PM8000 Datasheet
PM8000 Datasheet
PM8000 Datasheet
Schneider Electric
PM8000 Technical Datasheet
Advanced metering PM8000 series
Functions and characteristics
The PowerLogic PM8000 series meter is a highly accurate, extremely reliable power
PB113688
and energy meter with unmatched flexibility and usability. The meter combines
accurate 3-phase energy and power measurements with data logging, power quality
analysis, alarming and I/O capabilities not typically available in such a compact
meter.
The PM8000 series meters are compliant with stringent international standards that
guarantee their metering accuracy and power quality measurements. Ideal for
industrial and critical power installations that are responsible for maintaining the
operation and profitability of a facility.
vv Class 0.2S accuracy IEC 62053-22, ANSI C12.20 Class 0.2 (active energy).
vv Industry leading Class 0.5S* accuracy for reactive energy (IEC 62053-24).
vv Cycle-by-cycle RMS measurements updated every ½ cycle.
vv Full ‘multi-utility’ WAGES metering support.
vv Net metering.
vv Anti-tamper protection seals.
*Certification pending
2 plsed310058EN
Advanced metering PM8000 series
Functions and characteristics (cont.)
Ease of use
bb Easy installation and setup.
vv Panel and DIN rail mounting options, remote display option.
vv Pluggable connectors.
vv Free setup application simplifies meter configuration.
Adaptability
bb ION™ frameworks allow customizable, scalable applications, object-oriented
programming, compartmentalizes functions, and increases flexibility and
adaptability.
vv Applications include: access and aggregate data from Modbus devices on serial
port or across the network (Modbus TCP/IP), logging and/or processing data by
totalizing, unit conversion or other calculations, applying complex logic for
alarming or control operations, data visualization via web pages.
plsed310058EN 3
Advanced metering PM8000 series
Functions and characteristics (cont.)
bb Digital module
vv 6 digital status/counter inputs.
vv 2 Form C relay outputs, 250 V AC / 30 V DC, max current 8 A at 250 V AC or 5 A at
24 V DC, 20 k cycles (resistive).
bb Analogue module
PowerLogic PM8000 series meter with I/O modules. vv 4 analogue inputs (4-20 mA; 0-30 V).
vv 2 analogue outputs (4-20 mA; 0-10 V) for interfacing with building management
sensors and systems.
4 plsed310058EN
Advanced metering PM8000 series
Functions and characteristics (cont.)
plsed310058EN 5
Advanced metering PM8000 series
Functions and characteristics (cont.)
6 plsed310058EN
Advanced metering PM8000 series
Functions and characteristics (cont.)
Electromagnetic compatibility
Product standards IEC 62052-11 and IEC 61326-1
Immunity to electrostatic discharge IEC 61000-4-2
Immunity to radiated fields IEC 61000-4-3
Immunity to fast transients IEC 61000-4-4
Immunity to surges IEC 61000-4-5
Immunity to conducted disturbances IEC 61000-4-6
Immunity to power frequency IEC 61000-4-8
magnetic fields
Immunity to conducted disturbances, CLC/TR 50579
2-150 kHz
Immunity to voltage dips & IEC 61000-4-11
interruptions
Immunity to ring waves IEC 61000-4-12
Conducted and radiated emissions EN 55022, EN 55011, FCC part 15, ICES-003
Surge withstand Capability (SWC) IEEE C37.90.1
Safety
Safety Construction IEC/EN 61010-1 ed.3, CAT III, 400 V L-N / 690 V L-L
UL 61010-1 ed.3 and CSA-C22.2 No. 61010-1 ed.3, CAT
III, 347 V L-N / 600 V L-L
IEC/EN 62052-11, protective class II
Communication (1)
Ethernet to serial line gateway Communicates directly with up to 32 unit load ION slave
devices.
Web server Customisable pages, new page creation capabilities,
HTML/XML compatible.
Serial port RS 485 Baud rates of 2400 to 115200, pluggable screw terminal
connector.
Ethernet port(s) 2 x 10/100BASE-TX, RJ45 connector (UTP).
Protocol Modbus, ION, DNP3, IEC 61850, HTTP, FTP, SNMP, SMTP,
DPWS, RSTP, NTP, SNTP, GPS protocols.
Firmware characteristics
High-speed data recording Down to 1/2 cycle interval burst recording, stores detailed
characteristics of disturbances or outages. Trigger
recording by a user-defined setpoint, or from external
equipment.
Harmonic distortion Up to 63rd harmonic for all voltage and current inputs.
Sag/swell detection Analyse severity/potential impact of sags and swells:
magnitude and duration data suitable for plotting on
voltage tolerance curves per phase triggers for waveform
recording, control.
Disturbance direction detection Determine the location of a disturbance more quickly and
accurately by determining the direction of the disturbance
relative to the meter. Analysis results are captured in the
event log, along with a timestamp and confidence level
indicating level of certainty.
Instantaneous High accuracy of standard speed (1s) and high-speed
(1/2 cycle) measurements, including true rms per phase
and total for:
voltage, current, active power (kW),reactive power (kvar),
apparent power (kVA), power factor, frequency, voltage
and current unbalance, phase reversal.
Load profiling Channel assignments (800 channels via 50 data
recorders) configurable for any measurable parameter,
including historical trend recording of energy, demand,
voltage, current, power quality, or any measured
parameter. Trigger recorders based on time interval,
calendar schedule, alarm/event condition, or manually.
Trend curves Historical trends and future forecasts to better manage
demand, circuit loading, and other parameters. Provides
average, min, max and standard deviation every hour for
last 24 hours, every day for last month, every week for last
8 weeks and every month for last 12 months.
Waveform captures Simultaneous capture of all voltage and current channels
sub-cycle disturbance capture, maximum cycles is
100,000 (16 samples/cycle x 96 cycles, 10 MB memory),
max 256 samples/cycle.
Alarms Threshold alarms: adjustable pickup and dropout setpoints
and time delays, numerous activation levels possible for a
given type of alarm, user-defined or automatic alarm
threshold settings, user-defined priority levels (optional
automatic alarm setting).
plsed310058EN 7
Advanced metering PM8000 series
Functions and characteristics (cont.)
8 plsed310058EN
Schneider Electric Industries SAS As standards, specifications and designs develop from time to time, please ask
35, Rue Joseph Monier, for confirmation of the information given in this document.
CS 30323
F - 92506 Rueil Malmaison Cedex
Design: Schneider Electric
RCS Nanterre 954 503 439 Photos: Schneider Electric
Capital social 896 313 776
www.schneider-electric.com Over 75 % of Schneider Electric products
have been awarded the Green Premium ecolabel
PM8000 Meter