Voltage Drop Calculation Methods With Examples Explained in Details PDF
Voltage Drop Calculation Methods With Examples Explained in Details PDF
Home / Technical Articles / Voltage drop calculation methods with examples explained in details
<="" ins="" data-adsbygoogle-status="done" style="box-sizing: border-box;
height: 90px; width: 728px; display: block;">
The most common loads of this type are motor inrush currents during
starting. These loads cause a voltage dip on the system as a result of the
voltage drop in conductors, transformers and generators under the high
current. This voltage dip can have numerous adverse effects on equipment
in the system, and equipment and conductors must be designed and sized to
minimize these problems.
1. Approximate method
Voltage drop EVD = IR cosθ + IX sinθ where abbreviations are same as
below “Exact Method”.
2. Exact method #1
If sending end voltage and load PF are known.
where:
If the receiving end voltage, load current and power factor (PF) are known.
2. Exact Method #2
If receiving or sending mVA and its power factor are known at a known
sending or receiving voltage.
or
where:
Condition #1
Three or four single conductors in a conduit, random lay. For three-conductor
cable, actual voltage drop will be approximately the same for small conductor
sizes and high power factors. Actual voltage drop will be from 10 to 15%
lower for larger conductor sizes and lower power factors.
Condition #2
Voltage drops are phase-to-phase, for three-phase, three-wire or three-
phase, four-wire 60 Hz circuits. For other circuits, multiply voltage drop given
in the tables by the following correction factors:
Condition #3
Voltage drops are for a conductor temperature of 75 °C. They may be
used for conductor temperatures between 60 °C and 90 °C with reasonable
accuracy (within ±5%). However, correction factors in Table 1 can be applied
if desired. The values in the table are in percent of total voltage drop.
Go back to top ↑
Calculations
To calculate voltage drop:
Example #1
A 460 V, 100 hp motor, running at 80% PF, draws 124 A full-load
current. It is fed by three 2/0 copper conductors in steel conduit. The feeder
length is 150 ft (46 m).
What is the voltage drop in the feeder? What is the percentage voltage
drop?
124 A × 150ft (46m) = 18,600 A-ft
Divided by 100 = 186
Table: 2/0 copper, magnetic conduit,
80% PF = 0.0187
186 x 0.0187 = 3.48 V drop
3.48/460 x 100 = 0.76% drop
Conclusion: 0.76% voltage drop is very acceptable. (See NEC Article
215, which suggests that a voltage drop of 3% or less on a feeder is
acceptable.)
To select minimum conductor size:
Example #2
A three-phase, four-wire lighting feeder on a 208 V circuit is 250 ft (76.2 m)
long. The load is 175 A at 90% PF. It is desired to use aluminum 7
conductors in aluminum conduit.
Go back to top ↑