PLUMBING DESIGN ANALYSIS

PROJECT: PROPOSED LCC CITY SQUARE & BICOL CENTRAL TERMINAL

Rest room 1 (Ground Floor - FEMALE C.R.)

Fixtures no. of fixtures Equivalent Fixture Unit Total Fixture unit


1. Lavatory 4 1 4 FU
2. Urinal 0 2 0 FU
3. Water Closet 6 6 36 FU
4. Floor drain 4 2 8 FU
Total 48 FU

In the Presence of Water Closet Use Minimum Size of Discharge Pipe =75mm(min)
Use Vent Pipe size= 50mm(min)

Rest room 2 (Ground Floor - MALE C.R.)

Fixtures no. of fixtures Equivalent Fixture Unit Total Fixture unit


1. Lavatory 3 1 3 FU
2. Urinal 5 2 10 FU
3. Water Closet 3 6 18 FU
4. Floor drain 3 2 6 FU
Total 37 FU

In the Presence of Water Closet Use Minimum Size of Discharge Pipe =75mm(min)
Use Vent Pipe size= 50mm(min)

Rest room 3 (Ground Floor - PWD C.R.)

Fixtures no. of fixtures Equivalent Fixture Unit Total Fixture unit


1. Lavatory 1 1 1 FU
2. Urinal 1 2 2 FU
3. Water Closet 1 6 6 FU
4. Floor drain 1 2 2 FU
Total 11 FU

In the Presence of Water Closet Use Minimum Size of Discharge Pipe =75mm(min)
Use Vent Pipe size= 50mm(min)
Rest room 4 (Ground Floor - FEMALE C.R.)

Fixtures no. of fixtures Equivalent Fixture Unit Total Fixture unit


1. Lavatory 2 1 2 FU
2. Urinal 0 2 0 FU
3. Water Closet 2 6 12 FU
4. Floor drain 2 2 4 FU
Total 18 FU

In the Presence of Water Closet Use Minimum Size of Discharge Pipe =75mm(min)
Use Vent Pipe size= 50mm(min)

Rest room 5 (Ground Floor - MALE C.R.)

Fixtures no. of fixtures Equivalent Fixture Unit Total Fixture unit


1. Lavatory 2 1 2 FU
2. Urinal 3 2 6 FU
3. Water Closet 2 6 12 FU
4. Floor drain 3 2 6 FU
Total 26 FU

In the Presence of Water Closet Use Minimum Size of Discharge Pipe =75mm(min)
Use Vent Pipe size= 50mm(min)

Rest room 6 (Ground Floor - PWD C.R.)

Fixtures no. of fixtures Equivalent Fixture Unit Total Fixture unit


1. Lavatory 1 1 1 FU
2. Urinal 1 2 2 FU
3. Water Closet 1 6 6 FU
4. Floor drain 1 2 2 FU
Total 11 FU

In the Presence of Water Closet Use Minimum Size of Discharge Pipe =75mm(min)
Use Vent Pipe size= 50mm(min)
Rest room 7 (Ground Floor -STAFF TOILET)

Fixtures no. of fixtures Equivalent Fixture Unit Total Fixture unit


1. Lavatory 1 1 1 FU
2. Urinal 1 2 2 FU
3. Water Closet 1 6 6 FU
4. Floor drain 1 2 2 FU
Total 11 FU

In the Presence of Water Closet Use Minimum Size of Discharge Pipe =75mm(min)
Use Vent Pipe size= 50mm(min)

Rest room 8 (Second Floor - FEMALE C.R.)

Fixtures no. of fixtures Equivalent Fixture Unit Total Fixture unit


1. Lavatory 6 1 6 FU
2. Urinal 0 2 0 FU
3. Water Closet 9 6 54 FU
4. Floor drain 6 2 12 FU
Total 72 FU

In the Presence of Water Closet Use Minimum Size of Discharge Pipe =75mm(min)
Use Vent Pipe size= 50mm(min)

Rest room 9 (Second Floor - MALE C.R.)

Fixtures no. of fixtures Equivalent Fixture Unit Total Fixture unit


1. Lavatory 5 1 5 FU
2. Urinal 7 2 14 FU
3. Water Closet 4 6 24 FU
4. Floor drain 5 2 10 FU
Total 53 FU

In the Presence of Water Closet Use Minimum Size of Discharge Pipe =75mm(min)
Use Vent Pipe size= 50mm(min)
Rest room 10 (Second Floor - PWD C.R.)

Fixtures no. of fixtures Equivalent Fixture Unit Total Fixture unit


1. Lavatory 1 1 1 FU
2. Urinal 1 2 2 FU
3. Water Closet 1 6 6 FU
4. Floor drain 1 2 2 FU
Total 11 FU

In the Presence of Water Closet Use Minimum Size of Discharge Pipe =75mm(min)
Use Vent Pipe size= 50mm(min)

Rest room 11 (Third Floor - STAFF FEMALE C.R.)

Fixtures no. of fixtures Equivalent Fixture Unit Total Fixture unit


1. Lavatory 2 1 2 FU
2. Urinal 0 2 0 FU
3. Water Closet 2 6 12 FU
4. Floor drain 2 2 4 FU
Total 18 FU

In the Presence of Water Closet Use Minimum Size of Discharge Pipe =75mm(min)
Use Vent Pipe size= 50mm(min)

Rest room 12 (Third Floor - STAFF MALE C.R.)

Fixtures no. of fixtures Equivalent Fixture Unit Total Fixture unit


1. Lavatory 2 1 2 FU
2. Urinal 0 2 0 FU
3. Water Closet 2 6 12 FU
4. Floor drain 2 2 4 FU
Total 18 FU

In the Presence of Water Closet Use Minimum Size of Discharge Pipe =75mm(min)
Use Vent Pipe size= 50mm(min)

Total DFU 334 FU

Use Minimun Size of Discharge Pipe= 100mm(min)


Use vent pipe size= 50mm(min)