire to
Transformer mounting stud

Figure 2-3: Oper ating P


Operating o w er Connections
Po
22 50475 Rev D1 9/22/99 P/N 50475:D1
DC Power Output Connections
All DC power outputs are power-limited
Nonresettable Power (500 mA) 4-Wire Smoke Detector Power (500 mA)
24 VDC filtered, regulated, non- 24 VDC filtered, regulated, resettable power
resettable power can be obtained for 4-wire smoke detectors can be obtained
from TB2 Terminals 1 (+) and 2 (-). from TB2 Terminals 3 (+) and 4 (-).

Installation
1 2 3 4
Figure 2-4: A uxiliar
Auxiliar
uxiliaryy Po w er Connections
Po

2.4 Input Circuits The control panel has 10 zone input circuits. The maximum loop resistance limit for
each is 100 ohms. All field wiring of each zone is supervised for opens and ground
faults. Both conditions are visually and audibly annunciated as well as
communicated to a Central Station.

Each zone is a Style B (Class B) Initiating Device Circuit (IDC) designed to accept
any Normally-Open contact device and conventional 2-wire, 24 volt smoke
detectors. Refer to Figure 2-5 for information on wiring Style B circuits. Use the
CAC-10F Option Module (refer to Figure 2-11) to convert all 10 circuits to Style D
(Class A). Each zone is power-limited to 7.26 mA in standby and 42 mA in alarm.

The zones may be programmed as shown below. The factory default is 2-wire smoke
detector for all zones.
• 2-wire Smoke Detector (factory default) • Reset
• Pull Station • Silence
• Normally-Open Contact Device(s) • Drill
• Supervisory • Acknowledge
• Supervisory, Auto-Resettable • Auto-resettable critical and
• Waterflow, silenceable noncritical process monitoring
• Waterflow, nonsilenceable • Critical and noncritical process
monitoring

A maximum of five waterflow devices may be used on any circuit programmed as a


waterflow zone per NFPA 72.

Four-wire smoke detectors may be connected to any zone. Resettable power is


provided via TB2 Terminals 3 and 4. Refer to the Notifier Device Compatibility
Document for a list of compatible smoke detectors.

It is allowable to mix an assortment of device types (ie, smoke detectors, heat


detectors, pull stations) on any zone. However, this is not recommended since
specific and detailed reports will not be possible (particularly critical when using
Contact ID format). For example, the report of general fire alarm versus pull station
fire alarm or smoke detector fire alarm could not be distinguished.

Note: Process monitoring refers to circuits which do not specifically tie into
elements of the fire system as defined by NFPA codes. With the exception of
burglary functions, process monitoring circuits could be used to monitor any nonfire
functions such as water temperature, room temperature, door open/closed, gas
leakage, chemical leakage, etc.
50475 Rev D1 7/22/9 P/N 50475:D1
23
Process Monitoring may be accomplished for Local, Remote and Central Station
type services in the following ways:

• Central and Remote Station


When a critical process is detected, the DACT will transmit the critical process
alarm to the Central or Remote Station.

• Local
When a critical process is detected, the relays (fail-safe) programmed to
transfer will deenergize. The ACM-8R Remote Relay Module can only be
used with noncritical process monitoring.
Installat ion

Style B (Class B) Initiating Device Circuit (Supervised and


power-limited). 4.7KΩ, 1/2-Watt Part# 71252 UL listed.

UL listed compatible 2--wire smoke detector UL listed compatible 2--wire smoke detector

Manual Pull Station Manual Pull Station

Heat Detector Heat Detector

Dummy Load all unused Circuits (Part# 71245)

Figure 2-5: Style B Initiating Device Circuit Connections


Device

24 50475 Rev D1 9/22/99 P/N 50475:D1


2.5 Output Circuits Telephone Circuits
Provision to connect to two independent telephone lines is available via two
telephone jacks labeled PH1 (Primary) and PH2 (Secondary). Telephone line
control/command is possible via double line seizure as well as usage of an RJ31X
style interconnection. See Figure 2-8.

Notification Appliance Circuits


The SFP-1024 provides two Notification Appliance Circuits standard as Style Y
(Class B). Each circuit is capable of 3.0 amps of current. Total current drawn from
these as well as other DC power outputs cannot exceed 6.0 amps. Circuits are
supervised and power-limited. Refer to the Notifier Device Compatibility Document

Installation
for a listing of compatible Notification Appliances.

All Notification Appliance Circuits may be programmed as follows:


• Silenceable • Non Silenceable
• Enabled/Disabled • Silence Inhibited
• Auto Silence, 5 to 30 minutes • March Time, Temporal or California rates

Style Y (Class B) Notification Appliance Circuit (Supervised


and power-limited). 4.7KΩ, 1/2-Watt Part# 71252 UL listed.

Polarized Bell Polarized Bell

Polarized Horn Polarized Horn

Polarized Horn Polarized Horn

Note: Notification Dummy Load all unused Circuits


Appliance Circuit polarity (Part# 71245)
shown in alarm state.

Figure 2-6: Notification Appliance Circuit Connections

Standard Relays
The control panel provides two Form-A relays rated for 2.0 amps @ 30VDC
(resistive). Two Form-C relays can be added by installing the optional NAC-REM
(NAC/Relay) module.

Note: Relay connections may be power-limited or nonpower-limited, provided that


0.25" spacing is maintained between conductors of power-limited and
nonpower-limited circuits.

Figure 2-7: Prog


Progrr ammab le Rela
ammable Relayy Ter minals
erminals
50475 Rev D1 7/22/9 P/N 50475:D1
25
2.6 Digital Two independent telephone lines can be connected to the control panel. Telephone
Communicator line control/command is made possible via double line seizure as well as usage of an
RJ31X style interconnection. Note: It is critical that the panel's digital
communicator be located as the first device on the incoming telephone circuit to
properly function.

The control panel's digital communicator is built into the main board. Connection
and wiring of two phone lines is required as shown below:

(Primary Lines) (Secondary Lines)


Incoming Telco Incoming Telco
Installat ion

Phone Lines Tip Green Wire Phone Lines

Green Wire Ring Red Wire


Tip Ring Ring
To premise phones To premise phones
Red Wire
Ring Tip Tip

Note: Shorting bars


inside RJ31-X Jack
removed during male
plug insertion

7 foot cables
(MCBL-7)
not supplied -
order separately

Primary Phone Line PH-1

Modular Secondary Phone Line PH-2


Female
Connectors

Male Plug Connectors

Figure 2-8 : Wiring Phone Jacks


26 50475 Rev D1 9/22/99 P/N 50475:D1
2.7 UL Power- Power-limited and nonpower-limited circuit wiring must remain separated in the
limited Wiring cabinet. All power-limited circuit wiring must remain at least 0.25" away from any
nonpower-limited circuit wiring. Furthermore, all power-limited and nonpower-
Requirements
limited circuit wiring must enter and exit the cabinet through different knockouts
and/or conduits. A typical wiring diagram for the SFP-1024 is shown below.

Power-limited
Circuit
Note that power-limited
wiring is connected to

Installation
terminal block below the Nonpower-limited Power-limited Circuits
installed circuit board Circuit

Power-limited
Circuit

AC Power

Figure 2-9 : Typical Wiring Diagram for UL Power-limited Requirements

50475 Rev D1 7/22/9 P/N 50475:D1


27
2.8 Optional Module CAC-10F - Class A Converter Module
Installation The CAC-10F Module can be used to convert the 10 Style B (Class B) Initiating
Device Circuits to 10 Style D (Class A) IDCs and the two Style Y (Class B)
Notification Appliance Circuits to two Style Z (Class A) NACs. J1 of the module
plugs into connector J10 of the SFP-1024, which is located at the top center of the
FACP main circuit board.

Install the two supplied metal standoffs in the holes (see Figure 2-10) on the main
circuit board. Carefully align the two connectors and press the CAC-10F module
securely into place. Make certain the pins are properly aligned to prevent bending or
breaking of any pins. Secure CAC-10F module to standoffs using the two supplied
Installat ion

screws. It is important that the supplied screw and washer be used to secure the
module to the metal standoff. This is necessary in order to help protect against
electrical transients.

metal standoff J1 - on back of module metal standoff

Figure 2-10 : Installation of CAC-10F Module

Wire the Style Z (Class A) Notification Appliance Circuits (NACs) using TB4 of the
SFP-1024 and TB1of the CAC-10F module. Wire the Style D (Class A) Initiating
Device Circuits (IDCs) using TB5 of the SFP-1024 and TB2 of the CAC-10F
module. Make certain to observe polarity when connecting the devices to the
circuits. The B+ and A+ terminals must comprise the feed and return for the positive
side of a device and the B- and A- terminals must comprise the feed and return for
the negative side of a device. To configure any of the zones for Class B when the
CAC-10F is installed, simply wire to the B+ and B- inputs on TB5 of the main circuit
board and install the EOL resistor across the end of the circuit. Do not wire to the
corresponding A+ and A- terminals on TB2 of the CAC-10F module. Refer to
Figures 2-10 and 2-11.

Note: All unused


terminals must be
jumpered. Jumper A+
to B+ and A- to B-.

Figure 2-11 : Wiring NACs and IDCs for Class A Operation


28 50475 Rev D1 9/22/99 P/N 50475:D1
NAC-REM - NAC/Relay Expander Module
The NAC-REM (NAC/Relay) Module can be used to add two Style Y (Class B) or
Style Z (Class A) NACs (1.5 amps max. each) and 2 Form-C relays to the SFP-1024.
Connector J1 of the NAC-REM module plugs into connector J7 which is located at
the top left corner of the SFP-1024 main circuit board.

Install the two supplied metal standoffs into the FACP main circuit board (see Figure
2-12). Ensure that the metal standoff is installed in the position indicated in the
illustration below. Carefully align the two connectors and press the NAC-REM
module securely into place. Make certain the pins are properly aligned to prevent
bending or breaking of any pins. It is important that the supplied screw and washer

Installation
be used to secure the module to the metal standoff. This is necessary in order to help
protect against electrical transients.

NAC #4

Style Y (Class B) Supervised and


power-limited. 4.7KΩ, 1/2-Watt
NAC #3 Part# 71252 UL listed.
Style Z (Class A) Supervised
and power-limited.

Metal Standoff

Figure 2-12 : Installation and Wiring of NAC-REM Module


50475 Rev D1 7/22/9 P/N 50475:D1
29
Printer Interface Module
A remote printer may be permanently or temporarily connected to provide a hard-
copy printout of normal current system status and activity, program entries, history
file, troubleshoot mode voltages, and walk-test data. The Printer Interface Module
Part Number PRT-24 provides an EIA-232 conversion to adapt to most 40 and 80
column printers.

CAUTION: DO NOT connect a printer to the Fire Alarm Control Communica-


tor if a ground fault exists on the panel. Circuit damage may result.

Installation
Installat ion

Remote printers require a separate external primary power. Also required is the
PRT-24 which includes the Printer Interface Module and a 6 foot interface cable
prewired to a DB25 connector. Connect the interface cable to the PRT-24 as shown
in Figure 2-13. Insert the two supplied standoffs into mounting holes near the J4
connector on the main board. Connect the Printer Interface board to J4 on the main
circuit board, press onto standoffs, and connect the attached cable to the serial EIA-
232 port on the printer. The printer may be placed a maximum of 50 feet from the
panel. Note that a ground fault may occur on the control panel when this connection
is made. For this reason, it is important that there be no preexisting ground fault on
the panel. For permanent printer connection, a ground fault is not allowed.

Printer Configuration
The PRT-24 is required. Also refer to the documentation supplied with your printer.
Set the printer’s options as listed in the table below. Baud rate is programmable to
2400, 4800 or 9600.

Typical Printer Settings

Under the MENU area:


COMMUNIC. SETUP:
DATA BITS: 7
PARITY: EVEN
STOP BIT: 1 STOP
BAUD RATE: MUST MATCH FACP SETTING

J1 located on back
of PRT-24 board

PRT-24 connection to main board DB-25P Front View

Figure 2-13: Remote Printer Connections


30 50475 Rev D1 9/22/99 P/N 50475:D1
LED-10IM - EIA-485 Interface Module
The LED-10IM Interface Module provides an EIA-485 port to support the LED-10N
Remote Annunciator, LDM Series Annunciator, AFM Series Annunciator and the
ACM-8R Relay Module. EIA-485 wiring is supervised for open circuits by this
module. The LED-10IM mounts to connector J6 in the upper right corner of the
main board.

Install the two supplied standoffs into the FACP main circuit board. Ensure that the
metal standoff is installed in the position indicated in Figure 2-14. Carefully align
the two connectors and press the LED-10IM module securely into place. Make
certain the pins are properly aligned to prevent bending or breaking of any pins. It is

Installation
important that the supplied screw and washer be used to secure the module to the
metal standoff. This is necessary in order to help protect against electrical transients.

Metal Standoff

Figure 2-14: LED-10IM Installation

LED-10N Remote LED Annunciator


The LED-10N Annunciator connects to the SFP-1024 via the LED-10IM interface
module. It is recommended that overall foil/braided-shielded twisted pair cable with
a maximum length of 6,000 feet @ 18 AWG be used. Regulated power can be
supplied by the SFP-1024 or a remote UL listed filtered, regulated power supply
such as the Notifier FCPS-24.

LED-10N Annunciator

- + EIA-485
7 6 5 4 3 2 1

Earth Ground
- 24 VDC
Earth + 24 VDC + 24 VDC
Ground
Shield LED-10IM
- 24 VDC

Figure 2-15: Wiring LED-10IM to LED-10N


50475 Rev D1 7/22/9 P/N 50475:D1
31
ACM-8R Remote Relay Module
The ACM-8R Module provides eight Form-C relays with contacts rated for 5 amps.
Relays can be assigned to each of the ten Initiating Device
Circuits (two ACM-8R relay modules are required). The
module is installed on the EIA-485 line using the LED-
10IM interface module. Communication wiring is
supervised by the FACP. Power for the module must be
power-limited. Refer to the ACM-8R Manual for UL
power-limited wiring requirements and switch SW4
receive/transmit selection option.
Installat ion

Removable terminal blocks are provided for ease of


installation and servicing. DIP switch SW3 allows
assignment of relays to FACP IDCs.

The ACM-8R module can be mounted remotely in an


ABS-8R annunciator surface-mount backbox. ABS-8R Enclosure

ACM-8R Address and SW3 DIP Switch Settings


Each of the ten SFP-1024 IDCs can be assigned to an ACM-8R relay. Two relay
modules are required, with both set to the same address. Use the decade rotary
switches to set the address (i.e. for address '01', position the first (left) switch so the
arrow points to '0' and the second (right) switch so the arrow points to '1'). Refer to
Programming Level 3, Annunciator Maximum Monitored Address (02-03).

To assign the first eight relays of the first ACM-8R Relay Module to FACP IDCs 1-
8, set ACM-8R SW3 DIP switches 2 and 5 ON and 1, 3, 4, 6, 7 and 8 OFF.

To assign the first two relays of the second ACM-8R Relay Module to FACP IDCs 9
and 10, set ACM-8R SW3 DIP switches 3 and 5 ON and 1, 2, 4, 6, 7 and 8 OFF.
ACM-8R

NO
C
NC

To Next Device
SW4 SW3

Left Right
Decade Decade
Power-limited 24VDC
Switch Switch

LED-10IM
Figure 2-16: Wiring LED-10IM to ACM-8R
32 50475 Rev D1 9/22/99 P/N 50475:D1
LDM-32 Lamp Driver Module
The Lamp Driver Module is used to provide an interface to a custom graphic
annunciator. LDM-32 has 32 alarm lamp/LED driver outputs which sink current to
system common (-) on activation. A single positive (+) voltage is required to supply
total operating power for all lamps or LEDs when all drivers are activated. The
LDM-32 provides a separate driver for system trouble and inputs for a local lamp
test switch. A maximum of 16 external control switches may be wired to the LDM-
32. DIP Switch SW3 is used to enable or disable the onboard piezo, enable remote
switch functions, select a flashing LED function for new alarms and troubles, and
other functions. A green ON LINE LED flashes to indicate ongoing
communications with the host FACP. The LDM-32 is supplied with four standoffs

Installation
and screws for mounting to a CHS-4L chassis or custom backbox.

The LDM-32 is installed on the EIA-485 line using the LED-10IM Interface Module.
Communications wiring is supervised by the FACP. Power for module must be
power-limited.

LDM-32 Switch Settings


Use the decade rotary switches to set the address (i.e. for address '02', position switch
SW1 (top) so the arrow points to '2' and switch SW2 (bottom) so the arrow points
'0').

To Next
Device

EIA-485
-

Power-limited
24 VDC Source LDM-32

LED-10IM

Figure 2-17: Wiring LED-10IM to LDM-32


50475 Rev D1 7/22/9 P/N 50475:D1
33
AFM-16ATX and AFM-16AT Annunciators
The Annunciator Fixed Modules-16ATX and 16AT each contain 16 red alarm and
16 yellow trouble LEDs, a system trouble LED, an ON LINE/POWER LED and a
local piezo sounder with switches for FACP Acknowledge, Silence, Reset and Drill.
The AFM-16ATX is fixed at address '1' and is installed on the EIA-485 line using
the LED-10IM Interface Module.

AFM-16A Annunciator
The Annunciator Fixed Module-16A has 16 red alarm LEDs. The annunciator
address is fixed at '1' and communication is via the EIA-485 line using the LED-
10IM Interface Module. The Local Silence/Acknowledge switch functions as local
Installat ion

lamp test and silence for annunciator piezo. LEDs include ON LINE/POWER and
System Trouble.

To Next Device

-
EIA-485
+

Power-limited
24 VDC Source

LED-10IM

Figure 2-18: Wiring LED-10IM to AFM-16ATX


34 50475 Rev D1 9/22/99 P/N 50475:D1
3.0 Prog
Progrramming Instr uctions
Instructions
This section describes programming the panel from the onboard keyboard or the
remote site upload/download software which allows programming the control panel
off premises.

Programming of the control panel is possible at any time except when an alarm
condition is present or during a fire drill.

The control panel has been designed for many different types of applications. After
examining your specific application, review the programming options and choose the
entries best suited for your system.

The control panel has a built-in intelligent programmer. All programming selections
are stored in nonvolatile Electrically-Erasable Programmable Read-Only Memory
(EEPROM). This ensures that the control panel will remember all entries made in

Progrr amming
programming mode even if both AC and battery power are removed. Invalid entries
cause a 'beep' from the onboard piezo sounder.

The user must program the primary and secondary phone numbers, account numbers
and 24 hour test report times for each Central Station account and the current time
and date. The control panel comes with factory chosen options/features already

Prog
programmed. Other options/features may be programmed if desired. If all factory
default settings are acceptable, programming is complete.

Successful entry into Program Mode from the keypad shuts off the fire protection and
places the panel into trouble. A 'system off normal' message is transmitted to the
central station. Programming via the PK-1024 upload/download software is
accomplished with the fire protection active/on.

3.1 Entering Program Mode is divided into four levels:


Program Mode
1. Main Panel Options
2. Event Codes/Transmission Formats
3. Option Module Selections
4. Upload/Download

Each option of the Program Mode is entered by keying in the program mode entry
7764
7764) and pressing the ENTER/STORE key.
code (7764

☛ 7764 spells PROG on a Touch-Tone® phone

If an incorrect key is entered, reenter the proper 4-digit code before pressing the
[ENTER/STORE] key

___7
__77 Note that as you enter information into the
_776 control panel, the digits will scroll across the
7764 display from right to left

You are allowed a pause of up to 10 seconds in between each number while entering
the code. After pressing the [ENTER/STORE] key, the control panel will be in
Program Mode and display P__1 P__1, with the 1 flashing. If the [ENTER/STORE] key
is pressed, (1) Main Panel Options will be selected for programming. If (2) Event
Codes/Transmission Formats, (3) Option Module Selections or (4) Upload/Download
is keyed in and then the [ENTER/STORE] key pressed, the corresponding level will
50475 Rev D1 7/22/9 P/N 50475:D1
35
be selected for programming. You are allowed up to ten minutes of idle time at this
point before starting your programming, otherwise the control panel will go back to
Normal Mode. You also have a maximum of 10 minutes between any key stroke.
All entries made prior to the 10 minute time-out are valid and are stored.

Once in any of the four options of the Programming Mode, the control panel will:
• Blink the trouble LED.
• Activate the trouble relay.
• Disable the Notification Appliance Circuit(s).
• Disable the alarm relay.
• The display shows: 00_F
• Ignore all other keys other than those mentioned in this section.
• Continue to communicate any events not previously acknowledged at a
Central Station prior to entering Programming Mode.

While in any of the four levels of Programming Mode, the first two locations on the
Prog
Progrr amming

left of the display represent the memory address and the last location (farthest right)
represents the contents of the memory address. The first address displayed is shown
below:
00_F
(address)(data)

3.2 Switch The Function of each switch in program mode is shown below:
Functions
No function in Program Mode

- Select operating mode


- Increment memory address
Address entry keys are 0 to 9

Data entry keys are 0 to 9 and


A to F {
Figure 3-1: Control Panel K
Panel e ypad
Ke
- Decrement memory address
- Once = First memory address
Twice = type any address
- Save data, go to next address

3.3 Program Options 1. Level One - Main Panel Options

Note: Location 56 is factory defaulted to = 0, Control Panel only. This keeps the
communicator off until location 56 is changed to: 1= panel/communicator. Once
location 56 is set to 1 and a valid phone number is entered, entry into the program
mode will cause transmission of the "System off Normal" report.

Primary Central Station phone number. (00-15)


The first sixteen addresses, 00-15, are factory set to 'F' (from 00_F to 15_F
15_F).
Programming is typically done as follows: If your phone # is 484-7161, type 4 ,
00_4, press [ENTER/STORE] to save the entry to memory and
the display will read 00_4
increment to the next address 01_F
01_F.

Enter the remaining numbers in their respective addresses as shown below:

4 8 4 7 1 6 1 F F F F F F F F F
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 .
36 50475 Rev D1 9/22/99 P/N 50475:D1
Valid entries for both the primary and secondary phone numbers are 0 - F with the
numeric digits as dialed numbers and hex digits representing the following functions:

• A= * on a Touchtone phone keypad


• B= # on a Touchtone phone keypad
• C= look for secondary dial tone for up to 2 seconds (then, dial anyway)
• D= 3-second pause
• E= 5-second pause
• F= end of phone number (Note: F must be entered)

Primary Central Station Number Communication Format. (16)


One location is needed to select the Communication Format to the primary phone number.
Address 16 is used for this purpose. The default (factory setting) for this address is 'E',
which is Contact ID Format. You may enter '0' through 'D' in place of the default, then
press [ENTER/STORE]
[ENTER/STORE]. Choose from the list of formats below:

0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK

Progrr amming
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK

Prog
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Contact ID, DTMF, 1400/2300 ACK
F: Future use
Note: Consult your Central Station for proper selection or consult our factory
representatives. For any format chosen, the control panel automatically programs all of
the event codes. See Tables 3-2 through 3-7.

Caution: Default entries for event codes (as shown in tables 3-2 through 3-7) are
programmed into memory each time address '16' is altered. Be certain to double check
entries after programming the zone functions, addresses 64 - 73. Program the format
first, then program the zone(s) function. Do not alter while the communicator is active.

Primary Central Station Number Account Code (17-20) Four locations at addresses
17-20 default to all '0's. Valid entries are (0-9 and A-F). The number of digits entered
must match the format selection. If programming '2, 3, 4, or 5' into address 16, enter 3
digits (location 20 is ignored). If programming '0, 1, 6, 7, 8, 9, A, B, C, D or E' into
address 16, enter 4 digits.

Primary Central Station Number 24 Hour Test Time (21-24).


Use military time when entering the 24 hour 'test' time. The 24 hour test report to
phone number 1 takes up four locations, from addresses 21-24. The default is 00:00
(12:00 midnight). The limits for each location are as follows: 21: enter 0, 1, 2; 22:
enter 0-9; 23 : enter 0-5; 24: enter 0-9. Note: Do not use A-F.

Primary Central Station Number 24/12/8/6 Hour Test Time Interval (25). The test
report sent to the Primary phone number may be sent every 6, 8, 12 or 24 hours. If the
message is to be sent every 24 hours, leave the factory default entry of zero. If other test
report times are needed, enter 1=12, 2=8 and 3=6.
50475 Rev D1 7/22/9 P/N 50475:D1
37
Secondary Central Station Phone Number (26-41). Programming is similar to program-
ming the primary phone number located at addresses 00 - 15. The defaults are also all 'F's.

F F F F F F F F F F F F F F F F
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 .

Secondary Central Station Number Communication Format (42). Programming is the


same as the primary number's Comm Format at address 16. Default entry is 'E', Contact ID
Format. Choose one entry from the list below:

0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK


1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
Prog
Progrr amming

5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK


6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Contact ID Format
F: Future use

Note: Consult your Central Station for proper selection or consult our factory
representatives. For any format chosen, the control panel automatically programs all of
the event codes. See Tables 3-2 through 3-7.

Caution: Default entries for event codes (as shown in tables 3-2 through 3-7) are
programmed into memory each time address '42' is altered. Be certain to double check
entries after programming the zone functions, addresses 64 - 73. Program the format first,
then program the zone(s) function. Do not alter entry while the communicator is active.

Secondary Central Station Number Account Code (43-46) is programmed in addresses


43 - 46 in the same manner as the primary phone number Account Code. Default entries
are all '0s'.
Secondary Central Station Number 24-Hour Test Time (47-50) is programmed in
addresses 47-50 in the same manner as the primary number 24-Hour Test Time. Default is
00:00 (12:00 midnight).
Secondary Central Station Number 24/12/8/6 Hour Test Time (51) The test message
sent to the Secondary phone number may be sent every 6, 8, 12 or 24 hours. If the message
is to be sent every 24 hours, leave the factory default entry of zero. If other test report
times are needed, enter 1=12, 2=8 and 3=6.

38 50475 Rev D1 9/22/99 P/N 50475:D1


Alarm Presignal (52) Alarm Presignal is used to delay Notification Appliance Circuit(s)
activation while allowing for visual verification by a person. Once a zone triggers an
alarm, the mainboard piezo and the annunciator piezo turn on steady, the alarm LEDs on
the FACP and annunciator pulse, the FACP display indicates the activated zone, the
annunciator zone LED pulses and the Notification Appliance Circuits are held off for 15
seconds. During this time, if the Silence or Acknowledge switch is pressed, the piezos are
silenced and the Notification Appliances may be held off for up to 3 minutes. (See Alarm
Presignal Delay Timer Address 53-55). After the programmed delay period, the
Notification Appliances will activate if the source of the alarm is not cleared. Presignal
does not function for zones defined as Waterflow, Supervisory, Process Monitoring or zones
defined as Remote Switches. Factory default is '0' for no alarm presignal. Enter '1' to select
alarm presignal. During alarm presignal, access to other modes is prevented and the
communicator will not transmit a signal to the central station signifying that the alarm
presignal sequence has been initiated..
CAUTION: ACM-8R relays will activate during the Alarm Presignal sequence.

Alarm Presignal Delay Timer (53-55) The alarm presignal timer is factory set to 120

Progrr amming
seconds (2 minutes), address 53=1, 54=2 and 55=0. The timer may be programmed from 0
to 179 seconds. Location 52 must be set to '1'.

Communicator/Fire Panel Selection (56) Leaving address 56 at '0' causes the control
panel to operate as a fire panel only. Selecting '1' will make it operate as a Fire panel/

Prog
communicator.

Backup Reporting (57) Leaving address 57 at '0' means that reports will be transmitted to
the secondary Central Station phone number only if attempts to communicate to the
primary Central Station phone number are unsuccessful. Programming a '1' causes all
reports to be transmitted to both the primary and secondary Central Station phone numbers.
Programming a '2' causes reports to go to the first available receiver.
Caution: Do not alter this entry while the communicator is active.

Touchtone/Rotary Select for Primary Phone(58) A '0' programmed in this address by the
factory triggers Touchtone dialing over the primary phone line. Select '1' for rotary dialing.

Make Break Ratio for Primary Phone (59) Use this address only if you have chosen '1'
for address 58. The make/break ratio is factory set to '0' which is 67/33, but may be
changed to '1' which is a 62/38 ratio.

Touchtone/Rotary Select for Secondary Phone (60) A '0' programmed in this address by
the factory triggers Touchtone dialing over the secondary phone line. Select '1' for rotary
dialing.

Make Break Ratio for Secondary Phone (61) Use this address only if you have chosen '1'
for address 60. The make/break ratio is factory set to '0' which is 67/33, but may be
changed to '1' which is a 62/38 ratio.

Address (62) Leave default of '0'.

Address (63) Leave default of '0'.

Zones 1-10 Function Selection (64-73) The ten zones on the control panel may be
programmed as shown in the following list. Program entries alter zone function, transmittal
priority and, as a result of altering the zone definition, the transmitted event code message
is automatically changed. Remote switch entries '9, A, B and C' cause the zone function to
be altered to match the FACP keypad entries. Initial closure (or shorting) of a switch
causes the switch function to occur. The switch must be returned to its normal position.

50475 Rev D1 7/22/9 P/N 50475:D1


39
Program Entry Function
0 Operates 2-wire smoke detectors
1 Pull Station
2 Normally-Open Contact Device (heat detector, 4-wire smoke, etc)
3 Supervisory
4 Supervisory, auto-resettable. Self restore function, is not latched by the
control panel.
5 Waterflow, silenceable. Silencing of Silenceable Notification Appliance
Circuits allowed.
6 Waterflow, nonsilenceable. Silencing of Silenceable Notification Appliance
Circuits not allowed. Must clear waterflow alarm condition and press reset
key.
7 Critical and noncritical process monitoring
8 Autoresettable process monitoring
9 Remote reset switch
A Remote silence switch
Prog
Progrr amming

B Remote acknowledge switch


C Remote manual evacuate (drill) switch
Note: For remote switch applications, use Notifier P/N: AKS-1 or equivalent
UL listed switch.

Zone 1 Function Selection (64)


Factory default for zone 1 is '0', 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-
Open contact device; '3' for Supervisory; '4' for Supervisory, auto resettable; '5' for Waterflow,
silenceable; '6' for Waterflow, nonsilenceable; '7' for critical and noncritical process monitoring;
'8' for autoresettable process monitoring; '9' for remote reset switch; 'A' for remote silence switch;
'B' for remote acknowledge switch; or 'C' for remote manual evacuate (drill) switch.

Zone 2 Function Selection (65)


Factory default for zone 2 is '0', 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-
Open contact device; '3' for Supervisory; '4' for Supervisory, auto resettable; '5' for Waterflow,
silenceable; '6' for Waterflow, nonsilenceable; '7' for critical and noncritical process monitoring;
'8' for autoresettable process monitoring; '9' for remote reset switch; 'A' for remote silence switch;
'B' for remote acknowledge switch; or 'C' for remote manual evacuate (drill) switch.

Zone 3 Function Selection (66)


Factory default for zone 3 is '0', 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-
Open contact device; '3' for Supervisory; '4' for Supervisory, auto resettable; '5' for Waterflow,
silenceable; '6' for Waterflow, nonsilenceable; '7' for critical and noncritical process monitoring;
'8' for autoresettable process monitoring; '9' for remote reset switch; 'A' for remote silence switch;
'B' for remote acknowledge switch; or 'C' for remote manual evacuate (drill) switch.

Zone 4 Function Selection (67)


Factory default for zone 4 is '0', 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-
Open contact device; '3' for Supervisory; '4' for Supervisory, auto resettable; '5' for Waterflow,
silenceable; '6' for Waterflow, nonsilenceable; '7' for critical and noncritical process monitoring;
'8' for autoresettable process monitoring; '9' for remote reset switch; 'A' for remote silence switch;
'B' for remote acknowledge switch; or 'C' for remote manual evacuate (drill) switch.

Zone 5 Function Selection (68)


Factory default for zone 5 is '0', 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-
Open contact device; '3' for Supervisory; '4' for Supervisory, auto resettable; '5' for Waterflow,
silenceable; '6' for Waterflow, nonsilenceable; '7' for critical and noncritical process monitoring;
'8' for autoresettable process monitoring; '9' for remote reset switch; 'A' for remote silence switch;
'B' for remote acknowledge switch; or 'C' for remote manual evacuate (drill) switch.

40 50475 Rev D1 9/22/99 P/N 50475:D1


Zone 6 Function Selection (69)
Factory default for zone 6 is '0', 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-
Open contact device; '3' for Supervisory; '4' for Supervisory, auto resettable; '5' for Waterflow,
silenceable; '6' for Waterflow, nonsilenceable; '7' for critical and noncritical process monitoring; '8'
for autoresettable process monitoring; '9' for remote reset switch; 'A' for remote silence switch; 'B'
for remote acknowledge switch; or 'C' for remote manual evacuate (drill) switch.

Zone 7 Function Selection (70)


Factory default for zone 7 is '0', 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-
Open contact device; '3' for Supervisory; '4' for Supervisory, auto resettable; '5' for Waterflow,
silenceable; '6' for Waterflow, nonsilenceable; '7' for critical and noncritical process monitoring; '8'
for autoresettable process monitoring; '9' for remote reset switch; 'A' for remote silence switch; 'B'
for remote acknowledge switch; or 'C' for remote manual evacuate (drill) switch.

Zone 8 Function Selection (71)


Factory default for zone 8 is '0', 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-
Open contact device; '3' for Supervisory; '4' for Supervisory, auto resettable; '5' for Waterflow,

Progrr amming
silenceable; '6' for Waterflow, nonsilenceable; '7' for critical and noncritical process monitoring; '8'
for autoresettable process monitoring; '9' for remote reset switch; 'A' for remote silence switch; 'B'
for remote acknowledge switch; or 'C' for remote manual evacuate (drill) switch.

Zone 9 Function Selection (72)

Prog
Factory default for zone 9 is '0', 2-wire smoke detector. Enter '1' for Pull Station; '2' for Normally-
Open contact device; '3' for Supervisory; '4' for Supervisory, auto resettable; '5' for Waterflow,
silenceable; '6' for Waterflow, nonsilenceable; '7' for critical and noncritical process monitoring; '8'
for autoresettable process monitoring; '9' for remote reset switch; 'A' for remote silence switch; 'B'
for remote acknowledge switch; or 'C' for remote manual evacuate (drill) switch.

Zone 10 Function Selection (73)


Factory default for zone 10 is '0', 2-wire smoke detector. Enter '1' for Pull Station; '2' for
Normally-Open contact device; '3' for Supervisory; '4' for Supervisory, auto resettable; '5' for
Waterflow, silenceable; '6' for Waterflow, nonsilenceable; '7' for critical and noncritical process
monitoring; '8' for autoresettable process monitoring; '9' for remote reset switch; 'A' for remote
silence switch; 'B' for remote acknowledge switch; or 'C' for remote manual evacuate (drill)
switch.

Note: Programming any zone to function as supervisory or supervisory auto-resettable will cause
the defaulted zone alarm event codes (note in Table 3-2) to be automatically changed. The
defaulted code of '1' is changed to '8' for formats 3+1 and 4+1 Standard and Expanded, 4+2
Expanded and 4+1 Express (refer to Tables 3-2 and 3-5). The defaulted codes of 11 through 1A
are changed to 81 through 8A accordingly for formats 4+2 Standard and 4+2 Express (refer to
Tables 3-3 and 3-6). Programming any zone to function as process monitoring (Zone Function
Selections 7 or 8) will cause the alarm event code to be automatically programmed as '0' or '00'
which disables the report. Be certain to reprogram the alarm event code for each process
monitoring zone. Restoral codes remain unchanged from factory defaults.

When using Contact ID Format, zone alarm and zone restoral event codes change automatically
as shown in Table 3-1. Be certain to reprogram alarm event codes when selecting process
monitoring functions. Zone fault and disable event codes may also be user reprogrammed (refer
to Appendix D).

Programming a zone as a remote switch causes no transmission of an alarm or alarm restoral


event code. The zone wiring continues to be supervised for opens whereas a short simulates
closure of a reset, silence, drill or acknowledge switch. Zone fault and zone restoral codes
continue to be transmitted.

50475 Rev D1 7/22/9 P/N 50475:D1


41
Zone Function Selection Function Zone Alarm/Restoral
Event Code

0 2-wire Smoke 111

1 Pull Station 11 5

2 N.O. Contact Device 110

3 Super visor y 200

4 Auto-resettable Super visory 200

5 Waterflow (Silenceable) 113

6 Waterflow (Nonsilenceable) 113

7 Process Monitoring 000*

8 Auto Process Monitoring 000*

9 Reset Switch N/A

A Silence N/A

B Acknowledge N/A

C Drill N/A

* Be certain to program appropriate process monitoring functions (refer to Appendix D).


Tab le 3-1: Ev
able ent Code Changes ffor
Event or ID Contact F or
For mat
ormat
Waterflow Retard Timer (74-75)
A delay may be added prior to declaring a Waterflow type of alarm. Delays up to 89
seconds are allowed. The default for addresses 74 and 75 are '00' (no additional
delay). Valid keys for 74 are 0-8 and for 75, 0-9. Program an entry into this address
only if entering a '5 or 6' in any of the addresses 64-73. Be careful to include any built
in delays of the waterflow device.
Prog
Progrr amming

Alarm Verification (76)


Alarm verification works only on zones programmed as 2-wire smoke detector zones.
After detecting an alarm, the panel removes power from all zones for 6 seconds,
resetting all 2-wire smoke detectors. Power is reapplied and a 12 second retard period
allows detectors to stabilize. During the retard/reset period of 18 seconds, subsequent
alarms by the same initiating zone are ignored. An alarm detected on any other 2-wire
detector zone during the retard period will cause immediate verified alarms. A
subsequent alarm on the initiating zone occurring within the confirmation time will
cause a verified alarm. Note
Note: Mixing devices on zones designated as 2-wire smoke
zones is not recommended. The communicator will not transmit a signal to the central
station signifying that alarm verification is in progress.

During the alarm verification period, access to other modes of operation is prevented.
ALARM VERIFICATION PERIOD
0 Sec. 6 Sec. 18 Sec. 120 Sec

Detector Alarm Verification RESET RETARD

CONFIRMATION TIME
Detector Zone Goes Into Alarm Alarm Ignored Control Panel Processes Alarm if Same Detector Zone is Still in Alarm

0 30 60 90 120
Different Detector Zone
Alarms Control Panel Immediately Processes Alarm

Figure 3-2: Ver ification Timing Diag


erification Diagrr am
Factory Default selection is no verification which is '0'. Entering a '1' enables
verification. Note: Consult local Authority Having Jurisdiction (AHJ) prior to
altering this address.
42 50475 Rev D1 9/22/99 P/N 50475:D1
AC Loss Reporting Delay (77) Enter a digit of 0 - 9 or A - F corresponding to the
number of hours to be delayed in reporting loss of AC power. Factory default is 6-
hour delay. 0=6 hours, 1=7 hours, 2=8 hours, 3=9, 4=10, 5=11, 6=12, 7=15, 8=16,
9=17, A=18, B=19, C=20, D=21, E=22, F=23.

Programmable Relay 1 (78)


Relay #1 on TB3 of the SFP-1024 main circuit board can be programmed to activate
for any one of seven FACP conditions. The factory default for address 78 is '0' for
activation on alarm. Program a '1' for supervisory, '2' for supervisory auto-resettable,
'3' for trouble, '4' for communication fail, '5' for process monitoring, and '6' for process
monitoring auto-resettable.

Programmable Relay 2 (79)


Relay #2 on TB3 of the SFP-1024 main circuit board can be programmed to activate
for any one of seven FACP conditions. The factory default for address 79 is '3' for
activation on trouble. Program a '0' for alarm, '1' for supervisory, '2' for supervisory
auto-resettable, '4' for communication fail, '5' for process monitoring and '6' for process

Progrr amming
monitoring auto-resettable.

Notification Appliance Circuit #1 Enable (80)


Notification Appliance Circuit #1 may be programmed as 0=silenceable,
1=nonsilenceable or 2=disabled. Factory default is '0', silenceable. Note: Consult

Prog
local Authority Having Jurisdiction (AHJ) prior to altering this address.

Silence Inhibit Notification Appliance Circuit #1 (81)


Setting address number 81 to '1' prohibits silencing of Notification Appliance Circuit
#1 for one minute. Factory default is zero, no silence inhibit of Notification Appliance
Circuit #1.

Auto Silence Notification Appliance Circuit #1 (82)


Notification Appliance Circuit #1 may be auto-silenced after a programmed time
interval between 5 and 30 minutes. Enter 1=5 minute autosilence, 2=10 minutes, 3=15
minutes, 4=20 minutes, 5=25 minutes and 6=30 minutes. The factory default is '0' for
no autosilence.

Coding, Notification Appliance Circuit #1 (83)


Coding of Notification Appliance Circuit #1 is selectable for 1=March Time (120ppm),
2=California (10 seconds on, 5 seconds off) or 3=Temporal (.5 seconds on, .5 seconds
off, .5 seconds on, .5 seconds off, .5 seconds on, 1.5 seconds off). Factory default is
'0', steady, no coding.

Notification Appliance Circuit #2 Enable (84)


Notification Appliance Circuit #2 may be programmed as 0=silenceable,
1=nonsilenceable or 2=disabled. Factory default is '0', silenceable. Note: Consult local
Authority Having Jurisdiction (AHJ) prior to altering this address.

Silence Inhibit Notification Appliance Circuit #2 (85)


Setting address number 85 equal to '1' prohibits silencing of Notification Appliance
Circuit #2 for one minute. Factory default is zero, no silence inhibit of Notification
Appliance Circuit #2.

Auto Silence Notification Appliance Circuit #2 (86)


Notification Appliance Circuit #2 may be auto-silenced after a programmed time
interval between 5 and 30 minutes. Enter 1=5 minute autosilence, 2=10 minutes, 3=15
minutes, 4=20 minutes, 5=25 minutes and 6=30 minutes. The factory default is '0' no
autosilence.

50475 Rev D1 7/22/9 P/N 50475:D1


43
Coding, Notification Appliance Circuit #2 (87)
Coding of Notification Appliance Circuit #2 is selectable for 1=March Time
(120ppm), 2=California (10 seconds on, 5 seconds off) or 3=Temporal (.5 seconds
on, .5 seconds off, .5 seconds on, .5 seconds off, .5 seconds on, 1.5 seconds off)
Factory default is '0', steady, no coding.

Trouble Reminder (88) Factory default '0' disables the trouble reminder feature.
Selecting '1' will cause a reminding beep (after the Silence or Acknowledge switch is
pressed) every 15 seconds during an alarm and beep every two minutes during a
trouble condition. The beeps from the on board piezo sounder will occur until the
alarm or fault is cleared.

Programming the Real-Time Clock and Calendar (89-999)


Entering an address greater than 88 will cause a display of the current time. On
initial power up, the clock will start running from the factory setting of 00:01
(military time). The far left digit will be flashing, indicating that this is the first digit
Prog
Progrr amming

to be programmed.

Hours/Minutes
Select a digit then press [ENTER/STORE]
[ENTER/STORE]. The digit 2nd from the left will start
flashing. Select a digit then press [ENTER/STORE]
[ENTER/STORE]. Hours setting is complete.
With the digit 2nd from the right flashing, select a digit then press [ENTER/
STORE]
STORE]. The digit on the far right will start flashing. Select a digit then press
[ENTER/STORE]
[ENTER/STORE]. Minutes setting is complete. Note: If an invalid digit is selected
(i.e. 3 or higher for the first digit) the FACP piezo will beep and the digit will
continue to blink until a valid entry is made.

Year
After entering the last digit corresponding to minutes (far right digit) the display will
read 1996 with the digit 9, second from the right, flashing. Press [ENTER/STORE]
if acceptable or any digit. Entering a zero (0) will change the display to the year
2000. Repeat for digit to far right.

Month/Day
After the year is entered the display will show four digits representing the month and
day of the software release date. The month is represented by the two digits on the
left and the day by the two digits on the right. The digit on the far left will be
flashing. The month and day are set the same way as the hours and minutes. Once
the last digit corresponding to the day is entered, the display will show the contents
of address '00'. The real time clock/calendar keeps track of leap years automatically.

Note that the software for the SFP-1024 operates the internal clock based upon 60
Hz. The software for the SFP-1024E operates the internal clock based upon 50 Hz.

End Programming/Exit to Alternate Program Level


Exit Programming Mode by pressing MODE
MODE, followed by the 4-digit code
corresponding to an alternate mode of operation, then press [ENTER/STORE]
[ENTER/STORE]. To
enter a different Programming Level, press MODE and then press the [ENTER/
STORE] key. The display will show P__1 with the '1' flashing. Press the digit (2, 3
or 4) of the Programming Level to be accessed.

During Program Mode, if no key is pressed within 10 minutes, the panel will revert
to normal mode.

44 50475 Rev D1 9/22/99 P/N 50475:D1


2. Level Two - Event Codes/Transmission Formats

Each option of the Program Mode is entered by keying in the program mode entry
7764
7764) and pressing the ENTER/STORE key.
code (7764

☛ 7764 spells PROG on a Touch-Tone® phone

If an incorrect key is entered, reenter the proper 4-digit code before pressing the
[ENTER/STORE] key.

You are allowed a pause of up to 10 seconds in between each number while entering
the code. After pressing the [ENTER/STORE] key, the control panel will be in
Program Mode and display P__1P__1, with the 1 flashing. Press 2 on the keypad and
then the [ENTER/STORE] key to select the Event Codes/Transmission Formats
Level for programming. You are allowed up to ten minutes of idle time at this point
before starting your programming, otherwise the control panel will go back to

Progrr amming
Normal Mode. You also have a maximum of 10 minutes between any key stroke.
All entries made prior to the 10 minute time-out are valid and are stored.

Upon entering the Event Codes/Transmission Formats Level in programming mode,


the following will be displayed on the FACP 7-Segment Display.

Prog
00_1
(address)(data)

The first three locations on the left of the display represent the memory address 00 of
the Format Chart previously selected in address 16 of the Main Panel Options section
of programming mode. The last location 1 (farthest right) represents the contents of
memory address (00) which is the format setting. The only value which can be
altered in the Format Charts is the setting which is the last digit to the right. To
change the value, key in the new digit.

Use the Up and Down Arrow keys to increment to the next address or decrement to
the previous address.

When desired changes have been completed, exit programming mode by pressing the
MODE key, followed by the four-digit code for an alternate mode and then the
[ENTER/STORE] key. To enter a different Programming Level, press MODE and
then press the [ENTER/STORE] key. The display will show P__2 with the '2'
flashing. Press the digit (1, 3 or 4) of the Programming Level to be accessed.

During Program Mode, if no key is pressed within 10 minutes, the panel will revert
to normal mode.

The Format Charts which may be selected in the Main Panel Options (Level 1)
section of the Programming Mode are shown on the following pages of this section.
Format charts for the Primary and Secondary Central Station Numbers are included.

50475 Rev D1 7/22/9 P/N 50475:D1


45
3+1, 4+1 Express, 4+1 Standard and Expanded, 4+2 Expanded Formats
If '0, 2, 3, 4, 5, 6, 7, 8, 9, B or D' are entered for address 16 in Program Mode Level
1, the following data is automatically programmed for the Primary Central Station
phone number event codes. Enter '0' for the setting to disable the report.

Address Description Setting


0 Primary # Zone 1 Alarm Code 11
1 Primary # Zone 2 Alarm Code 11
2 Primary # Zone 3 Alarm Code 11
3 Primary # Zone 4 Alarm Code 11
4 Primary # Zone 5 Alarm Code 11
5 Primary # Zone 6 Alarm Code 11
6 Primary # Zone 7 Alarm Code 11
7 Primary # Zone 8 Alarm Code 11
8 Primary # Zone 9 Alarm Code 11
9 Primary # Zone 10 Alarm Code 11
10 Primary # Zone 1 Disabled Code 4
11 Primary # Zone 2 Disabled Code 4
Prog
Progrr amming

12 Primary # Zone 3 Disabled Code 4


13 Primary # Zone 4 Disabled Code 4
14 Primary # Zone 5 Disabled Code 4
15 Primary # Zone 6 Disabled Code 4
16 Primary # Zone 7 Disabled Code 4
17 Primary # Zone 8 Disabled Code 4
18 Primary # Zone 9 Disabled Code 4
19 Primary # Zone 10 Disabled Code 4
20 Primary # Drill Code 9
21 Primary # AC Fault Code 9
22 Primary # Zone 1 Fault Code F
23 Primary # Zone 2 Fault Code F
24 Primary # Zone 3 Fault Code F
25 Primary # Zone 4 Fault Code F
26 Primary # Zone 5 Fault Code F
27 Primary # Zone 6 Fault Code F
28 Primary # Zone 7 Fault Code F
29 Primary # Zone 8 Fault Code F
30 Primary # Zone 9 Fault Code F
31 Primary # Zone 10 Fault Code F
32 Primary # Earth Fault Code 6
33 Primary # Low Battery Fault Code 6
34 Primary # No Battery Fault Code 6
35 Primary # Telco Pri. Line Fault Code 6
36 Primary # Telco Sec. Line Fault Code 6
37 Primary # NAC #1 Fault Code 6
38 Primary # NAC #2 Fault Code 6
39 Primary # NAC #3 Fault Code 6
40 Primary # NAC #4 Fault Code 6
41 Primary # NAC #1 Disable Code 4
42 Primary # NAC #2 Disable Code 4
43 Primary # NAC #3 Disable Code 4
44 Primary # NAC #4 Disable Code 4
45 Primary # Comm Trouble Pri. # Code 6
46 Primary # Comm Trouble Sec. # Code 6
47 Primary # Printer Fault Code 6
48 Primary # Annunciator Fault Code 6
49 Primary # 485 Comm. Trouble Code 6
50 Primary # System Off Normal Code 6
51 Primary # Zone 1 Alarm Restore Code E
52 Primary # Zone 2 Alarm Restore Code E
53 Primary # Zone 3 Alarm Restore Code E
54 Primary # Zone 4 Alarm Restore Code E
55 Primary # Zone 5 Alarm Restore Code E
56 Primary # Zone 6 Alarm Restore Code E
57 Primary # Zone 7 Alarm Restore Code E
58 Primary # Zone 8 Alarm Restore Code E
59 Primary # Zone 9 Alarm Restore Code E
60 Primary # Zone 10 Alarm Restore Code E

Tab le 3-2: Ev
able ent Codes
Event Codes,, Pr imar
Primar
imaryy Centr al Station Number
Central
46 50475 Rev D1 9/22/99 P/N 50475:D1
Address Description Setting
61 Primary # Zone 1 Disabled Restore Code 5
62 Primary # Zone 2 Disabled Restore Code 5
63 Primary # Zone 3 Disabled Restore Code 5
64 Primary # Zone 4 Disabled Restore Code 5
65 Primary # Zone 5 Disabled Restore Code 5
66 Primary # Zone 6 Disabled Restore Code 5
67 Primary # Zone 7 Disabled Restore Code 5
68 Primary # Zone 8 Disabled Restore Code 5
69 Primary # Zone 9 Disabled Restore Code 5
70 Primary # Zone 10 Disabled Restore Code 5
71 Primary # Drill Restore Code 9
72 Primary # AC Fault Restore Code 9
73 Primary # Zone 1 Fault Restore Code D
74 Primary # Zone 2 Fault Restore Code D
75 Primary # Zone 3 Fault Restore Code D
76 Primary # Zone 4 Fault Restore Code D
77 Primary # Zone 5 Fault Restore Code D

Progrr amming
78 Primary # Zone 6 Fault Restore Code D
79 Primary # Zone 7 Fault Restore Code D
80 Primary # Zone 8 Fault Restore Code D
81 Primary # Zone 9 Fault Restore Code D
82 Primary # Zone 10 Fault Restore Code D
83 Primary # Earth Fault Restore Code A
84 Primary # Low Battery Fault Restore Code A

Prog
85 Primary # No Battery Fault Restore Code A
86 Primary # Telco Pri. Line Fault Restore Code A
87 Primary # Telco Sec. Line Fault Restore Code A
88 Primary # NAC #1 Fault Restore Code A
89 Primary # NAC #2 Fault Restore Code A
90 Primary # NAC #3 Fault Restore Code A
91 Primary # NAC #4 Fault Restore Code A
92 Primary # NAC #1 Disable Restore Code 5
93 Primary # NAC #2 Disable Restore Code 5
94 Primary # NAC #3 Disable Restore Code 5
95 Primary # NAC #4 Disable Restore Code 5
96 Primary # Comm Trouble Pri. # Restore Code A
97 Primary # Comm Trouble Sec. # Restore Code A
98 Primary # Printer Fault Restore Code A
99 Primary # Annunciator Fault Restore Code A
100 Primary # 485 Comm. Trouble Restore Code A
101 Primary # System Off Normal Restore Code A
102 Primary # System Test Report 9
103 Primary # System Abnormal Test Report F
104 Primary # Request for Up/Download 7
105 Primary # Successful Upload 7
106 Primary # Successful Download 7
107 Primary # Failed Up/Download 7

Note: 1Zones programmed as supervisory alarm transmit as Code 8 instead of Code 1.

Tab le 3-2: Ev
able ent Codes
Event Codes,, Pr imar
Primar
imaryy Centr al Station Number (cont.)
Central

50475 Rev D1 7/22/9 P/N 50475:D1


47
4+2 Standard and 4+2 Express Format
If '1, A or C' are entered for address 16 in Program Mode Level 1, the following data is
automatically programmed for the Primary Central Station phone number event codes.
Enter '00' for the setting to disable the report.

Address Description Settings


0-1 Primary # Zone 1 Alarm Code 11 1
2-3 Primary # Zone 2 Alarm Code 12 1
4-5 Primary # Zone 3 Alarm Code 13 1
6-7 Primary # Zone 4 Alarm Code 14 1
8-9 Primary # Zone 5 Alarm Code 15 1
10 - 11 Primary # Zone 6 Alarm Code 16 1
12 - 13 Primary # Zone 7 Alarm Code 17 1
14 - 15 Primary # Zone 8 Alarm Code 18 1
16 - 17 Primary # Zone 9 Alarm Code 19 1
18 - 19 Primary # Zone 10 Alarm Code 1A 1
20 - 21 Primary # Zone 1 Disable Code 41
22 - 23 Primary # Zone 2 Disable Code 42
Prog
Progrr amming

24 - 25 Primary # Zone 3 Disable Code 43


26 - 27 Primary # Zone 4 Disable Code 44
28 - 29 Primary # Zone 5 Disable Code 45
30 - 31 Primary # Zone 6 Disable Code 46
32 - 33 Primary # Zone 7 Disable Code 47
34 - 35 Primary # Zone 8 Disable Code 48
36 - 37 Primary # Zone 9 Disable Code 49
38 - 39 Primary # Zone 10 Disable Code 4A
40 - 41 Primary # Drill Code 97
42 - 43 Primary # AC Fault Code 92
44 - 45 Primary # Zone 1 Fault Code F1
46 - 47 Primary # Zone 2 Fault Code F2
48 - 49 Primary # Zone 3 Fault Code F3
50 - 51 Primary # Zone 4 Fault Code F4
52 - 53 Primary # Zone 5 Fault Code F5
54 - 55 Primary # Zone 6 Fault Code F6
56 - 57 Primary # Zone 7 Fault Code F7
58 - 59 Primary # Zone 8 Fault Code F8
60 - 61 Primary # Zone 9 Fault Code F9
62 - 63 Primary # Zone 10 Fault Code FA
64 - 65 Primary # Earth Fault Code 61
66 - 67 Primary # Low Battery Fault Code 62
68 - 69 Primary # No Battery Fault Code 63
70 - 71 Primary # Telco Pri. Line Fault Code 64
72 - 73 Primary # Telco Sec. Line Fault Code 65
74 - 75 Primary # NAC #1 Fault Code 66
76 - 77 Primary # NAC #2 Fault Code 67
78 - 79 Primary # NAC #3 Fault Code 68
80 - 81 Primary # NAC #4 Fault Code 69
82 - 83 Primary # NAC #1 Disable Code 4B
84 - 85 Primary # NAC #2 Disable Code 4C
86 - 87 Primary # NAC #3 Disable Code 4D
88 - 89 Primary # NAC #4 Disable Code 4E
90 - 91 Primary # Comm Trouble Pri. # Code 6A
92 - 93 Primary # Comm Trouble Sec. # Code 6B
94 - 95 Primary # Printer Fault Code 6C
96 - 97 Primary # Annunciator Fault Code 6D
98 - 99 Primary # 485 Comm. Trouble Code 6E
100 - 101 Primary # System Off Normal Code 6F
102 - 103 Primary # Zone 1 Alarm Restore Code E1
104 - 105 Primary # Zone 2 Alarm Restore Code E2
106 - 107 Primary # Zone 3 Alarm Restore Code E3
108 - 109 Primary # Zone 4 Alarm Restore Code E4
110 - 111 Primary # Zone 5 Alarm Restore Code E5
112 - 113 Primary # Zone 6 Alarm Restore Code E6
114 - 115 Primary # Zone 7 Alarm Restore Code E7
116 - 117 Primary # Zone 8 Alarm Restore Code E8
118 - 119 Primary # Zone 9 Alarm Restore Code E9
120 - 121 Primary # Zone 10 Alarm Restore Code EA

Tab le 3-3: Ev
able ent Codes
Event Codes,, Pr imar
Primar
imaryy Centr al Station Number
Central
48 50475 Rev D1 9/22/99 P/N 50475:D1
Address Description Settings

122 - 123 Primary # Zone 1 Disable Restore Code 51


124 - 125 Primary # Zone 2 Disable Restore Code 52
126 - 127 Primary # Zone 3 Disable Restore Code 53
128 - 129 Primary # Zone 4 Disable Restore Code 54
130 - 131 Primary # Zone 5 Disable Restore Code 55
132 - 133 Primary # Zone 6 Disable Restore Code 56
134 - 135 Primary # Zone 7 Disable Restore Code 57
136 - 137 Primary # Zone 8 Disable Restore Code 58
138 - 139 Primary # Zone 9 Disable Restore Code 59
140 - 141 Primary # Zone 10 Disable Restore Code 5A
142 - 143 Primary # Drill Restore Code 98
144 - 145 Primary # AC Fault Restore Code 93
146 - 147 Primary # Zone 1 Fault Restore Code D1
148 - 149 Primary # Zone 2 Fault Restore Code D2
150 - 151 Primary # Zone 3 Fault Restore Code D3
152 - 153 Primary # Zone 4 Fault Restore Code D4
154 - 155 Primary # Zone 5 Fault Restore Code D5
156 - 157 Primary # Zone 6 Fault Restore Code D6

Progrr amming
158 - 159 Primary # Zone 7 Fault Restore Code D7
160 - 161 Primary # Zone 8 Fault Restore Code D8
162 - 163 Primary # Zone 9 Fault Restore Code D9
164 - 165 Primary # Zone 10 Fault Restore Code DA
166 - 167 Primary # Earth Fault Restore Code A1
168 - 169 Primary # Low Battery Fault Restore Code A2
170 - 171 Primary # No Battery Fault Restore Code A3

Prog
172 - 173 Primary # Telco Pri. Line Fault Restore Code A4
174 - 175 Primary # Telco Sec. Line Fault Restore Code A5
176 - 177 Primary # NAC #1 Fault Restore Code A6
178 - 179 Primary # NAC #2 Fault Restore Code A7
180 - 181 Primary # NAC #3 Fault Restore Code A8
182 - 183 Primary # NAC #4 Fault Restore Code A9
184 - 185 Primary # NAC #1 Disable Restore Code 5B
186 - 187 Primary # NAC #2 Disable Restore Code 5C
188 - 189 Primary # NAC #3 Disable Restore Code 5D
190 - 191 Primary # NAC #4 Disable Restore Code 5E
192 - 193 Primary # Comm Trouble Pri. # Restore Code AA
194 - 195 Primary # Comm Trouble Sec. # Restore Code AB
196 - 197 Primary # Printer Fault Restore Code AC
198 - 199 Primary # Annunciator Fault Restore Code AD
200 - 201 Primary # 485 Comm. Trouble Restore Code AE
202 - 203 Primary # System Off Normal Restore Code AF
204 - 205 Primary # System Test Report 99
206 - 207 Primary # System Abnormal Test Report 91
208 - 209 Primary # Request for Up/Download 71
210 - 211 Primary # Successful Upload 72
212 - 213 Primary # Successful Download 73
214 - 215 Primary # Failed Up/Download 74

Note: 1Zones programmed as supervisory alarm transmit as 81, 82, 83, 84, 85, 86, 87,
88, 89, 8A (instead of 11, 12, 13, 14, 15, 16, 17, 18, 19, 1A).

Tab le 3-3: Ev
able ent Codes
Event Codes,, Pr imar
Primar
imaryy Centr al Station Number (cont.)
Central

50475 Rev D1 7/22/9 P/N 50475:D1


49
Ademco Contact ID Format
If 'E' is entered for address 16 in Program Mode Level 1, the following data is
automatically programmed for the Primary Central Station phone number event codes.
Enter '000' for the setting to disable the report. The Setting entry is programmable, the
Zone Number cannot be changed. Restoral code settings match the settings shown with
the addition of an 'R' code transmitted. Refer to Appendix D for additional information.

Address Description Settings Zone Number


0-2 Primary # Zone 1 Alarm Code 111 1 001
3-5 Primary # Zone 2 Alarm Code 111 1 002
6-8 Primary # Zone 3 Alarm Code 111 1 003
9 - 11 Primary # Zone 4 Alarm Code 111 1 004
12 - 14 Primary # Zone 5 Alarm Code 111 1 005
15 - 17 Primary # Zone 6 Alarm Code 111 1 006
18 - 20 Primary # Zone 7 Alarm Code 111 1 007
21 - 23 Primary # Zone 8 Alarm Code 111 1 008
24 - 26 Primary # Zone 9 Alarm Code 111 1 009
Prog
Progrr amming

27 - 29 Primary # Zone 10 Alarm Code 111 1 010


30 - 32 Primary # Zone 1 Disable Code 570 001
33 - 35 Primary # Zone 2 Disable Code 570 002
36 - 38 Primary # Zone 3 Disable Code 570 003
39 - 41 Primary # Zone 4 Disable Code 570 004
42 - 44 Primary # Zone 5 Disable Code 570 005
45 - 47 Primary # Zone 6 Disable Code 570 006
48 - 50 Primary # Zone 7 Disable Code 570 007
51 - 53 Primary # Zone 8 Disable Code 570 008
54 - 56 Primary # Zone 9 Disable Code 570 009
57 - 59 Primary # Zone 10 Disable Code 570 010
60 - 62 Primary # Drill Code 604 000
63 - 65 Primary # AC Fault Code 301 000
66 - 68 Primary # Zone 1 Fault Code 380 001
69 - 71 Primary # Zone 2 Fault Code 380 002
72 - 74 Primary # Zone 3 Fault Code 380 003
75 - 77 Primary # Zone 4 Fault Code 380 004
78 - 80 Primary # Zone 5 Fault Code 380 005
81 - 83 Primary # Zone 6 Fault Code 380 006
84 - 86 Primary # Zone 7 Fault Code 380 007
87 - 89 Primary # Zone 8 Fault Code 380 008
90 - 92 Primary # Zone 9 Fault Code 380 009
93 - 95 Primary # Zone 10 Fault Code 380 010
96 - 98 Primary # Earth Fault Code 310 000
99 - 101 Primary # Low Battery Fault Code 302 000
102 - 104 Primary # No Battery Fault Code 311 000
105 - 107 Primary # Telco Pri. Line Fault Code 351 000
108 - 110 Primary # Telco Sec. Line Fault Code 352 000
111 - 113 Primary # NAC #1 Fault Code 321 001
114 - 116 Primary # NAC #2 Fault Code 322 002
117 - 119 Primary # NAC #3 Fault Code 326 003
120 - 122 Primary # NAC #4 Fault Code 327 004
123 - 125 Primary # NAC #1 Disable Code 521 001
126 - 128 Primary # NAC #2 Disable Code 522 002
129 - 131 Primary # NAC #3 Disable Code 526 003
132 - 134 Primary # NAC #4 Disable Code 527 004
135 - 137 Primary # Comm Trouble Pri. # Code 354 001
138 - 140 Primary # Comm Trouble Sec. # Code 354 002
141 - 143 Primary # Printer Fault Code 336 000
144 - 146 Primary # Annunciator Fault Code 330 001
147 - 149 Primary # 485 Comm. Trouble Code 330 002
150 - 152 Primary # System Off Normal Code 308 000
153 - 155 Primary # System Test Message 602 000
156 - 158 Primary # System Abnormal Test Message 608 000
159 - 161 Primary # Upload/Download Request Code 411 000
162 - 164 Primary # Upload Successful Code 416 000
165 - 167 Primary # Download Successful Code 412 000
168 - 170 Primary # Upload/Download Failed Code 413 000
Note: 1Refer to Table 3-1 for list of zone alarm event codes.
Tab le 3-4: Ev
able ent Codes
Event Codes,, Pr imar
Primar
imaryy Centr al Station Number
Central
50 50475 Rev D1 9/22/99 P/N 50475:D1
3+1, 4+1 Express, 4+1 Standard and Expanded, and 4+2 Expanded Formats
If '0, 2, 3, 4, 5, 6, 7, 8, 9, B or D' are entered for address 42 in Program Mode Level
1, the following is automatically programmed for the Secondary Central Station
phone number event codes. Enter '0' for the setting to disable the report.

Address Description Setting


216 Secondary # Zone 1 Alarm Code 11
217 Secondary # Zone 2 Alarm Code 11
218 Secondary # Zone 3 Alarm Code 11
219 Secondary # Zone 4 Alarm Code 11
220 Secondary # Zone 5 Alarm Code 11
221 Secondary # Zone 6 Alarm Code 11
222 Secondary # Zone 7 Alarm Code 11
223 Secondary # Zone 8 Alarm Code 11
224 Secondary # Zone 9 Alarm Code 11
225 Secondary # Zone 10 Alarm Code 11
226 Secondary # Zone 1 Disabled Code 4
227 Secondary # Zone 2 Disabled Code 4

Progrr amming
228 Secondary # Zone 3 Disabled Code 4
229 Secondary # Zone 4 Disabled Code 4
230 Secondary # Zone 5 Disabled Code 4
231 Secondary # Zone 6 Disabled Code 4
232 Secondary # Zone 7 Disabled Code 4
233 Secondary # Zone 8 Disabled Code 4
234 Secondary # Zone 9 Disabled Code 4

Prog
235 Secondary # Zone 10 Disabled Code 4
236 Secondary # Drill Code 9
237 Secondary # AC Fault Code 9
238 Secondary # Zone 1 Fault Code F
239 Secondary # Zone 2 Fault Code F
240 Secondary # Zone 3 Fault Code F
241 Secondary # Zone 4 Fault Code F
242 Secondary # Zone 5 Fault Code F
243 Secondary # Zone 6 Fault Code F
244 Secondary # Zone 7 Fault Code F
245 Secondary # Zone 8 Fault Code F
246 Secondary # Zone 9 Fault Code F
247 Secondary # Zone 10 Fault Code F
248 Secondary # Earth Fault Code 6
249 Secondary # Low Battery Fault Code 6
250 Secondary # No Battery Fault Code 6
251 Secondary # Telco Pri. Line Fault Code 6
252 Secondary # Telco Sec. Line Fault Code 6
253 Secondary # NAC #1 Fault Code 6
254 Secondary # NAC #2 Fault Code 6
255 Secondary # NAC #3 Fault Code 6
256 Secondary # NAC #4 Fault Code 6
257 Secondary # NAC #1 Disable Code 4
258 Secondary # NAC #2 Disable Code 4
259 Secondary # NAC #3 Disable Code 4
260 Secondary # NAC #4 Disable Code 4
261 Secondary # Comm Trouble Pri. # Code 6
262 Secondary # Comm Trouble Sec. # Code 6
263 Secondary # Printer Fault Code 6
264 Secondary # Annunciator Fault Code 6
265 Secondary # 485 Comm. Trouble Code 6
266 Secondary # System Off Normal Code 6
267 Secondary # Zone 1 Alarm Restore Code E
268 Secondary # Zone 2 Alarm Restore Code E
269 Secondary # Zone 3 Alarm Restore Code E
270 Secondary # Zone 4 Alarm Restore Code E
271 Secondary # Zone 5 Alarm Restore Code E
272 Secondary # Zone 6 Alarm Restore Code E
273 Secondary # Zone 7 Alarm Restore Code E
274 Secondary # Zone 8 Alarm Restore Code E
275 Secondary # Zone 9 Alarm Restore Code E
276 Secondary # Zone 10 Alarm Restore Code E

Tab le 3-5: Ev
able ent Codes
Event Codes,, Secondar
Secondaryy Centr al Station Number
Central
50475 Rev D1 7/22/9 P/N 50475:D1
51
Address Description Setting
277 Secondary # Zone 1 Disabled Restore Code 5
278 Secondary # Zone 2 Disabled Restore Code 5
279 Secondary # Zone 3 Disabled Restore Code 5
280 Secondary # Zone 4 Disabled Restore Code 5
281 Secondary # Zone 5 Disabled Restore Code 5
282 Secondary # Zone 6 Disabled Restore Code 5
283 Secondary # Zone 7 Disabled Restore Code 5
284 Secondary # Zone 8 Disabled Restore Code 5
285 Secondary # Zone 9 Disabled Restore Code 5
286 Secondary # Zone 10 Disabled Restore Code 5
287 Secondary # Drill Restore Code 9
288 Secondary # AC Fault Restore Code 9
289 Secondary # Zone 1 Fault Restore Code D
290 Secondary # Zone 2 Fault Restore Code D
291 Secondary # Zone 3 Fault Restore Code D
292 Secondary # Zone 4 Fault Restore Code D
293 Secondary # Zone 5 Fault Restore Code D
294 Secondary # Zone 6 Fault Restore Code D
Prog
Progrr amming

295 Secondary # Zone 7 Fault Restore Code D


296 Secondary # Zone 8 Fault Restore Code D
297 Secondary # Zone 9 Fault Restore Code D
298 Secondary # Zone 10 Fault Restore Code D
299 Secondary # Earth Fault Restore Code A
300 Secondary # Low Battery Fault Restore Code A
301 Secondary # No Battery Fault Restore Code A
302 Secondary # Telco Pri. Line Fault Restore Code A
303 Secondary # Telco Sec. Line Fault Restore Code A
304 Secondary # NAC #1 Fault Restore Code A
305 Secondary # NAC #2 Fault Restore Code A
306 Secondary # NAC #3 Fault Restore Code A
307 Secondary # NAC #4 Fault Restore Code A
308 Secondary # NAC #1 Disable Restore Code 5
309 Secondary # NAC #2 Disable Restore Code 5
310 Secondary # NAC #3 Disable Restore Code 5
311 Secondary # NAC #4 Disable Restore Code 5
312 Secondary # Comm Trouble Pri. # Restore Code A
313 Secondary # Comm Trouble Sec. # Restore Code A
314 Secondary # Printer Fault Restore Code A
315 Secondary # Annunciator Fault Restore Code A
316 Secondary # 485 Comm. Trouble Restore Code A
317 Secondary # System Off Normal Restore Code A
318 Secondary # System Test Report 9
319 Secondary # System Abnormal Test Report F
320 Secondary # Request for Up/Download 7
321 Secondary # Successful Upload 7
322 Secondary # Successful Download 7
323 Secondary # Failed Up/Download 7

Note: 1Zones programmed as supervisory alarm transmit as Code 8 instead of Code 1.

Tab le 3-5: Ev
able ent Codes
Event Codes,, Secondar
Secondaryy Centr al Station Number (cont.)
Central

52 50475 Rev D1 9/22/99 P/N 50475:D1


4+2 Standard and 4+2 Express Formats
If '1, A or C' are entered for address 42 in Program Mode Level 1, the following is
automatically programmed for the Secondary Central Station phone number event
codes. Enter '00' for the setting to disable the report.

Address Description Setting


216 - 217 Secondary # Zone 1 Alarm Code 111
218 - 219 Secondary # Zone 2 Alarm Code 121
220 - 221 Secondary # Zone 3 Alarm Code 131
222 - 223 Secondary # Zone 4 Alarm Code 141
224 - 225 Secondary # Zone 5 Alarm Code 151
226 - 227 Secondary # Zone 6 Alarm Code 161
228 - 229 Secondary # Zone 7 Alarm Code 171
230 - 231 Secondary # Zone 8 Alarm Code 181
232 - 233 Secondary # Zone 9 Alarm Code 191
234 - 235 Secondary # Zone 10 Alarm Code 1A1
236 - 237 Secondary # Zone 1 Disable Code 41
238 - 239 Secondary # Zone 2 Disable Code 42
240 - 241 Secondary # Zone 3 Disable Code 43

Progrr amming
242 - 243 Secondary # Zone 4 Disable Code 44
244 - 245 Secondary # Zone 5 Disable Code 45
246 - 247 Secondary # Zone 6 Disable Code 46
248 - 249 Secondary # Zone 7 Disable Code 47
250 - 251 Secondary # Zone 8 Disable Code 48
252 - 253 Secondary # Zone 9 Disable Code 49
254 - 255 Secondary # Zone 10 Disable Code 4A

Prog
256 - 257 Secondary # Drill Code 97
258 - 259 Secondary # AC Fault Code 92
260 - 261 Secondary # Zone 1 Fault Code F1
262 - 263 Secondary # Zone 2 Fault Code F2
264 - 265 Secondary # Zone 3 Fault Code F3
266 - 267 Secondary # Zone 4 Fault Code F4
268 - 269 Secondary # Zone 5 Fault Code F5
270 - 271 Secondary # Zone 6 Fault Code F6
272 - 273 Secondary # Zone 7 Fault Code F7
274 - 275 Secondary # Zone 8 Fault Code F8
276 - 277 Secondary # Zone 9 Fault Code F9
278 - 279 Secondary # Zone 10 Fault Code FA
280 - 281 Secondary # Earth Fault Code 61
282 - 283 Secondary # Low Battery Fault Code 62
284 - 285 Secondary # No Battery Fault Code 63
286 - 287 Secondary # Telco Pri. Line Fault Code 64
288 - 289 Secondary # Telco Sec. Line Fault Code 65
290 - 291 Secondary # NAC #1 Fault Code 66
292 - 293 Secondary # NAC #2 Fault Code 67
294 - 295 Secondary # NAC #3 Fault Code 68
296 - 297 Secondary # NAC #4 Fault Code 69
298 - 299 Secondary # NAC #1 Disable Code 4B
300 - 301 Secondary # NAC #2 Disable Code 4C
302 - 303 Secondary # NAC #3 Disable Code 4D
304 - 305 Secondary # NAC #4 Disable Code 4E
306 - 307 Secondary # Comm Trouble Pri. # Code 6A
308 - 309 Secondary # Comm Trouble Sec. # Code 6B
310 - 311 Secondary # Printer Fault Code 6C
312 - 313 Secondary # Annunciator Fault Code 6D
314 - 315 Secondary # 485 Comm. Trouble Code 6E
316 - 317 Secondary # System Off Normal Code 6F
318 - 319 Secondary # Zone 1 Alarm Restore Code E1
320 - 321 Secondary # Zone 2 Alarm Restore Code E2
322 - 323 Secondary # Zone 3 Alarm Restore Code E3
324 - 325 Secondary # Zone 4 Alarm Restore Code E4
326 - 327 Secondary # Zone 5 Alarm Restore Code E5
328 - 329 Secondary # Zone 6 Alarm Restore Code E6
330 - 331 Secondary # Zone 7 Alarm Restore Code E7
332 - 333 Secondary # Zone 8 Alarm Restore Code E8
334 - 335 Secondary # Zone 9 Alarm Restore Code E9
336 - 337 Secondary # Zone 10 Alarm Restore Code EA

Tab le 3-6: Ev
able ent Codes
Event Codes,, Secondar
Secondaryy Centr al Station Number
Central
50475 Rev D1 7/22/9 P/N 50475:D1
53
Address Description Setting
338 - 339 Secondary # Zone 1 Disable Restore Code 51
340 - 341 Secondary # Zone 2 Disable Restore Code 52
342 - 343 Secondary # Zone 3 Disable Restore Code 53
344 - 345 Secondary # Zone 4 Disable Restore Code 54
346 - 347 Secondary # Zone 5 Disable Restore Code 55
348 - 349 Secondary # Zone 6 Disable Restore Code 56
350 - 351 Secondary # Zone 7 Disable Restore Code 57
352 - 353 Secondary # Zone 8 Disable Restore Code 58
354 - 355 Secondary # Zone 9 Disable Restore Code 59
356 - 357 Secondary # Zone 10 Disable Restore Code 5A
358 - 359 Secondary # Drill Restore Code 98
360 - 361 Secondary # AC Fault Restore Code 93
362 - 363 Secondary # Zone 1 Fault Restore Code D1
364 - 365 Secondary # Zone 2 Fault Restore Code D2
366 - 367 Secondary # Zone 3 Fault Restore Code D3
368 - 369 Secondary # Zone 4 Fault Restore Code D4
370 - 371 Secondary # Zone 5 Fault Restore Code D5
372 - 373 Secondary # Zone 6 Fault Restore Code D6
Prog
Progrr amming

374 - 375 Secondary # Zone 7 Fault Restore Code D7


376 - 377 Secondary # Zone 8 Fault Restore Code D8
378 - 379 Secondary # Zone 9 Fault Restore Code D9
380 - 381 Secondary # Zone 10 Fault Restore Code DA
382 - 383 Secondary # Earth Fault Restore Code A1
384 - 385 Secondary # Low Battery Fault Restore Code A2
386 - 387 Secondary # No Battery Fault Restore Code A3
388 - 389 Secondary # Telco Pri. Line Fault Restore Code A4
390 - 391 Secondary # Telco Sec. Line Fault Restore Code A5
392 - 393 Secondary # NAC #1 Fault Restore Code A6
394 - 395 Secondary # NAC #2 Fault Restore Code A7
396 - 397 Secondary # NAC #3 Fault Restore Code A8
398 - 399 Secondary # NAC #4 Fault Restore Code A9
400 - 401 Secondary # NAC #1 Disable Restore Code 5B
402 - 403 Secondary # NAC #2 Disable Restore Code 5C
404 - 405 Secondary # NAC #3 Disable Restore Code 5D
406 - 407 Secondary # NAC #4 Disable Restore Code 5E
408 - 409 Secondary # Comm Trouble Pri. # Restore Code AA
410 - 411 Secondary # Comm Trouble Sec. # Restore Code AB
412 - 413 Secondary # Printer Fault Restore Code AC
414 - 415 Secondary # Annunciator Fault Restore Code AD
416 - 417 Secondary # 485 Comm. Trouble Restore Code AE
418 - 419 Secondary # System Off Normal Restore Code AF
420 - 421 Secondary # System Test Report 99
422 - 423 Secondary # System Abnormal Test Report 91
424 - 425 Secondary # Request for Up/Download 71
426 - 427 Secondary # Successful Upload 72
428 - 429 Secondary # Successful Download 73
430 - 431 Secondary # Failed Up/Download 74

Note: 1Zones programmed as supervisory alarm transmit as 81, 82, 83, 84, 85, 86, 87,
88, 89, 8A.

Tab le 3-6: Ev
able ent Codes
Event Codes,, Secondar
Secondaryy Centr al Station Number (cont.)
Central

54 50475 Rev D1 9/22/99 P/N 50475:D1


Ademco Contact ID Format
If 'E' is entered for address 42 in Program Mode Level 1, the following data is
automatically programmed for the Secondary Central Station phone number event codes.
Enter '000' for the setting to disable the report. The Setting entries are programmable, the
Zone Number cannot be changed. Restoral code settings match the settings shown with
the addition of an 'R' code transmitted. Refer to Appendix D for additional information.
Address Description Settings Zone Number

216 - 218 Secondary # Zone 1 Alarm Code 1111 001


219 - 221 Secondary # Zone 2 Alarm Code 1111 002
222 - 224 Secondary # Zone 3 Alarm Code 1111 003
225 - 227 Secondary # Zone 4 Alarm Code 1111 004
228 - 230 Secondary # Zone 5 Alarm Code 1111 005
231 - 233 Secondary # Zone 6 Alarm Code 1111 006
234 - 236 Secondary # Zone 7 Alarm Code 1111 007
237 - 239 Secondary # Zone 8 Alarm Code 1111 008
240 - 242 Secondary # Zone 9 Alarm Code 1111 009
243 - 245 Secondary # Zone 10 Alarm Code 1111 010

Progrr amming
246 - 248 Secondary # Zone 1 Disable Code 570 001
249 - 251 Secondary # Zone 2 Disable Code 570 002
252 - 254 Secondary # Zone 3 Disable Code 570 003
255 - 257 Secondary # Zone 4 Disable Code 570 004
258 - 260 Secondary # Zone 5 Disable Code 570 005
261 - 263 Secondary # Zone 6 Disable Code 570 006
264 - 266 Secondary # Zone 7 Disable Code 570 007

Prog
267 - 269 Secondary # Zone 8 Disable Code 570 008
270 - 272 Secondary # Zone 9 Disable Code 570 009
273 - 275 Secondary # Zone 10 Disable Code 570 010
276 - 278 Secondary # Drill Code 604 000
279 - 281 Secondary # AC Fault Code 301 000
282- 284 Secondary # Zone 1 Fault Code 380 001
285 - 287 Secondary # Zone 2 Fault Code 380 002
288 - 290 Secondary # Zone 3 Fault Code 380 003
291 - 293 Secondary # Zone 4 Fault Code 380 004
294 - 296 Secondary # Zone 5 Fault Code 380 005
297 - 299 Secondary # Zone 6 Fault Code 380 006
300 - 302 Secondary # Zone 7 Fault Code 380 007
303 - 305 Secondary # Zone 8 Fault Code 380 008
306 - 308 Secondary # Zone 9 Fault Code 380 009
309 - 311 Secondary # Zone 10 Fault Code 380 010
312 - 314 Secondary # Earth Fault Code 310 000
315 - 317 Secondary # Low Battery Fault Code 302 000
318 - 320 Secondary # No Battery Fault Code 311 000
321 - 323 Secondary # Telco Pri. Line Fault Code 351 000
324 - 326 Secondary # Telco Sec. Line Fault Code 352 000
327 - 329 Secondary # NAC #1 Fault Code 321 001
330 - 332 Secondary # NAC #2 Fault Code 322 002
333 - 335 Secondary # NAC #3 Fault Code 326 003
336 - 338 Secondary # NAC #4 Fault Code 327 004
339 - 341 Secondary # NAC #1 Disable Code 521 001
342 - 344 Secondary # NAC #2 Disable Code 522 002
345 - 347 Secondary # NAC #3 Disable Code 526 003
348 - 350 Secondary # NAC #4 Disable Code 527 004
351 - 353 Secondary # Comm Trouble Pri. # Code 354 001
354 - 356 Secondary # Comm Trouble Sec. # Code 354 002
357 - 359 Secondary # Printer Fault Code 336 000
360 - 362 Secondary # Annunciator Fault Code 330 001
363 - 365 Secondary # 485 Comm. Trouble Code 330 002
366 - 368 Secondary # System Off Normal Code 308 000
369 - 371 Secondary # System Test Message 602 000
372 - 374 Secondary # System Abnormal Test Message 608 000
375 - 377 Secondary # Upload/Download Request Code 411 000
378 - 380 Secondary # Upload Successful Code 416 000
381 - 383 Secondary # Download Successful Code 412 000
384 - 386 Secondary # Upload/Download Failed Code 413 000
Note: 1Refer to Table 3-1 for list of zone alarm event codes.
Tab le 3-7: Ev
able ent Codes
Event Codes,, Secondar
Secondaryy Centr al Station Number
Central
50475 Rev D1 7/22/9 P/N 50475:D1
55
3. Level Three - Option Module Selections

Each option of the Program Mode is entered by keying in the program mode entry
7764
7764) and pressing the ENTER/STORE key.
code (7764

☛ 7764 spells PROG on a Touch-Tone® phone

If an incorrect key is entered, reenter the proper 4-digit code before pressing the
[ENTER/STORE] key.

You are allowed a pause of up to 10 seconds in between each number while entering
the code. After pressing the [ENTER/STORE] key, the control panel will be in
Program Mode and display P__1P__1, with the 1 flashing. Press 3 on the keypad and
then the [ENTER/STORE] key to choose the Option Module Selections. You are
allowed up to ten minutes of idle time at this point before starting your
Prog
Progrr amming

programming, otherwise the control panel will go back to Normal Mode. You also
have a maximum of 10 minutes between any key stroke. All entries made prior to
the 10 minute time-out are valid and are stored.

Upon entering the Option Modules Selections in programming mode, the following
will be displayed on the FACP Seven-Segment LED Display.
00_0
(address)(data)

The first two locations on the left of the display represent the memory address 00 of
the first Option Module (CAC-10F Converter Card). The last location 0 (farthest
right) represents the contents of memory address 00 which indicates that the card is
not installed. To install the card, press 1 on the keypad.

Use the Up and Down Arrow keys to increment to the next address or decrement to
the previous address.

When desired changes have been completed, exit programming mode by pressing the
MODE key, followed by the four-digit code for an alternate mode and then the
[ENTER/STORE] key. To enter a different Programming Level, press MODE and
then press the [ENTER/STORE] key. The display will show P__3 with the '3'
flashing. Press the digit (1, 2 or 4) of the Programming Level to be accessed.

During Program Mode, if no key is pressed within 10 minutes, the panel will revert
to normal mode.

Following are the various option modules and their addresses.

CAC-10F Class A Converter Card (00)


The factory default entry of '0' in address 00 informs the FACP that there is no CAC-
10F Class A Converter Card installed in the panel. When a CAC-10F is installed, '1'
must be entered for this address.

LED-10IM EIA-485 Interface Module (01)


The factory default entry of '0' indicates to the panel that an LED-10IM is not
installed. Enter a '1' in address 01 if an LED-10IM EIA-485 Interface Module is
installed.

56 50475 Rev D1 9/22/99 P/N 50475:D1


Annunciator Maximum Monitored Address (02-03)
Annunciator addresses may be set from a value of '01' up through '32'. Enter the
value of the highest or maximum address value selected on any annunciator or
ACM-8R connected to the EIA-485 port off of the LED-10IM module.

Devices which may be connected to the EIA-485 port include LDM graphic
annunciators, AFM LED type annunciators, LED-10N LED type annunciators and
ACM-8R relay modules. Included on the LDM, LED-10N and ACM-8R are
switches which select an address from 01 to 32. For each device added or connected
to the EIA-485 port via the LED-10IM select an address on each, with the exception
of the ACM-8R (refer to the applications section of the ACM-8R Manual P/N
50362). Addresses must be sequential with no gaps allowed. For example, if 13
devices are connected to the EIA-485 port, the maximum monitored address value
entered into locations 02-03 must be 02 = '1' and 03 = '3'. If 25 devices are
connected to the EIA-485 port, the maximum monitored address entered into
locations 02-03 must be 02 = '2' and 03 = '5'.

Progrr amming
All devices connected to the EIA-485 are fully supervised by the FACP. Note that
AFM series annunciators occupy address '01'. The address of the AFM series cannot
be altered. When using AFM series devices with LDMs, LED-10Ns and ACM-8Rs,
be certain that none of the other devices are set to address '01'. Factory default
entry is 02 = 0 and 03 = 1.

Prog
Printer Installed (04)
The factory default entry of '0' in address 04 informs the FACP that a printer is not
connected to the panel. This entry must be changed to '1' if a printer is connected.
The PRT-24 printer interface module must be installed on J4 of the SFP-1024 main
circuit board before a printer can be installed.

Printer Baud Rate (05)


Address 05 is used to set the Baud Rate when a printer is connected to the SFP-1024.
The factory default entry is '0' for 2400 Baud. Enter '1' for 4800 Baud; or '2' for
9600 Baud. An entry in address 05 is valid only if a printer has been enabled in
address 04.

NAC/Relay Option Module (06)


A Notification Appliance Circuit/Relay Option (NAC-REM) Module is available
which adds two Style Z (Class A) NAC circuits (NACs 3 and 4) and two
programmable Form-C relays (Relays 3 and 4). The factory default setting for
address 06 is '0' for no module installed. This entry must be changed to '1' if the
NAC/Relay module is installed.

Programmable Relay 3 Definition (07)


This address programs Relay 3 if the NAC/Relay Option Module has been enabled in
address 06. The factory default entry for Relay 3 is '1' for supervisory. Enter '0' for
alarm; '2' for supervisory autoresettable; '3' for trouble; '4' for communication fail; '5'
for process monitoring; '6' for autoresettable process monitoring.

Programmable Relay 4 Definition (08)


This address programs Relay 4 if the NAC/Relay Option Module has been enabled in
address 06. The factory default entry for Relay 4 is '4' for communication fail. Enter
'0' for alarm; '1' for supervisory; '2' for supervisory autoresettable; '3' for trouble; '5'
for process monitoring; '6' for autoresettable process monitoring.

50475 Rev D1 7/22/9 P/N 50475:D1


57
NAC #3 Type Selection (09)
This address programs NAC #3 if the NAC/Relay Option Module has been enabled
in address 06. The factory default entry for NAC #3 is '0' for enabled and
silenceable; Enter '1' for enabled and nonsilenceable; or '2' for disabled.

NAC #3 Silence Inhibit (10)


This address is used for the silence inhibit feature on NAC #3 if the NAC/Relay
Option Module has been enabled in address 06. The factory default entry for NAC 3
is '0' for no silence inhibit; enter '1' to enable the silence inhibit feature for NAC #3.
This will prevent the silencing of NAC #3 for one minute following activation of an
alarm.

NAC #3 Auto-silence (11)


This address is used for the autosilence feature on NAC #3 if the NAC/Relay Option
Module has been enabled in address 06. The factory default entry for NAC 3 is '0'
for no autosilence. If you wish NAC #3 to be automatically silenced after one of the
Prog
Progrr amming

following lengths of time (requires prior approval of local AHJ), enter '1' for 5
minutes; '2' for 10 minutes; '3' for 15 minutes; '4' for 20 minutes; '5' for 25 minutes;
or '6' for 30 minutes.

NAC #3 Signal Coding (12)


This address is used to select coding for NAC #3 if the NAC/Relay Option Module
has been enabled in address 06. The factory default entry for NAC 3 is '0' for steady
output (no coding). Enter '1' for March Time coding (120 PPM); '2' for California
Time coding (10 secs. on, 5 secs. off); or '3' for Temporal Time coding (0.5 secs. on,
0.5 secs. off, 0.5 secs. on, 0.5 secs off, 0.5 secs on, 1.5 secs off).

NAC #4 Type Selection (13)


This address programs NAC #4 if the NAC/Relay Option Module has been enabled
in address 06. The factory default entry for NAC 4 is '0' for enabled and silenceable;
Enter '1' for enabled and nonsilenceable; or '2' for disabled.

NAC #4 Silence Inhibit (14)


This address is used for the silence inhibit feature on NAC #4 if the NAC/Relay
Option Module has been enabled in address 06. The factory default entry for NAC 4
is '0' for no silence inhibit; enter '1' to enable the silence inhibit feature for NAC #4.
This will prevent the silencing of NAC #4 for one minute following activation of an
alarm.

NAC #4 Auto-silence (15)


This address is used for the autosilence feature on NAC #4 if the NAC/Relay Option
Module has been enabled in address 06. The factory default entry for NAC 4 is '0'
for no autosilence. If you wish NAC #4 to be automatically silenced after one of the
following lengths of time (requires prior approval of local AHJ), enter '1' for 5
minutes; '2' for 10 minutes; '3' for 15 minutes; '4' for 20 minutes; '5' for 25 minutes;
or '6' for 30 minutes.

NAC #4 Signal Coding (16)


This address is used to select coding for NAC #4 if the NAC/Relay Option Module
has been enabled in address 06. The factory default entry for NAC 4 is '0' for steady
output (no coding). Enter '1' for March Time coding (120 PPM); '2' for California
Time coding (10 secs. on, 5 secs. off); or '3' for Temporal Time coding (0.5 secs. on,
0.5 secs. off, 0.5 secs. on, 0.5 secs off, 0.5 secs on, 1.5 secs off).

58 50475 Rev D1 9/22/99 P/N 50475:D1


Canadian Supervisory Annunciation (17)
This address, when programmed to a '1', causes the annunciators (LDM, AFM, LED-
10N) to indicate a supervisory alarm by turning on the appropriate yellow zone LED
only. The yellow zone LED blinks at a ½ second ON/ ½ second OFF rate in alarm.
It blinks at a 1 second ON/ 1 Second OFF rate if the supervisory zone is in fault.
Should both an alarm and a fault occur on a supervisory zone at the same time, the
alarm takes priority and the blink rate is ½ second ON/ ½ second OFF.

The non-Canadian supervisory function will turn on the red zone alarm LED for any
type of zone function. The blink rate at the annunciators is 1 second ON/ 1 second
OFF for fire alarm, ½ second ON/ ½ second OFF for supervisory alarm and ¼
second ON/ ¼ second OFF for process monitored alarm. The default entry is '0' for
non-Canadian supervisory annunciation; enter '1' for Canadian Supervisory
Annunciation.

Note: UL and ULC require slide-in labels on all annunciators to be clearly marked
as to the function of each zone.

Progrr amming
Caution: When selecting this function, be aware that ACM-8R relays programmed
for alarm will not activate for supervisory alarms.

Prog
4. Level Four - Upload/Download Option

Each option of the Program Mode is entered by keying in the program mode entry
7764
7764) and pressing the ENTER/STORE key.
code (7764

☛ 7764 spells PROG on a Touch-Tone® phone

If an incorrect key is entered, reenter the proper 4-digit code before pressing the
[ENTER/STORE] key.

You are allowed a pause of up to 10 seconds in between each number while entering
the code. After pressing the [ENTER/STORE] key, the control panel will be in
Program Mode and display P__1P__1, with the 1 flashing. Press 4 on the keypad and
then the [ENTER/STORE] key to choose the Upload/Download Option. You are
allowed up to ten minutes of idle time at this point before starting your
programming, otherwise the control panel will go back to Normal Mode. You also
have a maximum of 10 minutes between any key stroke. All entries made prior to
the 10 minute time-out are valid and are stored.

Upon entering the Upload/Download Option in programming mode, the following


will be displayed on the FACP LCD.
00_0
(address)(data)

The first two locations on the left of the display represent the memory address 00
00.
The last location 0 (farthest right) represents the contents of memory address 00
which is the first digit of the Panel Identification Number. To change the Panel ID
Number, key in the first of the four digits for the ID. Increment to the next address
and key in the second number. Continue until all digits are programmed.

Use the Up and Down Arrow keys to increment to the next address or decrement to
the previous address.

50475 Rev D1 7/22/9 P/N 50475:D1


59
When desired changes have been completed, exit programming mode by pressing the
MODE key, followed by the four-digit code for an alternate mode and then the
[ENTER/STORE] key. To enter a different Programming Level, press MODE and
then press the [ENTER/STORE] key. The display will show P__4 with the '4'
flashing. Press the digit (1, 2 or 3) of the Programming Level to be accessed.

During Program Mode, if no key is pressed within 10 minutes, the panel will revert
to normal mode.

The SFP-1024 can be programmed remotely from a PC using a modem and the
telephone line. Information can also be retrieved from the FACP with the same
method. The Upload/Download Option allows an operator to set the necessary
parameters to allow the uploading and downloading of data between the FACP and
PC.

Following are the various parameters and their addresses.


Prog
Progrr amming

Panel Identification Number (00-03)


The Panel Identification Number is a 4-digit code (valid digits being 0 - F) that is
used to identify the installed panel. This code is separate from the 8-digit secret
code loaded in by the Service Terminal. It is important to program this 4-digit code
at the jobsite the first time that downloading is performed so that the called Service
Terminal can identify the control panel. Factory default is '0000'. (Future use).

Service Terminal Number 1 Phone Number (04-19)


Addresses 04 through 19 are reserved for the Service Terminal Number 1 phone
number. Factory default is all Fs. Valid entries are 0-9 plus A, B, C, D, and E. Use
'F' to designate the end of the phone number.

Ring Count on Primary Phone Line (20-21)


Use this address to designate the number of rings allowed on the primary phone line
prior to answering an incoming call from a Service Terminal. Factory default is 25
meaning the panel will not answer an incoming call until 25 rings are detected. This
entry may be programmed up to a maximum of 25 rings. A setting of 00 prevents
the panel from answering incoming calls.

FAX/Answer Machine, Primary Phone Line (22)


This entry is used when the primary phone line is being shared with a FAX,
answering machine or other device. Factory default is '0', no sharing of the primary
phone line. An entry of '1' indicates that another device is sharing the primary phone
line. The panel will wait for three consecutive calls from the Service Terminal
spaced 30 seconds apart, before responding.

Service Terminal Number 2 Phone Number (23-38)


Addresses 23 through 38 are reserved for the Service Terminal Number 2 phone
number. Factory default is all Fs. Valid entries are 0-9, A, B, C, D. Use 'F' to
designate the end of the phone number.

Ring Count on the Secondary Phone Line (39-40)


Use this address to designate the number of rings allowed on the secondary phone
line prior to answering an incoming call from a Service Terminal. Factory default is
25 meaning the panel will not answer an incoming call until 25 rings are detected.
This entry affects the secondary phone line only. This entry may be programmed up
to a maximum of 25 rings. A setting of 00 prevents the panel from answering
incoming calls.

60 50475 Rev D1 9/22/99 P/N 50475:D1


FAX/Answer Machine, Secondary Phone Line (41)
Factory default is '0' for no sharing of the secondary phone line with a FAX,
answering machine or other device. An entry of '1' allows the panel to wait for three
consecutive calls spaced 30 seconds apart from the Service Terminal before
responding.

Upload/Download Reports Sent to Secondary Central Station Phone #, Backup


or Always (42)
Leaving address 42 = 0 means that reports for request for 'up/download', 'successful
upload', 'successful download', and 'failed up/download' will be sent to the secondary
Central Station phone number only if attempts to the primary Central Station phone
number are unsuccessful. Programming a '1' causes all reports to be transmitted to
both the primary and secondary phone numbers. Factory default is '0' for secondary
backup only. Enter '1' to transmit to both Central Station phone numbers. Enter '2'
to transmit to the first available receiver.
Caution: Do not alter entry while the communicator is active.

Progrr amming
5. Def ault Pr
Default Proo g r amming

To return all program entries in all four levels to their factory original settings,
perform the following steps only when the system is idle in Normal standby

Prog
condition:

Press the MODE key followed by the four digit code 3337 and press the ENTER/
STORE key.

☛ 3337 DEF
DEFault P rogramming) on a Touch-Tone® phone
spells DEFP (DEF

If an incorrect key is entered, reenter the proper 4-digit code before pressing the
[ENTER/STORE] key.

Within five seconds, repeat this entry by again pressing the MODE key followed by
the four digit code 3337 and pressing the [ENTER/STORE] key. The display will
read 3337 while the E2 nonvolatile memory (storage area for all programming
options) is being reprogrammed with the original default settings. When
reprogramming is complete, the display will be blank.

50475 Rev D1 7/22/9 P/N 50475:D1


61
4.0 Operating Instructions
Operating Instructions

New - with ACK lettering Old - without ACK lettering

Figure 4-1: Ne
Neww and Old Ke ypad/Displa
Ke y
ypad/Display

Normal Mode The SFP-1024 has several modes of operation including: Normal, Program, Walk
Test, Troubleshoot, History, Lamp Test, Print and Upload/Download. There are
also four function modes: Drill, Zone Enable/Disable, NAC Enable/Disable and
Default Programming. Upon initial power up, the system will be in Normal Mode.
This section discusses operation of the control panel in the Normal Mode.

4.1 Switches Below is a description of the system function switches in Normal Mode:

RESET The System Reset Switches reset the system and any smoke detectors. Reset
switches may be located on the FACP key pad (illustrated above), any of the 10
zones programmed as a remote reset switch, remotely on any of the LED-10N
annunciators, the LDM graphic annunciators, or the AFM series annunciators. If any
of the System Reset Switches are pressed, the control panel will:

• Clear the display and status LEDs


• Turn off the Notification Appliance Circuits
• Reset all zones by temporarily removing power
• Silence the onboard piezo sounder
• Store 'reset' message in the History file
• Restore all system relays to normal
• Temporarily remove power from the resettable power output
TB2 terminals 3+4.
• Output 'reset' message to printer.

Any alarm, supervisory or trouble condition that exists after a system reset, will
resound the system, reactivating normal system activity. Upon release of a System
Reset Switch, the FACP display will read rES_ for six seconds.

SILENCE Silence switches may be located on the FACP key pad (illustrated above), any of the
10 zones programmed as a remote silence switch, remotely located on any of the
LED-10N annunciators, the LDM graphic annunciators, or the AFM series
62 50475 Rev D1 9/22/99 P/N 50475:D1
annunciators. The Silence Switch performs the same functions as the System
Acknowledge Switch, in addition, if any of the System Silence Switches are pressed:
• The silenceable Notification Appliance Circuits will be turned OFF.
• The main circuit board silence LED will be turned ON.
• The SILn message will be displayed (where n = NAC #).
• The system piezo sounders will be shut OFF.
• 'NAC #N Silenced' message will be stored in the History file.
• 'NAC #N Silenced' message will be sent to the printer

Upon the occurrence of a subsequent event (alarm or trouble), System Silence is


overridden and the control panel will respond to the new event. The System Silence
switches will be ignored for nonsilenceable waterflow type alarms.

ACKNOWLEDGE/STEP Acknowledge/Step switches (Up/Down arrow keys) are located on newer model FACP
keypads (see Figure 4-1), remotely located on any of the LED-10N annunciators, the
LDM graphic annunciators, or the AFM series annunciators and an option exists that
allows any of the 10 zones to be programmed to function as a remote acknowledge
switch.

Operating Instructions
The Acknowledge/Step switch silences the system piezo sounders and changes all
flashing system LEDs to steady. An acknowledge message is sent to the printer and
history files. The Step function permits scrolling through multiple stored events during
normal, history and walktest modes.

When more than one event exists, the first press of the Acknowledge/Step switch silences
the system piezo sounders and changes all flashing system LEDs to steady. The second
press of the switch stops the scrolling and holds the event on the display for five seconds.
Subsequent pressing of the switch 'steps' through each active event. The Acknowledge
Switch must be pressed within 15 seconds to prevent NACs from turning on if alarm
presignal is selected. For additional information on alarm presignal, refer to
Programming Section 3.0.

DRILL Drill switches may be located on any of the 10 zones programmed as a remote drill
switch, remotely on any of the LED-10N annunciators, the LDM graphic annunciators, or
the AFM series annunciators. To perform a drill from any of these switches, the Drill
switch must be pressed and held for two seconds (time to prevent accidental activation).
The SFP-1024 turns on all NACs and turns off the system silence LEDs. The message
shown on the display is dril
dril. The drill message is sent to the printer and history files.
The system silence keys will silence all silenceable NACs during a fire drill.

To perform a drill from the FACP, press the MODE key followed by the code 3745 then
press [ENTER/STORE]
[ENTER/STORE]. The display will read dril dril. The alarm relay is not activated.
There is an option to transmit the fire drill report code to the Central Station. During a
fire drill, the SILENCE key will silence all silenceable NACs and the RESET key
restores the panel to normal. All zones remain active during a fire drill.

MODE Pressing the Mode Switch followed by a valid 4-digit numerical code and [ENTER/
STORE] selects one of the six modes of operation.

☛ To enter normal mode from any other mode press MODE then
6676 [ENTER/STORE]
[ENTER/STORE]. 6676 spells NORM on a Touch-Tone® phone.

1st EVENT This switch along with the Up Arrow and Down Arrow keys, is used to display any
presently active alarm and/or fault conditions present in the system. Press the 1st Event
switch at any time to display the first event (alarm and/or trouble) that occurred.

50475 Rev D1 7/22/9 P/N 50475:D1


63
DOWN ARROW (ACK) Use the Down Arrow key to view other events (older) that have occurred and are
active - not cleared yet. It also acknowledges the event by silencing the local piezo.

UP ARROW (ACK) Use the Up Arrow key to view other events (newer), that have occurred and are
active - not cleared yet. It also acknowledges the event by silencing the local piezo.

[ENTER/STORE] See individual mode descriptions in other sections of this manual. In Normal Mode,
this key is used after pressing the MODE key followed by a four digit mode code
then the [ENTER/STORE] key.

4.2 Displays Four 7-segment red LED characters provide visual annunciation of status, events and
messages. A list of messages that may appear on the display in normal mode is
shown below:
d__1 Zone 1 Disabled F__9 Trouble Zone 9
d__2 Zone 2 Disabled F_10 Trouble Zone 10
d__3 Zone 3 Disabled F_85 Annunciator Bus Fault
d__4 Zone 4 Disabled F__A Annunciator Fault
d__5 Zone 5 Disabled F__E Earth Fault
Operating Instructions

d__6 Zone 6 Disabled F__P Printer Fault


d__7 Zone 7 Disabled Lo_b Low Battery
d__8 Zone 8 Disabled no_b No Battery
d__9 Zone 9 Disabled PH_1 Primary C. S. Number Communication Fault
d_10 Zone 10 Disabled Secondary C. S. Number Communication Fault
PH_2
d_b1 NAC/Bell #1 disabled bEL1 Bell 1 Fault
d_b2 NAC/Bell #2 disabled bEL2 Bell 2 Fault
d_b3 NAC/Bell #3 disabled bEL3 Bell 3 Fault
d_b4 NAC/Bell #4 disabled bEL4 Bell 4 Fault
drLL Fire Drill no_1 Primary Phone Line Fault
E__1 Zone 1 Enabled no_2 Secondary Phone Line Fault
E__2 Zone 2 Enabled PA_1 Process Monitoring Alarm Zone 1
E__3 Zone 3 Enabled PA_2 Process Monitoring Alarm Zone 2
E__4 Zone 4 Enabled PA_3 Process Monitoring Alarm Zone 3
E__5 Zone 5 Enabled PA_4 Process Monitoring Alarm Zone 4
E__6 Zone 6 Enabled PA_5 Process Monitoring Alarm Zone 5
E__7 Zone 7 Enabled PA_6 Process Monitoring Alarm Zone 6
E__8 Zone 8 Enabled PA_7 Process Monitoring Alarm Zone 7
E__9 Zone 9 Enabled PA_8 Process Monitoring Alarm Zone 8
E_10 Zone 10 Enabled PA_9 Process Monitoring Alarm Zone 9
A__1 Alarm Zone 1 PA10 Process Monitoring Alarm Zone 10
A__2 Alarm Zone 2 SIL1 NAC/Bell #1 Silenced
A__3 Alarm Zone 3 SIL2 NAC/Bell #2 Silenced
A__4 Alarm Zone 4 SIL3 NAC/Bell #3 Silenced
A__5 Alarm Zone 5 SIL4 NAC/Bell #4 Silenced
A__6 Alarm Zone 6 SU_1 Supervisory Alarm Zone 1
A__7 Alarm Zone 7 SU_2 Supervisory Alarm Zone 2
A__8 Alarm Zone 8 SU_3 Supervisory Alarm Zone 3
A__9 Alarm Zone 9 SU_4 Supervisory Alarm Zone 4
A_10 Alarm Zone 10 SU_5 Supervisory Alarm Zone 5
F__1 Trouble Zone 1 SU_6 Supervisory Alarm Zone 6
F__2 Trouble Zone 2 SU_7 Supervisory Alarm Zone 7
F__3 Trouble Zone 3 SU_8 Supervisory Alarm Zone 8
F__4 Trouble Zone 4 SU_9 Supervisory Alarm Zone 9
F__5 Trouble Zone 5 SU10 Supervisory Alarm Zone 10
F__6 Trouble Zone 6 _AC_ AC Power Loss
F__7 Trouble Zone 7 rES_ System Reset
F__8 Trouble Zone 8
64 50475 Rev D1 9/22/99 P/N 50475:D1
Individual LEDs are provided for:

System Fire Alarm


Alarm—A red LED that flashes when a fire alarm condition is detected
during the alarm presignal period. It turns on steady when the system silence or
acknowledge switches are pressed.

System Trouble
Trouble—This yellow LED blinks to indicate that a fault or abnormal
condition exists and that the fire alarm system may be inoperative. It turns on steady
when a system silence or acknowledge switch is pressed.

AC Power On On—A green LED that remains on while the A.C. power supply is within
correct limits. If this indicator fails to light under normal conditions, service the
system immediately.

Supervisory
Supervisory—A yellow LED that blinks to indicate the need for action in
connection with the supervision or maintenance of sprinklers, extinguishing systems
or other protective systems.

System Silence
Silence—A yellow LED that turns on to indicate that an Alarm or Trouble
condition exists in the system, but Notification Appliance Circuits (if programmed as

Operating Instructions
silenceable) and local piezo have been silenced.

Primary Line Active


Active—A red LED that indicates the primary phone line is active.

Secondary Line Active


Active—A red LED that indicates the secondary phone line is
active.

Kiss-Off —A green LED that blinks when a Central Station has acknowledged
receipt of each transmitted message or when a portion of up or downloaded data has
been accepted from a Service Terminal.

Modem —A green LED that stays on steady during modem types of


communications.

Kissoff LED

Primary Active LED

Modem LED Primary


Line

Secondary
Line

Secondary Active LED

Figure 4-1: Phone Connectors and LEDs


50475 Rev D1 7/22/9 P/N 50475:D1
65
4.3 Operation Normal mode is the standard mode of operation. In this mode, the panel continuously
monitors system status. When no alarm or trouble conditions exist, the display will be
blank and all LEDs will be off (except the AC Power LED). The Notification
Appliance Circuits will be off, all relays are in their normal state, the onboard piezo
sounder will be off and the printer (if connected) will not be printing. (The
communicator is not active, primary and secondary active LEDs are off).

All alarm and system trouble conditions are annunciated on the control panel's display.
The control panel will maintain an 'active event list' which will consist of all alarms,
supervisory alarms and system troubles currently active, and not cleared, requiring
immediate service. When the system is cleared and restored to normal, the display will
be blank. All alarms and troubles are stored in a history file and may be recalled at
any time.

Higher priority events take precedence over lower priority events. Display and
reporting of System Status is done on a priority basis. Priorities are, from highest to
lowest:
1. Alarms
2. Supervisory Alarms
Operating Instructions

3. System Troubles
4. Process Monitoring Alarms

If the events to be displayed consist of alarms and disabled zones only, (no troubles),
the control panel will scroll them on the display. As each new alarm occurs, it will be
displayed immediately on the display for five seconds. After this five second period,
the display will scroll all alarms in the system. Pressing the 1st Event key or one of the
'ACK' keys will stop the scrolling. The 1st Event key will also cause the display to
show the First alarm that occurred after the panel was last reset, cleared of all active
events and placed into normal mode. Operation of the Up and Down arrow keys will
display all remaining events in sequence.

If events to be displayed include system troubles, only one event is displayed at a time
and there is no scrolling. The event displayed is the highest priority. Pressing the 1st
Event key will cause the display of the first event that occurred after the panel was last
reset, cleared of all active events and placed into normal mode. Operation of the Up
and Down arrow keys will display all remaining events in order of their occurrences.

4.3.1 Fire Alarm Response


The control panel will, upon detection of an alarm condition:

• Blink the FACP alarm LED (1 second on, 1 second off).


• Display the alarm message, for example, A__1 Alarm on zone 1.
• Communicate the alarm to the central station.
• Store the alarm in the History file.
• Turn the Notification Appliance Circuits on.
• Turn the Piezo Sounder on steady.
• Turn on appropriate zone relay output (ACM-8R).
• Turn on any system relays (main circuit board) programmed for alarm activa-
tion.
• Output alarm message to printer.
• Terminate upload or download communications.
• Blink all remote annunciator general alarm LEDs (1 second on, 1 second off).
• Blink all remote annunciator zone alarm LEDs (1 second on, 1 second off).

Note that when any zone is programmed as a supervisory or process monitored zone, it
will not be processed in the same manner as a conventional alarm zone. See
Supervisory Condition and Process Monitored Alarm later in this section.
66 50475 Rev D1 9/22/99 P/N 50475:D1
4.3.2 Fire Alarm Restoral
The control panel returns to normal after all alarms have been cleared and a system
reset switch has been pressed (pull stations reset, smoke detectors reset and no
smoke is present, waterflow has stopped). The control panel will perform the
following upon restoral of all active alarms:

• Turn off the FACP alarm LED.


• Clear the 4-character display .
• Send all 'Zone Restoral' messages to the central station.
• Turn off the Notification Appliance Circuits.
• Turn off the Piezo Sounder.
• Turn off appropriate zone relay output (ACM-8R).
• Turn off any system relays (main circuit board) programmed for alarm
activation.
• Output alarm restoral message to printer.
• Terminate upload or download communications.
• Turn off all remote annunciator general alarm LEDs.
• Turn off all remote annunciator zone alarm LEDs.

4.3.3 System Supervisory Condition Response

Operating Instructions
Program zones for Supervisory in applications where a waterflow sensing device has
been employed and the wiring to the waterflow valve and/or a tamper switch is to be
monitored. If the tamper switch has been activated (Normally Open contacts close),
a supervisory alarm condition will occur.

When a supervisory condition occurs, the control panel will:


• Blink the FACP supervisory LED (.5 seconds on, .5 seconds off).
• Display the following message: (SUXX) (XX=Zone Number).
• Communicate the supervisory condition to the central station.
• Store the 'supervisory' message in the History file.
• Pulse system piezo sounders at 0.5 sec on 0.5 sec off rate.
• Turn on appropriate zone relay output (ACM-8R).
• Turn on any system relays (main circuit board) programmed for supervisory
activation.
• Output system supervisory message to printer.
• Terminate upload or download communications.
• Blink all remote annunciator general supervisory alarm LEDs (1/2 second on,
1/2 second off).
• Blink all remote annunciator zone supervisory alarm LEDs (1/2 second on, 1/2
second off).

4.3.4 System Supervisory Restoral Response


When the supervisory condition has been cleared (condition is restored and the reset
switch has been pressed) the control panel will perform the following:
• Turn off the supervisory LED.
• Clear the display of the 'SUXX' message.
• Communicate a supervisory restoral message to the central station.
• Shut off system piezo sounders.
• Turn off appropriate zone relay output (ACM-8R).
• Turn off any system relays (main circuit board) programmed for supervisory
activation.
• Output system supervisory restoral message to printer.
• Terminate upload or download communications.
• Turn off all remote annunciator general supervisory alarm LEDs.
• Turn off all remote annunciator zone supervisory alarm LEDs.
Note: For any zone programmed for Supervisory auto resettable, the Reset key does
not need to be pressed to clear the zone (Supervisory condition).

50475 Rev D1 7/22/9 P/N 50475:D1


67
4.3.5 Trouble Condition Response
The control panel will perform the following upon detection of one or more trouble
conditions:
• Blink the FACP trouble LED (one second on, one second off).
• Blink all annunciator general system trouble LEDs.
• Blink all affected zone trouble LEDs on all system annunciators.
• Activate any FACP trouble relay(s) if programmed for trouble activation.
• Display the appropriate trouble message(s) in priority fashion from the highest
priority to the lowest. Note: (Must press Up Arrow, Down Arrow, or 1st
Event key to view).
• Communicate the trouble conditions to the central station.
• Store the trouble conditions in the history file.
• Sound system piezo sounders at a rate of one second on, one second off.
• Output the system trouble messages to the printer.
• Terminate upload or download communications
Note
Note: When AC Brownout occurs the AC LED is turned off, and the Trouble LED
blinks. Should the brownout condition remain, it will be transmitted to the central
station after a delay (See Program Address number 77 of Level 1 Main Panel Options).
Operating Instructions

Possible trouble messages that may appear on the display are as follows:

_AC_ AC Loss (shown only when requested)


d__1 Zone 1 Disabled F__6 Trouble Zone 6
d__2 Zone 2 Disabled F__7 Trouble Zone 7
d__3 Zone 3 Disabled F__8 Trouble Zone 8
d__4 Zone 4 Disabled F__9 Trouble Zone 9
d__5 Zone 5 Disabled F_10 Trouble Zone 10
d__6 Zone 6 Disabled F__A Annunciator Fault
d__7 Zone 7 Disabled F__P Printer Fault
d__8 Zone 8 Disabled F__E Earth Fault
d__9 Zone 9 Disabled Lo_b Low Battery
d_10 Zone 10 Disabled no_b No Battery
F__1 Trouble Zone 1 PH_1 Primary C. S. Number Communication Fault
F__2 Trouble Zone 2 PH_2 Secondary C. S. Number Communication Fault
F__3 Trouble Zone 3 bEL1 Bell 1 Fault
F__4 Trouble Zone 4 bEL2 Bell 2 Fault
F__5 Trouble Zone 5 bEL3 Bell 3 Fault
d_b1 Bell 1 Disabled bEL4 Bell 4 Fault
d_b2 Bell 2 Disabled no_1 Primary Phone Line Fault
d_b3 Bell 3 Disabled no_2 Secondary Phone Line Fault
d_b4 Bell 4 Disabled

4.3.6 Trouble Condition Restoral


The control panel performs the following upon restoral of all trouble conditions:
• The trouble LED is shut OFF.
• FACP trouble relay(s) deactivate if programmed for trouble activation.
• If the trouble was loss of AC power, the control panel will turn on the AC
LED upon restoral.
• Clear the FACP display of the trouble message(s).
• Communicate the restored trouble condition(s) to the central station.
• Output the system trouble restoral message to the printer.
• Terminate upload or download communications.
• Turn off the system general trouble LED on all system annunciators if all
trouble conditions are cleared.
• Turn off all affected zone trouble LEDs on all system annunciators.
68 50475 Rev D1 9/22/99 P/N 50475:D1
4.3.7 Process Monitored Alarm Response
Upon detection of a critical or noncritical process monitored alarm condition on any
zone, the control panel will:

• Display the alarm message PAXX where XX = zone number.


• Communicate the alarm code programmed for the activated zone.
• Store the alarm in the History file.
• Pulse the piezo at a ¼ second rate.
• Turn on appropriate zone relay output (ACM-8R).
• Turn on any system relays (main circuit board) programmed for process alarm
activation.
• Output alarm message to printer.
• Terminate upload or download communications.
• Blink all remote annunciator zone alarm LEDs (¼ second ON, ¼ second OFF).

4.3.8 Process Monitored Alarm Restoral


The control panel returns to normal after all alarms have been cleared and a system
reset switch has been pressed (process monitored alarm devices reset). The control
panel will perform the following upon restoral of all active process monitored alarms:

Operating Instructions
• Clear the 4-character display.
• Communicate the alarm restoral code programmed for the activated zone.
• Store the alarm restoral message in the History file.
• Turn off the piezo sounder.
• Turn off appropriate zone relay output (ACM-8R).
• Turn off any system relays (main circuit board) programmed for process alarm
activation.
• Output alarm restoral message to printer.
• Terminate upload or download communications.
• Turn off all remote annunciator zone alarm LEDs.

Note: For any zone programmed for autoresettable process monitored alarm, the reset
key does not need to be pressed to clear the zone.

4.3.9 OFF Normal Reporting


Removing the panel from Normal Mode and placing it into Troubleshoot, Walktest or
Program Mode causes a transmission of an 'off normal' fault message. Returning the
panel to Normal Mode causes a transmission of a 'return to normal' restoral message.

4.3.10 Zone Disable/Enable


The zone disable feature may be used to disable any zone in the system. While in
Normal Mode or Walktest Mode, zones may be disabled if they are normal, in trouble
or alarmed. If the panel is in alarm, the silence switch must be pressed first before
zone disable will function in Normal Mode.

To disable a zone, press the MODE key once, (the display will go blank) you then
have 10 seconds to start entering the code 3472
3472. Next press the [ENTER/STORE]
key.

☛ 3472 spells DISA on a Touch-Tone® phone

50475 Rev D1 7/22/9 P/N 50475:D1


69
A flashing lower case d will appear on the far left of the display. Next, press the
zone number to be disabled. The number will appear on the far right display
character. Press [ENTER/STORE]
[ENTER/STORE]. The zone is disabled. All system annunciators
will show zone troubles and general trouble status. Note that the trouble relay is
activated and the trouble LED blinks.

The zone disable message will remain on the display until the zone is reenabled. To
reenable a zone, press the MODE key once, (the display will go blank) you then
have 10 seconds to start entering the code 3622
3622. Next, press the [ENTER/STORE]
key.
☛ 3622 spells ENAB on a Touch-Tone® phone

A flashing upper case E will appear on the left of the display. Next, press the zone
number to be enabled. The number will appear on the far right display character.
Press [ENTER/STORE]
[ENTER/STORE]. The zone is reenabled. Note that the trouble relay is
restored to normal and the FACP trouble LED is off and all system annunciator zone
trouble LEDs are off.

4.3.11 NAC (bell) Disable/Enable


Operating Instructions

The NAC/bell disable feature may be used to disable any of the four main panel
NAC/bell circuits. While in Normal Mode, NACs may be disabled if they are
normal, in trouble or alarmed.

To disable an NAC/bell, press the MODE key once, (the display will go blank).
You then have 10 seconds to start entering the code 3472
3472. Next, press the [ENTER/
STORE] key.

☛ 3472 spells DISA on a Touch-Tone® phone

A flashing lower case d will appear on the far left of the display. Next, press the b
key followed by the NAC number to be disabled. The b and the NAC number will
appear on the far right display characters. Press [ENTER/STORE]
[ENTER/STORE]. The NAC is
disabled. All system annunciators will show general trouble status and the main
panel display will show the NAC disabled message, turn on the system trouble LED
and activate relays programmed for system trouble.

The NAC disable message will remain on the display until the circuit is reenabled.
To reenable an NAC, press the MODE key once (the display will go blank). You
then have 10 seconds to start entering the code 3622
3622. Next, press the [ENTER/
STORE] key.

☛ 3622 spells ENAB on a Touch-Tone® phone

A flashing upper case E will appear on the left of the display. Next, press the b key
followed by the NAC number to be enabled. The b and the NAC number will
appear on the far right display characters. Press [ENTER/STORE]
[ENTER/STORE]. The NAC is
reenabled. Note that relays programmed as trouble are restored to normal and the
FACP trouble LED is off and all system annunciator general trouble LEDs are off.

4.3.12 Fire Drill


The DRILL (manual evacuate) feature turns on all Notification Appliance Circuits
(if programmed as enabled) and turns off the silence LED. To perform a fire drill,
press the MODE key followed by the code 3745 then enter. The display will read
drLL
drLL. The alarm relay is not activated. There is an option to transmit the fire drill
report code to the Central Station.

☛ 3745 spells dril


70 50475 Rev D1 9/22/99 P/N 50475:D1
During a fire drill, the SILENCE key will silence the silenceable Notification
Appliance Circuits and the RESET key restores the panel to normal. All zones
remain active during a fire drill.

4.4 Central Station The control panel transmits zone and system status reports to Central Stations via the
Communications public switched telephone network. Two supervised telephone line connections are
made to interface the control panel to the telephone lines. Two 7-foot telephone
cords P/N MCBL-7 may be used for this purpose.

The control panel supervises both telephone lines for proper voltage. A delay of two
minutes will occur before a fault in either phone line connection is reported as a
trouble. When a fault is detected, an audible trouble signal will sound, the yellow
trouble LED will blink, the 4 character display will show either 'no 1' or 'no 2'
(depending upon which telephone line has the fault. 'no 1' = Primary Line, 'no 2' =
Secondary Line) and the trouble condition will be reported to a Central Station over
the remaining good phone line.

The control panel comes with line seizure capability provided for both the primary
and secondary telephone line interfaces. Any time that the control panel needs to
make a call to a Central Station, line seizure will disconnect any local premises

Operating Instructions
phones sharing the same telephone line.

All transmissions to Central Stations will be sent over the Primary Central Station
phone line. In the event of noisy phone lines, transmissions will be sent over the
backup Secondary phone line.

Two phone numbers must be programmed, the Primary Central Station phone
number and the Secondary Central Station phone number. There are three options
for transmission to the central station:

1. All messages are always sent to the primary central station phone number
with the secondary central station phone number for emergency backup
purposes only.
2. All reports are sent to both central station phone numbers.
3. Reports are sent to the first available central station phone number only.

If 10 total attempts to communicate are unsuccessful, system relays programmed for


Communications Failure will be activated. The FACP will also display 'PH1' for
Communicator Failure to the primary central station phone number or 'PH2' for
Communicator Failure to the secondary central station phone number.

The SFP-1024 meets NFPA 72 National Fire Code reporting requirements for: (a)
the type of signal (b) condition and (c) location of the reporting premises. The
general priority reporting structure is:

1. Zone Alarms and Restores


2. Zone Troubles and Restores
3. System Troubles and Restores
4. 24-hour test

The control panel is capable of reporting detailed messages depending upon the
format in use. Table 4-1 shows the reporting structure for all formats.

50475 Rev D1 7/22/9 P/N 50475:D1


71
Format # Format # Format # Format #
0, 2, 4, 6, 8 3, 5, 7, 9 1, A, C B, D
Report 3+1/4+1/ Standard 3+1/4+1/Expanded 4+2/Standard 4+2/Expanded
4+1 Express 4+2 Express
Alarm SSS(S) A SSS(S) A SSSS AA2 SSSS AZ
AAA(A) Z
Alarm Restore SSS(S) RA SSS(S) RA SSSS RARA2 SSSS RAZ
RARARA(RA) Z
Zone Trouble SSS(S) TZ SSS(S) TZ SSSS TZTZ2 SSSS TZZ
(Zone Open) TZTZTZ(TZ) Z
Zone Trouble Restore SSS(S) RTZ SSS(S) RTZ SSSS RTZRTZ2 SSSS RTZZ
RTZRTZRTZ(RTZ) Z
System Trouble SSS(S) TS SSS(S) TS SSSS TSTS2 SSSS TSY
TSTSTS(TS) Y
Operating Instructions

System Trouble Restore SSS(S) RTS SSS(S) RTS SSSS RTSRTS2 SSSS RTSY
RTSRTSRTS(RTS) Y
Zone Disable SSS(S) DZ SSS(S) DZ SSSS RDZRDZ2 SSSS DZZ
DZDZDZ(DZ) Z
Zone Disable Restore SSS(S) RDZ SSS(S) RDZ SSSS RDZRDZ2 SSSS RDZZ
RDZRDZRDZ(RDZ) Z
Bell Disable SSS(S) DB SSS(S) DB SSSS DBDB2 SSSS DBDB2
Bell Disable Restore SSS(S) RB SSS(S) RB SSSS RBRB2 SSSS RBRB2
Low Battery SSS(S) L SSS(S) L SSSS LL2 SSSS LL2
Low Battery Restore SSS(S) RL SSS(S) RL SSSS RLRL2 SSSS RLRL2
No Battery SSS(S) N SSS(S) N SSSS NN2 SSSS NN2
No Battery Restore SSS(S) RN SSS(S) RN SSSS RNRN2 SSSS RNRN2
AC Loss SSS(S) P SSS(S) P SSSS PP2 SSSS PP2
AC Loss Restore SSS(S) RP SSS(S) RP SSSS RPRP2 SSSS RPRP2
Fire Drill SSS(S) Fd SSS(S) Fd SSSS FdFd2 SSSS FdFd2
Fire Drill Restore SSS(S) RFd SSS(S) RFd SSSS RFdRFd2 SSSS RFdRFd2
Supervisory Condition SSS(S) V SSS(S) V SSSS VV2 SSSS VZ
VVV(V) Z
Supervisory Condition SSS(S) RV SSS(S) RV SSSS RVRV2 SSSS RVZ
Restore RVRVRV(RV) Z
Test Report SSS(S) X SSS(S) X SSSS XX2 SSSS XX2
Up or Download SSS(S) UD SSS(S) UD SSS UDUD2 SSS UDUD2

Table 4-1: Format Selection Addresses (16+42)


Programming Level 1

Refer to Table 4-2 for an explanation of each letter code in Table 4-1.
Refer to Table 4-3 for a list of compatible receivers.

72 50475 Rev D1 9/22/99 P/N 50475:D1


Where:
SSS 0r
SSSS = Subscriber ID
A = Alarm (1st digit)
A2 = Alarm (2nd digit)
Z = Zone Number
RA = Alarm Restore (1st digit)
RA2 = Alarm Restore (2nd digit)
TZ = Zone Trouble (1st digit)
TZ2 = Zone Trouble (2nd digit)
RTZ = Zone Trouble Restore (1st digit)
RTZ2 = Zone Trouble Restore (2nd digit)
TS = System Trouble (1st digit)
TS2 = System Trouble (2nd digit)
RTS = System Trouble Restore (1st digit)
RTS2 = System Trouble Restore (2nd digit)
DZ = Zone Disable (1st digit)
DZ2 = Zone Disable (2nd digit)
RDZ = Zone Disable Restore (1st digit)
RDZ2 = Zone Disable Restore (2nd digit)
DB = Bell Disable (1st digit)
DB2 = Bell Disable (2nd digit)
RB = Bell Disable Restore (1st digit)
RB2 = Bell Disable Restore (2nd digit)

Operating Instructions
L = Low Battery (1st digit)
L2 = Low Battery (2nd digit)
RL = Low Battery Restore (1st digit)
RL2 = Low Battery Restore (2nd digit)
N = No Battery (1st digit)
N2 = No Battery (2nd digit)
RN = No Battery Restore (1st digit)
RN2 = No Battery Restore (2nd digit)
P = AC Loss (1st digit)
P2 = AC Loss (2nd digit)
RP = AC Loss Restore (1st digit)
RP2 = AC Loss Restore ( 2nd digit)
FD = Fire Drill (1st digit)
FD2 = Fire Drill (2nd digit)
RFD = Fire Drill Restore (1st digit)
RFD2 = Fire Drill Restore (2nd digit)
V = Supervisory Condition (1st digit)
V2 = Supervisory Condition (2nd digit)
RV = Supervisory Condition Restore (1st digit)
RV2 = Supervisory Condition Restore (2nd digit)
X = Test Report (1st digit)
X2 = Test Report (2nd digit)
Y = A Trouble Corresponding to The Following:
1 = Earth Fault
2 = Not Used
3 = Not Used
4 = Telco Primary Line Fault
5 = Telco Secondary Line Fault
6 = NAC #1 Fault
7 = NAC #2 Fault
8 = NAC #3 Fault
9 = NAC #4 Fault
A = Communication Failure to Primary Number
B = Communication Failure to Secondary Number
C = Printer Fault
D = Annunciator Fault
E = 485 Communication Failure
F = System Off Normal
UD = Upload/download 1st digit
UD2 = Upload/download 2nd digit

Note
Note: For Expanded Reporting, the control panel automatically adds the digit
corresponding to the zone number, and the second digit corresponding to any
system trouble condition. Only the first digit is programmable.

Table 4-2: Format Selection Address Explanation


50475 Rev D1 7/22/9 P/N 50475:D1
73
4.4.1 Transmittal Priorities
The integral communicator transmits highest priority events first. Events in terms of
priority are listed below in descending order:

1: Alarms (Highest Priority Level)


Pull Stations
Waterflow
Smoke Detector
Other Alarm Types
2: Supervisory Zone
3: System Troubles
Zone/NAC Disabled
Fire Drill
AC Fail (After Delay)
Zonal faults
Earth fault
Low battery/No battery
Telephone line fault
Notification Appliance Circuits fault
Operating Instructions

Communication Trouble
Printer Trouble
Annunciator Trouble
EIA-485 Fault
System off Normal
Process Monitoring Alarm
4: Restoral Reports
Zone Alarm
Supervisory
Zone(s) Enabled
Fire Drill
AC
Zone Fault
Earth
Battery
Telephone Line
Notification Appliance Circuits
Communication
Printer
Annunciator
EIA-485
System off Normal
Process Monitoring Restored
5: System Test (Lowest Priority)

Red LEDs are provided on the control panel circuit board to identify which
telephone line is activated. Also a green LED (labeled 'Kissoff') will turn on
whenever the control panel has successfully transmitted reports to the Central
Station. The 'Kissoff' LED may turn on several times during communications with a
Central Station.

74 50475 Rev D1 9/22/99 P/N 50475:D1


The chart below shows UL listed receivers compatible with the SFP-1024:

Osborne Hoffman

6000/6500 (5)
Models 1 & 2
Silent Knight

CS-4000 (3)

Surguard
3000R (7)
Radionics

MLR-2 (9)
CP220FB

Sescoa
Ademco
685 (1)
Format #

9000

FBI
(Addresses 16 & 42)

ITI
0 4+1 Ademco Express ✔ ✔ ✔
1 4+2 Ademco Express ✔ ✔ ✔
✔(8) ✔ ✔
2 3+1/Standard/1800/2300 ✔ ✔ (2) ✔ ✔ (4) ✔ ✔
✔(5,6) ✔ ✔
3 3+1/Expanded/1800/2300 ✔ ✔ (2) ✔ ✔ (4) ✔ ✔ ✔
4 3+1/Standard/1900/1400 ✔ ✔ (2) ✔ (4) ✔ ✔ ✔

Operating Instructions
5 3+1/Expanded/1900/1400 ✔ ✔ (2) ✔ (4) ✔ ✔ ✔
6 4+1/Standard/1800/2300 ✔ ✔ (2) ✔ ✔ (4) ✔ ✔ (5) ✔ ✔
7 4+1/Expanded/1800/2300 ✔ ✔ (2) ✔ (4) ✔ ✔ ✔
8 4+1/Standard/1900/1400 ✔ ✔ (2) ✔ (4) ✔ ✔ ✔
9 4+1/Expanded/1900/1400 ✔ ✔ (2) ✔ (4) ✔ ✔ ✔
A 4+2/Standard/1800/2300 ✔ ✔ (2) ✔ ✔ (4) ✔ ✔ (5) ✔ ✔
B 4+2/Expanded/1800/2300 ✔ ✔ (2) ✔ (4) ✔ ✔ ✔
C 4+2/Standard/1900/1400 ✔ ✔ (2) ✔ (4) ✔ ✔ ✔
D 4+2/Expanded/1900/1400 ✔ ✔ (2) ✔ (4) ✔ ✔ ✔
E Ademco Contact ID ✔ ✔ ✔ ✔

(1) With 685-8 Line Card with Rev 4.4d software.


(2) With 9002 Line Card Rev 9035 software or 9032 Line Card with 9326A
software.
(3) Rev. 4.0 software.
(4) FBI CP220FB Rec-11 Line Card with Rev 2.6 software and a
memory card with Rev 3.8 software.
(5) Model 6500 with Rev 600 software.
(6) Model 6000 with Rev 204 software.
(7) With Rev B control card at Rev 1.4 software and Rev C line card at Rev
1.5 software.
(8) Model 2 only.
(9) Version 1.62 software.

Table 4-3: Compatible UL Listed Receivers

50475 Rev D1 7/22/9 P/N 50475:D1


75
5.0 Ser vicing
Servicing
5.1 Walk Test Mode The SFP-1024 provides the capability to perform a one-man walk test of the system
without triggering the communicator, the ACM-8R zone relays, the system
annunciators or the alarm output relay. Walk Test allows for testing of the 10 zones
(initiating circuits). Zones defined as Reset, Acknowledge, Silence, Drill, Auto-
resettable Process Monitoring, or Process Monitoring are not part of the one-man
Walktest function. Zones defined as Pull Station, N.O. Contact, two or four-wire
smoke detector, waterflow or supervisory are functionally tested in Walktest mode.
An audible or silent walktest may be performed.

For an audible walktest, the first initiating device activated on a zone will cause the
Notification Appliance Circuits to turn on for four seconds. Subsequent device
activations on the same zone will cause the Notification Appliance Circuits to turn
on for one second. Any smoke detectors that are activated will be reset. Zonal faults
(open circuits) will cause the appliance circuit to remain on steadily. Prior to entering
Walk Test Mode, check to be certain that all system faults have been cleared.

Note: Trouble relays will be activated while the control panel is in this mode.
Placing the control panel into walk test mode will only be possible if the system has
no active alarms.

Pressing the MODE key followed by the 4-digit code 9255 [ENTER/STORE]
will place the control panel into Walk Test Mode.

☛ 9255 spells 'WALK' on a Touch-Tone® phone.

An S will be displayed on the left most character and a flashing 0 on the far right
Ser
Servicing

character. For audible walktest, press the [ENTER/STORE] key. For silent
walktest, press the 1 key followed by the [ENTER/STORE] key.
vicing

Once in Walk Test Mode, the control panel will immediately:

• Blink the trouble LED.


• Activate the trouble relay.
• If an audible walktest is performed, the SFP-1024 will turn on the Notification
Appliance Circuits for four seconds for the first alarm on a zone. Subsequent
alarms will sound for one second. Troubles cause the Notification Appliance
Circuits to remain on. For a silent walktest, all NAC outputs remain off.
• Disable the alarm relay.
• Display all alarm conditions as they occur.
• Display all zone troubles as they occur.
• Display all system troubles as they occur.
• Transmit 'off normal' message to Central Station(s).
• Continue to communicate any events not acknowledged at a Central Station
prior to entering Walk Test Mode.

During Walk Test Mode, zonal activity is displayed in real time as it occurs. At the
end of Walk Testing the system, the display will show the last event that occurred.
To view all events stored during Walk Test, use the Up Arrow, Down Arrow and 1st
Event keys. The Down Arrow key moves the Walk Test list to show older - previous
events. The Up Arrow key moves the Walk Test list to show newer - most recent
events. Pressing the 1st Event key at any time will cause the display of the first event
stored upon initial entry into Walk Test Mode. While in Walk Test Mode, the control
panel will store up to 256 events in the Walk Test File for later recall and display.

76 50475 Rev D1 9/22/99 P/N 50475:D1


A printer may be connected to the panel during Walk Test. All Walk Test events are
printed in real time as they occur.

Zone disable mode may be used while in Walktest mode. Should a faulty device
require repair, the zone may be disabled while the repair is performed. This allows
the user to return the system to Normal mode enabling all other zones. This also
prevents triggering of a false alarm.

To return the control panel to normal mode, press the mode key, the numbers 6676
and the [ENTER/STORE] key. To go to any other mode, press the MODE key
followed by the appropriate four digit code. To go from silent walktest to audible
walktest (or vice versa), press the MODE key followed by the [ENTER/STORE]
key. S__0 or S__1 will appear in the display. Simply alter the '0' or '1' entry then
press the [ENTER/STORE] key. Any delay between key entries greater than 10
seconds causes the control panel to remain in Walk Test Mode.

The control panel will automatically revert back to Normal Mode if no system
activity has occurred for 60 minutes. This would include pressing any keys or
activity on any zone. Exiting Walk Test mode leaves the Walk Test file in memory
such that it may be printed in Print Mode. Subsequent entries into Walk Test mode
delete the Walk test file.

During an audible Walktest, if a device remains latched in alarm (such as a Pull


Station that is not reset after activation), subsequent testing of devices on the same
zone will not trigger the NACs. Be certain to reset or clear each device after testing.

Note: Remote site upload or download is possible when the system is in Walk Test
mode.

5.2 History Mode All Normal Mode events are stored in a History File list for future recall. Recall is

Servicing
vicing
possible via the 4-character display or via an optional printer. See the following page
for a list and description of each event displayed.

The History File list is a first-in first-out (FIFO) buffer. Only the most recent events

Ser
may be called up from memory. Old events will be overwritten i.e., pushed out of the
FIFO.

The number of stored events is 256. The History File is kept in E2 memory. Complete
power loss will not erase the list.

Pressing the MODE key followed by 4478 [ENTER/STORE] places the control
panel into History Mode. This will not occur if there are any active alarm conditions
present. The fire protection remains active in History mode. If an alarm occurs, the
panel will automatically exit History mode. The event displayed, is the most recent
event.
☛ 4478 spells HIST on a Touch-Tone® phone.

Once in History Mode, the control panel will:

• Display all events as they occurred since the last time the History File list was
cleared. The most recent event will be displayed first.
• Ignore all other keys other than those mentioned in this section.
• Continue to communicate any events not previously acknowledged at the
Central Station prior to entering History Mode.

The Down Arrow key moves the History File to show older-previous events. The Up
Arrow key moves the History file to show newer-most recent events.
50475 Rev D1 7/22/9 P/N 50475:D1
77
Shown below is the list of messages as they will appear on the display:

DISPLAY EVENT DISPLAY EVENT


ACn_ Acknowledge key pressed F_85 Annunciator Bus Fault
A__1 Zone 1 Alarm d__1 Zone 1 disabled
A__2 Zone 2 Alarm d__2 Zone 2 disabled
A__3 Zone 3 Alarm d__3 Zone 3 disabled
A__4 Zone 4 Alarm d__4 Zone 4 disabled
A__5 Zone 5 Alarm d__5 Zone 5 disabled
A__6 Zone 6 Alarm d__6 Zone 6 disabled
A__7 Zone 7 Alarm d__7 Zone 7 disabled
A__8 Zone 8 Alarm d__8 Zone 8 disabled
A__9 Zone 9 Alarm d__9 Zone 9 disabled
A_10 Zone 10 Alarm d_10 Zone 10 disabled
SU_1 Supervisory 1 Alarm drLL Fire Drill
SU_2 Supervisory 2 Alarm E__1 Enable Zone 1
SU_3 Supervisory 3 Alarm E__2 Enable Zone 2
SU_4 Supervisory 4 Alarm E__3 Enable Zone 3
SU_5 Supervisory 5 Alarm E__4 Enable Zone 4
SU_6 Supervisory 6 Alarm E__5 Enable Zone 5
SU_7 Supervisory 7 Alarm E__6 Enable Zone 6
SU_8 Supervisory 8 Alarm E__7 Enable Zone 7
SU_9 Supervisory 9 Alarm E__8 Enable Zone 8
SU10 Supervisory 10 Alarm E__9 Enable Zone 9
PA_1 Process Alarm Zone 1 E_10 Enable Zone 10
PA_2 Process Alarm Zone 2 d_b1 Disable bell 1
PA_3 Process Alarm Zone 3 d_b2 Disable bell 2
PA_4 Process Alarm Zone 4 d_b3 Disable bell 3
PA_5 Process Alarm Zone 5 d_b4 Disable bell 4
PA_6 Process Alarm Zone 6 E_b1 Enable bell 1
PA_7 Process Alarm Zone 7 E_b2 Enable bell 2
PA_8 Process Alarm Zone 8 E_b3 Enable bell 3
Ser
Servicing

PA_9 Process Alarm Zone 9 E_b4 Enable bell 4


PA10 Process Alarm Zone 10 PH_1 Primary C. S. #
vicing

_AC_ AC Loss Communication Fault


F__1 Zone 1 Fault PH_2 Secondary C. S. #
F__2 Zone 2 Fault Commu nication Fault
F__3 Zone 3 Fault no_b No Battery
F__4 Zone 4 Fault Lo_b Low Battery
F__5 Zone 5 Fault SILE Silence Switch pressed
F__6 Zone 6 Fault SIL1 NAC/Bell #1 Silenced
F__7 Zone 7 Fault SIL2 NAC/Bell #2 Silenced
F__8 Zone 8 Fault SIL3 NAC/Bell #3 Silenced
F__9 Zone 9 Fault SIL4 NAC/Bell #4 Silenced
F_10 Zone 10 Fault no_1 Primary Phone Line Fault
bEL1 Bell 1 Fault (open or short) no_2 Secondary Phone Line Fault
bEL2 Bell 2 Fault (open or short) rES_ Reset Switch pressed
bEL3 Bell 3 Fault (open or short) POr Power On Reset (unit was
bEL4 Bell 4 Fault (open or short) powered off completely i.e.
F__E Earth Fault no AC and no battery)
F__A Annunciator Fault
F__P Printer Fault

To erase the list from E2 memory, press the SILENCE key twice before exiting the History Mode. A lack of keyboard
activity for a period of 10 minutes will cause the control panel to return to normal mode. If a printer is connected to
the panel, the history file will be printed upon successful entry into History Mode and a list of the most recent 256
events, time and date stamped, will print out.

Note: Remote site upload or download is possible when the system is in History mode.

78 50475 Rev D1 9/22/99 P/N 50475:D1


5.3 Troubleshoot In this mode, system voltages may be displayed on the 4-character display. An
Mode internal voltmeter measures the voltage present at: (1) the zone inputs, (2) the AC
power input (3) the battery terminal leads, (4) NAC #1, (5) NAC #2, (6) NAC #3, (7)
NAC #4 and (8) Resettable 24 volt power. A lack of keyboard activity for a period
of 20 minutes will cause the control panel to return to normal mode.

To enter the Troubleshoot Mode, press MODE 8768 and [ENTER/STORE]


[ENTER/STORE].
☛ 8768 spells TROU on a Touch-Tone® phone.

Once in this mode, the control panel will:

• Blink the FACP trouble LED.


• Blink all remote annunciator LEDs
• Activate the FACP trouble relays if programmed for trouble operation.
• Disable the Notification Appliance Circuits.
• Output all troubleshoot voltage readings to external printer.
• Disable the alarm relay.
• Transmit the 'off normal' message to the Central Station(s).
• Continue to communicate any events not yet acknowledged at the
Central Station prior to entering Troubleshoot Mode.

The UP Arrow key, Down Arrow key and 1st EVENT keys do not function in
this mode.

Zones Pressing 01 through 10 followed by [ENTER/STORE] displays the zone voltage


of the selected zone. Listed below are the nominal threshold voltages for each zone:

Zone # Normal w/E.O.L. Shorted Open CKT.


1 through 10 23.5V 0.00V 25.4V

Servicing
vicing
Readings will vary proportionately depending upon system load and AC line voltage.

A C Line Pressing A [ENTER/STORE] displays the AC input voltage as shown below. The
following lists the AC line voltage range. The AC ON indicator will turn off when the

Ser
AC line voltage drops below the Low Line threshold, and the trouble LED will turn on.

AC Line Voltage Low Line Normal High Line


SFP-1024: 102VAC 115VAC 132VAC
SFP-1024E: 204VAC 220VAC 264VAC

Batter
Batteryy Pressing B [ENTER STORE] will display the Battery Voltage. Shown below are the
critical battery threshold conditions:

Normal Low Battery No Battery


Battery Voltage: 27.6V 20.4V < 17.4V

Note: Make measurements after allowing 48 hours to charge depleted batteries. If


batteries do not show normal readings, replace them.
IMPORTANT
IMPORTANT:: The battery charger will turn off when the battery voltage drops to 17.4
VDC or less (No Battery condition). A battery with a higher voltage must be installed to
turn the charger back on.

Telephone Lines Pressing C for touchtone dialing or D for rotary dialing, followed by [ENTER/
STORE] causes seizure of the Primary phone line which in turn lights the red LED
signifying Primary phone line active. After a delay of three seconds, the control
panel goes off hook to acquire a dial tone.

50475 Rev D1 7/22/9 P/N 50475:D1


79
The control panel keypad may be used as a telephone touchpad for number dialing.
Once the first digit is pressed, the display will move the C or D character one
position to the left, while placing the digit to be dialed on the farthest right display
position. Continue to press the phone numbers to be dialed. Successive depressions
of the [ENTER/STORE] key hangs up and picks up the phone (places the phone on
or off the hook).

The secondary phone line may be tested by pressing the E key for touchtone dialing
or the F key for rotary dialing and then following the same procedure used for the
primary phone line.

A handset may be temporarily connected across transformer T1 as indicated in


Figure 5-1. The handset, when connected across T1, may be used only as an
amplifier/speaker and telephone with the control panel used for number dialing.

Note: Remote site upload or download is not possible while testing the phone lines in
this portion of Troubleshoot mode.

NA
NACC 1, 2, 3 & 4 Pressing B1 followed by [ENTER/STORE] displays the voltage on NAC #1.
Pressing B2 followed by [ENTER/STORE] displays the voltage on NAC #2.
Pressing B3 followed by [ENTER/STORE] displays the voltage on NAC #3.
Pressing B4 followed by [ENTER/STORE] displays the voltage on NAC #4.
NAC voltage readings are nominally -2.32 volts when an EOL resistor of correct
value is in place. A reading of 0.00 volts appears for shorts, -4.50 volts for opens.
Intermediate readings are also available.

Resettab le P
Resettable o w er
Po Pressing the RESET key followed by [ENTER/STORE] displays the resettable 24
volt power. Resettable 24 volt power must read 24 volts + or - 10%.
Ser
Servicing

5.4 Lamp Test To perform a Lamp Test, press MODE then 5267 followed by [ENTER/STORE]
[ENTER/STORE].
This will test all system LEDs on the FACP. The LEDs will stay on for five seconds,
then the control panel will return to normal mode.
vicing

☛ 5267 spells LAMP on a Touch-Tone® phone.

Both Primary and


Secondary Lines

Figure 5-1: Handset/Speaker Connection

80 50475 Rev D1 9/22/99 P/N 50475:D1


5.5 Print Mode See Section Two, Figure 2-13 for proper PRT-24 Interface module connection to
main circuit board before proceeding.

A printer may be temporarily or permanently connected to the panel. Program


address '4' in Program Mode Level 3 to a '1' to enable printer supervision. Once
enabled, normal system status as well as panel operations will be printed. If the
printer connection is removed, the system trouble LEDs will blink, the system piezo
sounders will pulse and the 4-character system LED display will read F__P
F__P.

Selecting Printer Mode by pressing the MODE key followed by 7746 then [ENTER/
STORE] will cause the display to read Prn and the following to be printed:

1 Entire program Entries


2 History File
3 Walktest File
4 Troubleshoot Mode Voltages
5 Current System Status

All activity is time and date stamped.

The fire protection remains active while in print mode. Remote site upload or
download is allowed while in Print mode. An alarm on any zone will take priority
causing the panel to exit print mode.

5.6 Printer Output This section illustrates sample printouts for various panel modes.

Real Time Status


06-26-1996 14:15:10
Zone 1 Verifying 2-Wire Smoke Detector Active 06-26-1996 14:15:20

Servicing
vicing
Zone 1 2-Wire Smoke Detector Active 06-26-1996 14:15:24
Zone 2 Pull Station Active 06-26-1996 14:15:29
Zone 3 N.O. Contact Device Active 06-26-1996 14:15:34
Zone 4 Supervisory Active 06-26-1996 14:15:37

Ser
Zone 5 Waterflow, Silenceable Active 06-26-1996 14:15:45
Zone 6 Process Monitoring Active 06-26-1996 14:15:49
System Silenced 06-26-1996 14:15:53
NAC 1 Silence 06-26-1996 14:15:56
NAC 2 Silence 06-26-1996 14:15:59
Zone 1 Alarm Cleared 06-26-1996 14:16:03
Low Battery Detected 06-26-1996 14:16:09
Normal Battery 06-26-1996 14:16:15
Loss of AC Power 06-26-1996 14:16:19
AC Power Restore 06-26-1996 14:16:42
Drill Mode Entered 06-26-1996 14:16:51
System Reset 06-26-1996 14:17:25
Drill Mode Cleared 06-26-1996 14:17:33

Entering Walktest Mode -


06-26-1996 14:32:15
Zone 2 Pull Station Active 06-26-1996 14:33:20

50475 Rev D1 7/22/9 P/N 50475:D1


81
Entering Trouble Shoot Mode 06-26-1996 14:47:12

Trouble Shoot Mode Data


06-26-1996 14:47:12
Zone 1 Voltage = 25.20
Zone 2 Voltage = 25.18
Zone 3 Voltage = 25.20
Zone 4 Voltage = 25.20
Zone 5 Voltage = 25.18
Zone 6 Voltage = 25.18
Zone 7 Voltage = 25.18
Zone 8 Voltage = 25.20
Zone 9 Voltage = 25.20
Zone 10 Voltage = 25.20
AC Line Voltage = 120.9
Battery Voltage = 27.20
NAC 1 Voltage = -2.09
NAC 2 Voltage = -2.29
Resettable 24 Volts = 26.03

Entering Lamp Test Mode -


06-26-1996 15:03:10

Entering Program Mode -


06-26-1996 15:08:13
Ser
Servicing
vicing

82 50475 Rev D1 9/22/99 P/N 50475:D1


6.0 Remote Site Upload/Do wnload
Upload/Download
The control panel may be programmed or interrogated off site via the public
switched telephone network. Any personal computer with Windows® 3.1 or greater
or Windows® 95, with a 1200 Baud Hayes™ compatible modem and Notifier Upload/
Download software P/N PK-1024, may serve as a Service Terminal. For details on
the remote site upload/download software package, refer to the PK-1024 Manual.
The Upload/Download software allows the following:

ü Download of the entire program


ü Download of an individual program item at Levels 1 - 4
ü Upload of the entire program
ü Upload of an individual program item at Levels 1 - 4
ü Download of a single program item (such as a Central Station phone
number)
ü Upload of the entrie program plus history file, walktest data, current status,
system voltages and time & date
ü Upload individually the history file, walktest data, current status, system
voltages or time & date
ü Real-time upload, either continuous or 'snapshot' (one time), of current
status or system voltages
ü Execution of control panel functions: Trouble Silence, Manual Evacuate,
Manual Evacate Restore, Zone/NAC Disable, Zone/NAC enable and Set
Time & Date.

WARNING: Changes to program entries occur as a result of the downloading process.


After successful downloading, make certain to perform the following steps:

1. Print out all programmed data via print mode or manually view
programmed entries and compare to intended program data.

Upload/Download
wnload
2. Test all affected panel operations.
3. Immediately correct any problems found.

6.1 Do wnloading
Downloading Any time that the control panel is downloaded, whether initiated at the jobsite or

Remote Site Upload/Do


Prog
Progrr am: remotely, a secret code (Factory Default 0000) is verified between the control panel
and the Service Terminal. Changing the Secret Code may only be accomplished at
General
the Service Terminal and subsequently loaded into the control panel. Future upload
or download requests cause verification of the secret code by the control panel
before processing of data is allowed. If the secret code is not verified, the control
panel will terminate the request immediately.

While the control panel is communicating with the Service Terminal, the panel's
green Modem LED and one of the red Line Seize LEDs will remain on steady. At
the conclusion of a successful download transaction, the green Kissoff LED will
come on steady for one second. Upon termination of communication, the green
Modem LED will turn off and the red Line Seize LED will turn off.

50475 Rev D1 7/22/9 P/N 50475:D1


83
In order to download the panel (whether initiated at the jobsite or remotely) the
following must be true:

ü The control panel may be in any mode of operation including Normal,


Program, History, Walktest, Print, Troubleshoot or Lamp Test. It is also
possible during any of the function modes including Disable, Enable and Drill.
Downloading is not possible if the communicator is active during Central
Station communications or while testing the phone lines while in Troubleshoot
mode.

ü There cannot be any active communications ongoing with a Central Station


receiver.

ü All active events must be successfully 'Kissed-off' by the Central Station(s).


(The Communicator must be in a standby state with no new information
waiting to be transmitted to a Central Station).

Two basic communication mechanisms are supported as follows:

ü Download with callback - The Service Terminal calls the control panel. The
control panel answers the call, confirms the calling party then hangs up. The
Service Terminal then waits for a callback from the control panel. After the
control panel calls the Central Station and successfully reports that a request for
downloading has been received, the control panel calls the Service Terminal
back. Upon secret code verification, data transfers occur. When the data
transfers are completed and the Service Terminal disconnects from the control
panel, the panel calls the Central Station back to confirm either successful or
nonsuccessful results.

ü Download with callback disabled - The Service Terminal calls the control
panel. No hangup sequence occurs. Data transfers proceed.
Remote Site Upload/Do

Note: Callback enable/disable is controlled by the master user at the Service Terminal
on a per call basis.

With program address location 56 set to '1' in Program Mode Level 1, anytime a
download with callback is initiated, the control panel will first either contact the primary
Central Station or contact both the primary and secondary Central Stations or contact
the first available Central Station Phone Number to report a 'request for up/download'
Upload/Download

message (depending upon the program entry in Program Level 4 address location 42).
Once the request is 'Kissed-off' by the Central Station(s), the control panel will then call
the appropriate Service Terminal and begin the downloading process.

With program address location 56 set to '1' in Program Mode Level 1, anytime a
download with callback disabled is initiated, the control panel and the Service Terminal
will communicate and transfer data without first contacting a Central Station. When the
wnload

data transfers are completed and the control panel disconnects from the Service
Terminal, the panel will call the Central Station and report:

1) Upload/download request received


2) Upload and/or download successful or
3) Upload/download failed

To prevent the 'request for up/download' message(s) from being reported to the Central
Station(s), make certain to leave address 56 = 0 or disable all upload/download reports
back to both Central Stations. Refer to Tables 3-2 through 3-7 for additional
information.
84 50475 Rev D1 9/22/99 P/N 50475:D1
During the downloading process, the fire protection remains active
active.. Should a
system trouble or alarm condition occur, the control panel immediately terminates
downloading and processes the trouble or alarm locally and transmits the
information to the Central Station(s).

6.1.1 Security Remote site upload and download with the control panel has been carefully designed
Features to include key security features to insure proper functionality. The key features are
listed and explained below.

Secret Code Verification


A secret code is stored in the control panel by a Service Terminal to prevent
unauthorized access. The secret code is created at the Service Terminal by a Master
user and cannot be viewed or changed by anyone other than a Master user. Viewing
of the secret code is prohibited at the control panel. Prior to allowing an upload or
download of data, the control panel will verify the secret code transmitted by the
Service Terminal.

Time-out at Control Panel


Upon answering an incoming call on either the primary or secondary Central Station
phone line, the panel will listen for a modem connection signal. If this signal is not
received within 30 seconds, the panel will disconnect the call.

Upon successful connection (i.e. secret code verified and callback complete, if
applicable), if no communication occurs within two minutes, the panel will
disconnect the call.

Callback to Service Terminal


Any time that the panel is remotely requested to allow an upload or download with
callback, it will confirm the source of the incoming call, hang-up and call the calling
party (Service Terminal phone number) back.

Panel Identification Number (future)

Upload/Download
wnload
The panel identification number will be used in the future to identify the panel to the
Service Terminal (when the panel calls the Service Terminal) automatically.

Calls initiated at the FACP must be coordinated at the Service Terminal manually.

Remote Site Upload/Do


Note that the Service Terminal will not pickup the incoming call unless operating on
the communications screen. The Service Terminal will not recognize an FACP
initiated call unless the secret code is at the factory default settings.

Error Checking
As each block of data is received by the control panel, it is checked for accuracy. If
an error is detected, the block is retransmitted until correct, up to a maximum of four
times. If the Secret Code is not verified and four errors occur, the call is
disconnected and the report that the upload/download was not successful is called to
the Central Station(s).

Central Station Acknowledge


There is an option whereby the control panel will report to one or both Central
Stations that a request for up or downloading has been received prior to processing
the call. This is called the 'callback' option. If the Central Station(s) does not
acknowledge receipt of this request, up or downloading is prohibited. If
acknowledged by the Central Station(s), another message is transmitted informing
the Central Station(s) that: (1) downloading was successful, (2) uploading was
successful or (3) uploading/downloading was not successful.

50475 Rev D1 7/22/9 P/N 50475:D1


85
Data Protection/Integrity
Options allow programming of single data entries, single programming levels (1 - 4)
and the entire programming of all four levels simultaneously. Use caution when
selecting programming choices and verify all entries via an upload or manual check at
the FACP. Data blocks containing user programming options are protected from
partial programming due to faulty phone connections, line noise and other errors.

6.2 Do wnloading
Downloading Before initiating the Download procedure, make certain that the control panel is: (1)
Initiated at in Normal mode, (2) Central Station communications are off or Main Panel Options
programming location 56 = 0, and (3) the communicator is in the standby state; red
Control P anel
Panel
Line Seize LEDs are off, green Modem and Kissoff LEDs are off.

Place the control panel into Program mode and program one or both of the Service
Terminal phone numbers. It is also advisable at this time to coordinate this call with
the Service Terminal operator to allow the Service Terminal operator to easily identify
the incoming call.

Exit the Program mode and return the panel to Normal mode. Press the Mode key
followed by the 4-digit code 3696 [ENTER/STORE]
[ENTER/STORE].

☛ 3696 spells DOWN on a Touch-Tone® phone.

The display to the far left will flash the letter 'S'. Press the digit '1' for Service
Terminal phone #1 or '2' for Service Terminal #2, followed by [ENTER/STORE]
[ENTER/STORE].
The control panel will now call the appropriate Service Terminal phone number. With
the Service Terminal set up with the correct download customer file and operating in
the communications window, the downloading process may begin.

Once the called Service Terminal accepts the incoming call (control panel) and verifies
the secret code, the downloading process is allowed to continue. Downloading
Remote Site Upload/Do

progresses until all programmed information has been successfully loaded into the
control panel. Communication terminates upon the Service Terminal hanging up or
upon the FACP hanging up after a two minute timeout following completion of data
transfer.

6.3 Do wnloading
Downloading Before initiating the Download procedure, make certain that the communicator is in
Initiated at a the standby state; red Line Seize LEDs are off, green Modem and Kissoff LEDs are off.
Ser vice
Service
Upload/Download

Once an incoming call is accepted/answered by the control panel, the panel will:
Ter minal
erminal
1. Establish basic modem connection
2. Verify secret code
3. Verify callback vs. no callback request from the Service Terminal. If callback
is requested then perform steps 4 through 10, if no callback is requested then
perform steps 9 and 10 only
wnload

4. Identify the Service Terminal location


5. Hang-up/Disconnect call
6. Call the Central Station(s) and transmit a request for upload/download
message (if programmed to do so). If this message is accepted, the control
panel will proceed to the next step
7. Return call to Service Terminal
8. Verify secret code
9. Begin downloading
10. Upon completion of download, call Central Station(s) back and report a
successful download or failed upload/download status (if programmed to do
so).
86 50475 Rev D1 9/22/99 P/N 50475:D1
6.4 Uploading Items that may be uploaded from the control panel to a Service Terminal are:
Initiated at a
• All or portions of programmed data plus the real time clock, time and date
Ser vice
Service
• Entire Walk Test data file in real-time continuous or as a 'snapshot'
Ter minal
erminal • Troubleshoot system voltages in real-time continuous or as a 'snapshot'
• Entire 256 event History file
• Current system status in real-time continuous or as a 'snapshot'

Uploading is possible at any time provided the following conditions are true:

ü The control panel may be in any mode of operation. Uploading is not


possible if the communicator is active or while testing the phone lines
while in troubleshoot mode.

ü There cannot be any active communications ongoing with a Central


Station receiver.

ü All active events must be successfully 'Kissed-off' by the Central


Station(s). (The Communicator must be in a standby state with no new
information waiting to be transmitted to a Central Station).

Once an incoming call is accepted/answered by the control panel, the panel will:

1. Establish basic modem connection


2. Verify secret code
3. Verify callback vs. no callback request from the Service Terminal. If
callback is requested then perform steps 4 through 10, if no callback is
requested then perform steps 9 and 10 only
4. Identify the Service Terminal location
5. Hang-up/Disconnect call
6. Call the Central Station(s) and transmit a request for upload/download
message (if programmed to do so). If this message is accepted, the control

Upload/Download
wnload
panel will proceed to the next step
7. Return call to Service Terminal
8. Verify secret code
9. Begin uploading

Remote Site Upload/Do


8. Upon completion of upload, call Central Station(s) back and report a
successful upload or failed upload/download status (if programmed to do
so).

During the uploading process, the fire protection remains active


active.. Should a system
trouble or alarm condition occur, the control panel immediately terminates
uploading and processes the trouble or alarm locally and transmits the information
to the Central Station(s).

6.5 Sim ultaneous


Simultaneous Uploading and downloading may take place on a single telephone call. Control and
Data Tr ansf ers
ansfers selection of the data transaction is coordinated at the Service Terminal. This
eliminates multiple phone calls, allows instant verification of downloaded data files
and simplifies the overall process.

50475 Rev D1 7/22/9 P/N 50475:D1


87
Appendix A: Batter
Batteryy Calculations

Use the Total Standby and Alarm Load Currents calculated in Tables A-2A and A-2B for the following battery
calculation.

Standby Load Required Standby Time in Hours


Current (Amps) X (24 or 60 Hours) = ______________
[ ] [ ]

Alarm Load Required Alarm Time in Hours


Current (Amps) X (i.e. 5 min. = 0.084 hours) = ______________
[ ] [ ]

Add Standby and Alarm Load for Required Ampere Hour Battery = ______________

Multiply by derating factor of 1.2 X 1.2 ______________

Note:
1) 12 Ampere Hour battery can be located in the Backbox.
2) 17 Ampere Hour batteries require the BB-17 Battery box.
Appendices

88 50475 Rev D1 9/22/99 P/N 50475:D1


The Main Power Supply

The SFP-1024 provides regulated power for operating the fire alarm control panel, operating external devices, and
operating the standby battery. The power for operating external devices is limited. Use Table A-2A (standby or
non-alarm) and Table A-2B (alarm) to determine if external loading is within the capabilities of the power supply.

Concerning 4-wire smoke detectors: Be sure to power detectors from TB2, Terminals 3 and 4.

Table A-2A: Regulated Load in Standby @24 VDC


External Devices connected to TB2 only

Total
# of Current
Device Type Current
Devices (Amps)
(Amps)
Main Circuit Board 1 X 0.138 = 0.138
LED-10IM (1 max.) X 0.017 =
PRT-24 (1 max.) X 0 = 0
CAC-10F (1 max.) X 0.004 =
NAC-REM (1 max.) X 0.002 =
2-wire Detector
[ ] X [ ]1 =
Heads
4-wire Detector
[ ] X [ ]1 =
Heads
Power Supervision
[ ] X 0.025 =
Relays
Current Draw from3
TB2 (nonalarm) =

Sum Column for Standby Load = Amps

Appendices
Note:
1) Refer to the Device Compatibility Document for 2-wire smoke detector standby current.
2) Must use compatible listed Power Supervision Relay.
3) The total standby current must include both the resettable (TB2 Terminals 3 & 4) and nonresettable
(TB2 Terminals 1 & 2) power. Caution must be taken to ensure that current drawn from these outputs
during alarm does not exceed maximum ratings specified (see Table a-2B).

50475 Rev D1 7/22/9 P/N 50475:D1


89
Table A-2B: Regulated Load in Alarm @24 VDC

Total
# of Current
Device Type Current
Devices (Amps)
(Amps)

Main Circuit Board 1 X 0.245 = 0.2454

LED-10IM (1 max.) X 0.017 =


PRT-24 (1 max.) X 0 = 0
CAC-10F (1 max.) X 0.020 =
NAC-REM (1 max.) X 0.075 =
4-wire Smoke1
[ ] X [ ] =
Detector
Power Super vision3
[ ] X 0.025 =
Relay
Notification5
[ ] X ______ =
Appliances
Notification6
[ ] X ______ =
Appliances
Current Draw1
from TB2 =
(alarm current)
Sum Column for Alarm Load 2 = Amps

Notes:
1) Current limitations of terminals:
• TB2, Terminals 1 and 2 = 0.500 amp, regulated filtered, 24VDC +/- 5%, 120HZ ripple @ 10 mV RMS.
Nonresettable Power (100 Hz ripple if SFP-1024E).
Appendices

• TB2, Terminals 3 and 4 = 0.500 amp, regulated filtered, 24VDC +/- 5%, 120HZ ripple @ 10 mV RMS.
Resettable Power (100 Hz ripple if SFP-1024E).

2) Total current draw listed above cannot exceed:


• 3.6 amps with standard transformer installed (only).
• 6.6 amps with both the standard and optional transformers installed.

3) Must use compatible listed Power Supervision Relay.

4) The current shown represents one zone on the Main Circuit Board in alarm. For all ten zones in alarm, the
current draw increases to 0.590 amps with communicator off and 0.610 amps with communicator on.

5) Current limitation of terminal TB4 circuits is 3 amps per Notification Appliance Circuit.

6) Current limitation of NAC-REM module circuits is 1.5 amps per Notification Appliance Circuit.

90 50475 Rev D1 9/22/99 P/N 50475:D1


Appendix B: Main Panel Options
Panel
Prog
Progrr amming Sheets
--- To enter Programming Level 1, press Mode: 7 7 6 4, '1', Enter

❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15

Addresses 00 to 15 store the Primary Central Station Phone Number. Enter 'F' to represent the end of the number.

❑ Primary Central Station Comm Format: Enter 0 - F.


16

❑ ❑ ❑ ❑ Primary Central Station Account Code: Valid keys are 0-F.


17 18 19 20

❑ ❑ ❑ ❑ Primary Central Station 24-Hour Test Time. Enter military time (i.e. 1400 for 2 pm).
21 22 23 24

❑ Primary Number Test Time Interval. Enter '0' for 24-hour; '1' - 12-hour; '2' - 8-hour; '3' for 6-hour.
25

❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41

Addresses 26-41 store the Secondary Central Station Phone Number. Enter 'F' to represent the end of the
number.

❑ Secondary Central Station Comm Format: Enter 0-F.


42

❑ ❑ ❑ ❑ Secondary Central Station Account Code: Valid keys are 0-F.


43 44 45 46

❑ ❑ ❑ ❑ Secondary Central Station 24-Hour Test Time. Enter military time (i.e. 1400 for 2 pm).
47 48 49 50

❑ Secondary Central Station Number Test Time Interval. Enter '0' for 24-hour; '1' - 12-hour; '2' - 8-hour; '3'
51
for 6-hour.
❑ Alarm Presignal. Enter '0' to disable; '1' to enable.
52

❑ ❑ ❑ Alarm Presignal Delay Time. Enter 0-179 additional seconds (default = 120 seconds).
53 54 55

❑ Communicator/ Fire Panel Selection. Enter '0' for fire panel only; '1' for fire panel/communicator opera-
56

tion.
❑ 57
Backup Reporting. Enter '0' to report to secondary phone # as backup only; '1' to report to both primary
and secondary phone number for all reports/messages; '2' reports go to first available receiver.
❑ Touchtone/Rotary Select for Primary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.

Appendices
58

❑ 59
Make/Brake Ratio for Primary Phone. Enter '0' for 67/33; '1' for 62/38.

❑ 60
Touchtone/Rotary Select for Secondary Phone. Enter '0' for touchtone dialing; '1' for rotary dialing.
❑ 61
Make/Brake Ratio for Secondary Phone. Enter '0' for 67/33; '1' for 62/38.

❑ 62
Future use.

❑ 63
Future use.

50475 Rev D1 7/22/9 P/N 50475:D1


91
❑ 64
Zone 1 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally-open
contact devices; '3' for supervisory devices; '4' for supervisory devices (auto resettable); '5' for water-
flow (silenceable); '6' for waterflow (nonsilenceable); '7' for process monitoring; '8' for auto-resettable
process monitoring; '9' for remote reset switch; 'A' for remote silence switch; 'B' for remote acknowl-
edge switch; 'C' for remote manual evacuate (drill) switch.
❑ 65
Zone 2 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open
contact devices; '3' for supervisory devices; '4' for supervisory devices (auto resettable); '5' for waterflow
(silenceable); '6' for waterflow (nonsilenceable); '7' for process monitoring; '8' for auto-resettable
process monitoring; '9' for remote reset switch; 'A' for remote silence switch; 'B' for remote acknowl-
edge switch; 'C' for remote manual evacuate (drill) switch.
❑ 66
Zone 3 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open
contact devices; '3' for supervisory devices; '4' for supervisory devices (auto resettable); '5' for water-
flow (silenceable); '6' for waterflow (nonsilenceable); '5' for waterflow (silenceable); '6' for waterflow
(nonsilenceable); '7' for process monitoring; '8' for auto-resettable process monitoring; '9' for remote
reset switch; 'A' for remote silence switch; 'B' for remote acknowledge switch; 'C' for remote manual
evacuate (drill) switch.
❑ 67
Zone 4 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open
contact devices; '3' for supervisory devices; '4' for supervisory devices (auto resettable); '5' for water-
flow (silenceable); '6' for waterflow (nonsilenceable); '7' for process monitoring; '8' for auto-resettable
process monitoring; '9' for remote reset switch; 'A' for remote silence switch; 'B' for remote acknowl-
edge switch; 'C' for remote manual evacuate (drill) switch.
❑ 68
Zone 5 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open
contact devices; '3' for supervisory devices; '4' for supervisory devices (auto resettable); '5' for water-
flow (silenceable); '6' for waterflow (nonsilenceable); '7' for process monitoring; '8' for auto-resettable
process monitoring; '9' for remote reset switch; 'A' for remote silence switch; 'B' for remote acknowl-
edge switch; 'C' for remote manual evacuate (drill) switch.
❑ 69
Zone 6 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open
contact devices; '3' for supervisory devices; '4' for supervisory devices (auto resettable); '5' for water-
flow (silenceable); '6' for waterflow (nonsilenceable); '7' for process monitoring; '8' for auto-resettable
process monitoring; '9' for remote reset switch; 'A' for remote silence switch; 'B' for remote acknowl-
edge switch; 'C' for remote manual evacuate (drill) switch.
❑ 70
Zone 7 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open
contact devices; '3' for supervisory devices; '4' for supervisory devices (auto resettable); '5' for water-
flow (silenceable); '6' for waterflow (nonsilenceable); '7' for process monitoring; '8' for auto-resettable
process monitoring; '9' for remote reset switch; 'A' for remote silence switch; 'B' for remote acknowl-
Appendices

edge switch; 'C' for remote manual evacuate (drill) switch.


❑ 71
Zone 8 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open
contact devices; '3' for supervisory devices; '4' for supervisory devices (auto resettable); '5' for water-
flow (silenceable); '6' for waterflow (nonsilenceable); '7' for process monitoring; '8' for auto-resettable
process monitoring; '9' for remote reset switch; 'A' for remote silence switch; 'B' for remote acknowl-
edge switch; 'C' for remote manual evacuate (drill) switch.
❑ 72
Zone 9 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open
contact devices; '3' for supervisory devices; '4' for supervisory devices (auto resettable); '5' for water-
flow (silenceable); '6' for waterflow (nonsilenceable); '7' for process monitoring; '8' for auto-resettable
process monitoring; '9' for remote reset switch; 'A' for remote silence switch; 'B' for remote acknowl-
edge switch; 'C' for remote manual evacuate (drill) switch.

92 50475 Rev D1 9/22/99 P/N 50475:D1


❑ 73
Zone 10 Function Select. Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open
contact devices; '3' for supervisory devices; '4' for supervisory devices (auto resettable); '5' for water-
flow (silenceable); '6' for waterflow (nonsilenceable); '7' for process monitoring; '8' for auto-resettable
process monitoring; '9' for remote reset switch; 'A' for remote silence switch; 'B' for remote acknowl-
edge switch; 'C' for remote manual evacuate (drill) switch.
❑ ❑ Waterflow Retard Timer. Enter 0-89 additional seconds.
74 75

❑ Alarm Verification. Enter '0' for no verification; '1' for verification of all 2- wire smoke zones.
76

❑ AC Loss Delay. Enter '0' for 6 hours; '1' for 7 hours; '2' for 8 hours; '3' for 9 hours; '4' for 10 hours; '5'
77

for 11 hours; '6' for 12 hours; '7' for 15 hours; '8' for 16 hours; '9' for 17 hours; 'A' for 18 hours; 'B' for 19
hours; 'C' for 20 hours; 'D' for 21 hours; 'E' for 22 hours; 'F' for 23 hours.
❑ 78
Programmable Relay #1 Definition. Enter '0' for alarm; '1' for supervisory; '2' for supervisory auto-
resettable; '3' for trouble; '4' for comm. fail; '5' for process monitoring; '6' for process monitoring auto-
resettable.
❑ 79
Programmable Relay #2 Definition. Enter '0' for alarm; '1' for supervisory; '2' for supervisory auto-
resettable; '3' for trouble; '4' for comm. fail; '5' for process monitoring; '6' for process monitoring auto-
resettable.
❑ 80
Notification Appliance Circuit #1 Selection: Enter '0' for enabled (silenceable); '1' for enable (nonsi-
lenceable); '2' to disable.
❑ 81
Silence Inhibit NAC #1. Enter '0' for no silence inhibit; '1' to inhibit silencing of NAC #1 for one minute.

❑ 82
Auto Silence NAC #1. Enter '0' for no auto silence; '1' for 5 minutes; '2' for 10 minutes; '3' for 15
minutes; '4' for 20 minutes; '5' for 25 minutes; '6' for 30 minutes.
❑ 83
Coding NAC #1. Enter '0' for steady; '1' for March Time (120 ppm); '2' for California (10 seconds on, 5
seconds off); '3' for Temporal (0.5 on, 0.5 off, 0.5 on, 0.5 off, 0.5 on, 1.5 off).
❑ 84
Notification Appliance Circuit #2 Selection: Enter '0' for enabled (silenceable); '1' for enable (nonsi-
lenceable); '2' to disable.
❑ 85
Silence Inhibit NAC #2. Enter '0' for no silence inhibit; '1' to inhibit silencing of NAC #2 for one minute.

❑ 86
Auto Silence NAC #2. Enter '0' for no auto silence; '1' for 5 minutes; '2' for 10 minutes; '3' for 15 min-
utes; '4' for 20 minutes; '5' for 25 minutes; '6' for 30 minutes.
❑ 87
Coding NAC #2. Enter '0' for steady; '1' for March Time (120 ppm); '2' for California (10 seconds on, 5
seconds off); '3' for Temporal (0.5 on, 0.5 off, 0.5 on, 0.5 off, 0.5 on, 1.5 off).

Appendices
❑ 88
Trouble Reminder. Enter '0' to disable; '1' to enable.

50475 Rev D1 7/22/9 P/N 50475:D1


93
Main Panel Options Prog
Panel Progrr amming Ref erence Sheet
Reference
Factor
actoryy Def ault Settings
Default
--- To enter Programming Level 1, press Mode: 7 7 6 4, '1', Enter


F ❑
F ❑
F ❑
F
00

F ❑
F
01

F ❑
F ❑
F
02

F ❑
F ❑
F ❑
03
F ❑
F ❑
F ❑
F
04 05 06 07 08 09 10 11 12 13 14 15

Addresses 00 to 15 store the Primary Central Station Phone Number. Enter 'F' to represent the end of the number.


E Primary Central Station Comm Format: ('E' for Ademco Contact ID Format).
16


0 ❑
0 ❑
17
0
18

0
19
Primary Central Station Account Code.
20


0 ❑
0 ❑
21
0
22

0
23
Primary Central Station 24-Hour Test Time. 0000 = 12:00 midnight.
24


0 Primary Central Station Number Test Time Interval. '0' for 24-hour.
25


F ❑
F
26

F
27

F
28
❑F
29
❑F ❑ F
30

F
31

F
32
❑F
33
❑F
34
❑F ❑
35
F ❑
F
36

F ❑
F
37 38 39 40 41

Addresses 26-41 store the Secondary C. S. Phone Number. Enter 'F' to represent the end of the number.


E Secondary Central Station Comm Format: ('E' for Ademco Contact ID Format).
42


0 ❑0
43
❑0
44
❑0
45
Secondary Central Station Account Code.
46


0 ❑0
47
❑0
48
❑0
49
Secondary Central Station 24-Hour Test Time. 0000 = 12:00 midnight.
50


0 Secondary Central Station Number Test Time Interval. '0' for 24-hour.
51


0 Alarm Presignal. 0 for no alarm presignal.
52


1 ❑
2 ❑
53
0
54
Alarm Presignal Delay Time. 120 second alarm presignal delay.
55


0 Communicator/ Fire Panel Selection. 0 for panel only operation.
56


0 Backup Reporting. '0' to report to secondary Central Station phone # as backup only.
57


0 Touchtone/Rotary Select for Primary Phone. '0' for touchtone dialing.
58


0 Make/Brake Ratio for Primary Phone. Enter '0' for 67/33.
59


0 Touchtone/Rotary Select for Secondary Phone. '0' for touchtone dialing.
60


0 Make/Brake Ratio for Secondary Phone. Enter '0' for 67/33.
Appendices

61


0 Future use. Leave default of '0'.
62


0 Future use. Leave default of '0'.
63


0 Zone 1 Function Select. '0' for 2-wire smoke detectors.
64


0 Zone 2 Function Select. '0' for 2-wire smoke detectors.
65


0 Zone 3 Function Select. '0' for 2-wire smoke detectors.
66


0 Zone 4 Function Select. '0' for 2-wire smoke detectors.
67


0 Zone 5 Function Select. '0' for 2-wire smoke detectors.
68

94 50475 Rev D1 9/22/99 P/N 50475:D1



0 Zone 6 Function Select. '0' for 2-wire smoke detectors.
69


0 Zone 7 Function Select. '0' for 2-wire smoke detectors.
70


0 Zone 8 Function Select. '0' for 2-wire smoke detectors.
71


0 Zone 9 Function Select. '0' for 2-wire smoke detectors.
72


0 Zone 10 Function Select. '0' for 2-wire smoke detectors.
73


0 ❑
0
74
Waterflow Retard Timer. '00' for no delay.
75


0 Alarm Verification. '0' = no alarm verification.
76


0 AC Loss Delay. '0' for 6 hours.
77


0 Programmable Relay #1 Definition. '0' for alarm.
78


3 Programmable Relay #2 Definition. '3' for trouble.
79


0 Notification Appliance Circuit #1 Selection: '0' for enabled (silenceable).
80


0 Silence Inhibit NAC #1. '0' for no silence inhibit.
81


0 Auto Silence NAC #1. '0' for no auto silence.
82


0 Coding NAC #1. '0' for steady, no coding.
83


0 Notification Appliance Circuit #2 Selection: '0' for enabled (silenceable).
84


0 Silence Inhibit NAC #2. '0' for no silence inhibit.
85


0 Auto Silence NAC #2. '0' for no auto silence.
86


0 Coding NAC #2. '0' for steady, no coding.
87


0 Trouble Reminder. '0', no trouble reminder.
88

Appendices

50475 Rev D1 7/22/9 P/N 50475:D1


95
Appendix C: Ev ent Codes/T
Event Codes/Trr ansmission For
For mat
ormat
Prog
Progrr amming Sheets
--- To enter Programming Mode Level 2, press Mode: 7 7 6 4, '2', Enter

4+2 Standar
Standardd and 4+2 Expr ess F
Express or
For ma
orma ts Pr
mats imar
Primar
imaryy Centr al Sta
Central tion
Station

❑ 0

1

2
❑ 3
❑ 4
❑ 5
❑ 6
❑ 7
❑ 8

9

10

11

12

❑ 13

14

15
❑ 16
❑ 17
❑ 18
❑ 19
❑ 20
❑ 21

22

23

24

25

❑ 26

27

28
❑ 29
❑ 30
❑ 31
❑ 32
❑ 33
❑ 34

35

36

37

38

❑ 39

40

41
❑ 42
❑ 43
❑ 44
❑ 45
❑ 46
❑ 47

48

49

50

51

❑ 52

53

54
❑ 55
❑ 56
❑ 57
❑ 58
❑ 59
❑ 60

61

62

63

64

❑ 65

66

67
❑ 68
❑ 69
❑ 70
❑ 71
❑ 72
❑ 73

74

75

76

77

❑ 78

79

80
❑ 81
❑ 82
❑ 83
❑ 84
❑ 85
❑ 86

87

88

89

90

❑ 91

92

93
❑ 94
❑ 95
❑ 96
❑ 97
❑ 98
❑ 99

100

101

102

103

❑ 104

105

106
❑ 107
❑ 108
❑ 109
❑ 110
❑ 111
❑ 112

113

114

115

116

❑ 117

118

119
❑ 120
❑ 121
❑ 122
❑ 123
❑ 124
❑ 125

126

127

128

129

❑ 130

131

132
❑ 133
❑ 134
❑ 135
❑ 136
❑ 137
❑ 138

139

140

141

142

❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
Appendices

143 144 145 146 147 148 149 150 151 152 153 154 155

❑ 156

157

158
❑ 159
❑ 160
❑ 161
❑ 162
❑ 163
❑ 164

165

166

167

168

❑ 169

170

171
❑ 172
❑ 173
❑ 174
❑ 175
❑ 176
❑ 177

178

179

180

181

❑ 182

183

184
❑ 185
❑ 186
❑ 187
❑ 188
❑ 189
❑ 190

191

192

193

194

❑ 195

196

197
❑ 199
❑ 199
❑ 200
❑ 201
❑ 202
❑ 203

204

205

206

207

❑ 208

209

210
❑ 211
❑ 212
❑ 213
❑ 214
❑ 215

96 50475 Rev D1 9/22/99 P/N 50475:D1


Ev ent Codes/T
Event Codes/Trr ansmission F or
For ma
orma ts Pr
mats Proo g r amming Sheets ffor
or
4+2 Standar
Standardd and 4+2 Expr ess F
Express or
For ma
orma ts Secondar
mats Secondary y Centr al Sta
Central tion
Station


216

217

218

219

220

221
❑ 222
❑ 223
❑ 224

225

226

227

228


229

230

231

232

233

234
❑ 235
❑ 236
❑ 237

238

239

240

241


242

243

244

245

246
❑247
❑ 248
❑ 249
❑ 250

251

252

253

254


255

256

257

258

259
❑260
❑ 261
❑ 262
❑ 263

264

265

266

267


268

269

270

271

272
❑273
❑ 274
❑ 275
❑ 276

277

278

279

280


281

282

283

284

285
❑286
❑ 287
❑ 288
❑ 289

290

291

292

293


294

295

296

297

298
❑299
❑ 300
❑ 301
❑ 302

303

304

305

306


307

308

309

310

311
❑312
❑ 313
❑ 314
❑ 315

316

317

318

319


320

321

322

323

324
❑325
❑ 326
❑ 327
❑ 328

329

330

331

332


333

334

335

336

337
❑338
❑ 339
❑ 340
❑ 341

342

343

344

345


346

347

348

349

350
❑351
❑ 352
❑ 353
❑ 354

355

356

357

358

❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑

Appendices
359 360 361 362 363 364 365 366 367 368 369 370 371


372

373

374

375

376
❑377
❑ 378
❑ 379
❑ 380

381

382

383

384


385

386

387

388

389
❑390
❑ 391
❑ 392
❑ 393

394

395

396

397


398

399

400

401

402
❑403
❑ 404
❑ 405
❑ 406

407

408

409

410


411

412

413

414

415
❑416
❑ 417
❑ 418
❑ 419

420

421

422

423


424

425

426

427

428
❑429
❑ 430
❑ 431

50475 Rev D1 7/22/9 P/N 50475:D1


97
--- To enter Programming Mode Level 2, press Mode: 7 7 6 4, '2', Enter

Ev ent Codes/T
Event Codes/Trr ansmission F or
For ma
matt Pr
orma Proo g r amming Ref er
Refer ence Sheet F
erence ac-
Fac-
tory Defaults
4+2 Standar
Standardd and 4+2 Expr ess F
Express or
For ma
orma
mats ts Pr imar
Primar
imaryy Centr al Sta
Central tion
Station


1
0

1
1

1
2

2
3

1
4
❑3
5

1
6

4
7

1
8

5
9

1
10

6
11

1
12


7
13

1
14

8
15

1
16

9
17
❑1
18

A
19

4
20

1
21

4
22

2
23

4
24

3
25


4
26

4
27

4
28

5
29

4
30
❑6
31

4
32

7
33

4
34

8
35

4
36

9
37

4
38


A
39

9
40

7
41

9
42

2
43
❑F 44

1
45

F
46

2
47

F
48

3
49

F
50

4
51


F
52

5
53

F
54

6
55

F
56
❑7 57

F
58

8
59

F
60

9
61

F
62

A
63

6
64


1
65

6
66

2
67

6
68

3
69
❑6 70

4
71

6
72

5
73

6
74

6
75

6
76

7
77


6
78

8
79

6
80

9
81

4
82
❑B 83

4
84

C
85

4
86

D
87

4
88

E
89

6
90


A
91

6
92

B
93

6
94

C
95
❑6 96

D
97

6
98

E
99

6
100

F
101

E
102

1
103


E
104

2
105

E
106

3
107

E
108
❑4 109

E
110

5
111

E
112

6
113

E
114

7
115

E
116


8
117

E
118

9
119

E
120

A
121
❑5 122

1
123

5
124

2
125

5
126

3
127

5
128

4
129


5
130

5
131

5
132

6
133

5
134
❑7 135

5
136

8
137

5
138

9
139

5
140

A
141

9
142


8

9

3

D

1
❑D ❑
2

D

3

D

4

D

5
Appendices

143 144 145 146 147 148 149 150 151 152 153 154 155


D
156

6
157

D
158

7
159

D
160
❑8 161

D
162

9
163

D
164

A
165

A
166

1
167

A
168


2
169

A
170

3
171

A
172

4
173
❑A 174

5
175

A
176

6
177

A
178

7
179

A
180

8
181


A
182

9
183

5
184

B
185

5
186
❑C 187

5
188

D
189

5
190

E
191

A
192

A
193

A
194


B
195

A
196

C
197

A
198

D
199
❑A 200

E
201

A
202

F
203

9
204

9
205

9
206

1
207


7
208

1
209

7
210

2
211

7
212
❑3 213

7
214

4
215

98 50475 Rev D1 9/22/99 P/N 50475:D1


Ev ent Codes/T
Event Codes/Trr ansmission F or
For ma
matt Pr
orma Proo g r amming Ref er
Refer ence Sheet F
erence ac-
Fac-
tory Defaults
4+2 Standar d and 4+2 Expr
Standard ess F
Express Foror ma
orma
matsts Secondar
Secondaryy Centr al Sta
Central tion
Station


1
216

1
217

1
218

2
219

1
220

3
221

1
222

4
223

1
224
❑5
225

1
226

6
227

1
228


7
229

1
230

8
231

1
232

9
233

1
234

A
235

4
236

1
237
❑4
238

2
239

4
240

3
241


4
242

4
243

4
244

5
245

4
246

6
247

4
248

7
249

4
250
❑8
251

4
252

9
253

4
254


A
255

9
256

7
257

9
258

2
259

F
260

1
261

F
262

2
263
❑F
264

3
265

F
266

4
267


F
268

5
269

F
270

6
271

F
272

7
273

F
274

8
275

F
276
❑9
277

F
278

A
279

6
280


1
281

6
282

2
283

6
284

3
285

6
286

4
287

6
288

5
289
❑6
290

6
291

6
292

7
293


6
294

8
295

6
296

9
297

4
298

B
299

4
300

C
301

4
302
❑D
303

4
304

E
305

6
306


A
307

6
308

B
309

6
310

C
311

6
312

D
313

6
314

E
315
❑6
316

F
317

E
318

1
319


E
320

2
321

E
322

3
323

E
324

4
325

E
326

5
327

E
328
❑6
329

E
330

7
331

E
332


8
333

E
334

9
335

E
336

A
337

5
338

1
339

5
340

2
341
❑5
342

3
343

5
344

4
345


5
346

5
347

5
348

6
349

5
350

7
351

5
352

8
353

5
354
❑9
355

5
356

A
357

9
358


8
359

9
360

3
361

D
362

1
363

D
364

2
365

D
366

3
367
❑D
368

4
369

D
370

5
371

❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
Appendices
D 6 D 7 D 8 D 9 D A A 1 A
372 373 374 375 376 377 378 379 380 381 382 383 384


2
385

A
386

3
387

A
388

4
389

A
390

5
391

A
392

6
393
❑A
394

7
395

A
396

8
397


A
398

9
399

5
400

B
401

5
402

C
403

5
404

D
405

5
406
❑E
407

A
408

A
409

A
410


B
411

A
412

C
413

A
414

D
415

A
416

E
417

A
418

F
419
❑9
420

9
421

9
422

1
423


7
424

1
425

7
426

2
427

7
428

3
429

7
430

4
431

50475 Rev D1 7/22/9 P/N 50475:D1


99
--- To enter Programming Mode Level 2, press Mode: 7 7 6 4, '2', Enter

Ev ent Codes/T
Event Codes/Trr ansmission F or
For ma
matt Pr
orma Proo g r amming Sheets ffor
or
All 3+1, All 4+1 and 4+2 Expanded F or
For
ormama
matsts Pr imar
imary
Primar y Centr al Sta
Central tion
Station
❑ 0
❑ 1

2
❑ 3
❑ 4
❑ 5
❑ 6
❑ 7
❑ 8

9

10

11

12

❑ 13
❑ 14

15
❑ 16
❑ 17
❑ 18
❑ 19
❑ 20
❑ 21

22

23

24

25

❑ 26
❑ 27

28
❑ 29
❑ 30
❑ 31
❑ 32
❑ 33
❑ 34

35

36

37

38

❑ 39
❑ 40

41
❑ 42
❑ 43
❑ 44
❑ 45
❑ 46
❑ 47

48

49

50

51

❑ 52
❑ 53

54
❑ 55
❑ 56
❑ 57
❑ 58
❑ 59
❑ 60

61

62

63

64

❑ 65
❑ 66

67
❑ 68
❑ 69
❑ 70
❑ 71
❑ 72
❑ 73

74

75

76

77

❑ 78
❑ 79

80
❑ 81
❑ 82
❑ 83
❑ 84
❑ 85
❑ 86

87

88

89

90

❑ 91
❑ 92

93
❑ 94
❑ 95
❑ 96
❑ 97
❑ 98
❑ 99

100

101

102

103

❑ 104
❑ 105

106
❑ 107

Ev ent Codes/T
Event Codes/Trr ansmission F
--- or
For ma
matt Pr
orma Proo g r amming Sheets fforor
All 3+1, All 4+1 and 4+2 Expanded F or
For ma
orma ts Pr
mats imar
Primar
imaryy Centr al Sta
Central tion
Station
❑ 216
❑ 217

218
❑ 219
❑ 220
❑ 221
❑ 222
❑ 223
❑ 224

225

226

227

228

❑ 229
❑ 230

231
❑ 232
❑ 233
❑ 234
❑ 235
❑ 236
❑ 237

238

239

240

241

❑ 242
❑ 243

244
❑ 245
❑ 246
❑ 247
❑ 248
❑ 249
❑ 250

251

252

253

254
Appendices

❑ 255
❑ 256

257
❑ 258
❑ 259
❑ 260
❑ 261
❑ 262
❑ 263

264

265

266

267

❑ 268
❑ 269

270
❑ 271
❑ 272
❑ 273
❑ 274
❑ 275
❑ 276

277

278

279

280

❑ 281
❑ 282

283
❑ 284
❑ 285
❑ 286
❑ 287
❑ 288
❑ 289

290

291

292

293

❑ 294
❑ 295

296
❑ 297
❑ 298
❑ 299
❑ 300
❑ 301
❑ 302

303

304

305

306

❑ 307
❑ 308

309
❑ 310
❑ 311
❑ 312
❑ 313
❑ 314
❑ 315

316

317

318

319

❑ 320
❑ 321

322
❑ 323
100 50475 Rev D1 9/22/99 P/N 50475:D1
--- To enter Programming Mode Level 2, press Mode: 7 7 6 4, '2', Enter

Ev ent Codes/F
Event or
Codes/For ma
matt Pr
orma Proo g r amming Ref er
Refer ence Sheet F
erence actor
Factor
actoryy Def aults
Defaults
All 3+1, All 4+1 and 4+2 Expanded F or
For
ormama ts Pr
mats imar
Primar
imaryy Centr
Centralal Sta tion
Station

1
0

1
1

1
2

1
3

1
4
❑1
5

1
6

1
7

1
8

1
9

4
10

4
11

4
12


4
13

4
14

4
15

4
16

4
17
❑4
18

4
19

9
20

9
21

F
22

F
23

F
24

F
25


F
26

F
27

F
28

F
29

F
30
❑F
31

6
32

6
33

6
34

6
35

6
36

6
37

6
38


6
39

6
40

4
41

4
42

4
43
❑4 44

6
45

6
46

6
47

6
48

6
49

6
50

E
51


E
52

E
53

E
54

E
55

E
56
❑E 57

E
58

E
59

E
60

5
61

5
62

5
63

5
64


5
65

5
66

5
67

5
68

5
69
❑5 70

9
71

9
72

D
73

D
74

D
75

D
76

D
77


D
78

D
79

D
80

D
81

D
82
❑A 83

A
84

A
85

A
86

A
87

A
88

A
89

A
90


A
91

5
92

5
93

5
94

5
95
❑A 96

A
97

A
98

A
99

A
100

A
101

9
102

F
103


7
104

7
105

7
106

7
107

Ev ent Codes/F
Event or
Codes/For ma
matt Pr
orma Proo g r amming Ref er
Refer ence Sheet F
erence actor
Factor
actoryy Def aults
Defaults
All 3+1, All 4+1 and 4+2 Expanded F or
For ma
orma
matsts Secondar
Secondaryy Centr
Centralal Sta tion
Station


1
216

1
217

1
218

1
219

1
220

1
221

1
222

1
223

1
224

1
225

4
226

4
227

4
228


4
229

4
230

4
231

4
232

4
233

4
234

4
235

9
236

9
237

F
238

F
239

F
240

F
241


F

F

F

F

F

F

6

6

6

6

6

6

6

Appendices
242 243 244 245 246 247 248 249 250 251 252 253 254


6
255

6
256

4
257

4
258

4
259

4
260

6
261

6
262

6
263

6
264

6
265

6
266

E
267


E
268

E
269

E
270

E
271

E
272

E
273

E
274

E
275

E
276

5
277

5
278

5
279

5
280


5
281

5
282

5
283

5
284

5
285

5
286

9
287

9
288

D
289

D
290

D
291

D
292

D
293


D
294

D
295

D
296

D
297

D
298

A
299

A
300

A
301

A
302

A
303

A
304

A
305

A
306


A
307

5
308

5
309

5
310

5
311

A
312

A
313

A
314

A
315

A
316

A
317

9
318

F
319


7
320

7
321

7
322

7
323
101
50475 Rev D1 7/22/9 P/N 50475:D1
--- To enter Programming Mode Level 2, press Mode: 7 7 6 4, '2', Enter

Ev ent Codes/T
Event Codes/Trr ansmission F or
For ma
matt Pr
orma Proo g r amming Sheets ffor
or
Ademco Contact ID Primary Central Station

❑ 0
❑1

2
❑ 3
❑ 4
❑ 5
❑ 6
❑ 7
❑ 8

9

10

11

12

❑ 13
❑14

15
❑ 16
❑ 17
❑ 18
❑ 19
❑ 20
❑ 21

22

23

24

25

❑ 26
❑27

28
❑ 29
❑ 30
❑ 31
❑ 32
❑ 33
❑ 34

35

36

37

38

❑ 39
❑40

41
❑ 42
❑ 43
❑ 44
❑ 45
❑ 46
❑ 47

48

49

50

51

❑ 52
❑53

54
❑ 55
❑ 56
❑ 57
❑ 58
❑ 59
❑ 60

61

62

63

64

❑ 65
❑66

67
❑ 68
❑ 69
❑ 70
❑ 71
❑ 72
❑ 73

74

75

76

77

❑ 78
❑79

80
❑ 81
❑ 82
❑ 83
❑ 84
❑ 85
❑ 86

87

88

89

90

❑ 91
❑92

93
❑ 94
❑ 95
❑ 96
❑ 97
❑ 98
❑ 99

100

101

102

103

❑ 104
❑105

106
❑ 107
❑ 108
❑ 109
❑ 110
❑ 111
❑ 112

113

114

115

116

❑ 117
❑118

119
❑ 120
❑ 121
❑ 122
❑ 123
❑ 124
❑ 125

126

127

128

129

❑ 130
❑131

132
❑ 133
❑ 134
❑ 135
❑ 136
❑ 137
❑ 138

139

140

141

142

❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
Appendices

143 144 145 146 147 148 149 150 151 152 153 154 155

❑ 156
❑157

158
❑ 159
❑ 160
❑ 161
❑ 162
❑ 163
❑ 164

165

166

167

168

❑ 169
❑170

102 50475 Rev D1 9/22/99 P/N 50475:D1


Ev ent Codes/T
Event Codes/Trr ansmission F or
For ma
matt Pr
orma Proo g r amming Sheets ffor
or
Ademco Contact ID Secondary Central Station


216
❑217

218

219

220

221
❑ 222
❑ 223
❑ 224

225

226

227

228


229
❑230

231

232

233

234
❑ 235
❑ 236
❑ 237

238

239

240

241


242
❑243

244

245

246

247
❑ 248
❑ 249
❑ 250

251

252

253

254


255
❑256

257

258

259

260
❑ 261
❑ 262
❑ 263

264

265

266

267


268
❑269

270

271

272

273
❑ 274
❑ 275
❑ 276

277

278

279

280


281
❑282

283

284

285

286
❑ 287
❑ 288
❑ 289

290

291

292

293


294
❑295

296

297

298

299
❑ 300
❑ 301
❑ 302

303

304

305

306


307
❑308

309

310

311

312
❑ 313
❑ 314
❑ 315

316

317

318

319


320
❑321

322

323

324

325
❑ 326
❑ 327
❑ 328

329

330

331

332


333
❑334

335

336

337

338
❑ 339
❑ 340
❑ 341

342

343

344

345


346
❑347

348

349

350

351
❑ 352
❑ 353
❑ 354

355

356

357

358

❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑

Appendices
359 360 361 362 363 364 365 366 367 368 369 370 371


372
❑373

374

375

376

377
❑ 378
❑ 379
❑ 380

381

382

383

384


385
❑386

50475 Rev D1 7/22/9 P/N 50475:D1


103
--- To enter Programming Mode Level 2, press Mode: 7 7 6 4, '2', Enter

Ev ent Codes/T
Event Codes/Trr ansmission F or
For ma
matt Pr
orma Proo g r amming Ref er
Refer ence Sheet F
erence ac-
Fac-
tory Defaults
Ademco Contact ID Primary Central Station


1
0

1
1

1
2

1
3

1
4
❑1
5

1
6

1
7

1
8

1
9

1
10

1
11

1
12


1
13

1
14

1
15

1
16

1
17
❑1
18

1
19

1
20

1
21

1
22

1
23

1
24

1
25


1
26

1
27

1
28

1
29

5
30
❑7
31

0
32

5
33

7
34

0
35

5
36

7
37

0
38


5
39

7
40

0
41

5
42

7
43
❑0 44

5
45

7
46

0
47

5
48

7
49

0
50

5
51


7
52

0
53

5
54

7
55

0
56
❑5 57

7
58

0
59

6
60

0
61

4
62

3
63

0
64


1
65

3
66

8
67

0
68

3
69
❑8 70

0
71

3
72

8
73

0
74

3
75

8
76

0
77


3
78

8
79

0
80

3
81

8
82
❑0 83

3
84

8
85

0
86

3
87

8
88

0
89

3
90


8
91

0
92

3
93

8
94

0
95
❑3 96

1
97

0
98

3
99

0
100

2
101

3
102

1
103


1
104

3
105

5
106

1
107

3
108
❑5 109

2
110

3
111

2
112

1
113

3
114

2
115

2
116


3
117

2
118

6
119

3
120

2
121
❑7 122

5
123

2
124

1
125

5
126

2
127

2
128

5
129


2
130

6
131

5
132

2
133

7
134
❑3 135

5
136

4
137

3
138

5
139

4
140

3
141

3
142


6

3

3

0

3
❑3 ❑
0

3

0

8

6

0

2
Appendices

143 144 145 146 147 148 149 150 151 152 153 154 155


6
156

0
157

8
158

4
159

1
160
❑1 161

4
162

1
163

6
164

4
165

1
166

2
167

4
168


1
169

3
170

104 50475 Rev D1 9/22/99 P/N 50475:D1


Ev ent Codes/T
Event Codes/Trr ansmission F or
For ma
matt Pr
orma Proo g r amming Ref er
Refer ence Sheet F
erence ac-
Fac-
tory Defaults
Ademco Contact ID Secondary Central Station


1
216

1
217

1
218

1
219

1
220
❑1
221

1
222

1
223
❑1
224

1
225

1
226

1
227

1
228


1
229

1
230

1
231

1
232

1
233
❑1
234

1
235

1
236
❑1 237

1
238

1
239

1
240

1
241


1
242

1
243

1
244

1
245

5
246
❑7247

0
248

5
249
❑7
250

0
251

5
252

7
253

0
254


5
255

7
256

0
257

5
258

7
259
❑0260

5
261

7
262
❑0
263

5
264

7
265

0
266

5
267


7
268

0
269

5
270

7
271

0
272
❑5273

7
274

0
275
❑6
276

0
277

4
278

3
279

0
280


1
281

3
282

8
283

0
284

3
285
❑8286

0
287

3
288
❑8
289

0
290

3
291

8
292

0
293


3
294

8
295

0
296

3
297

8
298
❑0299

3
300

8
301
❑0
302

3
303

8
304

0
305

3
306


8
307

0
308

3
309

8
310

0
311
❑3312

1
313

0
314
❑3
315

0
316

2
317

3
318

1
319


1
320

3
321

5
322

1
323

3
324
❑5325

2
326

3
327
❑2
328

1
329

3
330

2
331

2
332


3
333

2
334

6
335

3
336

2
337
❑7338

5
339

2
340
❑1
341

5
342

2
343

2
344

5
345


2
346

6
347

5
348

2
349

7
350
❑3351

5
352

4
353
❑3
354

5
355

4
356

3
357

3
358

❑ ❑ ❑ ❑ ❑ ❑3 ❑ ❑ ❑ ❑ ❑ ❑ ❑
Appendices
6 3 3 0 3 0 3 0 8 6 0 2
359 360 361 362 363 364 365 366 367 368 369 370 371


6
372

0
373

8
374

4
375

1
376
❑1377

4
378

1
379
❑6
380

4
381

1
382

2
383

4
384


1
385

3
386

50475 Rev D1 7/22/9 P/N 50475:D1


105
Appendix D: Ademco Contact ID Format
Event Code Descriptions
This appendix describes the various Event Codes and their messages which are available for the Ademco
Contact ID Format.

The reporting structure for the Ademco Contact ID format is as follows:

SSS 18 QXYZ GG CCC

where

SSSS = Four digit Subscriber ID Account Code (addresses 17 - 20 and 43 - 46)


18 = Identifies transmission as Contact ID to the receiver at the Central Station
Q = Event Qualifier where 1 = New Event and 3 = New Restore
XYZ = Event code (shown in Tables 3-4 and 3-7)
GG = Group number
CCC = Zone number

Notes:
1) GG Group Number is fixed at '00' and cannot be changed.
2) CCC Zone Number is transmitted as '001' for zone one up to '010' for zone 10.

Ademco Contact ID Reporting Structure

A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble reports in
the Ademco Contact ID Reporting Structure follows:

Time Date Rcvr/Line ID SSSS QXYZ GG CCCC


11:28 03/25 11 7777 E110 00 C001 - general fire alarm on zone one
11:28 03/25 11 7777 E111 00 C002 - smoke detector alarm on zone two
11:28 03/25 11 7777 E380 00 C003 - fault on zone 3
11:28 03/25 11 7777 E570 00 C009 - zone 9 disabled
11:28 03/25 11 7777 R110 00 C001 - zone 1 alarm restored
11:28 03/25 11 7777 R111 00 C002 - smoke detector zone 2 restored
11:28 03/25 11 7777 R380 00 C003 - zone 3 fault restored
Appendices

11:28 03/25 11 7777 R570 00 C009 - zone 9 reenabled


11:28 03/25 11 7777 E158 00 C006 - high temperature, zone 6
11:28 03/25 11 7777 E151 00 C007 - gas detected, zone 7

Notes:
1) 18
18, which is used in the reporting structure to identify the transmission as Contact ID, is not printed
out in the alarm and trouble report.

2) Q , which is the Event Qualifier for the reporting structure, is printed out in the report as an E for New
Event or R for New Restore.

106 50475 Rev D1 9/22/99 P/N 50475:D1


EVENT CODE CLASSIFICATIONS
CLASSIFICATIONS

100 200 300 400 500 600


ALARMS SUPERVISOR
SUPERVISORY
VISORY TROUBLES
TROUBLES OPEN/CLOSE DISABLES/ TEST/
REMOTE A
REMOTE CCESS
ACCESS BYPASSES
BYPASSES MISC.
Medical Fire System Open/Close System Test
Fire Sounder/Relay Remote Access Sounder/Relay
Panic System Peripheral Access Control System Peripheral
Burglary Communication Communication
General Protective Loop
24 Hour Sensor

EVENT MESSAGE
Medical Alarms - 100
100 Medical EMERG - Personal Emergency - #
101 Pendant transmitter EMERG - Personal Emergency - #
102 Fail to report in EMERG - Fail to Check-in - #

Fire Alarms - 110


110 Fire alarm FIRE - Fire Alarm - #
111 Smoke FIRE - Smoke Detector - #
112 Combustion FIRE - Combustion - #
113 Waterflow FIRE - Waterflow - #
114 Heat FIRE - Heat Sensor - #
115 Pull station FIRE - Pull Station - #
116 Duct FIRE - Duct Sensor - #
117 Flame FIRE - Flame Sensor - #
118 Near Alarm FIRE - Near Alarm - #

Appendices
Panic Alarms - 120
120 Panic Alarm PANIC - Panic - #
121 Duress PANIC - Duress
122 Silent PANIC - Silent Panic - #
123 Audible PANIC - Audible Panic - #

50475 Rev D1 7/22/9 P/N 50475:D1


107
EVENT MESSAGE
Burglar Alarms - 130
130 Burglary BURG - Burglary - #
131 Perimeter BURG - Perimeter - #
132 Interior BURG - Interior - #
133 24 Hour BURG - 24 Hour - #
134 Entry/Exit BURG - Entry/Exit - #
135 Day/Night BURG - Day/Night - #
136 Outdoor BURG - Outdoor - #
137 Tamper BURG - Tamper - #
138 Near Alarm BURG - Near Alarm - #

General Alarms - 140


140 General alarm ALARM - General Alarm - #
141 Polling loop open ALARM - Polling Loop Open - #
142 Polling loop short ALARM - Polling Loop Short - #
143 Expansion module failure ALARM - Exp. Module Fail - #
144 Sensor tamper ALARM - Sensor Tamper - #
145 Expansion module tamper ALARM - Exp. Module Tamper - #

24 Hour Non-Burglary - 150 and 160


150 24 Hour Non-Burg ALARM - 24 Hr. Non-Burg - #
151 Gas detected ALARM - Gas Detected - #
152 Refrigeration ALARM - Refrigeration - #
153 Loss of heat ALARM - Heating System - #
154 Water leakage ALARM - Water Leakage - #
155 Foil break ALARM - Foil Break - #
156 Day trouble ALARM - Day Zone - #
157 Low bottled gas level ALARM - Low Gas Level - #
158 High temp ALARM - High Temperature - #
159 Low temp ALARM - Low Temperature - #
161 Loss of air flow ALARM - Air Flow - #

Fire Supervisory - 200 and 210


200 Fire supervisory SUPER. - Fire Supervisory - #
201 Low water pressure SUPER. - Low Water Pressure - #
202 Low CO2 SUPER. - Low CO2
203 Gate valve sensor SUPER. - Gate Valve - #
204 Low water level SUPER. - Low Water Level - #
205 Pump activated SUPER. - Pump Activation - #
Appendices

206 Pump failure SUPER. - Pump Failure - #

System Troubles - 300 and 310


300 System trouble TROUBLE - System Trouble
301 AC loss TROUBLE - AC Power
302 Low system battery TROUBLE - System Low Battery
303 RAM checksum bad TROUBLE - Bad RAM Checksum (Restore not applicable)
304 ROM checksum bad TROUBLE - Bad ROM Checksum (Restore not applicable)
305 System reset TROUBLE - System Reset (Restore not applicable)
306 Panel program changed TROUBLE - Programming Changed (Restore not applicable)
307 Self-test failure TROUBLE - Self Test Failure
308 System shutdown TROUBLE - System Shutdown
309 Battery test failure TROUBLE - Battery Test Failure
310 Ground fault TROUBLE - Ground Fault - #
311 No battery TROUBLE - No Battery

108 50475 Rev D1 9/22/99 P/N 50475:D1


EVENT MESSAGE
Sounder/Relay Troubles - 320
320 Sounder/Relay TROUBLE - Sounder Relay - #
321 Bell 1 TROUBLE - Bell/Siren #1
322 Bell 2 TROUBLE - Bell/Siren #2
323 Alarm relay TROUBLE - Alarm Relay
324 Trouble relay TROUBLE - Trouble Relay
325 Reversing TROUBLE - Reversing Relay
326 Bell 3 TROUBLE - Bell/Siren #3
327 Bell 4 TROUBLE - Bell/Siren #4

System Peripheral Troubles - 330 and 340


330 System peripheral TROUBLE - Sys. Peripheral - #
331 Polling loop open TROUBLE - Polling Loop Open
332 Polling loop short TROUBLE - Polling Loop Short
333 Expansion module failure TROUBLE - Exp. Module Fail - #
334 Repeater failure TROUBLE - Repeater Failure - #
335 Local printer paper out TROUBLE - Printer Paper Out
336 Local printer failure TROUBLE - Local Printer

Communication Troubles - 350 and 360


350 Communication TROUBLE - Communication Trouble
351 Telco 1 fault TROUBLE - Phone Line #1
352 Telco 2 fault TROUBLE - Phone Line #2
353 Long range radio xmitter fault TROUBLE - Radio Transmitter
354 Fail to communicate TROUBLE - Fail to Communicate
355 Loss of radio supervision TROUBLE - Radio Supervision
356 Loss of central polling TROUBLE - Central Radio Polling

Protection Loop Troubles - 370


370 Protection loop TROUBLE - Protection Loop - #
371 Protection loop open TROUBLE - Protection Loop Open - #
372 Protection loop short TROUBLE - Protection Loop Short - #
373 Fire Trouble TROUBLE - Fire Loop - #

Sensor Troubles - 380


380 Sensor trouble TROUBLE - Sensor Trouble - #
381 Loss of supervision - RF TROUBLE - RF Sensor Supervision - #
382 Loss of supervision - RPM TROUBLE - RPM Sensor Supervision - #
383 Sensor tamper TROUBLE - Sensor Tamper - #

Appendices
384 RF transmitter low battery TROUBLE - RF Sensor Batt. - #

Open/Close - 400
400 Open/Close OPENING CLOSING
401 Open/Close by user OPENING - User # CLOSING - User #
402 Group Open/Close OPENING - Group User # CLOSING - Group User #
403 Automatic Open/Close OPENING - Automatic CLOSING - Automatic
404 Late Open/Close OPENING - Late CLOSING - Late
405 Deferred Open/Close Opening not used Closing not used
406 Cancel OPENING - Cancel Closing not used
407 Remote arm/disarm OPENING - Remote CLOSING - Remote
408 Quick arm Opening not applicable CLOSING - Quick Arm
409 Keyswitch Open/Close OPENING - Keyswitch CLOSING - Keyswitch

50475 Rev D1 7/22/9 P/N 50475:D1


109
EVENT MESSAGE
Remote Access - 410
411 Callback request made REMOTE - Callback Requested Restore not applicable
412 Success - download/access REMOTE - Successful Access Restore not applicable
413 Unsuccessful access REMOTE - Unsuccessful Access Restore not applicable
414 System shutdown REMOTE - System Shutdown
415 Dialer shutdown REMOTE - Dialer Shutdown
416 Success - upload/access REMOTE - Successful Access Restore not applicable

Access Control - 420


421 Access denied ACCESS - Access Denied - User # Restore not used
422 Access report by user ACCESS - Access Gained - User # Restore not used

System Disables - 500 and 510

Sounder/Relay Disables - 520


520 Sounder/Relay disable DISABLE - Sounder/Relay - #
521 Bell 1 disable DISABLE - Bell/Siren - #1
522 Bell 2 disable DISABLE - Bell/Siren - #2
523 Alarm relay disable DISABLE - Alarm Relay
524 Trouble relay disable DISABLE - Trouble Relay
525 Reversing relay disable DISABLE - Reversing Relay
526 Bell 3 disable DISABLE - Bell/Siren - #3
527 Bell 4 disable DISABLE - Bell/Siren - #4

System Peripheral Disables - 530 and 540

Communication Disables - 550 and 560


551 Dialer disabled DISABLE - Dialer Disable
552 Radio transmitter disabled DISABLE - Radio Disable

Bypasses - 570
570 Zone bypass BYPASS - Zone Bypass - #
571 Fire bypass BYPASS - Fire Bypass - #
572 24 hour zone bypass BYPASS - 24 Hour Bypass - #
573 Burglar bypass BYPASS - Burg. Bypass - #
574 Group bypass BYPASS - Group Bypass

Test.Misc. - 600
601 Manual trigger test TEST - Manually Triggered Restore not applicable
Appendices

602 Periodic test report TEST - Periodic Restore not applicable


603 Periodic RF transmission TEST - Periodic Radio Restore not applicable
604 Fire test TEST - Fire Test Restore not used
605 Status report to follow STATUS - Status follows Restore not applicable
606 Listen-in to follow LISTEN - Listen-in Active Restore not applicable
607 Walk test mode TEST - Walk Test Mode
608 System abnormal test TEST - System Abnormal Test

110 50475 Rev D1 9/22/99 P/N 50475:D1


Appendix E: Option Modules
Prog
Progrr amming Sheets
--- To enter Programming Mode Level 3, press Mode: 7 7 6 4, '3', Enter

❑0
CAC-10F Class A Converter Card installed. Factory default is '0' for card not installed; enter '1' for
card installed.

❑1
LED-10IM EIA-485 Interface Module installed. Factory default is '0' for no module installed; enter '1' for
module installed.
❑ ❑
2 3
Annunciator or ACM-8R maximum monitored address on EIA-485 line. Factory default is address
2 = 0, address 3 = 1. Enter the two digit address set on the switches of the annunciator or ACM-8R
Remote Relay module with the highest (maximum) address.
❑4
Printer installed. Factory default is '0' for printer not installed; enter '1' for printer installed (requires
PRT-24 printer interface module).
❑5
Printer Baud Rate. Factory default is '0' for 2400 Baud; enter '1' for 4800 Baud; '2' for 9600 Baud.

❑6
NAC/Relay Option Module installed. Factory default is '0' for no module installed; enter '1' for module
installed.
❑7
Programmable Relay #3 Definition. This selection determines the panel condition which will cause
Relay #3 to activate. Factory default is '1' for supervisory; enter '0' for alarm; '2' for supervisory auto-
resettable; '3' for trouble; '4' for communication fail; '5' for process monitoring; '6' for auto-resettable
process monitoring.
❑8
Programmable Relay #4 Definition. This selection determines the panel condition which will cause
Relay #4 to activate. Factory default is '4' for communication fail; enter '0' for alarm; '1' for supervisory;
'2' for supervisory auto-resettable; '3' for trouble; '5' for process monitoring; '6' for auto-resettable
process monitoring.
❑9
NAC #3 Type Selection. Factory default is '0' for NAC #3 enabled (silenceable); enter '1' for enabled
(nonsilenceable); '2' to disabled.
❑10
NAC #3 Silence Inhibit. Factory default is '0' for no silence inhibit; enter '1' to inhibit silencing of NAC
#3 for one minute after an alarm.
❑11
NAC #3 Autosilence feature which silences signals after a selected period. Factory default is '0' for no

Appendices
autosilence for NAC #3; enter '1' for 5 mins.; '2' for 10 mins.; '3' for 15 mins.; '4' for 20 mins.; '5' for 25
mins.; '6' for 30 mins.
❑12
NAC #3 Signal Coding. Factory default is '0' for steady (no coding); '1' for March Time code (120
PPM); '2' for California Time code (10 secs. on, 5 secs. off); '3' for Temporal Time code (0.5 secs. on,
0.5 secs. off, 0.5 secs. on, 0.5 secs. off, 0.5 secs. on, 1.5 secs. off).

50475 Rev D1 7/22/9 P/N 50475:D1


111
❑ 13
NAC #4 Type Selection. Factory default is '0' for NAC #4 enabled (silenceable); enter '1' for enabled
(nonsilenceable); '2' to disabled.
❑ 14
NAC #4 Silence Inhibit. Factory default is '0' for no silence inhibit; enter '1' to inhibit silencing of NAC
#4 for one minute after an alarm.
❑ 15
NAC #4 Autosilence feature which silences signals after a selected period. Factory default is '0' for no
autosilence for NAC #4; enter '1' for 5 mins.; '2' for 10 mins.; '3' for 15 mins.; '4' for 20 mins.; '5' for 25
mins.; '6' for 30 mins.
❑ 16
NAC #4 Signal Coding. Factory default is '0' for steady (no coding); '1' for March Time code (120
PPM); '2' for California Time code (10 secs. on, 5 secs. off); '3' for Temporal Time code (0.5 secs. on,
0.5 secs. off, 0.5 secs. on, 0.5 secs. off, 0.5 secs. on, 1.5 secs. off).
❑ 17
Canadian Supervisory Annunciation. Factory default is '0' for non-Canadian Supervisory Annunciation;
enter '1' for Canadian Supervisory Annunciation.
Appendices

112 50475 Rev D1 9/22/99 P/N 50475:D1


Option Module Prog
Progrr amming Reference Sheets F
Reference actor
Factor
actoryy Def aults
Defaults
--- To enter Programming Mode Level 3, press Mode: 7 7 6 4, '3', Enter


0
0
CAC-10F Class A Converter Card not installed.


0 EIA-485 annunciator or ACM-8R not installed.
1


0 ❑
1 Maximum annunciator or ACM-8R address on EIA-485 line.
2 3


0 Printer not installed.
4


0
5
Printer Baud Rate. ('0' = 2400 Baud).


0 NAC/Relay Option Module not installed.
6


1 Programmable Relay #3 Definition. ('1' = supervisory).
7


4 Programmable Relay #4 Definition. ('4' = communication fail).
8


0 NAC #3 Type Selection. ('0' for NAC #3 enabled, silenceable).
9


0 NAC #3 Silence Inhibit. ('0' = no silence inhibit).
10


0 NAC #3 Autosilence feature which silences signals after a selected period. ('0' = no autosilence for
11

NAC #3).

0
12
NAC #3 Signal Coding. ('0' = steady, no coding).


0
13
NAC #4 Type Selection. ('0' = NAC #4 enabled, silenceable)


0
14
NAC #4 Silence Inhibit. ('0' = no silence inhibit).


0
15
NAC #4 Autosilence feature which silences signals after a selected period. ('0' = no autosilence for
NAC #4).

0
16
NAC #4 Signal Coding. ('0' for steady, no coding).


0
17
Non-Canadian Supervisory Annunciation.

Appendices

50475 Rev D1 7/22/9 P/N 50475:D1


113
Appendix F: Upload/Do wnload
Upload/Download
Prog
Progrr amming Sheets
--- To enter Programming Mode Level 4, press Mode: 7 7 6 4, '4', Enter

❑ ❑ ❑ ❑ Panel Identification Number. Valid entries are 0-F.


0 1 2 3

❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Service Terminal # 1 Phone Number. Addresses 4-19 store the phone number of Service Terminal #1. Enter
'F' to represent the end of the number.

❑ ❑20 21
Ring Count on Primary Phone Line. Enter number of rings prior to panel answering call. Valid
entries are 0 - 25 (0 = no answer). Factory default is 25.
❑ FAX/Answer Machine, Primary Phone Line. Enter '0' for no sharing of phone line; '1' for sharing.
22

❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑ ❑
23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38

Service Terminal # 2 Phone Number. Addresses 23 - 38 store the phone number of Service Terminal #2.
Enter 'F' to represent the end of the number.
❑ ❑39 40
Ring Count on Secondary Phone Line. Enter number of rings prior to panel answering call. Valid
entries are 0 - 25 (0 = no answer). Factory default is 25.
❑ 41
FAX/Answer Machine, Secondary Phone Line. Enter '0' for no sharing of phone line; '1' for sharing.

❑ 42
Upload/Download Backup Reporting. Enter '0' for Upload/Download reports to go to the Secondary
Central Station Phone Number on backup only; '1' for Upload/Download reports to always go to the
Secondary; '2' for upload/download reports to go to the first available Central Station phone number.
Appendices

114 50475 Rev D1 9/22/99 P/N 50475:D1


Upload/Do wnload Prog
Upload/Download Progrr amming Reference Sheets F
Reference actor
Factor
actoryy Defaults
Defaults
--- To enter Programming Mode Level 4, press Mode: 7 7 6 4, '4', Enter


0 ❑
0 ❑
0
0 ❑
0 Panel Identification Number.
1 2 3


F ❑
F ❑
4
F ❑
F ❑
5
F ❑ F ❑
6
F ❑ F ❑
7
F ❑ F ❑
8
F ❑
F ❑
F ❑
F
9

F ❑
F
10 11 12 13 14 15 16 17 18 19

Addresses 4-19 store the phone number of Service Terminal #1. Enter 'F' to represent the end of the number.


2 ❑
5
20
Ring Count on Primary Phone Line.
21


0 FAX/Answer Machine, Primary Phone Line. (0' = no sharing of phone line).
22


F ❑
F
23

F ❑
F
24
❑F ❑F
25

F ❑
26
F ❑F
27

F ❑F
28
❑F
29
❑F
30

F ❑
31
F ❑
F
32 33 34 35 36 37 38

Addresses 23 - 38 store the phone number of Service Terminal #2. Enter 'F' to represent the end of the
number.

2 ❑
5
39
Ring Count on Secondary Phone Line.
40


0 FAX/Answer Machine, Secondary Phone Line. ('0' = no sharing of phone line).
41


0 Upload/Download Backup Reporting. ('0' = Upload/Download reports to go to the Secondary
42

Central Station Phone Number on backup only)

Appendices

50475 Rev D1 7/22/9 P/N 50475:D1


115
Appendix G: Wire Requirements
Connecting external system accessories to the SFP-1024 main circuits must be carefully considered to ensure proper
operation. It is important to use the correct type of wire, wire gauge and wire run length per each SFP-1024 circuit.
Reference the chart below to specify wire requirements and limitations for each SFP-1024.

CIRCUIT CONNECTIONS WIRE REQUIREMENTS

CIRCUIT TYPE CIRCUIT FUNCTION WIRE TYPE AND RECOMMENDED WIRE GUAGE
LIMITATIONS MAX DISTANCE
(FEET)

Initiating Device Connects to Initiating Untwisted, unshielded wire 10,000 12AWG Belden 9583 WPW999
Circuit Devices (Do not exceed 100 ohms) 8,000 14AWG Belden 9581 WPW995
(power-limited) 4,875 16AWG Belden 9575 WPW991
3,225 18AWG Belden 9574 WPW975

EIA-485 Connects to Twisted, shielded pair with a 6000 18 AWG


LED-10IM annunciator modules characteristic impedance of
Interface and relay module 120 ohms
Module
(power-limited)

EIA-232 PRT-24 output Twisted, shielded pair 50 18 AWG minimum


(power-limited) connects to remote
printer and PC
computer

24 VDC Connects to No more than 1.2 volt drop Distance limitation 12-18 AWG
Regulated annunciators and allowed from supply source set by 1.2 volt
Resettable, other accessories to end of any branch maximum line drop
Nonresettable
(power-limited)
Appendices

116 50475 Rev D1 9/22/99 P/N 50475:D1


Appendix H: Operation and Function Modes

OPERATION MODES
OPERATION

CODE ACTIVITY NOTES

6676 (NORM) Returns to normal operation Fire protection on

7764 (PROG) Enters Program Mode 4 levels of programming may be entered.


Fire protection is off.

9255 (WALK) Enters Walktest Mode May select silent or audible walktest function.
Fire protection is off.

4478 (HIST) View History File Use display or printer to view History File.
Fire protection is on.

8768 (TROU) Activates internal system voltmeter for Fire protection is off while voltmeter function
troubleshooting and diagnosing problems is enabled.

7746 (PRIN) Sends status, history file, walktest file, Fire protection is on. Requires PRT-24
troubleshoot voltages and entire option module.
programming selections to printer

5267 (LAMP) Turns on all LEDs on the main PCB and all Fire protection is on.
system annunciators for 5 seconds

3696 (DOWN) Allows for downloading the entire program Must have service terminal ready. Fire
file to the panel protection remains on.

FUNCTION MODES

Appendices
CODE ACTIVITY NOTES

3472 (DISA) Allows disabling of any input zone or NAC May only disable one NAC or zone at a time.
Places system into trouble.

3622 (ENAB) Allows enabling (return to normal) of any zone May only enable one NAC or zone at a time.
or NAC

3745 (DRIL) Performs drill function by turning on all NAC Transmission of drill function to central
outputs station is defaulted to ON.

3337 (DEFP) Reprograms all entries for Program Levels 1 Entry of code must be performed two times
through 4 to the original factory default in rapid succession as a safety feature. Use
settings. caution when using this feature.

50475 Rev D1 7/22/9 P/N 50475:D1


117
118 50475 Rev D1 9/22/99 P/N 50475:D1
50475 Rev D1 7/22/9 P/N 50475:D1
119
Limited Warr anty
arranty

NO TIFIER® warrants its products to be free from defects in materials and workmanship
NOTIFIER
for eighteen (18) months from the date of manufacture, under normal use and service.
Products are date stamped at time of manufacture. The sole and exclusive obligation
of NO TIFIER® is to repair or replace, at its option, free of charge for parts and labor,
NOTIFIER
any part which is defective in materials or workmanship under normal use and service.
For products not under NO TIFIER® manufacturing date-stamp control, the warranty
NOTIFIER
is eighteen (18) months from date of original purchase by NO TIFIER®'s distributor
NOTIFIER
unless the installation instructions or catalog sets forth a shorter period, in which
case the shorter period shall apply. This warranty is void if the product is altered,
repaired or serviced by anyone other than NO TIFIER® or its authorized distributors or
NOTIFIER
if there is a failure to maintain the products and systems in which they operate in a
proper and workable manner. In case of defect, secure a Return Material Authorization
form from our customer service department. Return product, transportation prepaid,
to NO TIFIER®, One Fire-Lite Place, Northford, Connecticut 06472-1653.
NOTIFIER

This writing constitutes the only warranty made by NO TIFIER® with respect to its
NOTIFIER
®
NO TIFIER
products. NOTIFIER does not represent that its products will prevent any loss by
fire or otherwise, or that its products will in all cases provide the protection for which
they are installed or intended. Buyer acknowledges that NO TIFIER® is not an insurer
NOTIFIER
and assumes no risk for loss or damages or the cost of any inconvenience,
transportation, damage, misuse, abuse, accident or similar incident.

NOOTT I F I E R ® GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF


MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR
OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE
HEREOF. UNDER NO CIRCUMSTANCES SHALL NO TIFIER® BE LIABLE FOR ANY
NOTIFIER
LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR
CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE
NO TIFIER® PRODUCTS. FURTHERMORE, NO
NOTIFIER TIFIER® SHALL NOT BE LIABLE
NOTIFIER
FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE
OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF
ITS PRODUCTS.

This warranty replaces all previous warranties and is the only warranty made by
NO TIFIER®. No increase or alteration, written or verbal, of the obligation of this warranty
NOTIFIER
is authorized.

"NOTIFIER" is a registered trademark.


"NOTIFIER"

One Fire-Lite Place, Northford, CT 06472


Phone: (203) 484-7161
FAX: (203) 484-7118

Technical Publishing Document WARNBG-E.P65 11/08/98

You might also like