Industry Sector, IA&DT

SCE Training Curriculum


For Integrated Automation Solutions
Totally Integrated Automation (TIA)
Siemens Automation Cooperates with Education

TIA Portal Module


PROFINET with IO Controller CPU 315F-2 PNDP
and IO Device ET 200S

Page 1 of 39
TIA Portal Module ‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
Suitable SCE trainer packages for these training curriculums

SIMATIC controllers
 SIMATIC S7-300 with CPU 314C-2PN/DP
Order no.: 6ES7314-6EH04-4AB3
 SIMATIC S7-300 with CPU 314C-2PN/DP (upgrade)
Order no.: 6ES7314-6EH04-4AB4
 SIMATIC S7-300 with CPU 315F-2PN/DP
Order no.: ES7315-2FH14-4AB1
 SIMATIC ET 200S with CPU IM151-8 F PN/DP
Order no.: 6ES7151-8FB00-4AB1
 SIMATIC ET 200S with IM151-3 F PN
Order no.: 6ES7151-3BA20-4AB1

SIMATIC STEP 7 Software for Training


 SIMATIC STEP 7 Professional V11 - Single license
Order no.: 6ES7822-1CC01-4YA5
 SIMATIC STEP 7 Professional V11 - Classroom license (up to 12 users)
Order no.: 6ES7822-1AA01-4YA5
 SIMATIC STEP 7 Professional V11 - Upgrade license (up to 12 users)
Order no.: 6ES7822-1AA01-4YE5
 SIMATIC STEP 7 Professional V11 - Student license (up to 20 users)
Order no.: 6ES7822-1AC01-4YA5

Page 2 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
PAGE:

1. Preface ....................................................................................................................................................... 4

2. Notes on using the CPU 315F-2 PN/DP ..................................................................................................... 6

3. Notes on using the ET 200S with IM 151-3 PN HF .................................................................................... 7

4. Commissioning the PROFINET (IO controller CPU 315F-2 PN/DP / IO device ET 200S) ........................ 8

4.1. Creating a project and configuring hardware .............................................................................................. 8

4.2. Generating and testing a program ............................................................................................................ 28

Page 3 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
1. PREFACE

Regarding its content, module SCE_EN_070-010 is part of the training unit ‘PROFINET’.

Basics of PLC
Programming
Module 10, Module 20
Simulation SIMIT
Module 150

Additional Functions for


PLC Programming
Module 30

More Programming PROFIBUS PROFINET


Languages AS-Interface
Module 60 Module 70
Module 40 Module 50

Safety/Security
Systems Sensor Technology Process Visualization Drives
Module 80 Module 110 (HMI) Module 90 Module 100

Training Objective:

This module provides the reader with information on how to commission the CPU 315F-2PN/DP as
IO controller and the ET 200S as IO device on PROFINET. The module demonstrates the general
procedure based on a brief example.

Requirements:

To successfully work through this module, the following knowledge is assumed:


 Proficiency in working with Windows.
 Advanced knowledge of PLC programming with the TIA Portal (e.g. module SCE_EN_020-
010_R1201_Startup Programming with SIMATIC S7-300 and module SCE_EN_030... ).

Page 4 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
Hardware and software needed

1 PC Pentium 4, 1.7 GHz 1 (XP) – 2 (Vista) GB RAM, free disk storage approx. 2 GB
operating system Windows XP Professional SP3/Windows 7 Professional/Windows 7
Enterprise/Windows 7 Ultimate/Windows 2003 Server R2/Windows Server 2008 Premium SP1,
Business SP1, Ultimate SP1
2 Software: STEP 7 Professional V11 SP1 (Totally Integrated Automation (TIA) Portal V11)
3 Ethernet connection between the PC, CPU 315F-2 PN/DP and ET 200S
4 PLC SIMATIC S7-300; for example, CPU 315F-2PN/DP with 16DI/16DO signal module. The inputs
have to be brought out to a panel.
5 Distributed IO ET 200S for PROFINET with 8 digital inputs and 8 digital outputs.
- Interface module: IM 151-3 PN HIGH FEATURE
- Power module: PM-E RO DV24V / 8A
- Electronic module 4DI HF DC24V (the inputs must be brought out to a panel)
- Electronic module 4DI HF DC24V (the inputs must be brought out to a panel)
- Power module: PM-E RO DV24V / 8A
- Electronic module 4DO HF DC24V/0.5A
- Electronic module 4DO HF DC24V/0.5A

2 STEP 7 Professional
1 PC V11 (TIA Portal)

3 Ethernet connection

4 S7-300 with
CPU 315F-2 PN/DP 5 ET 200S with
IM151-3 PN HIGH
FEATURE

Page 5 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
2. NOTES ON USING THE CPU 315F-2 PN/DP

The CPU 315F-2 PN/DP is a CPU which is supplied with 2 integrated interfaces.
- The first interface is a combined MPI/PROFIBUS DP interface which can be used as master or
slave on PROFIBUS DP to connect distributed IO/field devices with very fast response times. The
CPU can be programmed via MPI or via PROFIBUS DP.
- The second interface is an integrated PROFINET interface with 2 ports. This allows you to use the
CPU as PROFINET IO controller to operate distributed IO devices on PROFINET. You can also use
this interface to program the CPU.
- Failsafe I/O devices can also be used with both interfaces.
- In addition, CPU 315F-2 PN/DP features a web server that allows remote diagnostics to be
conducted using any browser, even without STEP 7 software

Notes:
- In this module, the CPU 315F-2 PN/DP is used as IO controller on PROFINET.
- A Micro Memory Card is required in order to operate this CPU.
- Parameters for the addresses of the input and output modules can be assigned for this CPU.

Page 6 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
3. NOTES ON USING THE ET 200S WITH IM 151-3 PN HF

SIMATIC ET 200S is a highly modular, distributed I/O device. It can be operated with various interface
modules. Here is a selection of these:
IM 151-1 BASIC, IM 151-1 STANDARD and IM 151-1 FO STANDARD for the connection of max. 63
I/O modules (all types, except PROFIsafe) to PROFIBUS DP; alternatively, bus connection with RS 485
D-Sub connector or using integrated fiber-optic connection.
IM 151-1 HIGH-FEATURE for connection of max. 63 IO modules (all types, including isochronous mode
for PROFIsafe) to PROFIBUS DP; bus connection with RS485 D-Sub connector.
IM 151-3 PN for connection of max. 63 IO modules (all types, including isochronous mode for
PROFIsafe) to PROFINET IO controller; bus connection with RJ45 connector.
IM 151-3 PN HF (HIGH FEATURE) for connection of max. 63 I/O modules (all types, including
isochronous mode for PROFIsafe) to PROFINET IO controller; bus connection with 2x RJ45 connectors.
IM151-8 F-CPU PN/DP, IM 151-7/F-CPU, IM 151-7/CPU and IM 151-7/CPU FO for connection of max.
63 I/O modules (all types, PROFIsafe only with IM151-8 F-CPU PN/DP and IM151-7/F-CPU) to
PROFINET or PROFIBUS DP (alternatively, bus connection with RS 485 D-Sub connector or using
integrated fiber-optic connection). With integrated CPU to preprocess the process data.

The following I/O modules, for example, can be used here:


Power modules to group load and encoder supply voltages separately and to monitor these voltages
Digital electronic modules to connect digital sensors and actuators
Analog electronic modules to connect analog sensors and actuators
Sensor module to connect IQ-Sense sensors
Technology modules Electronic modules with integrated technological functions, such as counting,
positioning, data exchange, etc.
Frequency converter and motor starter modules

Notes:
- The interface module IM151-3 PN HF is used as PROFINET IO device in this module.
- A Micro Memory Card is recommended for the operation of the IM151-3 PN HF to allow a device
replacement without programming device.

Page 7 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
4. COMMISSIONING THE PROFINET (IO CONTROLLER CPU 315F-2 PN/DP / IO DEVICE ET 200S)

Below, a description is provided on how to commission a PROFINET network with the


CPU 315F-2 PN/DP as IO controller and the ET 200S as IO device.
To test the configuration, a program is written in which an indicator light P1 is activated when the S1
button is pressed. Another indicator light P2 is activated if two buttons, S1 and S2, are pressed at the
same time.

Assignment list:
%I0.0 S1 Selector switch S1 (NO)
%I0.4 S2 Selector switch S2 (NO)
%Q0.0 P1 Indicator light P1
%Q0.4 P2 Indicator light P2

4.1. Creating a project and configuring hardware

1. The central tool is the ‘Totally Integrated Automation Portal’, which is opened with a double-click.
( TIA Portal V11)

Page 8 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
2. Programs for SIMATIC S7-300 are managed in projects. Such a project is now created in the portal
view. ( Create new project  ET 200S_PN  Create)

3. ‘First steps’ for configuring are now suggested. We first want to ‘Configure a device’.
( First steps  Configure a device)

Page 9 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
4. The next step is ‘Add new device’ with the ‘Device name control 001’.
Choose the ‘CPU 315F-2 PN/DP’ with the appropriate order number from the catalog. ( Add new
device  Control 001  PLC  SIMATIC S7-300  CPU  CPU 315F-2 PN/DP  6ES7 315-
2FJ14-0AB0  V3.2  Add)

Page 10 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
5. The software now switches automatically to the project view containing the opened hardware
configuration in the device view. Additional modules can be added from the hardware catalog (to
the right!).
To ensure that the software will access the correct CPU later, the IP address and the subnet mask
of the CPU must be set. In addition, this interface is also connected with a subnet.
( Properties  General  PROFINET interface  Ethernet addresses  Add new subnet 
PN/IE_1  Set IP address in the project  IP address: 192.168.0.1  Subnet mask:
255.255.255.0).
(See also: Module SCE_EN_020-010_R1110_Startup Programming with SIMATIC S7-300 to set
the programming interface).

Page 11 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
Notes on networking on Ethernet

MAC address:
The MAC address consists of a fixed and a variable part. The fixed part ("base MAC address") identifies
the manufacturer (Siemens, 3COM, ...). The variable part of the MAC address differentiates between the
various Ethernet devices and should be unique worldwide. A factory-assigned MAC address is imprinted
on each module.

Value range for the IP address:


The IP address consists of 4 decimal numbers of the range from 0 to 255, separated by a period; for
example, 141.80.0.16.

Value range for the subnet mask:


This mask is used to detect whether a device or its IP address belongs to the local subnet, or can be
accessed only by means of a router.
The subnet mask consists of 4 decimal numbers from the value range 0 to 255, separated by a period.
For example, 255.255.0.0.

In their binary representation, the 4 decimal numbers of the subnet mask must include a continuous
series of "1" values without any gaps from the left and a series of "0" values without any gaps from the
right. The "1" values specify the area of the IP address for the network number. The "0" values specify
the area of the IP address for the device address.

Example:
Correct values: 255.255.0.0 decimal = 1111 1111.1111 1111.0000 0000.0000 0000 binary
255.255.128.0 decimal = 1111 1111.1111 1111.1000 0000.0000 0000 binary
255.254.0.0 decimal = 1111 1111.1111 1110.0000 0000.0000.0000 binary
Incorrect value: 255.255.1.0 decimal = 1111 1111.1111 1111.0000 0001.0000 0000 binary

Value range for the address of the gateway (router):


The address consists of 4 decimal numbers from the value range 0 to 255, separated by a period. For
example, 141.80.0.1.

Relation of IP addresses, router address, and subnet mask:


The IP address and the address of the gateway may only differ at the positions at which there is a "0" in
the subnet mask.

Example: You have entered the following: for the subnet mask 255.255.255.0, for the IP address
141.30.0.5 and for the router address 141.30.128.1.

The IP address and the address of the gateway may only have a different value in the 4th decimal
number. In the example, however, the 3rd position is different.
In the example, you will therefore need to make one of the following changes:
- The subnet mask to: 255.255.0.0 or
- The IP address to: 141.30.128.5 or
- The address of the gateway to: 141.30.0.1.

Page 12 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
6. To connect the ET 200S with the CPU 315-2 PN/DP, you must go to the ‘network view’.
The relevant PROFINET module can be moved to the network view by means of drag-and-drop.
( Network view  Distributed IO  ET 200S  Interface module  PROFINET  IM151-3 PN
 6ES7 151-3BA23-0AB0)

Page 13 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
7. You then connect the Ethernet interfaces of the CPU 315-2 PN/DP and those of the IM 151-3PN

with the mouse. ( Ethernet  Ethernet)

Page 14 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
8. Next, set the properties of the 'IM 151-3 PN' and its 'PROFINET interface' and assign here an
appropriate IP address for the CPU. ( IM 151-3 PN  Properties  PROFINET interface [X1] 
IP protocol  IP address: 192.168.0.2)

9. After this, the device name has to be assigned under 'General'. ( General  Name: ET 200S)

Page 15 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
10. With the 'PROFINET interface' of the 'IM 151-3PN', this name is automatically applied as
PROFINET device name under the item 'PROFINET'. (PROFINET interface[X1]  PROFINET)

11. The settings for the ‘IO cycle’ such as 'Update time' and 'Watchdog time' for each device can be
set here. ( Update time  Watchdog time)

Page 16 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
12. In the device view, all other modules which are also inserted in the real ET 200S can now be
selected from the hardware catalog and inserted into the configuration table. To do this, click on the
name of the corresponding module, keep the mouse button pressed, and drag it to the appropriate
column of the configuration table. We start with the 2 power modules ‘PM-E DC24V / 8A RO’ which
are dragged to slots 1 and 4. ( PM  PM-E DC24V / 8A RO  6ES7 138-4CA80-0AB0)

Notes:
When several power modules are used, we have the option of switching the power supply to specific
areas on and off. In the event of an emergency stop, for example, the power supply to the output
modules can be switched off separately from the power supply to the input modules.

Page 17 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
13. We drag the input module ‘4DI x DC24V HF’ to slots 2 and 3.
( DI  4DI x DC24V HF  6ES7 131-4BD01-0AB0)

14. We drag the output module ‘4DO x DC24V / 0.5A HF’ to slots 5 and 6. ( DO  4DO x DC24V /
0.5A HF  6ES7 132-4BD00-0AB0)

Page 18 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
15. Addresses can be packed so that a new byte address does not need to be started with every
module. To do this, select the modules in question and right-click on ‘Pack addresses’.
( Pack addresses)

Page 19 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
16. ‘Properties’ for the modules can also be set in the ‘Module parameters’. E.g. ‘Diagnostics,
missing load voltage L+’ for the first power module. ( PM-E DC24V / 8RA RO_1  General 
Module parameters  Diagnostics  Missing load voltage L+)

17. Now, we save the project with the settings made so far. ( )

Page 20 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
Industry Sector, IA&DT

18. After the IO device ‘IM151-3PN’ has been selected, the ‘Assign device name’ step has to be
performed online. ( IM151-3PN  Assign device name)

Notes:
Before you do this, make sure that the programming device is connected to the IM 151-3PN via
Ethernet.

Page 21 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
19. The ‘Type of the PG/PC interface’ can be selected in the following dialog in order to then select
the ‘IM151-3PN’ and ‘Assign name’. ( Assign name)

Notes:
If there are several IO devices in the network, the device can be identified on the basis of the imprinted
MAC address.

Page 22 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
20. If the required module is not displayed, the view can be updated by clicking ‘Accessible devices in

the network’ . If the device name was successfully assigned, this is indicated in the status with

‘OK’. (  Close)

Page 23 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
21. To load your entire program to the CPU, first select the ‘Control 001’ folder and then click the
Download to device icon . ( Control 001  )

Page 24 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
22. In the following dialog, select ‘PN/IE’ as the PG/PC interface type and then the network card
installed in the PG/PC as PG/PC interface. After you have also activated the ‘Show all accessible
devices’ option and clicked ‘Refresh’, you should see an ‘S7-300’ with the matching MAC address
and be able to select it as target device. Next, click ‘Load’. ( Type of the PG/PC interface: PN/IE
 PG/PC interface: ……  Show all accessible devices  Refresh  S7-300  Load)

Page 25 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
23. The configuration is now compiled automatically, and an overview of the steps to be performed is
displayed once again for checking before the program is loaded. Click ‘Load’ to start loading the
program. ( Load)

Page 26 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
24. The successful load result is displayed in a window. Now, click ‘Start all’ and then ‘Finish’ to set
the CPU to Run mode again. ( Start all  Finish)

Page 27 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
4.2. Generating and testing a program

25. Because modern programming uses tags and not absolute addresses, the global PLC tags must
be defined here as an initial step.

These global PLC tags are descriptive names with a comment for each input and output used in the
program. The global PLC tags can then be accessed later during programming via their names.
These global tags can be used in all blocks anywhere in the program.

For this purpose, select ‘Control 001 [CPU 315F-2 PN/DP]’ and then ‘PLC tags’ in the project tree.
Double-click the ‘Default tag table’ to open it and enter the names for the inputs and outputs as shown
below. ( Control 001 [CPU 315F-2 PN/DP]  PLC tags Default tag table)

Page 28 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
26. The program sequence is written to so-called blocks. The organization block Main [OB1] is already
provided as standard. This block represents the interface to the CPU operating system and is
automatically called and cyclically processed by this operating system.
From this organization block, additional blocks can be called in turn for structured programming,
e.g., the program view [FC1] function.
The purpose is to break down an overall task into partial tasks. This makes it easier to solve these
tasks and to test their functionality.

Program structure of the example:

Organization block
Main [OB1]

Block called cyclically


by the operating
system. Here, the
program view [FC1]
function is called

Program view [FC1]


function

Contains the actual


program in this
example. Is called
by Main [OB1].

Page 29 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
27. To create the program view [FC1] function, select ‘Control 001 [CPU 315F-2 PN/DP]’ in the project
tree and then ‘Program blocks’. Afterwards, double-click ‘Add new block’. Select ‘Function (FC)’
and assign the name ‘program view’. Specify the ‘FBD’ function block diagram as programming
language. The numbering will be automatic. Since this FC1 will be called using its symbolic name
later in any case, the number does not play an important role. Click ‘OK’ to accept your entries.
( Control 001‫اﺗوﻣﺎﺳﯾون‬ PN/DP]’  Program
‫آﻣوزش‬/‫ﺗوزﯾﻊ‬/‫ﺗﺎﻣﯾن‬
[CPU 315F-2 ‫ ﻧﺻر ﻣﺎد‬blocks  Add new block  Function (FC) 
‫ﺷرﮐت ﺳﯾﻣﯽ‬
program view  
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
FBD OK)

Page 30 of 39
28. The ‘program view [FC1]’ block then opens automatically. The interface of the block must be
declared before the program can be written. In the interface declaration, the local tags known only
in this block are defined.

The tags are divided into two groups:

 Block parameters that form the block interface for the call in the program.

Type Designation Function Available in

Parameters whose values are Functions, function blocks, and some


Input parameters Input
read by the block. types of organization blocks

Output / Parameters whose values are


Output parameters Functions and function blocks
Return written by the block.

A parameter whose value is read


by the block when it is called and
In/out parameters InOut is written back by the block to Functions and function blocks
the same parameter after it is
processed.

 Local data that is used for saving intermediate results.

Type Designation Function Available in

Tags that are used to store


temporary intermediate results. Functions, function blocks, and
Temporary local data Temp
Temporary data is retained for organization blocks
only one cycle.

Tags that are used for saving


static intermediate results in the
instance data block. Static data
Static local data Static
is retained until it is overwritten, Function blocks
which may be after several
cycles.

Page 31 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
29. The following tags are required in our example for declaration of the local tags.

Input:

selection01 Selector switch 1


selection02 Selector switch 2

Output:

lamp01 Indicator light 1


lamp02 Indicator light 2

In this case, all of the tags are ‘Bool’ type tags. That is, they are binary tags that can only have the state
‘0’ (false) or ‘1’ (true).
All local tags should also be provided with a sufficiently descriptive comment for better understanding.

Note:
To avoid confusion with the PLC tags, it is helpful to write the local tags with lowercase letters.

Page 32 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
30. Once the local tags have been declared, you can start to create the program shown here. To
provide a better overview, we program in networks. A new network can be inserted by clicking on

the symbol ‘Insert network’. Like the block itself, each network should be documented in the
title line at least. If a longer text is needed for the description, the ‘Comment’ field can be used in
addition.

Page 33 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
31. Before we double-click to open the block ‘Main[OB1]’, we select ‘FBD’ as its programming
language.
( Main[OB1]  Switch programming language  FBD  Main[OB1])

Page 34 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
32. The ‘program view’ block can then be moved to Network 1 of the Main[OB1] block by means of
drag-and-drop. The interface parameters of the ‘program view’ block must now be connected to
the global PLC tags as shown here. Don't forget to document the networks in the Main[OB1] block.
( Program view [FC1])

Page 35 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
‫‪33. The button‬‬ ‫‪is then used to save the project once again.‬‬

‫‪("EMERGENCY STOP" ‬‬ ‫‪‬‬ ‫)‬

‫‪Page 36 of 39‬‬
‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‪/‬ﺗوزﯾﻊ‪/‬آﻣوزش اﺗوﻣﺎﺳﯾون‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
34. To only load the program blocks to the CPU, first select the ‘Program blocks’ folder and click the
Download to device icon . ( Program blocks  )

Page 37 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
35. The program is now compiled automatically, and an overview of the steps to be performed is
displayed once again for checking before the program is loaded. Click ‘Load’ to start loading the
program. ( Load)

Page 38 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬
36. Clicking the icon (Monitoring on/off) allows you to monitor the state of the input and output tags

on the ‘program view’ block. ( )

Page 39 of 39
‫آﻣوزش اﺗوﻣﺎﺳﯾون‬/‫ﺗوزﯾﻊ‬/‫ﺷرﮐت ﺳﯾﻣﯽ ﻧﺻر ﻣﺎد ﺗﺎﻣﯾن‬
‫ﺻﻧﻌﺗﯽ و اﺑزار دﻗﯾﻖ و ﺗﺟﮭﯾزات ﻓﺷﺎر ﺿﻌﯾف زﯾﻣﻧس‬

You might also like