This document provides a quick reference guide for a VLT 2800 frequency converter. It includes sections on parameter lists, control keys, status messages, warnings and alarms. The parameter list section details the factory settings for various adjustable parameters related to items like language selection, local/remote operation, reference values and more. The control keys section describes the functions of keys for tasks like changing parameters, starting and stopping the drive. Status messages shown on the display provide real-time readings for output frequency, current, voltage and other values.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
412 views2 pages

Danfoss Quick Reference Guide PDF

This document provides a quick reference guide for a VLT 2800 frequency converter. It includes sections on parameter lists, control keys, status messages, warnings and alarms. The parameter list section details the factory settings for various adjustable parameters related to items like language selection, local/remote operation, reference values and more. The control keys section describes the functions of keys for tasks like changing parameters, starting and stopping the drive. Status messages shown on the display provide real-time readings for output frequency, current, voltage and other values.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

VLT 2800 Quick Reference Guide

■ Parameter list ■ Status messages Parameter- Selection/range Factory Setting


This list can be used for checking and F r # description setting
making a note of your parameter settings. The frequency converter shows the present 001 Language [0]=English, [1]=German, [2]=French, [0]=English
The list can be folded and placed in the output frequency in Hertz [Hz]. [3]=Danish, [4]=Spanish, [5]=Italian
enclosed plastic folder. 002 Local/remote [0]=Remote operation, [0]=Remote
I o operation [1]=Local operation operation
■ Control keys The frequency converter shows the present 003 Local reference 0-fMAX / RefMIN-RefMAX / -RefMAX - +RefMAX 000,000.000
[QUICK MENU] gives access to output current in Amps [A].
the parameters used in the 004 Active Setup [0]=Factory Setup, [1]=Setup 1, [1]=Setup 1
Quick menu. The [QUICK [2]=Setup 2, [3]=Setup 3, [4]=Setup 4,
U o [5]=Multi Setup
MENU] key is also used if a change of a The frequency converter shows the present
parameter value is not to be carried out. 005 Programming [0]=Factory Setup, [1]=Setup 1, [5]=Active Setup
output voltage in Volts [V].
Setup [2]=Setup 2, [3]=Setup 3, [4]=Setup 4,
See also [QUICK MENU] + [+].
[5]=Active Setup
U d 006 Setup See manual [0]=No copying
[CHANGE DATA] is used for The frequency converter shows the copying
changing a setting. The intermediate circuit voltage in Volts [V]. 007 LCP copy [0]=No copying, [1]=Upload all [0]=No copying
[CHANGE DATA] key is also parameters, [2]=Download all para-
used for confirming the change of a meters, [3]=Download power-
P o
parameter setting. The frequency converter shows the independent parameters
calculated output power in kilowatts [kW]. 008 Display scaling of 0.01 - 100.00 1.00
[+] / [-] are used for selecting a output frequency
parameter and for changing 009 Large display See manual [4]=Frequency
notrun readout [Hz]
the chosen parameter value. This message is displayed if an attempt is
010 Small display See manual [1]=Reference
These keys are also used in made to change a parameter value, while readout 1.1 [%]
Display mode for switching the motor is running. Stop the motor to 011 Small display See manual [6]=Motor
between operating variable change the parameter value. readout 1.2 current [A]
read-outs. 012 Small display See manual [8]=Power [kW]
LCP readout 1.3
[QUICK MENU]+[+] This message is shown if an LCP 2 control 013 Local control [0]=Local not active, [4]=Remote
keys must be pressed unit has been installed and the [QUICK [1]=Local control and open loop, operated control
simultaneously to give MENU] or [CHANGE DATA] key has been [2]=Remote operated control and open as par. 100
access to all activated. loop, [3]=Local control as par. 100,
[4]=Remote operated control as par. 100
parameters. With an LCP 2 unit installed, it is only
014 Local stop/Reset [0]=Not active, [1]=Active [1]=Active
possible to change parameters via this unit.
[STOP/RESET] is used for 015 Local jog [0]=Not active, [1]=Active [0]=Not active
stopping the connected motor or Err.
for resetting the frequency A warning or alarm will be shown by means 016 Local reversing [0]=Not active, [1]=Active [0]=Not active
converter after a trip. of a digit code on the display, e.g. Err
13. A warning will be shown on the 017 Local reset [0]=Not active, [1]=Active [1]=Active
[START] is used for starting the display until the fault has been corrected, of trip
frequency converter. Is always and an alarm will flash until [RESET] is 018 Lock for [0]=Not locked, [1]=Locked [0]=Not locked
active, but the [START] key data change
activated.
019 Operating mode [0]=Auto restart, use saved ref. [1]=Forced stop,
cannot override a stop command.
at power-up, [1]=Forced stop, use saved ref. use saved ref.
Ha local operation [2]=Forced stop, set ref. to 0
The frequency converter shows the present 020 Lock for Hand [0]=Not active, disable [1]=Active, enable
Hand mode reference in Herz [Hz]. mode [1]=Active, enable
024 User-defined [0]=Not active, [1]=Active [0]=Not active
Quick Menu
■ Warnings/alarm messages 025 Quick Menu [Index 1-20] 000
The list below gives a description of the Setup Value 0-999
different warnings and alarms. 100 Configuration [0]=Speed regulation, open loop [0]=Speed
After a Trip locked, the mains supply must [1]=Speed regulation, closed loop regulation,
[3]=Process regulation, closed loop open loop
be disconnected and the fault must be
101 Torque [1]=Constant torque [1]=Constant
corrected. Connect the mains supply again characteristic [2]=Variable torque, low torque
and reset the frequency converter. The [3]=Variable torque, medium
frequency converter is now ready for [4]=Variable torque, high
operation. [5]=Variable torque, low CT start
A Trip can be reset manually in three [6]=Variable torque, medium CT start
different ways: [7]=Variable torque, high CT start
- Via the control key [STOP/RESET] [8]=Special motor characteristic
- Via a digital input. 102 Motor power PM,N 0.37-11 kW Depends on unit
103 Motor 200-240 V/380-480 V Depends on unit
- Via serial communication.
voltage UM,N
104 Motor 24-1000 Hz 50 Hz
The manual gives a description of the frequency fM,N
different faults. 105 Motor 0.01-IMAX Depends on
current IM,N choice of motor
No. 2 Live zero fault 106 Rated 100-fM,N x 60 (max. 60000 rpm) Depends on
No. 4 Mains phase fault motor speed choice of motor
No. 5 Voltage warning high 107 Automatic [0]=Optimisation off [0]=Optimisation
No. 6 Voltage warning low motor tuning [2]=Optimisation on off
No. 7 Overvoltage 108 Stator 0.000-X.XXX Ω Depends on
resistance RS choice of motor
No. 8 Undervoltage
109 Stator 0.00-X.XX Ω Depends on
No. 9 Inverter overload
reactance XS choice of motor
No. 10 Motor overload 119 High start torque 0.0 - 0.5 sec. 0.0 sec.
No. 11 Motor thermistor
No. 12 Current limit 120 Start delay 0.0-10.0 sec. 0.0 sec.
No. 13 Overcurrent 121 Start function [0]=DC hold during start delay time [2]=Coasting
No. 14 Earth fault [1]=DC brake during start delay time during start
No. 15 Switch mode fault [2]=Coasting during start delay time delay time
No. 16 Short-circuit [3]=Start frequency/voltage clockwise
No. 17 Serial communication time-out [4]=Start frequency/voltage in reference
No. 18 HPFB bus time-out direction
122 Function at stop [0]=Coasting [0]=Coasting
No. 33 Out of frequency range
[1]=DC hold
No. 34 HPFB communication fault 123 Min. frequency 0.1 - 10.0 Hz 0.1 Hz
No. 35 Inrush fault for activating of
No. 36 Overload temperature function at stop
Nos. 37-45 Internal faults 126 DC brake time 0-60 sec. 10 sec.
No. 50 AMT RS outside limit
No. 51 AMT fault re. nameplate data 127 DC brake cut-in 0.0 (OFF) - par. 202. Output frequency OFF
No. 52 AMT faulty motor phase frequency high limit, fMAX
No. 53 AMT motor too small 128 Motor thermal See manual [0]=No
protection protection
No. 54 AMT incorrect motor
130 Start frequency 0.0-10.0 Hz 0.0 Hz
No. 55 AMT timeout
No. 56 AMT warning during AMT 131 Voltage at start 0.0 - 200.0 V 0.0 V
No. 99 Locked

MG.28.D5.02 - VLT is a registered Danfoss trademark 195R0033


Parameter- Selection/range Factory Setting Parameter- Selection/range Factory Setting
# description setting # description setting
132 DC brake 0-100% of max. DC brake voltage 0% 310 Term. 53, Max. 0 - 10.0 V 10.0 V
voltage scaling
133 Start voltage 0.00-100.00 V Depends on unit 314 Term. 60, analo- [0]=No operation, [1]=Reference [0]=No operation
gue input current [2]=Feedback
134 Load 0.00-300.0% 100,0% 315 Term. 60, Min. 0.0 - 20.0 mA 0.0 mA
compensation scaling
135 U/f ratio 0.00-20.0 at Hz Depends on unit 316 Term. 60, Max. 0.0 - 20.0 mA 20.0 mA
scaling
136 Slip -500 - +500% of rated 100% 317 Time out 1 - 99 sec. 10 sec.
compensation slip compensation
137 DC 0-100% of max. DC hold voltage 0% 318 Function after [0]=No operation, [1]=Freeze output [0]=No operation
hold voltage time out frequency, [2]=Stop, [3]=Jog,
138 Brake cut 0.5 - 132.0/1000.0 Hz 3.0 Hz [4]=Max. speed, [5]=Stop and trip
out value 319 Term. 42, See manual [7] = 0-IINV.
139 Brake cut 0.5 - 132.0/1000.0 Hz 3.0 Hz analogue output 0-20 mA
in frequency 323 Relay output See manual [1]=Drive ready
140 Current, minimum 0 - 100% of Within 0% 327 Pulse/reference 150 - 67600 Hz 5000 Hz
value feedback
142 Spread 0.000-XXX.XXX Ω Depends on 341 Term. 46, See manual [1]=Drive ready
reactance choice of motor digital output
143 Internal fan [0]=Automatic, [1]=Always switched [0] = Automatic 342 Term. 46, Max.
control on, [2]=Always switched off pulse output 150 - 10,000 Hz 5000 Hz
144 Gain AC brake 1.0 - 1.50 1.30 343 Precise stop See manual [0] = Normal
146 Reset voltage [0]=Off [0]=Off function ramp stop
vector [1]=Reset 344 Counter value 1 - 999999 100000 pulses
349 Speed comp 0 - 100 ms 10 ms
200 Output [0]=Only clockwise, 0-132 Hz [0]=Only clock- delay
frequency range [1]=Both directions, 0-132 Hz wise, 0-132 Hz 400 Brake function [0]=Off, [1]=Resistor brake Depends on unit
[2]=Only anti-clockwise, 0-132 Hz [4] AC brake, [5]=Load sharing
[3]=Only clockwise, 0-1000 Hz 405 Reset function See manual [0]=Manual reset
[4]=Both directions, 0-1000 Hz
[5]=Only anti-clockwise, 0-1000 Hz 406 Automatic 0 - 10 sec. 5 sec.
201 Output frequency 0.0 - fMAX 0.0 Hz restart time
low limit, fMIN 409 Trip delay 0 - 60 sec. (61=OFF) OFF
202 Output frequency fMIN - 132/1000 Hz 132 Hz overcurrent
high limit, fMAX 411 Switching 3000 - 14000 Hz 4500 Hz
203 Reference/ [0]=Min. ref./fb - Max. ref./fb [0]=Min. ref./fb - frequency
feedback range [1]=-Max. ref./fb - Max. ref./fb Max. ref./fb 412 Output frequency [2] = No LC-filter [2] = No LC-filter
204 Min. reference Par. 100 Config. = Open loop [0] 0.000 Hz dependent [3] = LC-filter fitted
RefMIN - 100,000.000 - par. 205 Ref MAX switching
Par. 100 Config. = Closed loop [1]/[3] 0.000 413 Overmodulation [0]=Off, [1]=On [1]=On
- Par. 414 Min. fb - Par. 205 RefMAX function
205 Max. reference Par. 100 Config. = Open loop [0] 50.000 Hz 414 Min. feedback, -100,000.000 - par. 415 FBMAX 0.000
RefMAX Par. 204 Ref MIN-1000.000 Hz FBMIN
Par. 100 Config. = Closed loop [1]/[3] 50.000 415 Max. feedback, par. 414 FB MIN - 100,000.000 1500.000
Par. 204 Ref MIN- Par. 415 Max. fb FBMAX
206 Ramp type [0]=Linear [1]=Sine-shaped [0]=Linear 416 Process units See manual [0]=No unit
[2]=Sine- 2shaped
207 Ramp-up time 1 0.02-3600 sec. 3.00 sec. 417 Speed PID pro- 0.000 (OFF) - 1.000 0.010
portional gain
208 Ramp-down 0.02-3600 sec. 3.00 sec. 418 Speed PID 20.00 - 999.99 ms (1000 = OFF) 100.00 ms
time 1 integral time
209 Ramp-up time 2 0.02-3600 sec. 3.00 sec. 419 Speed PID 0.00 (OFF) - 200.00 ms 20 ms
differential time
210 Ramp-down 0.02-3600 sec. 3.00 sec. 420 Speed PID 5.0 - 50.0 5.0
time 2 D-gain limit
211 Jog ramp time 0.02-3600 sec. 3.00 sec. 421 Speed PID 20 - 500 ms 20 ms
lowpass filter time
212 Quick stop 0.02-3600 sec. 3.00 sec. 423 U1 voltage 0.0 - 999.0 V par. 103
ramp-down time
213 Jog frequency 0.0- Par. 202 Output frequency 10.0 Hz 424 F1 frequency 0.0 - par. 426 F2 frequency par. 104
high limit Motor frequency
214 Reference [0]=Sum [0]=Sum 425 U2 0voltage 0.0 - 999,0 V par. 103
function [1]=Relative
[2]=External/preset 426 F2 frequency Par. 424 F1 frequency - par. 104
215 Preset ref. 1 -100.00% - + 100.00% 0.00% par. 428 F3 frequency Motor frequency
427 U3 voltage 0.0 - 999.0 V 0.0 V
216 Preset ref. 2 -100.00% - + 100.00% 0.00%
428 F3 frequency Par. 426 F2 frequency - 1000 Hz par. 104
217 Preset ref. 3 -100.00% - + 100.00% 0.00% Motor frequency
437 Process PID [0]=Normal, [1]=Inverse [0]=Normal
218 Preset ref. 4 -100.00% - + 100.00% 0.00% Normal/inverse
control
219 Catch up/slow 0.00-100% of the current reference 0.00% 438 Process PID [0]=Not active, [1]=Active [1]=Active
down reference anti windup
221 Current limit, [A] = x-xxx.x% of IMAX 160% 439 Process PID fMIN - fMAX (par. 201/202) Par. 201 Output
ILIM start frequency frequency low
223 Warning: 0.0 - Par. 224 Warning: High current, 0.0 A limit, fMIN
Low current IHIGH 440 Process PID 0.0 - 10.00 0.01
224 Warning: Par. 223 Warning: Low current, IMAX proportional gain
High current ILOW - IMAX
225 Warning: 0.0 - par. 226 Warning: High frequency, 0.0 Hz 441 Process PID 0.01 - 9999.99 ms (OFF) OFF
Low frequency fHIGH integration time
226 Warning: Par 225 f LOW - 120/1000 Hz 132.0 Hz 442 Process PID 0.00 (OFF) - 10.00 sec. 0.00 sec.
High frequency differentiation time
227 Warning: 100,000.000 - par. 228 -4000.000 443 Process PID diff. 5.0 - 50.0 5.0
Low feedback, Warning: FBHIGH gain limit
FBLOW 444 Process PID 0.02 - 10.00 0.02
228 Warning: Par. 227 - Warning: 4000.000 lowpass filter time
High feedback, FBLOW - 100,000.000 445 Flying start [0]=Off, [1]=OK same direction, [0]=OFF
FBHIGH [2]=OK both directions,
229 Frequency bypass, 0 (OFF) - fMAX 0 Hz [3]=DC brake and start
bandwidth 451 FF factor 0 - 500% 100%
230 Frequency 0 -132/1000 Hz 0.0 Hz
bypass 1 452 Controller 0 - 200% 10%
231 Frequency 0 -132/1000 Hz 0.0 Hz range
bypass 2 456 Brake voltage 0 - 25 V if 200V device 0
302 Digital input See manual [7]=Start reduce 0 - 50 V if 400V device 0
Terminal 18
303 Digital input See manual [9]=Reversing
Terminal 19
304 Digital input See manual [3]=Reset and
Terminal 27
305 Digital input See manual
coasting inverse
[13]=Jog
Terminal Rail Layout
Terminal 29
307 Digital input See manual [0]=No operation
Terminal 33
308 Term. 53, analo- [0]=No operation, [1]=Reference [1]=Reference
gue input voltage [2]=Feedback
309 Term. 53, Min. 0.00 - 10.0 V 0.0 V
scaling