Space To Height Ratio

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Lighting Science, Theory and Calculations 37

________________________________________________________________________

Example 1.9

Calculate the Utilisation Factor for a room with the following dimensions:
Length 8m; Width 6m; Height 3m; height of working plane 0.8m. The room
reflectances are Ceiling 0.5; Walls 0.3 and Floor 0.2.

LxW 8x6
R.I. = ------------ = ------------ = 1.558 (say 1.5)
(L + W) Hm (8 + 6)2.2

From Table 1.8 the Utilisation factor can be read as 0.63

1.9.5 SPACE: HEIGHT RATIO (SHR)

This is the ratio of space between


luminaires (S) to their height above the
S working plane (Hm).

Hm Manufacturers will specify a


working plane
recommended SHR for each of their
luminaires. Ensuring that luminaires
are spaced within the recommended
value will mean an acceptable variation
in illuminance across the working
Fig. 1.24
plane. This is expressed in terms of the
Uniformity Ratio (see definitions).

Example 1. 10 A factory area is 40m long, 20m wide and is 8m high.


Point source luminaires are suspended 1.5 metres below ceiling level. The
working plane is 1 metre high. Calculate the minimum number of luminaires
which must be installed to conform with a recommended SHR of 1.5 : 1.

1.5m Hm = 8 - (1.5 + 1) = 5.5m

8m SHR = 1.5 : 1

W.P.
1.0m therefore S = 1.5 x 5.5 = 8.25m
Fig. 1.25

________________________________________________________________________
Interior Lighting Design - A Student's Guide KK/KO'C 97
Lighting Science, Theory and Calculations 38
________________________________________________________________________

W 20
Min. no. of rows = --- = ---- = 2.4 (3 rows)
S 8.25

L 40
Min. no. of luminaires per row = --- = ---- = 4.85 (5 luminaires)
S 8.25

This means that the minimum number to conform with SHR. requirement is 3
rows with 5 luminaires per row. More than this number can be used if desired
for reasons such as balance, effect, control or ease of installation.

Assuming that three rows of five luminaires is suitable, the actual spacing is
determined as follows:
W 20
Spacing between rows (S) = ----------- = ---- = 6.67m.
No of rows 3

Note: The spacing between the last row and the wall should < 0.5 S. i.e.< 3.33m

L 40
Spacing in rows (S) = ------------ = ------ = 8m
No per row 5

Layout diagram
40m
3.33
4.0 8.0 8.0 8.0 8.0 4.0

6.67

20m

6.67

3.33

Fig. 1.26
Note: If work is to be carried out at the perimeter of the room, a spacing of 0.33 S
to the wall may be used.

________________________________________________________________________
Interior Lighting Design - A Student's Guide KK/KO'C 97
Lighting Science, Theory and Calculations 39
________________________________________________________________________

Linear Luminaires

The relevant spacing maximum transverse and axial spacing data will be
supplied by the manufacturer. The spacing is usually taken between centres.

(Note: the maximum recommended transverse SHR is usually different from the
axial SHR where linear luminaires are used).

Where high levels of illuminance


Transverse spacing are required, it is common practice
to use continuous rows of
luminaires with the transverse
spacing at the maximum
permissible. In this way, installation
costs will be kept to a minimum,
particularly where luminaires are
Axial spacing suspended below the ceiling.

The lighting installation must


however be co-ordinated with other
services and compromise with air
conditioning outlets and other
Fig. 1.27 ceiling mounted equipment is often
necessary in practice.

Example 1.11

The factory in example 1.10 is to be illuminated using continuous rows of twin


1500mm fluorescents. Calculations indicate that 72 luminaires are required.
Design a suitable layout given a mounting height above the working plane of
5.5m and the following SHR's apply.

Transverse 2.00 : 1 (spacing between rows)


Axial 1.75 : 1 (spacing in rows)

(i) Spacing between rows: Hm = 5.5m, therefore S = 5.5 x 2 = 11m

Two continuous rows of fluorescents 10 metres apart and 5 metres from each
side wall would conform with the SHR requirement, this would mean using 36
luminaires per row and these would not fit in the 40m available.
i.e. 36 x 1.5 = 54m. which is longer than the building.

Note the actual physical dimensions of luminaires with 1.5m tubes is 1.6m
approximately.
________________________________________________________________________
Interior Lighting Design - A Student's Guide KK/KO'C 97
Lighting Science, Theory and Calculations 40
________________________________________________________________________

40
Try 3 rows of luminaires with 24 luminaires per row. (--- = 1.67m.) seems O.K.
24

Transverse spacing i.e. the luminaires will be spaced 1.67m


apart (centre to centre) and
1.67
0.83
---- = 0.83 m from end walls
3.33 6.67 6.67
2
gap 1.67 The transverse spacing is now 20m
0.07 divided by 3, which is 6.67m. Since this
is less than the maximum spacing, the
effect will give a more uniform
distribution of light.
Fig. 1.28

Example 1.12

An office area measures 16m x 8m and is 2.7 metres high. It is to be illuminated


to an average value of 500 lux. 600mm x 600mm recessed luminaires, each
containing 4 lamps are used. Each lamp has an output of 1400 lumens.
Utilisation factor is 0.5 and maintenance factor is 0.75.

(i) Calculate the number of luminaires required.


(ii) Sketch a layout of the scheme indicating the spacing between luminaires.

E x A
N = --------------------
MF x UF x (n x φ)
E = 500 lux
A = 16 x 8 = 128m2
2.0m
MF = 0.75
2.7m UF = 0.5
n = 4 lamps
0.7m φ = 1400 lumens
500 x 128
N = ---------------------- = 30.5 luminaires.
Fig. 1.29 0.75 x 0.5 x (4 x 1400)

________________________________________________________________________
Interior Lighting Design - A Student's Guide KK/KO'C 97

You might also like