INT69 KF2® Diagnose

INT69 KF2® Diagnose


Application
The motor protector INT69 KF2 Diagnose is a further development of
the reliable KRIWAN motor protectors.
The INT69 KF2 Diagnose automatically saves operational and error
data in a non-volatile memory. This data can be retrieved on a PC and
analysed for diagnosis. The full scope of the diagnosis is achieved by
using a KRIWAN-specific AMS sensor.
This motor protector is mainly employed on compressors which are
qualified acc. to IEC/EN 60335.
Functional description
The temperature monitoring in the motor winding is done according to
the static evaluation process; the motor is switched off immediately if
the nominal response temperature of the built-in AMS or PTC sensors
INT69 KF2 Diagnose
is reached.
L1 A short circuit at an AMS or PTC input also leads to a switch-off.
L2 After expiration of the reset delay and elimination of the error or cool-
L3
N down, the compressor can be restarted.
PE For operation in the specified manner, the supply voltage has to be on
INT69 KF2 Diagnose DP
permanently on the INT69 KF2 Diagnose.
Technical specifications
K1 T2 T1 S2 S1 M2 M1
Supply voltage
F1 K1 - 22 A 620 ... 115-230V ~ 50Hz ±10% 3VA
M °C
120-240V ~ 60Hz ±10% 3VA
3 AC
F2 HP - 31 A 620 ... 24V ~ 50/60Hz ±10% 3VA
LP Permitted ambient temperature -30...+70°C
Motor PTC
Temperature measuring circuits
- Type 1-2 AMS sensors in series
Wiring diagram alternative 1-9 PTC acc. to
DIN 44081, DIN 44082 in series
76.5 35 - R25,total <1.8kΩ
4.7

- Rtrip, static 4.5kΩ ±20%


- Rreset 2.75kΩ ±20%
- Max. length connection line 30m
Short circuit monitoring system
PTC Typically <30Ω
Reset delay
81.5
72.1

- .. A 620 S80 30min ±5min


- .. A 620 S81 60min ±5min

Product group A
Reset of reset delay Main reset >5 sec. only possible if
there is no error current
Relay
Ø3.84 64.8 5.85 15.9 - Connection Refer to wiring diagram
30.8 Max. 2.5A C300
Dimensions in mm - Mechanical service life Approx. 1 million switching cycles
The mounting, maintenance and operation are to be carried out Interface Diagnose port (DP)
by an electrician. The valid European and national standards for Protection class acc. to EN 60529 IP00
connecting electrical equipment and cooling installations have to Connection type 6.3mm flat connection
be observed. Connected sensors and connection lines that Housing material PA glass-fibre-reinforced
extend from the terminal box have to feature at least a basic insu- Mounting Screw mounted
lation. Dimensions Refer to dimensions in mm
Edition: 710.00430.1

To determine the compressor running times, the INT69 KF2 Weight Approx. 200g
Diagnose has to be the last protection unit before the compressor
Check base IEC/EN 60335, IEC/EN 60730
contacter (see wiring diagram). For that, the INT69 KF2 Diagnose
EN 61000-6-2, EN 61000-6-3
and the safety circuit have to be connected to the same phase of
EN 61010-1
the same supply network.
Overvoltage category II
Order data Pollution level 2
INT69 KF2 Diagnose (AC 115-230V, 30min) 22 A 620 S80 Approval UL File no. E75899 cURus
INT69 KF2 Diagnose (AC 115-230V, 60min) 22 A 620 S81 VDE certification no. 40022017
INT69 KF2 Diagnose (AC 24V, 30min) 31 A 620 S80
Accessories and application
information see www.kriwan.com
Technical changes reserved