Mivii
Mivii
Mivii
Applications
• Voltage and/or frequency protection at any voltage in
automatic transfer systems, generators, motors, lines and
busbars
Features
Protection and Control Monitoring and Metering
• Three-phase over and undervoltage, ground overvoltage • 24-event record
• Voltage unbalance, over and underfrequency, with the • Analog/digital oscillography - 24 cycles at 8 samples per
following options: cycle
- Four independent time delay phase under/overvoltage • Frequency and per-phase voltage
elements complete with two independent fixed time ground • Monitoring of the last 5 trips information from the display
overvoltage elements
- Four units of frequency protection User Interfaces
- Both voltage protection and two elements of frequency • 2x16 character LCD display
protection • 6 LED indicators, 4 configurable in function and color
• Circuit Breaker control (open/close) • Front RS232 and rear RS485 ports using ModBus® RTU
• Configurable I/O protocol up to 19,200 bps
• 6 outputs, four configurable, plus trip and alarm • EnerVistaTM software - an industry leading suite of software
tools that simplifies every aspect of working with GE Multilin
devices
g Digital Energy
Multilin
513
MIV II Voltage/Frequency Protection System
Overview
The MIV II, a member of the M II Family, is
a digital device that provides voltage and
frequency protection for a wide range of
applications at any voltage level.
NOTE: The MIV II includes four independent
time delayed phase under/overvoltage
elements, and two independent fixed time
ground overvoltage elements, the MIV II
2000 includes frequency functions (four
units), and the MIV II 3000 includes both
voltage and frequency (two) units.
The basic MIV II has two fixed digital inputs
and six fixed digital outputs. An option is
provided allowing the two inputs and four
Specialized Protection & Control
514 www.GEDigitalEnergy.com
MIV II Voltage/Frequency Protection System
Event Recording
Events consist of a broad range of change
of state occurrences, including pickups,
trips, contact operations, alarms and
self test status. The MIV II stores up to
24 events time tagged to the nearest
millisecond. This provides the information
needed to determine sequence of events
which facilitates diagnosis of relay
www.GEDigitalEnergy.com 515
MIV II Voltage/Frequency Protection System
Self-Test Diagnostics over long cable runs. MultiNet setup is Documents made available include:
Comprehensive self-test diagnostics occur simple, with a Windows®based EnerVistaTM
at power up and continuously during relay software program for installing and • Manuals
operation. Any problem found by self-tests configuring the communication drivers.
• Application Notes
causes an alarm and an event is logged. • Guideform Specifications
Communication Ports
EnerVistaTM Software • Brochures
The EnerVista™ Suite is an industry- • Wiring Diagrams
A front mounted RS232 and a rear RS485
leading set of software programs that
port allow easy user interface via a PC. • FAQs
simplifies every aspect of using the relay.
ModBus® RTU protocol is used for all ports. • Service Bulletins
The EnerVistaTM suite provides all the tools
The relay supports baud rates from 300 to
to monitor the status of the protected
19,200 bps. Up to 32 GE Multilin devices can Viewpoint Monitoring
asset, maintain the relay, and integrate
be addressed on a single communications
information measured into DCS or SCADA Viewpoint Monitoring is a simple-to-use
channel. A unique address must be
monitoring systems. Convenient waveform and full-featured monitoring and data
assigned to each relay via a setting when
recording software package for small
Specialized Protection & Control
516 www.GEDigitalEnergy.com
MIV II Voltage/Frequency Protection System
User Interface
DISPLAY
16x2 characters LCD display for
viewing setpoints, actual value
messages, and fault reports
CONTROL AND
PROGRAMMING KEYS
Escape, Reset, Enter, Menu Up,
and Menu Down keys for complete
access to settings and information
without a computer
PROGRAMMING PORT
RS232 Communications Port
for connection to a computer
Dimensions
6.243 10.472 5.35(136)
( 158,6 ) (266)
4.33(110)
O0
.27
(0
.7)
Optional depth
reducing collar
4.0 (101.6)
7.0 (178)
ESC
7.131 ENTER
(181,1) MENU
EN MIFII DIM C
6.819
(173)
9.276
(235,5)
www.GEDigitalEnergy.com 517
MIV II Voltage/Frequency Protection System
Typical Wiring A
B
C NOTE: 14 AWG wiring
recommended
AC
OR
DC
NOTES:
SUITABLE DISCONNECT DEVICES (SWITCH OR CIRCUIT B1 B2 B3 B4 A3 A4 A1 A2
BREAKER) RECOMMENDED LOCATED NEAR THE RELAY
OVERVOLTAGE CATEGORY: II
VI N VII N VIII N +/L -/N
POWER
INTERNALLY FUSED
1A / 250V FAST BLOW
VOLTAGE INPUTS
RS485
g
TRIP
Specialized Protection & Control
B5
JX
A9 CC2
B9
A10 COM
RS232 B10
SAFETY
GND GROUND A7 INPUT
GROUND BUS
(*) Terminals B12, A12 and B11 must be connected to SELV (safety extra-lowvoltage) parts (on the PLC).
They are not to be tested for hipot test under any circumstance
(**) The default configuation of inputs and outputs is as follows:
CC1: Block phase voltage functions Block frequency functions Block voltage functions
CC2: Block ground voltage functions External trip command Block frequency functions
B1 B2 B3 B4 A3 A4 B1 B2 B3 B4 A3 A4 B1 B2 B3 B4 A3 A4
518 www.GEDigitalEnergy.com
MIV II Voltage/Frequency Protection System
Technical Specifications
PROTECTION POWER SUPPLY Metering
VOLTAGE ELEMENTS (P1, P2, P3, P4) LOW RANGE Frequency: ±10 mHz
Voltage: Phasor Rated DC Voltage: 24 to 48 Vdc Voltage: ±1% in the metering range(50/80V)
Function Type: Overvoltage or Undervoltage Min./Max. DC Voltage: 19 / 58 Vdc ±3% or 0.5V in the complete range
selected by setting HIGH RANGE MECHANICAL CHARACTERISTICS
Pickup Level: 10.0 - 250.0V in steps of 0.1V for Rated DC Voltage: 110 to 250 Vdc Stainless-steel 304 housing in 1/4 of a 19’’ rack,
range 0 models (High range) Min./Max. DC Voltage: 88 / 300 Vdc 4 units high
2.0 - 60.0V in steps of 0.1V for Rated AC Voltage: 110 to 230 Vac @ 48 IP52 protection degree
range 1 models (Low range) – 62 Hz
Dropout Level: 97% (typical) of the pickup value Min./Max. AV Voltage: 88 / 264 Vac @ 48 ENVIRONMENTAL
for overvoltage – 62 Hz Temperature:
103% (typical) of the pickup value Power Consumption: Max. = 15 W Storage: -40ºC to +80ºC
for undervoltage Backup time: (date, time and log Operation: -20ºC to +60ºC.
Level Accuracy: ±3% in the complete range. memory) without Humidity: Up to 95% without condensing.
Timer: 0 - 600s in steps of 0.01 s power supply voltage
Reset Type: Instantaneous > 1 week PACKAGING
Operation time: < 30 ms at 1.20 x pickup @ 50 Hz Approximate Weight:
Timing Accuracy: ±3% of operation time or ±30 ms. Net: 2.7 kgs (5.9 lbs)
(whichever is greater) INPUTS Ship: 3.2 kgs (7 lbs)
Supervision: By minimum voltage (level selected AC VOLTAGE
by setting) High Range
By breaker position (enabled by Secondary Rated 50-240 Vac TYPE TESTS
setting) Voltage: Test Standard Class
Reset Time: One power cycle (typical) Frequency: 50 / 60 Hz ±3 Hz (The unit InsulationTest Voltage:
GROUND OVERVOLTAGE ELEMENT (59N1, 59N2) can be set to 50 or 60 Hz) IEC 60255-5 2kV, 50/60 Hz 1
Voltage: Measured or calculated depending Relay Burden: < 0.2 VA @ 120 Vac min
www.GEDigitalEnergy.com 519
MIV II Voltage/Frequency Protection System
Ordering
MIV II * 0 * 0 * 0 0 ** * * Description
Position 1 Voltage functions
2 Frequency functions
3 Voltage & Frequency functions
Voltage Range 0 10-250V (all models)
1 2-60 V (only MIVII1000)
Language E English Language
F French Language
Power Supply LO 24-48 Vdc (Range: 19~58 Vdc)
HI 110-250 Vdc (Range: 88-300 Vdc)110-230 Vac (Range: 88-264 Vac)
Conformal Coating 0 Without Conformal Coating
H With Conformal Coating
Special Models * * For special models contact factory.
Specialized Protection & Control
520 www.GEDigitalEnergy.com
090810-v7