1474-Opt Manual Rev2
1474-Opt Manual Rev2
1474-Opt Manual Rev2
OPERATING MANUAL
75,000 TPA
HYDROGEN GENERATION UNIT
Page 1 of 413
REVISION NO. 0 1 2
PREPD. BY/DATE PPD/17.6.08 PDK/10.2.09 PDK/9.6.09
CHKD. BY/DATE MS/17.6.08 MS/10.2.09 MS/9.6.09
APPD. BY/DATE SMC/17.6.08 SMC/10.2.09 SMC/9.6.09
Page 2 of 413
DESIGN & OPERATING MANUAL
1. INTRODUCTION .................................................................................................. 18
2.8.9 Power..................................................................................................................45
3.6.4 Reforming...........................................................................................................65
3.6.8 Reformer Heat Supply & Flue Gas Heat Recovery ............................................67
4. CONTROL PERFORMANCE............................................................................... 77
4.2.12 Control of Convection Section Duties, Bypass of Hot Stage Air Preheater .......83
4.3.4 Reformer.............................................................................................................94
7.2.3 I-2, Low-Low Level Sour Naphtha Surge Drum (92-V-01) .............................197
7.2.12 I-11, Sour Naphtha Pump Change Over (92-P-01 A/B) ...................................200
7.2.24 I-29, Sweet Naphtha Surge Drum Level Low Trip 92-V-11 ............................209
7.2.25 I-30, Sweet Naphtha Surge Drum Level High Trip 92-V-11............................209
7.2.26 I-31, Cold Condensate Separator Level Low Trip 92-V-18 .............................209
7.2.28 I-33, Fuel Naphtha Storage Tank Level Low Trip (92-V-19) ..........................210
7.2.35 I-40, Process Gas Air Cooler Fan Trip 92-AC-13 ............................................212
7.2.40 I-46, Fuel Naphtha KO Pot Level High Trip (92-V-20) ...................................213
7.2.49 I-61, Flare KOD pump Start / Stop with KOD level ........................................216
7.2.50 I-62, Acid Flare KOD pump Start / Stop with KOD level................................216
Page 9 of 413
DESIGN & OPERATING MANUAL
7.2.51 I-63, CBD pump Start / Stop with CBD level ..................................................217
7.2.52 I-64, bearing Cooling Water Pump Start / Stop with level ...............................217
7.2.54 I-66, Sour Naphtha Pump trip with XV-1104 valve closure.............................217
7.7.3 Nitrogen............................................................................................................225
8.2.6 List of Equipment & Tools Needed for Catalyst Loading ................................272
8.8.2 Regeneration.....................................................................................................294
8.10.3 Prereformer.......................................................................................................306
9.5.2 Equipment.........................................................................................................350
9.6 SAMPLING........................................................................................................................355
11.1 GENERAL......................................................................................................................386
14.1.3 Drawings...........................................................................................................399
14.4.4 Fixed Water Spray System – Medium Velocity Water Spray (MVWS) ..........404
14.4.5 Auto Operated Fixed Water Curtain & Water Spray System ...........................405
1. Introduction
Page 18 of 413
DESIGN & OPERATING MANUAL
1. Introduction
The Purpose of this design and Operating Manual is to describe the General
Principles of Commissioning, Start-up Operation and Shut-down as well as safety
aspects for the 75,000 MTPA hydrogen Plant at IOCL, Haldia.
Feed Pre-desulphurization.
Final desulphurization.
Prereforming.
Reforming.
Shift Conversion.
Purification by PSA unit.
2. Design Basis
Page 20 of 413
DESIGN & OPERATING MANUAL
2. Design Basis
2.1 A Brief Description of the Plant
Naphtha Pre-desulphurization.
Naphtha Vaporization and Final desulphurization.
Prereforming.
Naphtha Steam Reforming.
Shift Conversion (HT / LT).
Process Gas Heat recovery and cooling.
Hydrogen Purification.
Steam system.
Fuel System.
The Hydrogen required for the Sulphur conversion is provided from the
Hydrogen product.
The sweet Naphtha from the PDS section is used as feed to the
Hydrogen unit and is pumped to the operating conditions before it is
vaporized and passes through a final desulphurization step, which also
removes the residual chlorides.
The feed is then mixed with steam before entering the pre-reformer
followed by Reformer where the Naphtha reforms in the presence of
steam to Hydrogen, Methane, Carbon monoxide and carbon Dioxide.
The process condensate is separated and used as feed water for steam
generation and gas is fed to Pressure Swing adsorption section.
In the PSA unit pure hydrogen gas is separated from the mixture of
incoming gases and the off gases (purge gases) from PSA are used as
fuel along with sour Naphtha in the reforming section.
The steam system is of duel deaerator kind. The steam generated within
hydrogen unit is used as process steam as well as a heating medium.
The additional generated steam is sent to B.L as superheated Medium
High Pressure steam (SSMH).
A dedicated pump is provided for exporting the BFW from the degasser
system.
Page 22 of 413
DESIGN & OPERATING MANUAL
Over Turn
Design % down %
Tray columns 15 40
Packed columns 20 50
Condensers 25 NA
Compressor (Centrifugal) 25 60
Compressor (Reciprocating) 25 50
NA = Not Applicable.
Page 24 of 413
DESIGN & OPERATING MANUAL
Superscript 4 : Two Fans for reformer with 100% capacity and both
running simultaneously.
Page 25 of 413
DESIGN & OPERATING MANUAL
PLANT SECTION
Quality
IBP ºC 43 46 36-40
LOSS Vol %
Diolefins - - 24 -
Fluorides ppm wt - - -
Nitrogen ppm wt - 12 5
IMPURITIES
Arsenic ppb wt 20
Lead ppb wt 20
Nickel ppb wt 20
Vanadium ppb wt 20
Copper ppb wt 20
Iron ppb wt 20
Note:
Sweet Naphtha from the tank OSBL to be returned at 4 Kg/cm2g and
40ºC, when required for Hydrogen Unit, in the event of interruption of
supply, supplies C5-90 sweet Naphtha from the PDS unit. The C5-90
Naphtha is only a check case.
Page 28 of 413
DESIGN & OPERATING MANUAL
TYPE
Quality
Water -
Dust distribution2
> 10 µm mg / Nm3
< 10 µm mg / Nm3
Conductivity <2500
s/cm
SiO2 <8
mg/Kg
Fe <2
mg/Kg
Cu
mg/Kg
TDS *
mg/Kg
Oil
mg/Kg
CO2
mg/Kg
NH3 *
mg/Kg
Phenols
mg/Kg
COD mg/l *
BOD5 mg/l
Flow
Kg/h
Minimum
Page 30 of 413
DESIGN & OPERATING MANUAL
Pressure1
Kg/cm2g
Minimum
Normal 7 3 5
Maximum 21
Temperature1
º
C
Minimum
Normal 40 45 50 50
Maximum
Notes:
Pre
PLANT SECTION Hydrogen Unit
Desulphurization
Flue Sour Flue Vent
Type
Gas * Gas Gas steam
Quality
Hydrogen Vol % 67.2
Nitrogen Vol % 68.4 56.3
Oxygen Vol % 1.7 1.13
Argon Vol % 0.8 0.69
Carbon Dioxide Vol % 8.9 23.59
Water / Steam Vol % 20.3 Balance 18.33
H2S Vol % 17.2
Hydrocarbons Vol %
Sulfur Dioxide mg/Nm3
NOx (dry @ 3% O2)
mg/Nm3
Chlorides mg/Nm3
Carbon Monoxide
mg/Nm3
Ammonia mg/Nm3 14.1
Solid Particles mg/Nm3
Avg Molecular Wt 27.6 17.9 30.08
Flow Kg/h
Minimum
Normal 2443 116 322099
Maximum
Pressure1 Kg/cm2g
Minimum
Normal 0 5.5 0
Maximum
Temperature1 º
C
PLANT SECTION Pre Desulphurization Hydrogen Unit
Flue Flue Vent
Type Sour Gas
Gas * Gas steam
Minimum
Normal 540 40 145
Maximum 200
Hardness as CaCO3
ppm mg/l grains/ mva/l French German
wt. U.S. degrees degrees
gal
1 ppm wt. 1.0 1.0 0.058 0.020 0.10 0.056
1 grain/U.S. gal 17.1 17.1 1.000 1.000 1.71 0.958
1 mval/l 50 50 0.342 0.342 5.0 2.8
1 French 10.0 10.0 0.583 0.583 1.00 0.560
degree
1 German 17.8 17.8 1.044 1.044 1.78 1.000
degree
Notes:
1) Operating conditions. For mechanical design pressure &
temperature see Section 2.12. Liquid pressures are at
grade.
2) Main reformer make-up fuel is vaporized sour naphtha.
However, a line will be provided for use of sweet naphtha
(ex –PDS) as makeup fuel.
3) For the reformer start up, fuel gas is used.
4) Relieving temperature of Fuel gas KOD (92-V-09) is 563ºC
in case of the external fire scenario. The vessel MOC
being CS, it may rupture due to this high relieving
temperature. Hence a water sprinkling system has been
provided on Fuel Gas KOD to ensure cooling of the vessel
wall during external fire.
Page 39 of 413
DESIGN & OPERATING MANUAL
Note:
1) Operating conditions. For mechanical design pressure &
temperature see Section 2.12. Liquid pressures are at
grade.
2) For pre-reformer start-up, maximum allowable oxygen level
is 200 ppmv (preferably < 5 ppmv).
3) In addition to the main supply header to HGU, a dedicated
nitrogen header is provided for PSA unit (92-M-12)
Page 41 of 413
DESIGN & OPERATING MANUAL
Existing H2 Existing H2
Source
plant bullets
Composition:
vol%
Hydrogen purity, minimum 99.99 99.99
Carbon monoxide ppm vol
Carbon dioxide ppm vol 15 15
Methane - -
Ethane - -
Propane - -
Isobutane - -
N-butane - -
Isopentane - -
N-Pentane - -
C6 - -
Oxygen - -
HCI ppm vol 1 1
Chloride ppm vol Traces Traces
Nitrogen ppm vol - -
Oil ppm vol - -
H2O ppm vol - -
H2S ppm vol - -
Other impurities 2) ppm.wt. - -
Supply pressure:1)
kg/cm2g
Minimum 19
Normal 20
Maximum 78
Supply temperature:1)
ºC
Minimum 40 40
Normal 45
Maximum 45
Max. quantity available 3300 2000
Nm3/h
Notes:
1) Operating conditions. For mechanical design pressure &
temperature see Section 2.12. Liquid pressures are at
grade.
2) e.g. Cl2, NH3, etc.
3) Deleted
4) Deleted
Page 43 of 413
DESIGN & OPERATING MANUAL
2.8.8 Chemicals
2.8.9 Power
2.9.1 Aromatics
N.A
Location:
Exact location site : Haldia, West Bengal
Elevation above sea level : 3.6m
Plant datum level : …….
Soil bearing capacity : ……. kPa
Earthquake:
Earthquake : Yes
Seismic Intensity (Mercalll scale) : IS-1893, Seismic zone IV
& IS-4326
Barometric pressure:
Highest absolute barometric pressure :101.59 kPa
Lowest absolute barometric pressure :101.06 kPa
Annual average barometric pressure :101.19 kPa
(Process design)
Temperature:
Average maximum temperature (hottest month) : …. ºC
Extreme highest temperature : 44 ºC
Average minimum temperature (coldest month) : …. ºC
Extreme lowest temperature :7 ºC
Average ambient temperature (process design) : …. ºC
Design air temperature for Air-coolers : 43 ºC
Design air temperature for Stacks :…. ºC
Design wet bulb temperature (cooling towers) : 29 ºC
Minimum temperature (process design) : …. ºC
Minimum temperature (metallurgical design) :7 ºC
Frost line (bellow surface) : …. m
Relative humidity:
Relative humidity in summer : ….. %
Relative humidity in water : ….. %
Design Relative humidity in summer : ….. %
Design Relative humidity in water : ….. %
Rainfall:
Maximum daily rainfall : 372.1 mm
Maximum hourly rainfall : 96 mm
Average yearly rainfall : …. mm
Monthly maximum rainfall : …. mm
Page 50 of 413
DESIGN & OPERATING MANUAL
Wind direction:
Prevailing wind direction whole year : South – East
Prevailing wind direction Summer : South – East
Prevailing wind direction Winter : South – East
Wind velocity:
Average wind velocity (process design) : 2 – 19km /h
Average maximum wind velocity : 200 km/h
(10 m above ground level)
Basic wind pressure (based on above) : …… kPa
Maximum snowfall depth : …… cm
Design snow load : …… kPa
Note:
* Details to be furnished by IOCL.
Page 51 of 413
DESIGN & OPERATING MANUAL
Process Lines
Note:
Utility Lines
Note:
Refer attached table Battery Limit Connections and Conditions- UTILITY
LINES for the detailed description. Refer section 15.7.
Page 53 of 413
DESIGN & OPERATING MANUAL
2.13 Economics
3. Theory of Process
Page 55 of 413
DESIGN & OPERATING MANUAL
3. Theory of Process
Introduction
The design feed stock is a mixture of C5-140ºC Naphtha and FCC gasoline in a
weight ratio of 80%: 20%.
Basis of Design
Process Flow Diagram
P&I Diagram
Heat & Material Balance
Operating conditions stated in the process description are related to the above
design feed stock at 100% capacity, unless other wise stated.
RSH + H2 ↔ RH + H2S
RCl + H2 ↔ RH + HCl
R=R + H2 ↔ R-R
The normal catalysts used for the above reactions are CoMOx / NiMOx,
which needs to be in their sulphided form.
For the Pre-reformer & Hydrogen generation unit catalyst, Sulphur and
chloride are catalyst poisons even at very low levels (concentrations).
The catalyst employed for the pre-reforming process is extremely
sensitive to Sulphur compounds since these will cause deactivation or
“poisoning”. Thus in the final desulphurization process, a further catalytic
hydrogenation of the residual organic Sulphur compounds takes place
followed by absorption of the hydrogen sulphide on selective adsorbents
(Aluminum Oxide, Zinc Oxide) The consumption of adsorbent is limited
by the incorporation of the upstream pre-desulphurization unit, which
removes the bulk of Sulphur compounds.
Since the HCl will react with the Zinc oxide to ‘mobile’ ZnCl, which will
not be adsorbed on the chlorine guard, the chlorine guard bed is
installed before ZnO bed.
CoMOX catalyst
RSH + H2 H2S.
Chlorine Guard
Al2O3 + 6HCl 2 AlCl + 3H2O
The other reaction is hydrogen with olefins to alkanes, both the reactions
are exothermic and will result in to adiabatic temperature rise, so regular
check on the feed stock is recommended.
Page 58 of 413
DESIGN & OPERATING MANUAL
2) CO + H2 O ↔ CO2 + H2 +Q
In order to achieve high yield of hydrogen from the feed stock, after pre-
reforming the methane is converted in the reformer, which operates at
high temperature.
The second reaction is referred as water shift reaction; the mixture at the
reformer outlet will be essentially at equilibrium for the shift reaction.
The steam quantity is controlled at fixed ratio with the feed stock at the
inlet of the pre-reforming section.
Four different steams to carbon ratios are used to define the amount of
steam that has to be added:
CH4 ↔ 2H2 +C
2CO4 ↔ CO2 +C
CO + H2 ↔ H2 O + C
A low steam to carbon ratio will result into carbon deposition on the
catalyst.
Page 60 of 413
DESIGN & OPERATING MANUAL
CO + H2 O ↔ CO2 + H2
The optimum temperature at the reactor inlet will change while the
catalyst ages and can be based on CO slip from the reactor.
The start run inlet temperature of the HT shift reactor is 327ºC, over the
life of the catalyst it increases to about 343ºC.
The start of run inlet temperature of the LT shift reactor is 193ºC, over the
life of the catalyst it increases to about 232ºC.
Page 61 of 413
DESIGN & OPERATING MANUAL
PSA technology is used to remove the impurities from the reformed gas.
This is achieved by molecular sieve, which adsorb the contaminants and
allow the hydrogen to pass. To regenerate the molecular sieves the
adsorber is depressurized. This releases the contaminants and after
pressurization the adsorber ready for reuse.
The feed stock is mixed with hydrogen under ratio control and
preheated in 92-E-11 to about 120ºC in the recovery section. This
feed is vaporized completely against a portion of HT shift effluent
Page 64 of 413
DESIGN & OPERATING MANUAL
3.6.4 Reforming
After heat recovery, the gas is fed to the LT shift reactor 92-R-15
under temperature control. This reactor is filled with 35.3 m3 of
Katalco 83-3 or equivalent. The SOR temperature is 193ºC and
EOR temperature is 232ºC. The reaction is adiabatic and the
EOR efflux temperature is about 270ºC. This effluent provides
heat for the following purposes:
In the PSA unit, the hydrogen is separated from the process gas
with a recovery of 89.5%. The hydrogen leaving the PSA has a
purity of more than 99.9 Vol% and the rest of the process gas is
purge gas and serves as primary fuel for the reformer. The PSA
purge gas leaves the PSA unit via the H2 PSA surge drums at a
normal pressure of 0.3 kg/cm2g.
Hence the plant operators can reduce the steam drum operating
pressure upto 48.5 kg/cm2g to avoid spurious opening of the
steam drum PSV- 2406 tag.
Condensate from the process is re-used within the unit B.L after
degassing in the Process Condensate Degasser (92-V-22)
operating at approximately 0.3 kg/cm2g. The following streams
are directed to the Process Condensate Degasser:
The demin water from battery limit is received under level control
in demin water storage tank 92-T-01. From here it is pumped
pumps 92-P-15 A/B to the demin water degasser 92-V-21. The
flow from these pumps is regulated by the level control of 92-V-21.
The condensate is fed directly to the demin water degasser 92-V-
21. From this degasser export of LP BFW is carried out at 29
kg/cm2g by means of dedicated pumps 92-P-16 A/B after heating
this water to 125°C against SM level steam in exchanger 92-E-28.
High pressure supply of BFW at max 54 kg/cm2g is carried out
from pumps 92-P-12 A/B/C. Both the above exports are under
flow control set at maximum 29 t/hr respectively.
Independent flare systems for acid gas and normal hydrocarbon are
developed for hydrogen unit. The PSVs or the on-off valves (for
depressurization) outlet lines which may release H2S along with process
gas are connected to acid gas flare piping. Both normal hydrocarbon flare
and acid flare systems are having dedicated flare KO drums to collect the
condensates. Dedicated pumps are provided for each flare KO drums to
pump out the collected condensates to off-site slop tanks.
PSVs and all the relief system outlets, mainly from the PDS section are
connected to the acid flare network. The B/L pressure of the acid flare is
0.3-1.5 kg/cm2g.
KOD pumps operate based on KO drum levels. When the KOD drum
levels reaches on high level interlock I-62 will act and one pump will
automatically start running. Similarly when KO drum level reaches low
level I-62 interlock will act and stop the running pump. One independent
level transmitter is also available in the acid flare KO drum for level
indication, KO drums level high-high and level low-low alarms are
available from this independent transmitter for operator to take action in
case of pump not starting or stopping with I-62 interlock. For local
indication a level gauge is also provided. H2S gas detector with DCS
alarm indication is provided near acid flare KOD to ensure safe working
environment.
The entire acid flare piping except the KOD is steam traced.
indicates choking of the strainer due to dirt in fuel gas lines (like
scale, rust, welding slag etc.).
(HAZOP recommendation)
Following table gives the list of PSVs / Depressurization valves which are
connected to the acid flare network.
Relief
Sr. Tag Load Relieving Phase Fluid Relieving Cond.
No. kg/hr Case Pressure Temp
2
kg/cm g °C
Note:
Hydrocarbon flare:
All the non sour PSV relief streams are connected to the hydrocarbon
(HC) flare header and is fed to the HC flare KOD. The B/L pressure of the
acid flare is 0.3-1.5 kg/cm2g
KOD pumps operate based on the level of the collected liquid in the drum.
Interlock I-61 starts one pump automatically when the level reaches high.
When the level reaches low, the pump automatically stops. Additional
level indicator is also provided in the system to activate low and high level
alarms indications in DCS. Such situations can arise due to pump
malfunctioning and in such case immediate manual intervention is
required. For local inspection one level gauge is also provided in the
system. A HC gas detector with DCS alarm indication is provided in the
vicinity of the HC flare KOD to ensure safe working environment.
Following table gives the list of PSVs which are connected to the
hydrocarbon flare network.
Sr. Relieving Cond.
Tag Relieving Relief
No.
Case Load
Pressure Temp
kg/hr kg/cm2g °C
7
92-PSV-2302 fire 227.3 37 691
13 92-PSV-3605 A/B 15
fire 6308 284
blocked out let 7175 220
92-PSV-7208 A/B
14 blocked out let 234.08 42 107.78
112
1295
18 92-PSV- 5507 fire 7 /40
/167/4.48
/563
3 92-P-16 BFW
A/B export
pumps
4. Control Performance
Page 77 of 413
DESIGN & OPERATING MANUAL
4. Control Performance
4.1 General
This simplified guide has been prepared to aid operating personnel in the
analysis of some operating situations, which may be encountered in the
hydrogen plant.
Page 78 of 413
DESIGN & OPERATING MANUAL
4.2.1 General
If the pressure in the front-end increases too much, PIC 2207 will
send the excess feed to the spill back air cooler. Condensed
naphtha will be returned to sweet naphtha surge drum, non-
condensable will be send to flare
The excess feed rate over the reformer requirement is then vented
out through PV-2211. When the manipulated value of the
Page 80 of 413
DESIGN & OPERATING MANUAL
To maintain the required ratio between the feed and the steam,
two controls are operating simultaneously. The overall steam to
carbon ratio, is set by HIC-2504 and the steam to feed ratio to the
pre-reformer is set by HIC-2509. Both ratios can only be adjusted
within a certain operation range. The steam rate to the pre-
reformer is controlled by FIC-2504 which acts on the steam valve
in the process as steam line to the pre-reformer. The overall
steam rate is controlled by FIC-2503, acting on the steam valve in
the steam line to the reformer.
The pressure & temperature of the feed & steam flows can vary
with the capacity and other operation set-points and the flow
signals are also corrected for pressure & temperature within a
certain range.
This plant has two steam drums, convection section steam drum &
PGB steam drum.
The boiler water level in the convection section steam drum (92-V-
14) is also controlled using a three element control. Based on the
set point received from level in the steam drum (LIC-2703) &
steam flow from steam drum (FI-2701), FIC-3402 determines the
amount of BFW required to maintain the level in the steam drum
(92-V-14). Convection section BFW pumps, continuously feed to
steam drum based on LIC-3402 (Process condensate degassfier
level control), whereas FV-3402, which is placed on PGB BFW
pumps discharge, feeds rest of BFW based on the signal received
from FIC-3402.
It is essential that these coils are operated with sufficient duty for
following reasons :
This coil provides the final preheating for the COMOX II reactor.
Inadequate temperature at this reactor can cause incomplete
conversion of organic sulphur and consequently poisoning of
prereformer catalyst. Temperature at the COMOX II reactor shall
be maintained between 380°C and 400°C for optimum
performance.
To ensure that sufficient duty can be transferred from the flue gas
to the process side of these coils, a bypass arrangement is
installed for the hot stage air preheater. By opening of the
bypass, the duties of the three downstream coils are all affected in
a similar way. Therefore the automatic control of the bypass is
linked to the steam temperature from the steam superheater 92-E-
54.
Detailed Description
Though the naphtha super heater coil is designed for a fully, open
bypass valve at full load operation, opening of the bypass should
be reduced to a minimum. It is preferred that the operator
reduces the set point of TIC-2419 when TV-2419B opens TV-
2201.
The three coils downstream the hot stage air preheaters are
protected against excessive temperature by a high temperature
switch on the flue gas side. A too large bypass on the air side of
the hot stage combustion air pre heater will result in a high
temperature of the flue gas in the intermediate flue gas cross-
over, which could result in excessive temperatures in the
downstream coils. The switch ensures that all downstream coils
are protected against overheating. Exceeding of the trip set point
will result in total reformer trip (ESD).
Page 85 of 413
DESIGN & OPERATING MANUAL
The parallel exchangers like E12 & E17, E18 & E19, E20 & E21,
E11 & E22 at the exit of shift reactors are provided for heat
recovery from the process to improve overall efficiency. It must be
noted that the gas flow splits across these exchangers vary
depending on the feedstock (straight run naphtha / FCC SRN
naphtha) and also the catalyst conditions (SOR / EOR).
Reference is made to the various heat and material balance cases
to serve as a guide line in adjustments.
Desulphurisation
Olefin Saturation
Denitrogenisation
Deoxygenation
Demetallization
The longest cycle length and greatest total catalyst life are
attained by operating at the lowest temperature commensurate
with achieving the desired product quality. The temperature
should be increased only as required due to normal catalyst
ageing and/or change in process conditions. Increasing the
hydrogen partial pressure increases the apparent catalyst activity
and reducing the hydrogen partial pressure reduces the apparent
activity.
The ZnO bed and chlor guard are split into two beds. The gas
leaving the first beds should be sampled regularly to detect
sulphur and chloride slippage from the bed as early as possible, to
provide 2-3 months time in which a plant shut-down can be
scheduled for catalyst change-out. When the sulphur or chloride
level approaches 0.2 ppm wt, the ZnO or chlor guard in the
leading bed is to be replaced as the exit specification confirms the
life limit for the adsorbent.
Page 91 of 413
DESIGN & OPERATING MANUAL
4.3.3 Pre-Reformer
Temperature
Temperature Profile
Feedstock Purity
Effect of Steam
4.3.4 Reformer
Note :
If the total steam flow is too low for the amount of feed gas
being processed, one or more of the following will occur :
Reformer Tubes
Tube Expansion
Catalyst Activity
- Catalyst breakdown
- Tube blockage
- Thermal Aging
- Carbon Deposition
Temperature
Catalyst
Temperature
As for the HT shift converter, for LT shift converter also,
the outlet composition is dependent both on the equilibrium
of the reaction and the catalyst activity. The typical inlet
temperature operation range for the LT shift is 193ºC to
232ºC. This inlet temperature is controlled by a process
gas bypass around the upstream boiler feed water
preheater. There are 4 thermocouples provided in LT shift
reactor. The exotherm/temperature profile over the bed
shows the catalyst activity.
Catalyst
Feed to pre-reformer
Where :
For the shift reaction the same principle holds. However due to
the nature of the reaction, the calculated equilibrium temperature
is normally higher than the actual temperature. Therefore, in the
design of a reformer, the approach to CO equilibrium is normally
taken as 0ºC.
CO + H2O CO2 + H2
Page 107 of 413
DESIGN & OPERATING MANUAL
And using Keqco values as per Table 4.2.2, a second check on the
reformer outlet temperature can be made.
W = WD D
DD
Meter reads in mass units, (for instance kg/h) for gases :
W = WD P TD M
P D T MD
Q = QD D
DD
N = ND P TD MD
PD T M
Where :
Note:
Refer attached document from chapter 15 section 15.18 of this
document.
Page 111 of 413
DESIGN & OPERATING MANUAL
Control of the recycle gas header pressure routed to the recycle gas
compressor
Gas phase from the naphtha separator (92-V-02) is recycled back to the
hydrogen recirculation compressor. Pressure from this line is sensed by
PIC 1601 B and is used to modulate 92-PV-1601B provided on the purge
gas stream from 92-V-02, which is a side branch of the recycle gas
header. Hence recycle gas pressure is controlled indirectly, when purge
gas pressure is modulated.
Control of the sour water level in the boot leg of the naphtha separator
(92-V-02)
LIC 1405 is provided on the boot leg of 92-V-02 which modulates 92-LV-
1405 on the outlet sour water line from the boot routed to the B/L of the
SWS unit.
Control of the flow of the naphtha from the naphtha separator (92-V-02)
Master controller LIC 1402 senses the level in the vessel and sends
controlling signal to the slave controller FIC 1402, which in turn modulates
92-FV-1402.
Master controller LIC 1504 senses the level in the sump of the stripper
92-C-01 and sends controlling signal to the slave controller FIC 1403,
which in turn modulates 92-FV-1403.
Loop1:
Loop2:
Signal from MP steam feed line (FIC 1501) and the signal from naphtha
separator 92-V-02 outlet line (FIC 1402) are fed to the naphtha /steam
ratio controller FY 1501 which modulates 92-FV-1501 in order to maintain
steam/naphtha ratio as per the set point from HIC 1502.
LIC 1502 is provided for sensing the level of the condensate in the
condensate pot and 92-LV-1502 provided on the outlet line of the
condensate pot is modulated accordingly.
FIC 1502 senses flow from the reflux line at the discharge of the reflux
pump (92-P-02 A/B). Master controller LIC 1507 senses the level of the
liquid in the stripper-overhead separator (92-V-06) and gives controlling
signal to the slave controller FIC 1502, which in turn modulates 92-FV-
1502 provided on the reflux line.
Slip stream line from reflux pump (92-P-02 A/B) is diverted to the wild
naphtha surge drum (91-B-37) from OHCU section. FIC 1505 on this line
is modulating 92-FV-1505.
Control of sour water level in the boot of the stripper O/H separator (92-V-
06)
LIC 1509 is provided to sense the level in the boot leg of the stripper O/H
separator (92-V-06) which modulates 92-LV-1509 provided on the sour
water outlet line of the boot routed to the B/L of the SWS unit.
Page 113 of 413
DESIGN & OPERATING MANUAL
PIC 1508 senses the gas pressure in the vessel 92-V-06 and modulates
92-PV-1508 on the outlet sour gas line from 92-V-06 routed to the B/L of
the Amine Treating Unit.
Control of the pressure of the sour gas stream at the B/L of the Amine
Treatment unit
PIC 1511 senses pressure in the sour gas header routed to the B/L of the
Amine Treatment unit and modulates 92-PV-1511 which in turn releases
excess pressure to the acid flare system.
Control of the inert gas blanket (and pressure) in the sweet naphtha surge
drum(92-V-11)
PIC 2102A and 2102B sense pressure from vessel and separately
modulate 92-PV-2102A and 92-PV-2102B respectively.
Control of the flow of the sweet naphtha from the sweet naphtha surge
drum 92-V-11
FIC 2102 senses flow from the discharge of the sweet naphtha feed
pump 92-P-11A/B and sends a signal to the recycle H2 / naphtha ratio
controller which controls ratio of feed and recycle gas at the
desulphuriser. The ratio controller modulates 92-FV-2102 to maintain this
ratio at the set point specified by HIC 2109.
PIC 2307 senses the pressure at the outlet of the pre reformer and then
modulates 92-PV-2307 provided on the vent line connected to the flare.
This valve is closed normally and operates only in case of overpressure.
Page 114 of 413
DESIGN & OPERATING MANUAL
There are three valves acting in combination to control the preheated air
temperature.
92-TV-2416A and 92-TV-2416B are provided on the inlet air lines to the
combustion air pre heaters 92-E-56A/B respectively. Where as 92-TV-
2416C is provided on the bypass line of these preheater to control
temperature at the outlet of the preheater where all three streams meet
together.
92-TV-2201 is located on the bypass line of the naphtha super heater 92-
E-55. TIC 2201 senses temperature at the inlet of the desulphuriser 92-R-
12A/B and signal is generated to control 92-TV- 2201 so as to control the
flow through 92-E-55.
LIC 2604 senses level in the flash drum and accordingly modulates 92-
LV-2604 provided on the condensate outlet line
Control of the temperature of the PGB process gas feed stream to the HT
converter
(92-R-14)
TIC 2815 senses the PGB process gas feed line to HT converter (92-R-
14) and modulates 92-TV-2815 to regulate flow rate of the PGB process
gas to 92-R-14.
PIC 2801 senses pressure of the steam going out from the steam super
heater 92-E-17 and modulate 92-PV-2801 accordingly to maintain
pressure in 92-E-17.
Page 115 of 413
DESIGN & OPERATING MANUAL
Another tapping is drawn from the same line (outlet of the 92-E-54) which
is venting excess steam to a safe location. PIC 2804 senses pressure of
the steam at the outlet of the desuperheater 92-E-54 and in case of
overpressure scenario modulates 92-PV-2804 to release excess steam to
92-M-14. The valve is in the closed condition normally.
TIC 2808 senses the temperature of BFW at the outlet of the convection
section BFW preheater-I (92-E-18) and modulates inlet process gas
stream flow to 92-E-19 using 92-TV-2808, which is in parallel to 92-E-18.
Hence indirectly it modulates flow of process gas to 92-E-18, thereby
maintaining temperature of BFW fed to 92-V-14.
FIC 2504 senses signal from pre reformer S/C control block and
modulates 92-FV-2504 provided on the inlet steam line to 92-M-18
thereby modulating steam generated in 92-M-18.
The differential pressure across the fan is sensed by PDIC 3201. Signal
from air fuel ratio controller block is generated depending on the
combustion air pressure sensed by PIC 3204 at burner feed header,
purge gas flow sensed by FIC 3204A and other relevant inputs so as to
maintain air fuel ratio as per the set point. These two signals activate a
relay system to modulate 92-PV-3201, there by achieving air flow control.
Signal from the burner feed air / fuel ratio control block is fed to FIC 3203.
PIC 3206A senses pressure at the naphtha feed header and the
combined out put is used to modulate 92-FV-3203A/B. 92-FV-3203B is
designed to work in sliding split range.
Control of the flow of the purge gas from the PSA unit to the burner
FIC 3204 senses flow of the purge gas to the burner and is fed to the
burner air / fuel ratio controller. The signal generated from ratio controller
modulates 92-FV-3204 provided on the purge gas supply line to the
burner.
Control of the hydrogen pressure from bullet to pre reformer through 92-
E-53 and LT converter (92-R-15) during start up operations
PIC 5005 senses pressure in the hydrogen line providing hydrogen to the
LT converter (92-R-15) and pre reformer through 92-E-53 from the bullet
and modulate 92-PV-5005 provided on the same line accordingly.
Hydrogen from bullet is fed to the injection spot (during start-up only)
under the control of the valve 92-FV-2103C. FIC 2103 senses the flow of
hydrogen in this line and modulates 92-FV-2103C accordingly.
Pressure is sensed by FIC 2103 from the line injecting hydrogen into
naphtha feed and is fed to the compressor control block, which in turn
modulates 92-FV-2103A/B. HIC 2103A/B switches are provided to select
compressor which ever is on line.
LIC 4101 senses level of the tank 92-T-01 and modulates 92-LV-4101
provided on the line supplying DM water to the tank from the B/L.
Control of the DMW flow to the injection nozzle prior to the naphtha cooler
92-AC-01
The ratio of naphtha and DM water is maintained as per the set point from
HIC 1109 by using a ratio controller. Signal from this controller is fed to
92-FV-4103 based on the calculated ratio and the valve is modulated
accordingly to maintain the ratio.
LP BFW from 92-P-16 is fed to the heater 92-E-28 under the control of
the control block HP/LP BFW export and degasifier level control. LIC
3302 senses the level of the degasifier (92-V-21) and accordingly, a
signal is fed to FIC 5805 which in turn modulates 92-FV-5805 provided on
the BFW inlet line to 92-E-28, which supplies LP BFW for export.
TIC 5804 senses the temperature of the BFW at the outlet of the heater
92-E-28 and accordingly modulates 92-TV-5804 provided on the MP
steam supply line to 92-E-28, to maintain temperature of the export BFW
stream.
Control of the level of condensate in the flash drum associated with 92-E-
28
LIC 5801 senses the level of condensate in the flash vessel and
modulates 92-LV-5801 provided on the MP condensate out let line from
flash vessel, routed to the degasifier (92-V-21).
Page 118 of 413
DESIGN & OPERATING MANUAL
5.1 General
Although the work will proceed generally in the order given, overlapping
may be permitted. During the pre-commissioning operations, any defect
should be disclosed, thus allowing timely rectifications to be effected. To
obtain complete confidence in the state of the plant and equipment, site
staff must be particularly attentive to systematic checking for possible
defects. At subsequent start-up and partial start-ups, when perhaps only
one item of the plant has been isolated for short maintenance, equal
diligence must be applied to appropriate pre-operational checks.
Page 120 of 413
DESIGN & OPERATING MANUAL
The following operations must be carried out on all sections before start-
up can take place.
Piping
Instrumentation
Fans
Pumps
Electrical motors
Furnace
After completion of the unit erection and hydrostatic tests, all lines
and equipment must be cleaned.
Cleaning Methods :
i) Water flushing
ii) Air blowing
iii) Steam blowing
iv) Mill scale removal
v) Steam spalling
Water Flushing :
Air Blowing
- Instrument lines
- Nitrogen lines
- Air lines
- Fuel gas lines
- Process gas lines
Page 130 of 413
DESIGN & OPERATING MANUAL
Steam Blowing
Steam blowing is used when the water quantity and quality are not
suitable for cleaning purposes, or when it is imperative that all rust
and mill scale be thoroughly removed. Additionally, steam blowing
is easier and faster to carry out.
- Steam lines
- Liquid hydrocarbons
- Furnace piping (as convection and radiant section)
- Decoke system
Steam Spalling
Important
Safety Precautions
General
Steam
Disconnect all steam traps, open all vents and drains to the
atmosphere and slowly let steam into the system. First flush the
main headers, disconnecting the flanges at the end of piping
systems, followed by the branch lines up to the equipment and
inlet of steam traps.
Shut off the vents when the system is considered free from air and
when it is adequately flushed, start the steam traps and check
their operation.
Service Air
Flush the system with air, execute seal tests with air and eliminate
moisture by blowing.
Page 134 of 413
DESIGN & OPERATING MANUAL
Instrument Air
Cooling Water
Disconnect the inlet flanges of water coolers and wash the lines;
when clean water is seen emerging, reconnect and continue with
the washing. When washing is completed, a tightness test should
be performed and the system commissioned. Note any abnormal
pressure losses in the system during the pre-start-up check.
Nitrogen Network
Perform tightness test of the network with air. Once the seal test
has been completed, purge the network with nitrogen, blowing
through intermittently to eliminate all the air. Commission the
nitrogen system.
Raw Water
Electrical Equipment
Fire-Fighting Equipment
Make sure that equipment is in place ready for operation and that
the fire water header has the proper pressure. Try out all water
hydrants and check jet length and cooling capacities. Refer
chapter 14 Auxiliary systems for details.
Page 136 of 413
DESIGN & OPERATING MANUAL
- Ambient temperature
- Motor current at start
- Motor current running
- Bearing temperature at drive end
- Bearing temperature at non-drive end
- Frame temperature
- Vibration levels in axial, vertical & horizontal planes
- In addition a record shall be made of the following :
- Rotation looking on drive end
- Run-up time
- Run-down time
5.3.2 Fans
Prior to starting up for the first time, clean the internal part of the
fan and clear it from any foreign matter, waste or remains that
may be left. Remove likewise foreign matters from connecting
ducts. Check whether fan rotates freely when moved by hand,
and whether impeller does not rub against static parts. If
necessary, proceed to correction forthwith.
Introduction
Start-Up
For the initial start-up of the pump, the pump check and the run
test must be completed. During normal start-up always check that
the pump has free rotation, and a proper cooling water supply. A
daily check of the oil level is required. Open the suction valve
slightly, or the warm-up line, and pressurize the pump. When the
pump is up to pressure, blow off any vapour through the pump
casing or discharge high point vent. Always make sure that any
dangerous gases or highly inflammable liquids are vented /
drained to a safe location. Check that the main breaker for the
pump in the sub-station is in the “on” position.
Page 138 of 413
DESIGN & OPERATING MANUAL
Open the suction valve to full open position and make sure that
the discharge valve is in fully closed position for centrifugal pumps
and fully open position for positive displacement pump before
starting the pump. Start the electric motor. When the motor is up
to speed and the discharge pressure is established, slowly open
the discharge block valve to fully open position in case of the
centrifugal pump and obtain the desired flow. A close watch
should be kept on the discharge pressure during this time.
TROUBLE SHOOTING
Running Case
1. Discharge pressure
2. Motor amperage
3. Suction pressure (if present)
4. Bearing oil
5. Bearing temperatures for pump and motor
6. Seal oil (if present)
7. Vibrations
Introduction
The compressor may have been idle for some time. A check
should therefore be made to see if the compressor has been run
in. The mechanical supervisor normally does this. If the machine
has been run in, the auxiliary lube oil pump should be started and
the compressor barred over once a day. If the loading valves
have been removed or pipe work disconnected, the open ends
must be covered to prevent entry of foreign material or water into
the compressor.
Initial Check
Double check the cooling water flows. Also ensure that the
compressor is free moving by rotating the shaft 360°C. Purge the
compressor with nitrogen, if there is a possibility of presence of
oxygen.
Start-up
The suction block valve can then be opened. This must be done
slowly to avoid overloading the machine by a sudden surge of
gas. Allow it to run for a minute unloaded and check the operation
of the cylinder lubricators (that is if they are driven from the main
shaft). Also, note the Amps.
Page 140 of 413
DESIGN & OPERATING MANUAL
Loading
With the motor running correctly and all suction and discharge
valves open, the compressor may then be loaded. The
compressor must always be loaded from the driver end to
outboard end (unloading is the reverse of this) and in the case of
two compressors being run off one motor, both sides should be
equally loaded to prevent imbalance in the machine. Always
check the manufacturer’s starting/operating instructions. Many
machines are fitted with make-up or variable pockets and during
normal operation these are not in use. They are only used when
the seals wear and gas passes back and the machine begins to
lose its efficiency.
The leak test is to be carried out after final installation by air, nitrogen and
the proper process.
All joints, flanges, packaging glands, etc. must be tested for leaks by
means of soap solution. Flanged connections are tested by sealing with
tape and making a pinhole (for low temperature duty only).
Insulation of flanges shall be done after the final pressure test of the
section, and warming up of the unit.
6.1 General
When all pre-operational testing has been completed satisfactorily for all
sections of the plant, and the operators are judged to be adequately
trained, the plant can be made ready for start-up. All the critical interlocks
should by now have been checked for proper response, and set at their
correct trip points, with the emergency shutdown system now fully
functional.
If troubles do not develop, or if only minor ones occur and are overcome,
the plant may be brought slowly toward design feed rates and operating
conditions. This is usually done in steps, after evaluations of operating
conditions and product quality.
The frequency will generally be much greater now than when plant
operation has become routine. After the data have been evaluated, the
log sheets should be carefully filed, so that the data will be available for
comparison with data taken later, if troubles should begin to appear.
If printer data logs are available from microprocessors, both regular and
special printouts should be accumulated, studied and filed.
Soon after the start-up, laboratory data will begin to accumulate. Analysis
of process streams, as well as of the final product, will permit further
evaluation of operations. Laboratory analysis should be reliable and
results promptly available.
The start-up procedure outlined below is written specifically for the initial
plant start-up. It assumes that all necessary preparatory work as
described under the pre-commissioning sections of this manual, has been
completed.
Page 147 of 413
DESIGN & OPERATING MANUAL
6.2.2 N2 Circulation
Remarks:
IMPORTANT:
Process
Min Nor Max
parameter
1 1.5 2.5
Flow rate (m3/h)
Pressure @
FV-1505 inlet
-- 10.92 --
(kg/cm2g)
Temperature (˚C) --
40 --
- Plant purging.
- Satisfying shutdown logic.
- Nitrogen circulation.
- Heating-up of nitrogen.
- Process steam introduction.
- Feedstock introduction and hydrogen production.
The plant (process feed, fuel and feedstock system) is purged free
of oxygen by means of nitrogen. An oxygen concentration less
than 0.5 vol% in the vented nitrogen is acceptable. Care should
be taken that no branch lines are forgotten during purging. An
extensive use of P&I diagrams is required to ensure a good
procedure.
The plant has a dual steam system i.e., Convection steam system
and the Process gas boiler (PGB) steam system.
Start one of the BFW pumps 92-P-12 A/B/C (Put other two in
stand by mode) and establish the level in the PGB steam drum
(92-V-16). For convection section steam drum (92-V-14), start
one of the BFW pumps 92-P-13 A/B, establish the level. Before
doing so, open both steam drum vent block valves towards the
silencer 92-M-13 via 3”-SMH-27-03-A3-3FH-P & 4”-SMH-26-02-
A3-3FH-P.
Page 156 of 413
DESIGN & OPERATING MANUAL
Due to high pressure difference between the boiler feed water and
steam drum pressure at this stage, fill the PGB steam drum via
the bypass of FV-2901 (SPM-17) and convection section steam
drum via bypass of LV-3402A & FV-3402 (SPM-15/18 resp.) by
seeing steam drum level.
6.3.4.1 General
6.3.5.1 General
Remarks
IMPORTANT :
42 30 74 24 73 33 43
12 45 19 46 20 47 14
75 1 65 66 67 3 76
26 54 39 7 36 53 28
82 15 55 58 59 17 81
62 83 88 34 89 84 64
9 40 5 91 6 41 10
63 86 87 35 90 85 61
79 18 56 57 60 16 80
29 51 38 8 37 52 27
78 4 70 69 68 2 77
44 32 71 25 72 31 41
- Purging of firebox
- Pressuring test
- Holding test
Purging of Firebox :
When all this conditions are met, the purge timer will start
and the “purge in progress” lamp on the local panel (XL-
3221) and on the DCS screen will light.
If all the conditions remain true and the tightness test does
not fail (see further) for the duration of the timer, then the
“purge in progress” light will go out and the “purge
completed” lamp on the local panel (XL-3219) and on the
DCS screen will light.
Pressurisation Test :
When all these conditions are true then the “ready for
tightness test naphtha” lamp on the local panel (XL-3215)
and on the DCS screen will light.
If the tightness test fails for any reason then the “naphtha
tightness test in service” lamp (XL-3216) will go out and
the “naphtha tightness test failed” lamp (XL-3218) on the
local panel and on the DCS screen will light.
Page 166 of 413
DESIGN & OPERATING MANUAL
Once the high test pressure is reached, the test gas valves
are closed and the holding test will be started.
HOLDING TEST
The objectives of this part of the test are to close the test
gas valves and hold the header under pressure for a
predetermined time. The time is calculated as the time
taken to depressurize the header from the high tightness
test pressure setting to the low tightness test pressure
setting through one burner.
The local operator may open the main fuel gas block
valves to the reformer in order to do this the following
conditions should be present.
The operator may reset the fuel gas block valves using the
push button on the local panel. This will result in the
following :
See the table below for the dew point as a function of the system
pressure. Prior to admitting steam, warm-up all steam lines and
drain dead-legs to ensure no condensed water reaches the
catalyst bed.
Page 171 of 413
DESIGN & OPERATING MANUAL
Limit for the time being, the process steam flow rate (FIC-
2503) at 30000 – 32000 kg/h with FIC-2503 on manually
open. Prior to steam introduction, verify that the steam
pressure is at least 5 kg/cm2, above the reformer inlet
pressure. During this phase, steam is being mixed with
cold nitrogen, so operations should be made slowly to
prevent thermal shocks to equipment.
Note :
With this control system, the well known swell and shrink
phenomena in the steam drum for steam production
changes is eliminated (a standard single element level
control would act in a direction opposite to the demand
situation). In the three element control, the steam
production flow rate measurement (FI-2601) biases the
level controller output (LIC-2601). The biased signal
represents the amount of BFW make-up, and is used as a
set point to the BFW flow controller (FIC-2901).
Page 175 of 413
DESIGN & OPERATING MANUAL
Increase the set point of PIC-3102 to 20.5 kg/cm2g and check that
PV-3102 fully closes. Switch the recycle hydrogen from B.L.
towards the recycle hydrogen produced from the PSA unit by
opening the block valve in the line 3”-H-31-04-A3G-3F.
Once the PSA unit is started, purge gas will become available and
will be used as primary fuel in the reformer. Before purge can be
fed to the reformer, tightness should be made on the purge gas
fuel system. The purge gas fuel tightness test will be started by
HS-3208 in the field. For purge gas test refer to section 6.3.5.4.
Once the tightness test is completed, admit purge gas fuel to the
reformer. Decrease the purge gas pressure set point (PIC-3207)
from 0.3 kg/cm2g for tightness test to 0.15 kg/cm2g. Introduce
purge gas to reformer by opening XV-3205, XV3206 and FV-3204
to purge gas burners. The purge gas has to be introduced slowly
to avoid reformer firing disturbances.
Page 182 of 413
DESIGN & OPERATING MANUAL
6.4.1 General
Drain out liquid naphtha from all the vessels. Also all low
points to be drained of possible liquid naphtha.
DETAILED DESCRIPTION
- Stop PSA unit. Process gas will then automatically vent via
PV-3002.
Page 185 of 413
DESIGN & OPERATING MANUAL
- Recycle hydrogen will still be fed into the unit via the
recycle hydrogen compressor 92-K-11 A/B, which is taking
at this stage backup hydrogen from B.L. Close off PSA
inlet block valve downstream of 92-V-18. If the PSA
system is to be shutdown for a long time, purge, the PSA
system with nitrogen, following procedure is given by “PSA
Vendor”.
The PSA unit can go into a partial failure, this being a 12 beds
mode, or into full failure, where the whole system is stopped. Full
operating instructions for this section are given in the design and
operation manual by “UOP”. In the case of a total PSA unit
shutdown, the plant capacity has to be brought to approx. 40%
using only vaporized naphtha as fuel. On loss of the PSA section
all purge gas production is lost, so the purge gas pressure to the
burners will fall to zero in a matter of seconds. Take more
naphtha burners in line so as to maintain more than 780ºC
reformer effluent temperature and put the reformer on turndown
capacity. Nevertheless it is advisable that the operator has
knowledge on the expected set points for operation at 40%
capacity without PSA unit, so that in case manual adjustment is
still needed in order to cope with the drastically changed plant
load.
7.1 General
Hand switch HS-1107 A at main panel in the central control room is for
shutdown of the PDS (I-1).
The plant’s automatic shutdown system has been divided into the
following :
I-62 Acid Flare pump Start / Stop with Acid Flare KOD level
I-64 Bearing Cooling Water Sump Pump Start / Stop with Sump
level
Page 196 of 413
DESIGN & OPERATING MANUAL
r. Opening of PV-1301.
Once the trip signals are healthy, the operator may reset by the
‘Reset ESD’ push button HS-1107B.
a. Shutdown of FV-1103.
b. Shutdown of FV-1103.
It will trip.
Only one sour naphtha pump should be running at any time. The
pump duty selector switch (HS-1102) is on position ‘B duty, A
Standby’. When the pump B discharge pressure goes low low
(PALL-1108B) then pump A will automatically started. Then the
operator should rush to the field to stop the pump B and
investigate the cause. If any of the conditions ‘a’ to ‘d’ are not
present or the pump STOP push button (HS-1102B) has been
activated, then the pump will trip. The same logic is implemented
for auto-starting pump B.
High vibration in Naphtha air cooler (92-AC-01) motor will trip the
fan.
Only one pump should be running at any time. When the pump B
discharge pressure goes low low (PALL-1504B) then pump A will
be automatically started. Then the operator should rush to the
field to stop the pump B and investigate the cause. If any of the
conditions ‘a’ to ‘d’ are not present or the pump STOP push button
(HS-1501B) has been activated, then the pump will trip. The
same logic is implemented for auto-starting pump B.
Once the trip signals are healthy, the operator may reset the total
plant trip, using HS-2113 on the DCS.
In addition to the total plant trip, the following will cause a total
reformer trip.
a. Manual trip using the push button in the control room HS-
3217, HS-3214 in the reformer panel & three push buttons
HS-3216 A/B/C at three different locations in the field.
Any of the above will cause a total reformer trip. This will cause
following actions :
Once the trip signals return to the healthy state, the operator may
then reset the reformer trips.
Any one of the above will cause a partial reformer trip. This will
cause the following actions
Once the trip signals return to the healthy state, the operator may
then reset the PSA unit shutdown logic
As the level goes high the valve XV-3302 will open. As the level
comes to normal in the deaerator valve XV-3302 will reset
automatically.
As the level goes low the pumps 92-P-12 A/B/C & 92-P-16 A/B will
trip.
Page 209 of 413
DESIGN & OPERATING MANUAL
7.2.24 I-29, Sweet Naphtha Surge Drum Level Low Trip 92-V-11
7.2.25 I-30, Sweet Naphtha Surge Drum Level High Trip 92-V-11
Only one pump will be running at any time. When the naphtha
feed pump discharge pressure should go low-low (PALL-2107A),
then pump B will be automatically started.
If any of the conditions ‘a’ or ‘c’ are not present or the pump STOP
push button (HS-2105A) has been activated, then the pump will
trip. Then the operator should rush to the field to stop the pump B
and investigate the cause.
7.2.28 I-33, Fuel Naphtha Storage Tank Level Low Trip (92-V-19)
Only one fuel naphtha pump will be running at any one time.
Should the discharge pressure of the running pump go low and
the pump duty selector switch is in the correct position, then the
standby pump will be automatically started. The operator may
then manually shutdown the critical pump if required.
a. The total plant trip logic and reformer trip logic is healthy.
b. The fuel naphtha surge drum level is not low low. This is a
2 out of 3 voting system monitored by LT-3501 A/B/C.
Only one pump should be running at any time the pump duty
selector switch (H-3402) is on position ‘B duty, A standby’.
Only one pump will be running at any time. When the DM water
pump discharge pressure should go low (PALL-4103A), then
pump B will be automatically started.
If any of the conditions ‘a’ or ‘c’ are not present or the pump STOP
push button (HS-4106A) has been activated, then the pump will
trip. Then the operator should rush to the field to stop the pump B
and investigate the cause.
Only one pump will be running at any time. When the BFW pump
B discharge pressure should go low PALL-3315 B) then pump A
will be automatically started. Then the operator should rush to the
field to stop the pump B and investigate the cause. If any of the
conditions ‘a’ to ‘c’ are not present or the pump STOP push button
(HS-3403 B) has been activated, then the pump will trip. The
same logic is implemented for auto-starting pump B.
7.2.49 I-61, Flare KOD pump Start / Stop with KOD level
In case of high / low level of HC liquid in Flare KOD 92-B-25
(LAH/LAL-5403) the Flare KOD pumps 92-P-21 A/B will start/stop
respectively. Pumps can also be started or stopped using
respective start/stop pushbuttons (HS-5402 A/B & HS-5401 A/B).
7.2.50 I-62, Acid Flare KOD pump Start / Stop with KOD level
In case of high / low level of HC liquid in Acid Flare KOD 92-B-27
(LAH/LAL-5203) the Acid Flare KOD pumps 92-P-22 A/B will
start/stop respectively. Pumps can also be started or stopped
using respective start/stop pushbuttons (HS-5202 A/B & HS-5201
A/B).
7.2.52 I-64, bearing Cooling Water Pump Start / Stop with level
In case of high / low level of HC liquid in BCW Pit 92-M-25
(LAH/LAL-5301) the CBD pump 92-P-25 A/B will start / stop
respectively.
Only one pump should be running at any time. The pump duty
selector switch (HS-5201 central panel mounted) is on position ‘B
duty, A standby’. When the pump B discharge pressure goes low
low, than pump A will automatically started.
7.2.54 I-66, Sour Naphtha Pump trip with XV-1104 valve closure
The pump 92-P-01 A/B should trip as soon as the valve XV-1104
leaves the open position as indicated by its open limit switch.
Page 218 of 413
DESIGN & OPERATING MANUAL
In case of fire in the PDS section, especially when the reactor or fired
heaters are exposed to fire, the chances of metal temperature exceeding
the allowable limits is prevalent. Hence to avoid such material failure, a
depressurisation valve XV-1402 is provided over the naphtha separator.
In case of fire emergency the operator should cautious open the
depressurisation valve is arranged such that the valve will depressurise
the system to 50% of the initial pressure in 15 minutes. Once the
pressure has reached less than 50% of the normal operating value, the
operator can close the depressurisation valve. The vent valve PV-1601B
to be provided in auto to control the pressure in the naphtha separator, till
the emergency condition is reverted back.
Page 220 of 413
DESIGN & OPERATING MANUAL
When a furnace total shutdown has been initiated, the following action
needs to be taken :
1. Check and ensure that all the trip actions were taken place as per
the cause and effect diagram. In particular check that feed & fuel
to the reformer is located & associated pumps are stopped.
3. Isolate all the burners in the reformer top (close individual burner
valves on make-up fuel & purge gas fuel line). Depressurise the
fuel naphtha header and purge with nitrogen.
7. As the nitrogen across the prereformer will also pass through the
reformer, the steam temperature will get reduced. Operator
should ensure that the steam inlet to reformer is atleast 50ºC more
than the steam dew point.
8. If the trip also resulted in trip of ID / FD fans, start the one last of
FD Fan & ID Fan to ensure a reformer box purge & to ensure a
small negative pressure in the radiant box. The air flow also cools
the radiant box & convection section.
9. Once the flue gas cross over temperature reduces to 600ºC &
below, cut of steam to reformer. Reduce the pressure of the
reformer to near atmospheric. Purge entire loop from Naphtha
feed shut off valve till cold condensate separator with once
through nitrogen. Once the impurities in the nitrogen are reduced
to less than 500 ppmv (CO, CO2, CH4, H2) then start pressurising
the loop & start nitrogen circulation via the short loop.
10. The section between the naphtha feed control valve and the
naphtha shutoff valve is locked and not purged. The Operator
should strictly ensure that the loop is depressurised through RO-
2501 and any liquid naphtha collection is drained, even before
stopping the steam admission to reformer.
Page 222 of 413
DESIGN & OPERATING MANUAL
11. Start to depressurise the front end after the trip and ensure that
pressure reduction does not exceed 2 kg/cm2 per minute.
Depressurising of the system is essential to :
13. Once the hydrocarbon content is less than 100 ppm wt, in the
nitrogen circulation, long loop circulation could be started, keeping
the low point drains at pre reformer inlet, reformer inlet and other
catalyst inlets open. This is to ensure no liquid is locked up in the
nitrogen loop.
- Reformer tubes and exit headers are made from special alloy,
which is reasonably ductile at normal operating temperatures but
relatively brittle in the region of 600ºC and below. Therefore these
furnace parts are liable to fracture if subjected to thermal shock.
Header failure is a potentially serious hazard as it may result in a
fire. For this reason, care should be taken when increasing or
decreasing temperatures to do so as smoothly as possible. Any
condition which could lead to rapid cooling of tubes and exit
headers must be guarded against most rigorously.
As instrument air pressure fails, all air operated valves will move
towards the safe condition. It will be noted that certain valves in
these circumstances go to fully closed, others go to fully open and
the remainder become locked in the last controlled position. The
controllers actuating the first two groups of valves should be put to
manual and adjusted to fully closed and fully open to maintain the
valves in the safe position when air pressure is eventually
restored. Control valves, which lock on air failure, need not to be
reset.
The actions of all control valves (FC or FO) are shown on the
P&IDs.
7.7.3 Nitrogen
If the nitrogen supply fails for a short period on the flare header
and/or within the compressor itself, shutdown of the hydrogen
generation plant will not normally be necessary.
Apart from loosing the raw supply towards sample coolers and
utility stations, the hydrogen generation plant is entirely unaffected
by a lack of raw water supply.
7.7.9 Electricity
In the event of an electrical failure all electrical units will stop and
the plant will trip.
Page 227 of 413
DESIGN & OPERATING MANUAL
2. XV-2101
closes
3. Initiation of I-30
3. Initiation of I-29
2. Closure of XV-
2201
3. Initiation of I-41
2. Initiation of I-21
after time delay
Check reformer
firing system.
VAHH-2301 high Tripping of air Mechanical failure Stop & repair fan
vibration of air cooler fan through
cooler fan initiation of I-38
If ruptured, shut
down and repair.
2. Reformer trip
(During start-
up only)
3. Restart BFW
pump.
3. Failure of BFW
supply
2. Repair
3. Failure of BFW
supply
2. Shut-off XV-
2901
2. Shut-off XV-
3002
Initiation of I-22
(During Start-up)
Initiation of I-45
Initiation of I-44
2. Possible feed
pump
cavitation
2. XV-1101
closes
3. Superheater
trip
2. Off spec
product due to
lower reflux
3. Possible reflux
pump trip
Note:
* Refer compressor vendor Dresser Rand PID (chapter 15, section 15.4)
for these tags.
Page 251 of 413
DESIGN & OPERATING MANUAL
For tabulated information on alarm & trip list refer following document
from chapter 15 (of the same manual) DRAWINGS / DOCUMENTS
PSVs are provided for protecting equipments and piping from over
pressurising. Depending on the relief properties and type of PSV, the relief
locations are different. The table provided here lists all PSVs in the plant
List of PSV
Set
Sr. Relief
No.
Tag Nos. Pressure Service
2
Kg /Cm g destination
92-PSV-1403
2 2.3 Naphtha Separator Acid flare
A/B
6"-CWR-92-14-01-A3-
3 92-TSV-1410 4.5 Atmospheric
1F
6"-CWR-92-14-02-A3-
4 92-TSV-1411 4.5 Atmospheric
1F
92-PSV-1505
5 7.2 Naphtha Stripper Acid flare
A/B
6"-CWR-92-15-01-A3-
6 92-TSV-1506 4.5 Atmospheric
1F
92-PSV-1512
8 11 Sourgas Header Acid flare
A/B
Hydrogen Circulation
9 92-PSV-1608 2.3 Acid flare
KO Pot
Set
Sr. Relief
No.
Tag Nos. Pressure Service
2
Kg /Cm g destination
92-PSV-2205 /
11 42 Desulphuriser HC flare
PSV-2206
6"-CWR-92-22-01-A3-
12 92-TSV-2209 7 Atmospheric
1F
92-PSV-2212
13 7 Spill Back Accumulator HC flare
A/B
92-PSV-2301/
14 37 Prereformer HC flare
2302
92-PSV-2405
15 40.7 H2 + Feed Header HC flare
A/B
Convection Section
21 92-PSV-2702 50 Atmospheric
Steam Drum
Convection Section
22 92-PSV-2703 51.5 Atmospheric
Steam Drum
12"-CWR-92-30-01-
23 92-TSV-3001 7 Atmospheric
A3-1F
92-PSV-3303
25 3.5 Demin Water Degasser Atmospheric
A/B
92-PSV-3502
27 4.5 Fuel Naphtha Drum HC flare
A/B
Set
Sr. Relief
No.
Tag Nos. Pressure Service
2
Kg /Cm g destination
A/B Vaporiser
2"-CWR-92-37-02-A3-
31 92-TSV-3712 18 Atmospheric
1F
Nitrogen Compressor
32 92-PSV-3807 11.5 HC flare
KOD
92-PSV-4308
33 20 Export Mp Steam Atmospheric
A/B
92-PSV-2824
36 28 LT Shift Reactor HC flare
A/B/C
Hydrogen Circulation
37 PSV 7108A/B 38 Acid flare
Compressor
Hydrogen Circulation
38 PSV 7109A/B 14 Atmospheric
Compressor
92-P-04A/B
40 PSV 1703 A/B 41.5 DMDS Dosing Pump
Suction
PSV 3106
41 5 PSA Purge Stream HC flare
A/B/C
Recycle Hydrogen
42 PSV 7208 A/B 42 HC flare
Compressor
Recycle Hydrogen
43 PSV 7209 A/B 14 Atmospheric
Compressor
Set
Sr. Relief
No.
Tag Nos. Pressure Service
2
Kg /Cm g destination
Top Up Hydrogen
53 PSV 7408 6.3 HC flare
Compressor
Top Up Hydrogen
54 PSV 7409 6.5 Atmospheric
Compressor
Top Up Hydrogen
55 PSV 7413 2.5 HC flare
Compressor
Top Up Hydrogen
56 PSV 7414 13.9 Atmospheric
Compressor
Notes:
1) All the PSVs venting to the flare have been provided with an upstream
rupture disc.
2) The rupture discs are provided with tell-tale pressure gauge assembly.
3) In case of PSV provided with spare, the isolation valves shall be
mechanically interlocked to ensure the availability of one PSV all the time.
4) To restrict the noise level generated by any equipment to less than 85
dB(A) (as in section 2.9.7) at a distance of 1 m from the source the
following PSVs are provided with silencer assembly
8. Special Operations
Page 256 of 413
DESIGN & OPERATING MANUAL
8. Special Operations
8.1 General
8.2.1 General
If the drum lid cannot be replaced, then the catalyst should be re-
drummed without delay.
DRUM HANDLING
SIEVING OF CATALYST
GENERAL
All that is required is to load the reformer tubes with catalyst such
that the instrument measures the same value across each tube.
As well as establishing that packing in uniform, the inlet and exit
branches of the reformer tube can also be checked to ensure that
they are free from debris. The actual pressure across the catalyst
depends on the tube diameter and the length packed with catalyst,
as well as the size and shape of the catalyst used.
CATALYST LOADING
After the pressure drop survey of the empty tubes (check for
blockage in exit branch), has been completed, and, all tubes
appear to be free of foreign matter, catalyst loading can be
started. The normal method of charging reformer tubes is with
pre-filled polythene socks or canvas socks still to be filled at site.
Loading of pre-socked bags is done in a similar way as described
under “charging”. The catalyst to be loaded, should be inspected
prior to charging and any fines which could cause an excessive
pressure drop when charged, should be screened out. The
reforming catalyst should be weighed before charging to provide a
check on the quantity of the catalyst loaded to each tube.
CHARGING
Using the sock method for loading catalyst in the former tubes, it
is important to ensure that the socks are of the correct size so that
they will slide easily up and down the tube when they contain
catalyst. The sock should be about 1500 mm long. The outside
diameter of the charged sock should be about 15 mm less than
the internal diameter of the tube. If it is larger than this, the sock
will not slide easily, and if it is smaller the lower end of the sock
may not unfold correctly as the sock is raised.
As reformer tubes are not exactly the same size and the catalyst
is not always exactly the same density, the charged weight will
only show major discrepancies in the tube charging, so it is more
important to charge to the correct level and pressure drop. As the
catalyst is locked, it is necessary to vibrate the tube to give
uniform packing and ensure even gas distribution. A few blows on
the top flange with a wooded, rubber or leather-faced hammer
after each sock is loaded, is an effective way ensuring even
setting. Electric vibrators may also be used at the top of the tubes
or in the furnace itself. It is important to use the same method to
vibrate all the tubes, so that the degree of catalyst setting is
similar throughout (top level of filled catalyst is in the same range
for all tubes and pressure drop across the catalyst bed also).
This test is necessary to make sure that all tubes are evenly
loaded, i.e., that no voids have been formed as a result of bridging
of particles and that the catalyst has not been disintegrated too
much as a result of careless loading or excessive tube vibration.
Pressure drop measurements across each loaded tube carried out
in the same way as described under pressure drop measurements
on empty tubes.
It is extremely important that the tubes are free from voids and not
overfilled i.e. that the catalyst is properly packed. An error in
charging will result in a tube having a low or high dP, with the
following consequences:
Low DP : This is the result of void age and will allow an excessive
flow of lead gas and process steam through the tube when “on
line”, resulting in cools tube conditions, and a breakthrough of
higher hydrocarbons.
After the entire catalyst is loaded and the manhole closed on the
process gas boiler, the inlet pigtails can be checked for
obstructions. The same device for pressure drop measurements is
used, this time the plug used before for the measurements of
empty and charged tub is omitted. All pressure drops must be
recorded and should be equal within the accuracy of the
measuring device. An inlet pigtail without obstructions shows a
negligible pressure drop. Any inlet pigtail that shows a higher
pressure drop must be investigated for restrictions. After all above
operations are completed satisfactory, reformer tubes flanges can
be re-installed using new gaskets.
PRE-CHARGING CHECKS
Inspect the catalyst grid supports and screens to ensure that the
screens are properly overlapped and that the edges of the screen
are properly sealed and firmly held down (no gaps, no holes).
Faults at this point are difficult, if not impossible; to rectify once the
catalyst is in place. Particular attention should be given to the
insertion of thermocouples that they are in the correct position
relative to the bed.
The catalyst should be loaded to the specified bed height and the
depth and weight of catalyst loaded must be recorded. The
weight of catalyst material rejected during screening must be
recorded and allowed for.
The weight of the fines should be recorded and deducted from the
weight of catalyst discharged from the drums onto the screen.
Care must be taken not to overload the screen or inefficient
screening will result.
When the drums have been opened the catalyst should be visually
inspected. For what concerns the prereformer and high
temperature shift catalyst, the pellets should be well-formed and
uniform in length. There should be little signs of capping (a clear
shear fracture of one end of the pellet) or other irregularities and
there should be no clearly visible amount of fines. Any doubtful
material should be rejected until further inspection is possible.
Five samples should be taken at each level, one from the centre
and 90º apart. These individual samples should subsequently be
combined by coning and quartering to give a 1 kg representative
sample of the catalyst at that level. All samples should be labelled
in such a way that the label cannot become detached nor the
information erased.
Date of sampling
Numbers of drums represented by the sample
Position of the contents of the drums in the catalyst bed-
upper and lower limits
Since entry into the vessel is required to properly load and
level catalyst, the vessel must be prepared for safe entry.
The catalyst should not fall freely for more than 500 mm.
The reasons for the first and third are self-evident. The reason for
distributing the catalyst evenly over the surface of the bed is to
avoid concentrating fines in one area, with subsequent mal-
distribution of reactants and products. Catalyst must not be
poured into the vessel at one spot. This would result in
classification of the particles. Smaller particles and dust will stay
under the discharge point and restrict the gas flow in this portion
of the vessel, while the larger particles roll towards the edge of the
heap creating a preferential gas flow in this place. The loading
sock should be kept moving in a figure eight pattern. Plus, it is
important to keep the catalyst bed as level as possible during
loading so that the loaded catalyst density is uniform throughout
the bed.
After catalyst loading is complete and the reactors are headed up,
the rector systems should be placed under a slight positive
nitrogen pressure (1 till 2 kg/cm2g), to await unit start-up.
Page 271 of 413
DESIGN & OPERATING MANUAL
Remarks
When molecular sieves are exposed to water they can give off
sufficient heat to approach the temperature of boiling water. For
this reason, molecular sieves should not be put in the mouth or
come in contact with the eyes. Also, while molecular sieves will
adsorb water out of the air, experience has shown that water
vapour does not readily penetrate into a packed bed from
atmospheric air. Several minutes of exposure during loading does
not cause significant water pick-up. If the unit is loaded and not
placed into service for several weeks, it is recommended that the
vessels be “blinded” off from the rest of the process until placed in
service. This will prevent trace contaminants and moisture from
being introduced into the system and causing difficulty in the initial
start-up.
Reformer
Vessels
INTRODUCTION
Note:
1. Drain the water from Steam Drum (92-V-14) until the level
is below the manhole as seen by the level gauge. Open
the manway ready for introduction of the chemicals.
10. During the boil-out operation, ensure that the boiler water
level is kept visible in the sight glass. Introduce boiler feed
water make-up as required. Initially, the boiler water will
be at boiler feed water temperature but will heat up as the
dry-out progresses.
11. The blow-off valve to vent should be operated at least
once per hour to blow out as much as possible, this will
ensure a good circulation within the system.
12. As more burners are lit in the furnace, the blow-off valve on
the steam drum should be opened slightly to maintain a
constant steam drum pressure.
Notes:
Note:
The refractory of new furnace, or furnace which has been idle for
a long period, should be dried out slowly to permit accumulated
water vapour to escape. In this way, entrained water will vaporize
slowly rather than boil violently, causing damage to refractory
lining.
92-R-15 → 92-E-20 →
92-E-21
Page 282 of 413
DESIGN & OPERATING MANUAL
92-E-11
Note:
Before putting the burners into service check should be made for
the burner system.
Also during this holding period, the outer wall surface of the
radiant and convection sections outlet header and process gas
boiler (92-E-16) must be checked for hot spots and the holding
period extended if necessary.
During the second step of the dry-out, the flue gas temperature
(TIC-2402) of the radiant section can be raised at 15ºC/H to 270ºC
and then held for 24 hours. If all is satisfactory, the flue gas
temperature (TIC-2402) at radiant cross-over can again be raised
at 15ºC/H to 540ºC. The holding period is 24 hours.
Note :
Continuously change over and check the burners during the dry-
out cycle, so that any of the common burner problems such as dirt
or coke in the lines are noticed and rectified during the dry-out
cycle. This avoids problems later. A dry-out curve is given in
enclosed figure.
Subsequent Start-up
8.5.1 General
Detailed Description
General
The H2S content (equivalent to the complete reaction of DMDS) in the gas
at the inlet of reactor should be 1 vol%. The hydro-desulphurisation
catalyst theoretically can fix around 8.7 wt% sulphur, which corresponds
to 12.5 wt% of DMDS.
Pre-Sulphidation Procedure
Start injecting DMDS at reactor inlet slowly. Inject the liquid into
the hydrogen gas as to maintain upto 5 mole % sulphur in the
stream.
If the catalyst bed is cool and has to be regenerated, then the Hydrogen
circulation compressor (92-K-01 A/B) is to be utilised to heat up the bed.
Circulation loop discussed in Chapter 6, Section 6.2.2 for initial start up
shall be used for he same. The catalyst bed is preheated with nitrogen.
After checking that the reactor temperatures are high enough (>50ºC
above steam dew point) to avoid steam condensation on the catalyst,
stop the heater and cut off nitrogen circulation immediately without
allowing the bed to cool down.
At earliest possible time, the sour naphtha super heater (92-F-01) &
CoMOx reactor – I (92-R-01) to be lined up in the regeneration circuit.
Maintain a slight positive pressure of nitrogen in the heater and reactor by
admitting nitrogen through 3”-N-92-45-04-A3-1F. In regeneration circuit,
CoMoX reactor I (92-R-01) effluent should be lined up to sour naphtha
superheater (92-F-01) stack. As soon as the loop is ready, ensuring the
bed temperatures are still above dew point and introduce steam at rate of
0.5 – 1.0 kg steam per kg of catalyst and furnace is immediately fired.
Start admitting steam through the fired heater at flow of 0.5 – 1.0
kg of steam / kg of catalyst. The fired heater should be lighted up.
Raise the bed temperature gradually at a rate of 50ºC until the bed
inlet temperature has been raised up to 370ºC. The back
pressure of the MP steam should be continuously monitored
which indicates the coke potential.
After steam stripping, air is slowly and carefully injected into the flow of
steam. The combustion develops from the top to the bottom of the
reactor. As long as combustion takes place, the air flow must be adjusted
to limit the temperature raise through the catalyst bed at 80ºC and also
maintain the maximum temperature of the catalyst bed below 455ºC.
when the wave of combustion is completed, the air flow is increased by
steps to each 3.0 vol% oxygen within the flow of steam. Air should not be
raised more than 5 vol% O2 level, observing carefully any restart of the
combustion. If necessary reduce or stop the air injection to maintain the
maximum temperature below 455ºC.
Analyse the non-combustible gases exit reactor for CO2 and O2. When
O2 content increases, then increase catalyst bed temperature until O2
disappears. When the O2 remain at the same level on raising the bed
temperature, then regeneration can be considered almost near
completion.
When the oxygen content in the flow reaches 3 vol % and there is no
increase in temperature across the reactor, the inlet temperature is
increased up to 450ºC. Then the air injection is carefully increased to
reach 5.0 vol % of oxygen in the flow. Never exceed 450ºC over the
Comox Reactor-I (92-R-01) catalyst bed.
At the end of the step-3, air injection is stopped and the reactor is cooled
down to 200ºC, steam is stopped to avoid any condensation over the
catalyst bed.
Regeneration will be definitely completed when the exit gas from reactor
shows over O2 15 vol% and less then 2.0 vol % CO2. Regeneration of
catalyst will completed almost in 16 hours.
WARNING
During coke burning operation, the air flow rate must be adjusted
so that the temperature rise over the Comox Reactor-I (92-R-01)
catalyst bed should not be more than 80ºC per hour.
Temperature over the catalyst bed should not exceed 450ºC, for
NiMoX catalyst protection.
Page 294 of 413
DESIGN & OPERATING MANUAL
8.8.2 Regeneration
Note:
The plant being designed with two beds of ZnO & Chlor guard in
series, enables the lead bed to be rum to saturation before
changing. This approach is particularly attractive to units operating
with high levels of sulphur in the feed, because by using a bypass
each bed of absorber can be changed without having to take the
plant off-line.
a. Open the 8” block valve in the top inlet line towards 92-R-
12B. Now 92-R-12B & 92-R-12A are in parallel operation.
Once the on stream reactor has reached the end of its life, it will
be necessary to execute the following activities:
NOTE:
During the initial phase of heating up the nitrogen flow through the
electric heater can be increased more than the heater design of
4500 nm3/hr, as the electric heater duty is not limiting. Once the
temperature exit the electric heater is high at around 500ºC, the
circulation will get restricted to design flow through the electric
heater by the heater duty.
Open the reactor R-13B outlet isolations gradually and then the
inlet isolation valve 1” bypasses slowly & then closes the isolation
valves on the 2” line from the R-13A to R-13B. Establish the flow
of process gas across the bed and ensure the temperature profile
of the reactor. Then slowly line up the inlet main isolation valves.
Now both R-13A & B are in parallel operation. Isolate the reactor
R-13A both at its inlet and outlet and ensure positive isolation.
Page 301 of 413
DESIGN & OPERATING MANUAL
The reactor at end of run will have the operating conditions with
S/C ratio at 2.4 and 500ºC while the reactor at start of run should
be operated with S/C ratio at 3.0 and inlet temperature of 460ºC.
Once the reactor R-13B is taken in line completely, revise the
operating conditions to start of run condition of the catalyst.
8.10.1 General
If, however the inert gas supply does not match the rate of
extraction, some air will be drawn down into the vessel and into he
top of the catalyst. This will cause local heating, which may affect
the discharge apparatus.
Cold ZnO and Chlor guard catalyst are not pyrophoric after use
whether or not they contain sulphur. After conventional
desulphurisation duties it is possible that finely divided carbon,
from the pre-heater, may be deposited on the catalyst which could
ignite during the discharge.
8.10.3 Prereformer
GENERAL
CATALYST DISCHARGE
Nitrogen may be used for this purpose. The catalyst bed must first
be cooled to near ambient temperature by feeding nitrogen
through the 3”-N-92-4516-A3-IF connection at the inlet line to
nitrogen circulation K.O.POT (92-V-13). The nitrogen circulation
can be established through the nitrogen circulation compressor
(92-K-12), keeping nitrogen Electric Heater (92-E-15) off to pre-
reformer (92-R-13 A/B) and venting to flare via the PV-2307 line at
outlet of 92-R-13 A/B until the nitrogen is hydrocarbon free,). The
reactor pressure should then be reduced to near atmospheric.
In order to avoid the chimney effect the top man way of the reactor
should be closed off before the catalyst discharge hand hole at the
bottom of the reactor is removed.
Prior to this step, all necessary drums, chutes, staging, etc.,
should have been assembled ready for the catalyst to be
discharged without delay.
Catalyst discharge
When the hand hole cover is removed there will be a tendency for
inert gas to flow out of the reactor and be replaced by air. To
counter this, nitrogen should be continuously supplied to the
reactor while this cover is off.
In any event once the hand hole cover is removed, the objective
should be to complete the discharging operation as quickly as
possible with the minimum of interruptions. If it proves necessary
to endure a lengthy interruption, overnight for example the cover
must be replaced and a supply of blanketing nitrogen gas
restored.
Page 308 of 413
DESIGN & OPERATING MANUAL
The catalyst should be run off or raked out of the bottom hand
hole directly into catalyst drums, which should be filled to the top
as quickly as possible. Drums with well fitting lids should be
selected and, before filling, a lump of solid CO2 (about 500 g)
should be placed in each.
The lid should then be placed loosely in position until all the
carbon dioxide has sublimed. It should then be clamped and
sealed with tape (“Denso” tape is satisfactory).
The catalyst can then be stored indefinitely, but the drum content
must always be regarded as potentially pyrophoric and suitable
precautions taken.
Due regard should be paid to local fire hazards since wind borne
particles may become incandescent as the nitrogen or carbon
layer disperses.
After a day or so the front should reach the bottom of the rum.
Confirmation of oxidation can be obtained by transferring the
catalyst in an oxidized drum to an empty drum when no
temperature rise should occur. Again this should be done in a safe
area and care taken to avoid wind born dust.
To vacuum the catalyst out of the tube the vacuum cleaner should
generate 25 m/sec velocity at the nozzle of the suction hose. To
prevent pulverization of the catalyst the velocity at the nozzle
should be below 40 m/sec. The inside of the hose should be
smooth and there should be no sharp bends in the hose. A rubber
or canvas baffle should be installed in the collector drum to
minimize damage to the catalyst by cushioning impact.
The gulper nozzle should be heavy duty with the same inside
diameter as the hose. If it is not heavy duty, then a 500 till 750 mm
length of pipe of the same size can be used on the end of the
suction hose to break-up fused catalyst.
The piping in the collector drum should come directly into the
drum and should not have bends. The cover should be air-tight to
prevent loss of vacuum.
Page 311 of 413
DESIGN & OPERATING MANUAL
If the catalyst has been operated in the fully sulphided state care
will be needed during discharge because iron sulphide (FeS), is
pyrophoric. The sulphur can be removed by steaming, until the
concentration of H2S in the steam has been reduced to less than
80 – 100 ppm by volume.
Catalyst containing nickel, zinc and precious metals may be sold after use
to firms dealing in the recovery of such materials. The economics of the
scale will depend on the location of the plant, the composition of the
catalyst, and the prevailing metal prices.
Catalyst which has been discharged in the reduced state must be allowed
to become stable in air before despatch.
There are few hazards associated with the use of catalysts, but the
following points should borne in mind.
Short term exposure to the metals and metal oxides used in catalysts
may give rise to irritation of the skin, eyes and respiratory system. Over
exposure can give rise to more serious effects. Product safety data
sheets should be consulted for information. Catalysts should be handled
as far as possible in well-ventilated areas and in a way which avoids the
excessive formation of dust. Operators who handle catalyst must wear
suitable protective body clothing, gloves and goggles. Inhalation of dust
should be avoided and the appropriate occupational exposure limits
should be strictly observed. If these limits are likely to be exceeded
respiratory protection should be used.
When a vacuum truck is used to suck the catalyst out of the equipment,
careful grounding of the equipment is necessary to dissipate static
electricity build-up as the catalyst travels through the hose.
DMDS is the agent used for sulphiding COMOX catalyst beds (92-R-01
and 92-R-11). This enhances activity of the catalyst. This chemical is
added to the reactors by using a special feed circuit comprising of a
DMDS dosing tank, two dosing pumps and one unloading pump.
The capacity of the DMDS storage drums is 200 liters. DMDS from the
storage drums is unloaded into dosing tank (92-V-07). The capacity of the
DMDS storage tank is 2.61 m3 and the operating volume of the tank is
2.0 m3. It takes around 10 minutes for the pump to unload a drum.
The unloading operation is carried out with air operated drum pumps (92-
P-28 A/B) with capacity 1.4 m3/hr and head 20 m. Air is supplied from the
plant air header and the pressure is reduced to 30 psig by PCV 1709.
Flexible hose connections are used for the pump suction and discharge
connections. The pump rests on a platform and takes its suction from the
drum through a flexible hose. The system must be manually monitored as
there is no automatic control or DCS indication provided for this
intermittent operation
.
Page 316 of 413
DESIGN & OPERATING MANUAL
BFW dosing system is designed to meet the boiler feed specified water
quality. The plant has two separate steam systems with its dedicated
Degassers (92-V-21 & 92-V-22) and BFW supply pumps (92-P-12, 92- P-
13 & 92-P-16). DM water Degasser (92-V-21) uses fresh DM water as its
feed whereas Process Condensate Degasser (92-V-22) uses all process
condensates as its feed. Degasification is carried out with the help of LP
steam.
A common BFW dosing system is designed for both the steam system
with dedicated dosing pumps.
Three different dosing systems are designed for BFW to meet the boiler
feed water quality specified.
1. Deposit Control
2. pH Control
3. Oxygen Scavenging
HAZOP recommendation
1) Degasser 92-V-21 30
2) Degasser 92-V-22 10
Total (lph) 41
Solution preparation:
HAZOP recommendation
Total (lph) 15
Solution preparation:
HAZOP recommendation
2) Degasser 92-V-22 25
Solution preparation:
9. Safety
Page 322 of 413
DESIGN & OPERATING MANUAL
9. Safety
9.1 General
The following rules shall be followed by the personnel who take part in
the operation of the plant.
The personnel shall be familiar with the process flow diagrams, the
piping and instrumentation diagrams and safety regulations.
During initial operations the position of all the valves shall be checked.
Adequate records or loggings of the plant operation shall be kept.
Fire and explosion risks and toxicity are major hazards associated with
the storing, handling and processing of the chemicals.
It is essential that all the operating personnel are fully aware of the
potential hazards associated with the each process material, also
precautions to be taken to ensure safety in their handling and use.
Inhalation
Ingestion
Before bringing flammable (gases or liquid) into the unit, the area
should be cleaned of all unnecessary construction materials,
which might offer a fire or accident hazard.
Steam lances should be in their racks around and in the unit. Fire
blankets, special clothing and hand chemical extinguishers should
be available and ready for use. First aid supplies and telephone
service for medical aid should be readily available.
Lower Upper C
Lower Upper C
Gas masks suitable for use with hydrogen sulphide must be worn
during work in exposure to it is likely to occur; masks must be
frequently checked to ensure they are functional. When working
under conditions of likely exposure, the presence of a second
operator is compulsory.
- Ensure that the victim’s mouth and nose are clean and dry.
- Place both hands on his lower ribs and press down and in
to squeeze his chest. Press hard for three seconds.
Rub the patient’s arm and legs and apply hot water bottles,
blankets or other means to keep him warm.
9.2.4 Hydrogen
Edema and haemorrhages in the lungs and brain have been found
in fatal cases.
Ni + 4 CO - Ni (CO) 4
9.2.8 Hydrazine
DATASHEET
CH3SSCH3: M.W.94
CAS: 624-92-0
DATASHEET
PRODUCT: MORHOLINE
First aid: If eye contacted, flush with plenty of water & get
medical attention.
UN number: 1760
CAS: 110-91-8
Page 336 of 413
DESIGN & OPERATING MANUAL
- Restricted Areas :
Continuously,
Intermittently, or
Due to an abnormal or transient condition.
- Open Areas :
Welding in a welding-yard,
Laboratory work, etc.
General
Furnace Explosions
General
Explosion Theory
Heater flame-out
Heater light-off
Note: During the light-off the burner, check very carefully through
the end-wall peepholes and/or burner peep sights to ascertain that
the pertaining burners are really ignited and are not impinging on
the heater tubes.
General
Respiratory protection
All gases other than air are harmful to man when inhaled in
sufficient concentrations. Toxic gases may be classified as either
asphyxiating or irritating.
Page 341 of 413
DESIGN & OPERATING MANUAL
- Provide ventilation.
These are full face masks into which fresh air is blown
through a long hose from a manually operated blower,
placed outside the hazardous area. The masks can be
used in any concentration of toxic gases and can be used
for a long time and permit relatively easy breathing.
- Body protection
- Free the equipment for repairs, etc, when the gas test has
passed.
Note: Never make lines gas-free with air, when they have
contained hydrocarbons.
Isolating an equipment
Isolation of an equipment item means that all the lines to and from
that equipment must be disconnected or a blind must be inserted.
Therefore, reliance should never be placed on valves to ensure
gas-free conditions.
Unheading a vessel
Gas testing.
Page 346 of 413
DESIGN & OPERATING MANUAL
% oxygen testing
Loosen the bolts in the most inaccessible areas of the flange first.
Installation
Rotating Machinery
Sign example:
WARNING
DO NOT CLOSE
INLET AND OUTLET
UNLESS YOU FIRST OPEN THE DRAIN OR VENT
Care should also be taken that equipment and lines are not left
filled with light hydrocarbon liquids an then blocked in since there
is the possibility that any external heat (also the heat of the sun)
can cause liquid expansion or vaporization
9.4.8 Housekeeping
9.5.1 Introduction
9.5.2 Equipment
General
Whatever the size of the job, make sure you know exactly what is
involved before starting.
Always tell the area supervisor what you are going to do, and if
necessary have another operator for assistance. For example,
when changing a burner for cleaning, no assistance may be
needed, but the supervisor should be informed. When the furnace
is being lit up from cold, some planning will be necessary and
three or four operators will be needed on the job.
General Precautions
- Always make sure that the burner tip and venturi are clean
before lighting to prevent blowback.
- If for any reason the fuel to the furnace fails, the furnace
should be purged and analyzed for the presence of an
explosive fuel-air mixture as described elsewhere, before
an attempt is made to re-light burners.
The fuel supply must be closed off at all burners, and the main
supply valves closed as well, to prevent leakage into the firebox.
General
A “hot” furnace is one where all or nearly all burners are alight and
the furnace brickwork and burner tiles are red hot.
A “cold” furnace is one where the brickwork is not red hot; this
may be because the furnace has only just been started up, or only
a few burners are alight, or the plant is on a low through put.
Page 353 of 413
DESIGN & OPERATING MANUAL
Hot Furnace
Cold Furnace
a) Purging
b) Lighting torch
Cool-down rate should not exceed 50ºC per hour at the fuel gas
cross-over.
Upon passing under 250ºC flue gas temperature at flue gas cross-
over, close all burners and isolate fuel gas system. Close all air
shutters to prevent forced cooling and reduce draft to a minimum.
Shut down both the induced and the forced draft fan.
Page 355 of 413
DESIGN & OPERATING MANUAL
9.6 Sampling
- Open flames
- Automotive vehicles
- Static electricity.
Note:
For details of fire fighting system refer Chapter 14
Page 359 of 413
DESIGN & OPERATING MANUAL
Cut off all electric power except that required for the
operation
Do not rely on closed block valves only for positive isolation, since
there is always the possibility of leakage or inadvertent operation.
The block valve itself should be tagged “DO NOT OPERATE”
Before allowing any working personnel to enter the area for the
purpose of proceeding with inspection or maintenance, the unit
should be thoroughly ventilated with air.
Permits
Special permits are issued for each work category (“hot works,
excavations, electrical works, vessel entry, etc.), with all special
requirements for personnel and plant protection clearly stated.
Such permits should be issued for a special period, (e.g. to cover
one operating shift), and only renewed after full re-inspection of
working area.
9.10 MSDS
Note:
MSDS for feed streams FCC Gasoline and Straight Run Sour
Naphtha are to be obtained from IOCL and attached.
Page 365 of 413
DESIGN & OPERATING MANUAL
10.1 General
Streams to be analysed.
Analysis to be performed.
In this section all the recommended method which are the most
applicable for control analysis by plant personnel.
These methods are selected for their simplicity, rapid and more accuracy
in results.
Sample containers shall be gas tight and easy for handling and
sampling.
The test results are often used for custody transfer and pricing
determination, so it is very essential that the sample must be
representative. Extreme judgement ands skill is necessary to
ensure a sample which represents the general and average
conditions of the sample.
Sample taken by
Date of sampling
Time of sampling
Kind of Gas
Page 371 of 413
DESIGN & OPERATING MANUAL
On request
Page 372 of 413
DESIGN & OPERATING MANUAL
Sample
To Atmosphere
As soon as the gas blows out at the drain valve, take the second
reading on the wet gas meter and close the drain valve on the
separator and sample cooler.
Gas Vol%
CH4 6.65
CO 13.5
CO2 8.80
H2 70.30
N2 0.75
From this ratio and the complete dry gas analysis, a material
balance can be made which will permit an estimation of the steam
to carbon ratio at the inlet of the reformer.
ASTM-D- On-request
1688
Required
Sr. Stream
Chemical Vessel Tag concentration
No. components
% (W/W)
Catalyst DMDS
1 sulphiding 92-V-07 + Note 2
agent Naphtha
CHIMEC
Corrosion -1044 7.5
2 92-V-08
inhibitor + (in naphtha)
Naphtha
DM water
3 pH control 92-V-29 + 1.5
Morpholine
DM water
Deposit
4 92-V-30 + 3
control TSP
DM water
Oxygen
5 92-V-28 + 0.2
scavenger Hydrazine
Note:
1. For all the dosing chemicals sampling must be done at
the charging of a new batch. A new batch is generally
charged after 48 hrs.
2. Catalyst sulphiding agent is used only during the
charging of the new batch of catalyst. Hence sampling is
done on request.
3. Sample analysis should be as per the standard IOCL
refinery laboratory procedures.
Page 381 of 413
DESIGN & OPERATING MANUAL
Feed Stock
Desulphurizer effluent
Pre-reformer
Reformer Effluent
HTS converter
Product Hydrogen
Purge gas
10.9.2 Water
Oxygen
Silica
Conductivity
Turbidity
Sulphate
TDS
Phosphates
pH
Hydrazine
Hardness
Chlorides
Carbon dioxide
Calcium
Alkalinity
11. Corrosion
Page 386 of 413
DESIGN & OPERATING MANUAL
11. Corrosion
11.1 General :
The wash water is injected upstream of the Naphtha air cooler, 92-AC-01
to avoid HCl and ammonium salt deposit and corrosion.
Due to the presence of chlorides in the feed naphtha, HCl and ammonium
salt is formed in the reactor (92-R-01).Therefore upstream of the air cooler
(92-AC-01) wash water is injected to the reactor effluent. Provision is also
made to inject wash water in the heat exchanger train (92-E-01
A/B/C/D/E/F) during start-up.
Wash water pumps 92-P-03A/B supply DMW from the DMW storage tank
(92-T-01).
Page 389 of 413
DESIGN & OPERATING MANUAL
Corrosion can cause serious failures, which lead to large economic loss,
sometimes combined with environmental pollution, or risk of personnel injuries.
The most important steps in order to hinder or reduce the extent of such failures
are sufficiently early detection, proper diagnosis and effective prevention
measures.
When unacceptable corrosion is detected, the first step should be to estimate the
cost of repair or replacement and the consequence of new attack after such
repair. This will affect the decision on extent and content of further investigations.
In many cases, the preliminary examination is sufficient to decide that a relatively
simple action is adequate to solve the problem. In more complex cases, more
extensive examinations have to be carried out.
Sometimes, failures may have occurred due to human error. If this is the case,
steps must be taken to avoid repetition. Improvement in routines of supply and
labeling of materials, information on experienced failures, and further education
of technical personnel, may by appropriate.
Page 392 of 413
DESIGN & OPERATING MANUAL
11.5 Passivation:
Austenitic stainless steel (300 series alloys with nominally 18% Cr-8% Ni
compositions) process equipment and piping are subjected to failure by corrosion
cracking, if not adequately protected to prevent corrosive environments from
occurring.
The acids attack the metal grain boundary and thus deplete the chromium
content.
Note : The licensor (Technip) has not recommended passivation of any of the SS
components in the plant. The above background is based on general
understanding and practice followed elsewhere.
Neutralization procedure :
Instrument details are required for the reference of the operating and,
maintenance personnel. Details of the instruments are provided in tabulated form
Note:
Detailed information about the equipment and its internals is useful for many
applications such as maintenance operations, normal operation, de bottlenecking
and equipment testing.
List of all the equipments in the plant is classified on the basis of the type of
equipment and is presented in a tabular form.
Note:
The catch basins have open top as they are meant to collect the
storm water and fire water from the floor of the plant area. These
basins also have a vent.
14.1.3 Drawings
Following drawings are attached for reference*:
Note:
14.3.1 PA system is has a common central exchange for HCU and HGU.
This exchange is located in new OHCU control room.
14.3.2 The central control exchange is having provision for integration &
hook up with the following systems
Existing PA system
Existing FA system
Existing EPBAX & radio paging system
Telephone and walkie talkies within HCU and HGU unit
14.3.4 PA system has having one more flameproof junction box for N2
area which PA caters field call stations (FCS) in N2 area.
14.3.5 There are total 10 nos. flame proof type and 2 nos. industrial type
field call stations (FCS) with loud speakers located at various
locations in HGU plant.
14.4.1 Objectives
ii) Reduce the heat radiation to enable safe escape and evacuation
to the main entrance
iii) Reduce the total heat flux to enable an effective fire fighting.
i) The existing / modified fire water ring main around east, west
& south side of HGU unit is provided by owner (IOCL).
ii) The hydrant systems are provided as per TAC/ OISD for the
HGU unit considering the risks to be classed as “High
Hazard Class B”. Existing hydrants are marked with prefix
“ExH” for ease of identification and is defined in P&ID Dwg.
no. 10144-PEIN05-92-2899-P010 and Fire water layout
Dwg. no. 10144-PEIN05-92-2899-P001 for clarity.
14.4.4 Fixed Water Spray System – Medium Velocity Water Spray (MVWS)
Vessel 92-V-02
14.4.5 Auto Operated Fixed Water Curtain & Water Spray System
i) One side fed Auto water spray system for water curtains for
heater area, based on gas detection around heater (92-F-01)
area to cut off ingress of gas.
ii) One side fed Auto water spray system for water curtains for
reformer, based on gas detection around reformer (92-F-11)
area to cut off ingress of gas.
iii) One side fed Auto water spray system actuated by hydraulic
(water) detection using quartzoid bulb detectors for 92-V-02 as
per process requirement.
Page 406 of 413
DESIGN & OPERATING MANUAL
The exact location of H2, H2S & Hydrocarbon detectors are as per
Gas detector layout drawing 10144-PEIN05-92-5811-P002, Rev 2.
All gas detectors are connected directly to DCS for monitoring &
alarm. No dedicated Fire & Gas system is provided. As per the
required set point, the digital output is generated in DCS to
actuate hooters and beacons. Hooters are provided in the control
room and in the field. Four beacon are provided in the field
(Location as decided on site. Generally located at the four corners
of the plant.)
15.1 PFDs
15.2 P&IDs
15.14 MSDS
Note:
* All the documents listed above are provided in separate file enclosed with the
manual .Refer “Attachments” VOLUME 2 OF 2.
Page 412 of 413
DESIGN & OPERATING MANUAL
The following are the vendors for the respective equipments / packages :
16.2 Enereff
For modes of operation, maintenance methods, safety precautions &
other related information on Fired Heater (92-F-01) refer Enereff -
Operating & Maintenance manual for Naphtha Superheater No. 92-F-01
Doc. No 1120-3-OM-063.
16.3 Chromalox
For different modes of operation, safety precautions & other related
information on 92-E-15 refer Operating manual given by Chromalox.
16.4 UOP
For modes of operation, maintenance methods, safety precautions &
other related information on UOP Polybed PSA Unit (92-M-12) refer UOP-
Operating manual Doc. No E-H6265-720.
16.5 BOC
For modes of operation, maintenance methods, safety precautions &
other related information on Cryogenic Nitrogen generation unit (Unit 96)
refer Operating & Maintenance manual for Cryogenic Nitrogen generator
given by BOC.
92-K-01
Operation & Control Philosophy
92-K-11
Operation & Control Philosophy
92-K-12
Operation & Control Philosophy
92-K-13
Operating Manual For Naphtha Superheater
92-F-01
Operating Manual For Electric Heater
92-E-15
A 07/07/08 FIRST ISSUE JYB CM JYB
ETIREX SAS
PR N° 10118-PEIN02-000-3000-PR14 Rév. 0
P.O N° : PEIN05/160007
Document Number
Document title :
TRANSPORTATION , STORAGE ,
INSTALLATION INSTRUCTIONS
1 – ELECTRIC HEATER
1.1. Transportation
1.5. Lifting
1.6. Installation
2/21
ETIREX SAS
Refer to general arrangement drawing :
N° 550874
IMPORTANT :
PRELIMINARY NOTES :
• Machined parts must always be protected from rain, water and any
aggressive medium.
1.7.1.Opening
3/21
ETIREX SAS
Take all necessary precautions to prevent any wounds on the
threaded parts of the cover / enclosure and on the cable
entries.
1.7.2. Closing
2.1. Transportation
4/21
ETIREX SAS
2.4. Handling prior erection
2.6. Lifting
2.7. Installation
Thyristor control panel will be installed and anchored to the floor. Refer to
drawing
N° 61045
The control panel can be positioned with its back against a wall.
The control panel will be installed in order that doors can be easily opened to
allow easy access to the connection and all the components.
5/21
ETIREX SAS
2.8.Connections
See drawing for all details and connection to or from different parts of the
system (control room, field, DCS, Substation, out going volt free contacts,
...).
2.9.2 Power
2.9.3 Earthing
6/21
ETIREX SAS
PRE-COMMISSIONING INSTRUCTIONS
1.1. Check that electric heaters , local and thyristor control panel have
been correctly installed.
1.2. Check that power cabling has been made with appropriated cables in
accordance with current regulation.
1.3. Check that thermocouples cabling has been made with appropriated
compensation cables in accordance with current regulation.
1.4. Check that transmitters cabling has been made with appropriated
compensation cables in accordance with current regulation.
1.5. Make sure that cables do not transmit efforts on cable glands and
check tightness of these cable glands.
1.6. Check that earthing of the electric heaters and control panel has been
made.
7/21
ETIREX SAS
1.9. When electric heaters are under pressure check the efficiency of the
gaskets and tighten if necessary.
8/21
ETIREX SAS
COMMISSIONING INSTRUCTIONS
- supply voltage
- cleanliness and good state of the electrical connections
- tightening of the electrical connections
- earthing wiring
- good state of the supply cables
- take off the desiccants bags
- insulation under 500 VDC between phase and earth on each
power output. The value must be higher than 1 MOhms for each
step.
9/21
ETIREX SAS
OPERATION INSTRUCTIONS
FOR ELECTRIC HEATER
1 – BEFORE ENERGIZING
Check that all piping connections are correctly done (efficiency of the
gasket, tightness…).
Check that heaters have been purged if necessary (use the vent nozzle
at the top of the heaters if available).
Check that all installation data (fluid nature, inlet and outlet
temperature, flow, etc…) conform to the PROCESS specification / data
sheet for each electric heater.
Ensure that no flammable condition can occur in the heater ( no
explosive gas / gas mixture inside the heater )
2 – ENERGIZING
10/21
ETIREX SAS
In this case, make sure that dessicant bags have been removed and
that there is no humidity, condensation or water in the enclosure.
- repeat the same procedure for each over temperature cut out
controller.
4 – WORKING
IMPORTANT
12/21
ETIREX SAS
OPERATION INSTRUCTIONS
FOR CONTROL PANEL
1 - ENERGIZING
1.1 - Remove the dessicant bags if any and all foreign things.
1.2 - Check supply connections, heaters cable connection and all control
cabling connection.
1.3 - Check the correct setting for the earth leakage controller (i.e : 500 mA).
1.5 - Check that the ambient temperature thermostat (B1) set point is 45°C
(above this temperature default will be signalled contactor will be opened.
2- WORKING
From this moment, the power will be proportionnal to the value of 4-20 mA
analogic signal given by TIC (DCS).
WARNING :
2.2. Start :
2.3.1 Normal :
- remote stop order from DCS (shutdown due to low flow rate / safety
stop due to high gas temperature, high heating element T° , etc...).
- Stop order can also be given by operator when selector switch S2 is in
position ( local “ by pushing S4 push button
-
2.3.2 Safety :
-Wattmeter W1 ( incoming )
- Audio-alarm ( hooter )
This alarm will be activated on any default
4.3 - DCS
5 - VERY IMPORTANT
15/21
ETIREX SAS
For all the above described default, manual reset must be provided in order
that no automatic start-up can be done before cause has been investigated
and corrective action has been taken.
16/21
ETIREX SAS
MAINTENANCE MANUAL
FOR ELECTRIC HEATER
1 – PERIODICITY
First maintenance operation to be done one month after initial start up. After
this first maintenance operation minimum maintenance period is 6 months.
2 – MAINTENANCE OPERATION
2.3. Periodically check the state of the heating elements of the heater
(particularly check that there is no sludge or deposit on the heating
elements).
Note : any dirt on the heating elements would increase the skin
temperature and would be detected by the thermocouples.
In any case, water or steam may not contain more than 20 chloride
ppm.
2.6. Refer to local regulation for periodical tests to perform on this heater
(pressure vessel local regulation).
17/21
ETIREX SAS
IMPORTANT :
control panel (check tightness of all power and control connections, and
good state of all components)
control panel to supply cabling
heater elements :
- insulation resistance
- cleanliness of connections
- physical damage
3.2.2. Check that the gas flow through the heater is correct and unrestricted
(both upstream and downstream).
3.2.3. Check if the demand signal from the remote temperature control
system to the thyristor driver is present when the flow conditions through
the heater does not necessitate the relative degree of power input to the
heater.
Preliminary note :
18/21
ETIREX SAS
A heating bundle may only be dismounted if the temperature of heating
elements is near from ambient temperature (less than 50°C).
4.3. Check that the lifting ring on the tubesheet is in the right position as
shown on heating bundle drawing.
4.5. Pull the heating bundle out of the vessel taking care not to damage
baffles or spacer, heating elements, thermocouples, junction boxes…
5 – RE-FITTING
5.1. Heating bundle should be re-fitted in the vessel using a new gasket
unless it is of the reusable type.
5.2. The flange nuts must be tightened in the correct sequence and to
correct torque
5.3. Make sure that the gasket is in the right position and that its
efficiency is perfect.
19/21
ETIREX SAS
MAINTENANCE MANUAL
FOR THYRISTOR AND LOCAL CONTROL PANEL
1 – PERIODICITY
- check voltage supply with H0 lamp for 230 VAC presence voltage and
voltmeter V.
- test lamp (S6 push button)
- audio-alarm ( klaxon ) test (S12 push button)
- check of trips (lamps)
- high gas temperature ( TISH )
- PECA measure display ( intensity )
- Ammeter
- check of trips (lamp )
3 – MAINTENANCE INSTRUCTIONS
It should be kept clean, both inside and outside. Do not allow any ingress of
water vapour, as this will precipitate corrosion of the electrical components
and promote carbon cracking.
20/21
ETIREX SAS
4 – TRIP CONDITIONS / TROUBLE SHOOTING
a. check the panel air thermostat is correctly set (45°C) and that all
wiring associated with it is complete and secure.
a. check that the particular cutout unit is correctly set. (see 3.1. of
control panel operation instructions).
b. the demand signal from the remote temperature control system to
the thyristor driver is present when the flow conditions through the
heater does not necessitate the relative degree of power input to the
heater . Investigate the remote temperature control system in this
case.
c. heater load current is high in relation to the demand from the
remote temperature controller. Check the thyristor driver for
malfunction in this case.
a Check that the particular cutout unit is correctly set. (see 3.2. of
21/21
ETIREX SAS
control panel operation instructions).
b The demand signal from the remote temperature control system to
the thyristor driver is present when the flow conditions through the
heater does not necessitate the relative degree of power input to the
heater . Investigate the remote temperature control system in this
case.
c Heater load current is high in relation to the demand from the
remote temperature controller. Check the thyristor driver for
malfunction in this case.
If the trip occurs, this means that one of the power fuses is faulty.
Identify the faulty fuse(s) and replace.
a. check the panel air thermostat is correctly set (45°C) and that all
wiring associated with it is complete and secure.
5- PERIODIC CHECKS
5.1. Check that the over temperature cutout units trip correctly by
simulating a trip condition at the set point potentiometer.
5.2. Check the contactors contact set for wear or pitting and replace
if necessary.
5.3. Clean the control panel paintwork, check for corrosion and
repair if necessary.
5.4. Check lamps (test lamp push button).
22/21
ETIREX SAS
23/21
Operating Manual For Polybed PSA Unit
92-M-12
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 1 of 80
By : T. Cnop
This sheet is a record of all revisions to this specification. For convenience, the
nature of each revision is briefly noted under description, however, the
description is not a part of this specification.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 3 of 80
By : T. Cnop
OPERATING MANUAL
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 4 of 80
By : T. Cnop
TABLE OF CONTENTS
1. INTRODUCTION 8
2. OPERATING CONDITIONS 9
2.1 PERFORMANCE 9
3.1 GENERAL 16
3.4 SWITCHOVER 24
4.2 AUTOMATIC SEQUENCING OF THE POLYBED® PSA UNIT WITH 10- OR 8-BEDS 37
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 5 of 80
By : T. Cnop
6. PROCESS SAFEGUARDS 43
7. START-UP 48
8.4 TROUBLESHOOTING 59
9. SHUTDOWN 64
9.1 GENERAL 64
10.1 SWITCHOVER FROM 12-BED TO 10-BED OPERATION AND FROM 10-BED TO 8-BED
OPERATION 66
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 6 of 80
By : T. Cnop
12. SAFETY 77
12.2 HAZARDS 77
REFERENCE DOCUMENTS 80
P & ID B-H6265-002 80
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 7 of 80
By : T. Cnop
NOTE
The design of this POLYBED PSA UNIT is confidential and shall be available only under the
terms of the contracts between UOP N.V. and IOCL. The operating instructions and drawings
appended hereto shall not be duplicated, disclosed or used for any purpose other than for
instruction on the equipment described herein.
WARNING
Hydrogen is extremely hazardous when proper safety measures are not observed. All
persons involved with this POLYBED PSA UNIT should read and understand this manual.
Improper operation can result in poor performance, damage to equipment and safety
hazards. Special consideration should be given to the chapter “Safety”.
The feed, product and tail gas from the POLYBED PSA Unit contain high concentrations of
highly flammable and toxic components. Failure to apply the necessary safety measures can
result in equipment damage and safety hazards, possibly with fatal consequences.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 8 of 80
By : T. Cnop
1. INTRODUCTION
This OPERATING MANUAL covers the operation of the 12-bed UOP POLYBED® PSA Unit
92-M-12. Before any attempt is made to start and operate the POLYBED® PSA Unit, the
operator ought to read the operating manual thoroughly. Improper operation may result in
safety hazards, adsorbent degradation and below design performance.
The POLYBED® PSA Unit purifies reformed hydrogen rich feed gas (via an adsorption
process) producing a product stream of high purity hydrogen (available at 20.3 kg/cm²g) and
a purge stream containing the impurities (available at 0.33 kg/cm²g). The purge gas stream is
sent to the steam reformer burners (under flow control).
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 9 of 80
By : T. Cnop
2. OPERATING CONDITIONS
2.1 PERFORMANCE
The unit is designed to produce max. 107266 Nm³/h of product gas from 167620 Nm³/h of
reformed naphtha feed (guarantee hydrogen recovery 89.5%).
The feed must be free of entrained solids and liquids since these will cause permanent
adsorbent deactivation. The effect of non-design components must be confirmed with UOP
prior to their introduction into the PSA unit in order to prevent possible adsorbent activity loss.
Alternatively the unit can produce max 107152 Nm³/h of product from 167464 Nm³/h of feed -
expected recovery 89.5%.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 10 of 80
By : T. Cnop
TABLE 2.1
Nitrogen - -
Temperature 40 40
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 11 of 80
By : T. Cnop
TABLE 2.2
Methane - -
Carbon dioxide - -
Nitrogen - -
Water - -
Temperature 45 45
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 12 of 80
By : T. Cnop
TABLE 2.3
Nitrogen - -
Temperature 30 30
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 13 of 80
By : T. Cnop
In case of a valve malfunction, the unit will automatically switch from 12- to 10-bed operation.
In 10-bed mode, the unit will be able to process 100% of the feed flow in 12-bed mode. The
hydrogen recovery will be lower. Expected recovery in 10-bed mode is 86%.
In case of a valve malfunction in 10-bed mode, the unit will switch over to 8-bed operation. In
8-bed mode, the unit will still be able to process 100% of the feed flow in 12-bed mode. The
reformer does not have to be turned down after a switchover to 8-bed operation. Expected
recovery in 8-bed mode is 82%.
Pressure maximum
normal 6 kg/cm²g
minimum 4 kg/cm²g
The instrument air system will also be used for air supply to air masks, ventilation of
columns, vessels, etc. The utilisation of this air shall be such that no contamination can
occur.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 14 of 80
By : T. Cnop
2.7.2 Nitrogen
Dry nitrogen is required for start-up and purging the unit in the event of a prolonged
3 3
shutdown. Consumption ca. 21000 Nm for start-up with a normal flow of 5200 Nm /h
during 4 hours (minimum flow = 2600 Nm3/h; maximum flow = 10400 Nm3/h)
Pressure: maximum
normal 6 kg/cm²g
minimum 5 kg/cm²g
The unit will be leak tested with nitrogen at 5kg/cm2g, 10kg/cm2g and full operating pressure of
21.2 kg/cm2g (See section 7.4 in this document and E-H6265-507 Site Erection Specification).
When pressurising the adsorbers, the guidelines as explained in the specific sections in this
operating manual should be followed. Valves should be opened carefully to prevent any
disturbance of the adsorbent. Pressurising should not occur faster than 1 kg/cm2 per minute.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 15 of 80
By : T. Cnop
According to:
- Process Flow Diagram : C-H6265-001
- Piping and Instrument Diagram : B-H6265-002
- Pressure Sequence Chart : B-H6265-003
- Valve Sequence Chart : B-H6265-004
TAG NUMBERS
Note: All vessel and instrument tag numbers are prefixed by 92-
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 16 of 80
By : T. Cnop
3.1 GENERAL
The PSA process is based on the selective adsorption of impurities on an adsorbent at high
pressure in order to produce high purity hydrogen gas (min. 99.9%), followed by the
regeneration of the adsorbent by desorption of the adsorbed impurities at low pressure.
There is no change in temperature, except for that caused by the heat of adsorption and de-
sorption.
The performance of the unit is strongly affected by the purge gas pressure. Maximum
regeneration and therefore maximum capacity and efficiency are reached when desorption
occurs at minimum purge gas pressure.
The cyclic pressure variation (“swing”) occurring during the process explains the name by
which it is known (Pressure Swing Adsorption).
Every adsorber operates on a repeated cycle basis consisting of adsorption and regeneration
phases. The cycles are staggered in order to provide a continuous product and purge gas
flow.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 17 of 80
By : T. Cnop
1) After the adsorption phase, the adsorber is depressurised to the tail gas drum pressure.
1a) At first, the hydrogen that is still stored in the bed is used to pressurise
(equalisation 1, 2 and 3) or purge (providing purge) other adsorbers in the
process of regeneration. This internal recovery of hydrogen improves the
performance of the PSA unit in terms of total hydrogen recovery.
1b) Subsequently, the adsorber is depressurised to tail gas drum pressure during
which most impurities are desorbed and removed via the bottom (dump).
2) The adsorber is purged at low pressure with hydrogen recovered from a depressurising
adsorber in order to remove the remaining impurities from the adsorbent (purge).
A subcycle is divided into 3 steps. The control of the PSA unit is based on the subcycles and
steps. When step 1 ends, the unit switches to step 2 etc. With step 3, the subcycle ends and
the process will continue in step 1 of the next subcycle.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 18 of 80
By : T. Cnop
To reduce hydrogen losses during depressurisation and to obtain high performance, the
POLYBED® PSA unit uses twelve adsorbers. The use of twelve adsorbers allows optimum
utilisation of hydrogen stored in each adsorber at the end of adsorption for partial
repressurisation and for purging of other adsorbers.
Each adsorber is cycled through the same adsorption – regeneration sequence. The cycles
are staggered, so that at any one time three adsorbers are on adsorption while the other nine
are in various stages of regeneration, as illustrated by the pressure sequence chart
(B-H6265-003, sheet 1). The sequence by which the adsorbers come on adsorption is V-31,
V-32, V-33, V-34, V-35, V-36, V-37, V-38, V-39, V-40, V-41 and V-42 #. As a result of these
staggered cycles a continuous uninterrupted product flow is obtained.
#
In this manual, only the last part of the adsorber numbering is used. e.g. V-31 corresponds to 92-V-31 in
unit 92-M-12
This section describes in detail each cycle step in sequence for an adsorber going through
one complete cycle of adsorption and regeneration. For the purpose of this description,
reference is made to adsorber V-31, however, it is applicable to any adsorber and can be
made to apply by substitution of the corresponding tag numbers.
The following valve numbering scheme has been applied: UCV 39363
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 19 of 80
By : T. Cnop
Example: Valve UCV 39363 is the Provide Purge valve associated with adsorber V-36
Note: In this manual, only the last three digits of the valve numbering will be used (eg. valve
311 corresponds to UCV 39311
Note: As there is only one valve °2 and °5 per pair of adsorbers, the valve is given the lowest
adsorber number of the pair. Eg. valve 332 is the product valve of V-33 and V-39.
TABLE 3.1
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 20 of 80
By : T. Cnop
The feed gas at the specified pressure of 21.2 kg/cm²g and temperature of 40°C enters
through valve 311 and flows upward through adsorber V-31 as well as through two other
adsorbers and their corresponding feed valves. All the impurities are selectively adsorbed
and high purity hydrogen flows into the product line through valve 316 and 312. To
maintain guaranteed purity and recovery, the cycle time is made capacity dependent (see
section 3.5). At full capacity the subcycle time is approximately 30 seconds. Each vessel
remains on adsorption during three subcycles (approx. 90 s at full capacity).
At the end of adsorption, adsorber V-31 has been partially loaded with impurities, the
concentrations of which are the greatest at the bottom and quickly decrease towards the top
of the vessel. In order to recover most of the hydrogen stored in the adsorber, that would
otherwise be lost in the tail gas, several co-current depressurisations are performed from
bottom to top. During these depressurisations, the impurities front migrates towards the top
section of the bed. The depressurisation effluent (hydrogen) is used internally in the
POLYBED® PSA unit to repressurise (EQUALISATION 1, 2 & 3) and purge (PROVIDE
PURGE) other adsorbers.
In order to maximise the hydrogen recovery, one strives to allow the impurities front to
migrate as high as possible into the bed without allowing impurities to break through in the
product.
The co-current depressurisation is allowed to proceed until the impurities reach the top of the
adsorbent. At that moment, the flow in the vessel is reversed and the vessel is depressurised
counter-currently (DUMP) (in the downward direction) to purge gas pressure. The impurities
leave the vessel during this depressurisation for the tail gas drum.
Following the dump step, the adsorber is further regenerated by purging the adsorber with
the high purity stream provided by another adsorber during the provide purge step. The
remaining impurities are removed and sent to tail gas drum. This tail gas drum, which
receives both dump and purge gas, guarantees a steady homogeneous tail gas flow.
Before going back into the adsorption step, the adsorber has to be repressurised with gas
provided by the three equalisations and by a slip stream of the feed gas.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 21 of 80
By : T. Cnop
During the first depressurisation, the high pressure hydrogen remaining in adsorber V-31 is
used to partly repressurise adsorber V-35 by equalising these two vessels.
The gas flows out of the top of adsorber V-31 and flows through valves 316, 315, 355 and
356 to adsorber V-35. The rate of equalisation flow is controlled by valves 316 and 356
(valves 315 and 355 fully open). The equalisation is ended by a timer condition, when
adsorber V-31 and V-35 are expected to have reached the same pressure of approximately
15.84 kg/cm²g. Equalisation 1 takes place during step 1 which lasts approx 11 s.
During the second depressurisation step, the high pressure hydrogen remaining in adsorber
V-31 is used to partly repressurise adsorber V-36 by equalising these two vessels.
The gas flows out of the top of adsorber V-31 and flows through 316, 315, 365 and 366 to
adsorber V-36.
The rate of equalisation flow is controlled by valves 316 and 366 (valves 315 and 365 fully
open). At the end of the second equalisation (determined by a timer) both adsorbers will have
reached the same pressure of approximately 9.44 kg/cm²g. Equalisation 2 takes place during
step 3. In step 2, between equalisation 1 and 2, the adsorber V-31 is isolated (closing valve
316; valve 315 remains open) as equalisation 2 with V-36 cannot start before V-36 has
terminated equalisation 3.
During the third equalisation step, the high-pressure hydrogen remaining in adsorber V-31 is
used to partly repressurise V-37. The gas flows out of top of adsorber V-31 and flows through
valves 316 and 376 to adsorber V-37. The depressurisation of adsorber V-31 is cut-off when
the pressure of V-31 has dropped to 4.86 kg/cm². At design capacity equalisation 3 will be
about 87% finished. The pressure difference between adsorbers V-31 and V-37 at the end of
equalisation 3 is expected to be 1.05 kg/cm² (i.e. end pressure V-31= 4.86 kg/cm²g, end
pressure V-37= 3.81 kg/cm²g). Equalisation 3 takes place in step 1 and 2.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 22 of 80
By : T. Cnop
During and after the third equalisation the adsorber is further depressurised to provide a high
purity stream to purge other adsorbers. In the first part (PP1 during steps 1 and 2), a slip
stream passes through 313 (which is in throttled position) and enters V-38, V-39, V-40 via
383, 393 and 403 (100% open) to purge these adsorbers. In the second part (PP2 during
step 3), gas flows through the throttled valve 313 to adsorbers V-38, V-39, V-40 and V-41.
The flow and composition of the purge gas varies in time. The provide purge step terminates
when the pressure in adsorber V-31 has reached the set pressure of 2.37 kg/cm²g.
The final depressurisation to tail gas drum pressure is carried out counter-currently to the
adsorption flow direction. Final pressure is about 0.55 kg/cm²g. Gas flows out of the
bottom of adsorber V-31 through valve 314, which is in a throttled position during dump.
The opening of valve 314 will be adjusted to control the rate of depressurisation such that
dump is completed in the available dump time as a function of the capacity of the unit. A
more detailed explanation is given in section 3.5.
3.3.2.6 Purge
At 0.55 kg/cm²g, the lowest pressure in the cycle, adsorber V-31 is purged, counter-
currently to adsorption flow direction, with high purity streams from different adsorbers on
providing purge.
Gas for purging adsorber V-31 will be supplied by adsorbers in the following sequence:
first by adsorber V-33, then by V-34 and V-35 and finally by V-36. The purge gas enters
adsorber V-31 through valve 313 (which is 100% open), de-sorbs the impurities from the
adsorbent and leaves for the tail gas drums through valve 314 (100% open). The latter is
also fully open during purge to maintain low pressure in the adsorber. The time is the
same as for approximately three and a half subcycles (approximately 106 seconds at full
capacity). The purge flow and hence time are capacity controlled as the opening of the
valves of the adsorbers providing purge (333, 343, 353 and 363 resp.) is a function of
capacity (see section 3.5.).
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 23 of 80
By : T. Cnop
3.3.2.7 Repressurisation
Before an adsorber can be brought back in the adsorption step after it has been
regenerated, it has to be pressurised to the feed pressure.
Adsorber V-31 is initially repressurised using hydrogen gas from pressure equalisations:
First from adsorber V-37 during equalisation 3 via valves 376 and 316;
there from adsorber V-38 during equalisation 2 via valves 386, 325, 315 and 316
finally from adsorber V-39 during equalisation 1 via valves 396, 335, 315 and 316.
During equalisation 1 adsorber V-31 receives also, through valve 311 in throttled position,
a continuous small slip stream of feed gas from the feed line.
At the end of equalisation 1 (both V-39 and V-31 reached 15.84 kg/cm²g) valve 315 closes
and repressurisation to adsorption pressure continues with feed gas taken from the feed
line via valve 311 in throttled position. Repressurisation time varies with the cycle time as
explained in section 3.5. The opening of valve 311 is controlled such that adsorber V-31
reaches the adsorption pressure at the end of the subcycle. As soon as the adsorption
pressure is reached, adsorber V-31 is again switched to adsorption.
The fact that, both during equalisation 1 and during the repressurisation following
equalisation 1, a constant slipstream of feed is taken for repressurisation purposes,
ensures a smooth flow of product to downstream users.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 24 of 80
By : T. Cnop
3.4 SWITCHOVER
In order to guarantee the continuity of the hydrogen production during maintenance or in case
of an equipment failure, two switchover levels are provided away from the main mode of
operation, i.e. 10-bed and 8-bed mode. The control system will automatically switch to a lower
level of operation in case of an equipment failure (valve, adsorber pressure transmitter) taking
out the adsorber with which the failing equipment is associated and the adsorber to which it is
paired. The operator can also manually switch to a lower level of operation when (preventive)
equipment maintenance is required.
When the unit is operating in 8-bed mode and a new (third) equipment failure occurs, the unit
will automatically go in shut down (See §6.2).
In case of switchover from 12-bed to 10-bed mode, one pair of adsorbers is taken out of
operation (adsorbers are grouped in 6 pairs of 2 adsorbers i.e. V-31 & V-37, V-32 & V-38, V-
33 & V-39, V-34 & V-40, V-35 & V-41 and V-36 & V-42). In 10-bed mode, the adsorbers are
called A to J, depending on which adsorbers are taken out of operation, as shown on the
table of the Pressure Sequence Chart B-H6265-003, sheet 2 and Valve Sequence Chart B-
H6265-004, sheet 2. In every adsorber pair, one adsorber is always at high pressure while
the other is at low pressure. Taking both adsorbers out whenever a switchover is desired
guarantees minimal fluctuations, both in the product and in the tail gas.
The cycle is very much similar to the 12-bed cycle, the main difference being that only two
adsorbers are in the adsorption step at the same time.
The approximate final pressures of the various steps are presented in table 3.2.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 25 of 80
By : T. Cnop
In case of switchover from 10-bed to 8-bed mode, another adsorber pair is taken out of the
cycle. In 8-bed operation the adsorbers are called S to Z, depending on which adsorber is
taken out of operation as shown on the table on pressure sequence chart B-H6265-003
sheet 3 and valve sequence chart B-H6265-004 sheet 3.
The cycle differs only slightly from the 10-bed cycle. The main difference is that there are only
2 equalisations;
The approximate final pressures of the various steps are presented in table 3.2.
TABLE 3.2
step 1 11 12 10
step 2 3 2 1
step 3 16 16 19
#
Step duration at 100% capacity (design conditions)
repr 6.88
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 26 of 80
By : T. Cnop
The control of the PSA process is based on automatic capacity control. As such the PSA unit
will automatically operate at different capacities (different feed flows) at optimum recovery
without the need for operator intervention. The subcycle time is automatically adjusted in
function of the capacity signal from FT-3001 in order to maintain the hydrogen recovery over
a wide feed flow range.
An adsorber can adsorb a fixed quantity of impurities and therefore purify a fixed quantity of
feed gas during adsorption. As a consequence the PSA unit will operate at short cycle times
at high capacity, while at low capacity, the unit will operate at long cycle times.
The control of the cycle time is done according to the following procedure: Over one subcycle
(which is the time interval between two consecutive adsorbers coming in adsorption) the
signal from FT-3001 is averaged. At the start of the next subcycle, a new subcycle time is
calculated INVERSELY PROPORTIONAL to the average capacity signal from the previous
subcycle.
There are two modes of operation, i.e. AUTO time mode (see 3.5.1) and MANUAL time mode
(see 3.5.2).
The cycle time adjustment is based on the capacity signal (FT-3001). This is the time mode
to be selected during normal operation of the unit. To accommodate for deviations from
design conditions, the operator can adjust KF to change the programmed subcycle time while
maintaining the capacity dependence.
In AUTO mode, the programmed subcycle time is adjusted in line with the capacity factor as
follows:
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 27 of 80
By : T. Cnop
1000 30 * 167620
TIME = * = 44s
1000 114286
The default design value for KF is 1000. If hydrogen purity specification is not met (eg.
because the feed quality is worse than design) the KF should be lowered (eg. to 950). The
cycle time will be shorter, resulting in a higher product purity but a lower hydrogen recovery.
In case the operator is not aware of deviations of the design, there is only one criterion: the
hydrogen purity. When there is CO breakthrough in the product (whatever the cause is) the
operator should reduce the KF factor accordingly because the adsorber stays too long in
adsorption since there is a breakthrough of impurities. Changes in the KF factor are in fact
only justified by changes in hydrogen purity
The AUTO subcycle time is at all time copied into the MANUAL subcycle time in order to
ensure bumpless transfer from AUTO to MANUAL TIME mode.
The operator has the possibility to switch the subcycle time to a constant (hence independent
of capacity) subcycle time. One has to be careful doing this in order to avoid overloading the
adsorbent which will result in impure product. This mode should NOT be used unless FT-
3001 (feed flow transmitter) is not available (defective or maintenance). When selecting this
mode, the unit (and especially the product purity) should be monitored closely.
The logic will switch automatically to MANUAL TIME mode when FT-3001 gives a BADPV
alarm. Whenever the unit switches from AUTO to MANUAL TIME mode, an alarm will be
generated to warn the operator.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 28 of 80
By : T. Cnop
In order to reduce internal and external flow fluctuations, repressurisation, dump and provide
purge times are varied with the subcycle time and thus with the unit capacity. The parameters
to calculate the time available for repressurisation and depressurisation (provide purge 2 and
dump) as well as the parameters fixing the pressure profiles for repressurisation, dump and
providing purge are set by the UOP NV start-up engineer. The loops can only be in CAS
(remote setpoint) or MAN (selection is done by control logic). Operator interventions on these
loops are NOT possible.
The objective of repressurisation control is to minimise product flow fluctuations. The purpose
of dump and purge control is to minimise purge gas flow variations into the tail gas drum in
order to limit purge gas pressure variations.
a) During step 1, loop 1 is in MAN and the valve acted upon receives a manual output in
function of capacity (directing a slipstream of the feed in the repressurising adsorber
during EQ1).
- The setpoint is calculated in function of the available repressurisation time. The starting
point is the pressure of the repressurising adsorber sampled at the end of equalisation1
- The setpoint is automatically calculated (in function of the running time) and directed to
the adsorption pressure by the end of repressurisation. The adsorption pressure being
the output of the PT of the adsorber in its first adsorption subcycle. The time in which
the setpoint moves to the desired end pressure is capacity dependent (subcycle time
less step 1 time).
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 29 of 80
By : T. Cnop
a) During the first few seconds of dump, loop 2 is in MAN in order to make sure that the
correct start opening of dump control is marked.
b) During steps 1, 2, 3 and 1, 2 of the next subcycle loop 2 is in CAS controlling the
depressurisation to tail gas drum pressure.
- The pressure at the start of dump is sampled (start step 1 – end of provide purge) and
serves as starting setpoint.
The setpoint is then directed towards the tail gas drum pressure according to a specific
pressure profile (set by the start-up engineer) within a time which is capacity dependent
(function of subcycle time).
- The output signal goes to valve UCV314…424 of the dumping adsorber in dump.
There are two provide purge phases, one of which is controlled by a loop (loop 3).
Provide purge is started during equalisation 3 (last equalisation which takes place during
steps 1 and 2). During this phase, the valve of the adsorber providing purge (UCV313
…423) receives a manual output. Valves UCV313…423 of the adsorbers receiving purge
during equalisation 3 are 100% open. Valves UCV314…424 of the adsorbers receiving
purge are 100% open.
During step 3, provide purge is continued under control of loop 3 which is in CAS.
- The setpoint is directed from the starting setpoint (pressure of the adsorber sampled at
the start of this phase) to the desired end pressure according to a selected pressure
profile within a time which is capacity-dependent (function of subcycle time). The profile
is set so that purge gas flow to the tail gas drum is steady.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 30 of 80
By : T. Cnop
- The output signal goes to valve UCV313…423 of the adsorber providing purge. The
valves UCV313…423 of adsorbers receiving purge are 100% open. Also valves
UCV314…424 of adsorbers receiving purge are 100% open.
The initial valve opening of the control loops to valves UCV311…421 (repressurisation during
equalisation 1), valves UCV313…423 (provide purge) and valves UCV314…424 (dump) are
capacity dependent.
These signals are the average of the output to the respective loops calculated during the first
approx. 7 seconds of each control session. In this way, calibration errors will not influence the
process control (within limits).
The tail gas to the steam reformer burners is controlled by FY-3204. This controller can be in
MAN, AUTO (local setpoint) or CAS (remote setpoint). Purpose is to keep the flow of tail gas
to the burners as constant as possible in order to keep the heat input to the burners constant.
The flow will be kept constant in function of the capacity and hence in function of the feed
flow to the PSA unit.
1) MANUAL
2) AUTO
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 31 of 80
By : T. Cnop
3) CAS
- A remote setpoint is calculated for FY-3204 by the PSA control logic (PLC) in function of
(i) the difference between PW (sample of tail gas drum pressure taken at the start of
each subcycle) and SPW (operator setpoint for the tail gas drum pressure).
2) When one switches from MAN to AUTO, the last process variable will become the first
local setpoint
3) When switching from AUTO to CAS, the last local setpoint will become the first remote
setpoint
4) When passing from CAS to AUTO, the last remote setpoint becomes the first local
setpoint
5) When passing from CAS or AUTO to MAN, the last opening of FV-3204 will be kept as
output to the valve until changed by the operator
The principle behind the calculation of the remote setpoint is the following:
(i) If PW > SPW, the remote setpoint will increase; when PW < SPW, the remote setpoint
will decrease.
(ii) When the subcycle time is long (low capacity), the expected purge gas flow will be low
and the remote setpoint should be lower than when the subcycle time is short (high
capacity) and expected flow will be higher. This desired capacity dependence is
implemented by including TSC (function of capacity) in the formula to calculate the
remote setpoint.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 32 of 80
By : T. Cnop
This is a standard pressure control loop with a local setpoint (operator input in AUTO-mode)
controlling valve PV-3105 to flare.
The setpoint is set a little higher than the normal tail gas drum pressure (e.g. 0.6 kg/cm²g) in
order to ensure that the valve to flare will remain closed during normal operation. It will only
open in case of small disturbances (e.g. upon switchover from 12- to 10-bed and from 10- to
8-bed mode).
1) MAN mode
2) AUTO mode
Transition between the two modes occurs bumpless. During normal operation, PY-3105
should be in AUTO.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 33 of 80
By : T. Cnop
The automatic sequencing of the PSA unit is controlled. The DCS sends the sequencing
signals to operate the process control valves. The process will automatically run through the
various steps (checking the end of step conditions) without operator interventions.
Below is a description of the 12-bed sequence. Only open valves are mentioned in the
description. Description is valid for subcycle 1. In other subcycles, description will be similar
(tag numbers will have to be changed).
Step 1 covers the first equalisation and takes approximately 11 seconds. Step 3 covers
equalisation 2. Step 3 is capacity-dependent. Steps 1 and 2 combined cover the third
equalisation and take approximately 14 seconds. During step 1, 2 and 3 Provide Purge takes
place which continues until at the end of step 3 the required end pressure is reached. Dump
starts in step 1 and continues until the end of step 2 of the next subcycle.
2. The adsorber in repressurisation reaches at least the adsorption pressure less 2 kg/cm²
(reading from PT-311).
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 34 of 80
By : T. Cnop
Valves
UCV406, 326 Valves ramp open to perform EQ 1 between V-40 (providing) and
V-32 (receiving).
XV345, 325 Valves 100% open to perform EQ 1 between V-40 (providing) and
V-32 (receiving). XV345 delayed open to assure that XV342 is
closed first.
UCV396, 336 Valves ramp open to perform EQ 3 between V-39 (providing) and
V-33 (receiving). UCV336 delayed open to assure that XV335 is
closed first.
UCV384, 374 Adsorber V-38 and V-37 depressurise to tail gas drum pressure;
both valves receive the output from loop 2 (dump). Valve 384
delayed open to assure UCV334 is closed first (to prevent too
much tail gas).
UCV363, 353, 343 Adsorbers V-36, V-35 and V-34 receiving purge; valves 100%
UCV364, 354, 344 open.
UCV321 Valve receives the manual output from loop 1 to repressurise V-32
with a slip stream from the feed.
Loops
Loop 2 (dump) is in CAS;
Loop 1 (repress.) and loop 3 (provide purge) are in MANUAL.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 35 of 80
By : T. Cnop
Valves
UCV326 Valve goes to 100% opening as to prepare for the adsorption step
in the next subcycle. No flow passes through as UCV406, XV322
and XV325 are closed.
XV345 Valves stays 100% open in the isolation step between EQ1 and
EQ2. No flow passes through as UCV346 and UCV406 are closed.
UCV384, 374 Adsorber V-38 and V-37 depressurise to tail gas drum pressure;
both valves receive the output from loop 2 (dump).
UCV363, 353, 343 Adsorbers V-36, V-35 and V-34 receiving purge; valves 100%
UCV364, 354, 344 open.
UCV321 Valve receives the auto output from loop 1 to repressurise V-32
with a slip stream from the feed.
Loops
Loop 1 (repress.) and loop 2 (dump) are in CAS;
Loop 3 (provide purge) is in MANUAL.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 36 of 80
By : T. Cnop
Valves
UCV326 Valves keeps 100% opening as to prepare for the adsorption step
in the next subcycle. No flow passes through.
UCV406, 336 Valves ramp open to perform EQ 2 between V-40 (providing) and
V-33 (receiving).
XV345, 335 Valves 100% open to perform EQ 2 between V-40 (providing) and
V-33 (receiving). XV335 delayed open to assure UCV396 is closed
UCV393 Adsorber V-39 providing purge to V-34,V-35, V-36 and V-37; valve
receives auto output from loop 3 (provide purge).
UCV373, 363, 353, 343 Adsorbers V-37, V-36, V-35 and V-34 receiving purge; valves
UCV374, 364, 354, 344 100% open
UCV321 Valve receives the auto output from loop 1 to repressurise V-32
with a slip stream from the feed.
Loops
Loop 1 (repress.), loop 2 (dump) and loop 3 (provide purge) are in
CAS.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 37 of 80
By : T. Cnop
4.2 AUTOMATIC SEQUENCING OF THE POLYBED® PSA UNIT WITH 10- OR 8-BEDS
Reference is made to the Valve Sequence Chart B-H6265-004, sheets 2 and 3. From these
drawings the sequencing in 10-bed and 8-bed can easily be deduced.
AUTO MANUAL In AUTO TIME mode, the logic will set the MANUAL time equal to
the AUTO time. By operator intervention, the logic can switch to MANUAL TIME mode. At
that moment, the TIME mode indication will switch from AUTO to MAN. From the start of the
NEXT subcycle, the logic will use the MANUAL time as subcycle time.
We urge very strongly to operate the unit in AUTO TIME mode. As such, the capacity-
dependence of the subcycle time is ensured. One has to be extremely careful using
MANUAL TIME (preferably to be used ONLY when FT-3001 fails or is not available
(calibration)). See § 3.5.2
KF changes are limited to steps of 50. Manual time changes are limited to steps of 10s.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 38 of 80
By : T. Cnop
1) Valves UCV311...421 can only be opened 100% when the pressure of the
relevant adsorber is higher than PT-301 – 2 kg/cm².
2) When the pressure of the relevant adsorber is lower than PT-301 – 2 kg/cm²,
the maximal opening of the valves UCV311...421 is limited to a value pre-set by
the UOP NV start-up engineer.
3) At any time a feed valve (UCV311...421) can only open when the purge
valve (UCV314...424) of the same adsorber is closed. Likewise, a purge
(or dump) valve can only open when the corresponding feed valve is
closed.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 39 of 80
By : T. Cnop
The logic controlling the PSA process sequence is programmed on a redundant MODICON
QUANTUM server PLC system. The operator control screens are available on a DCS
system. Data between PLC and DCS are exchanged over a MODBUS PLUS connection.
This section describes a typical PSA control system. In a later stage, this section will be
rewritten to reflect the real situation on site.
This display shows a general overview of the POLYBED® PSA unit. Via this display the
operator is able to perform all interventions.
The display also shows any alarm messages generated, except when they are standard
messages (such as high pressure, low pressure).
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 41 of 80
By : T. Cnop
This data logging shows the most important computer generated variables of the last
complete cycle (meaning last 12 subcycles in 12-bed, last 10 subcycles in 10-bed and the last
8 subcycles in 8-bed).
The data logging is used for diagnostic purposes by the supervisor or engineer.
- Actual subcycle time and pre-set subcycle time expressed in seconds. (The actual
subcycle time is the really required time before switching to the next subcycle.)
- FT-3001 Feed flow averaged over each subcycle, Nm³/hr
- PT-3105 Tail gas drum pressure averaged over each subcycle, kg/cm²g
- Actual and pre-set time of the depressurisation to purge
- End pressures of adsorbers performing equalisation 1, 2 and 3 (both receiving and
providing), kg/cm²g
The updating of the data-logging table takes place at the start of every subcycle.
In 10-bed, resp. 8-bed operation, the rows of subcycle 11 and 12, resp. 9, 10, 11 and 12 are
not updated.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 42 of 80
By : T. Cnop
e) Select AUTO TIME or MANUAL TIME mode; adjust the cycle time via the capacity
factor KF (AUTO TIME mode) or via the introduction of a new manual time (MANUAL
TIME mode); maximal step changes on KF of 50 and on manual time of 10s.
i) Switching FY-3204 to CAS (remote setpoint), to AUTO (local set-point) and to MAN.
Adjustment of local setpoint in AUTO and the output signal in MAN.
j) Switching PY-3105 to AUTO (local setpoint) and to MAN; adjusting local setpoint in
AUTO and output signal in MAN.
k) Switch the unit to 10-bed mode and to 8-bed mode and vice versa by taking OUT/IN a
pair of adsorbers.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 43 of 80
By : T. Cnop
6. PROCESS SAFEGUARDS
The alarm messages listed below have been programmed to warn the operator when
abnormal process conditions are met. The messages will be listed in the ALARM SUMMARY
and printed on the ALARM PRINTER.
When the output of the subcycle timer exceeds the value of 1.2 times the capacity-dependent
AUTO time, the alarm LONG ADSORPTION TIME is generated.
When the pressure change (up or down) of one of the two equalising adsorbers during the
first 7 seconds of Equalisation 1, 2 or 3 deviates from the pressure change during the
equalisation during the previous subcycle, the alarm DEVIATION EQUALISATION 1, 2 or 3 is
generated.
When the deviation between setpoint and process variable for one of the internal control
loops (Repressurisation, Dump, Provide purge) exceeds the alarm limit, the alarm
REPRESSURISATION DEVIATION, DUMP DEVIATION or PURGE DEVIATION is
generated.
When the pressure change (up or down) of the isolated vessel (between EQ 1 and EQ 2)
exceeds the alarm limit, the ISOLATION DEVIATION alarm is generated.
When the actual repressurisation time exceeds the pre-set repressurisation time, the LONG
REPRESSURISATION TIME alarm is generated.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 44 of 80
By : T. Cnop
This alarm is generated when the adsorption pressure drops below the low alarm limit.
This alarm is generated when the process control is switched from the primary to the
secondary PLC.
When the redundant PLC is no longer on stand-by, the alarm NO STAND-BY PLC is
generated.
When the unit switches from 12-bed to 10-bed mode or from 10-bed to 8-bed mode, the
alarm PSA SWITCHOVER is generated.
This alarm is generated when the tail gas drum pressure increases above the high alarm
limit.
This alarm is generated when the tail gas drum pressure drops below the low alarm limit.
When the operator attempts to start the PSA unit and the adsorber pressures are not in
agreement with the start conditions, the alarm VERIFY ADSORBER PRESSURES will be
generated. The same alarm is generated when in case of switchback, the pressure of the
adsorber pair to be brought into operation is not in agreement with the entry point conditions.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 45 of 80
By : T. Cnop
When an open or close command is given to a valve, an individual valve timer starts timing.
When the valve timer reaches its pre-set value and the signal from the proximity switch is not
found to be in agreement with the output signal to the valve, the alarm VALVE FAILURE XV...
or UCV… is generated. The failing valve is identified in the alarm message. For an analogue
valve (UCV…) the valve timer starts only when the analogue output signal to the particular
valve exceeds a certain minimum valve opening (set at 20%).
When the output of one of the transmitters drops below 3mA, the alarm FAILURE PT-
311…421, PT-301, PDT-303, PT-305, FT-3001 will be generated.
When one of the adsorber pressure transmitters fails, the vessel with which the failing
transmitter is associated, is taken out of operation together with its associate (switchover to
10-bed or 8-bed). When the unit was already in 8-bed mode, the PSA unit will shut down.
When FT-3001 fails, the logic switches from AUTO TIME mode to MANUAL TIME mode.
This alarm is generated when the PSA unit shuts down for whatever reason.
This alarm is generated when the PSA unit shuts down due to a remote shutdown signal.
When the logic or the operator switches the time mode from AUTO to MANUAL, the alarm
MANUAL TIME MODE SELECTED alarm will be generated.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 46 of 80
By : T. Cnop
When the instrument air pressure drops below 4.0 kg/cm²g, the LOW INSTRUMENT AIR
PRESSURE ALARM is generated.
When the output of the subcycle timer exceeds the value of 2.0 times the capacity-dependent
AUTO time, the alarm LONG LONG ADSORPTION TIME is generated. The unit will
shutdown.
When the instrument air pressure drops below 3,5 kg/cm²g, the LOW LOW INSTRUMENT
AIR PRESSURE is generated and the unit will shut down.
When the OVERRIDE mode is selected, the OVERRIDE alarm will come on every 10
minutes.
When the INHIBIT mode is selected, the INHIBIT alarm will come on every 10 minutes.
This alarm is generated when differential pressure over the product filter(s) increases above
the high alarm limit.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 47 of 80
By : T. Cnop
The unit shuts down and all valves go into closed position and all timers and time related
variables freeze in their last position under one of the following conditions:
- The alarm Low Low Instrument Air Pressure is ON during more than 5 seconds.
- The alarm Long Long Adsorption Time is ON and the unit is not in OVERRIDE mode.
- When the unit is in 8-bed mode and one of the transmitters of one of the adsorbers still in
operation drops below 3mA.
When the OVERRIDE mode is selected, the LONG LONG ADSORPTION TIME stop is
bypassed; the alarm message however will continue to be generated.
During shutdown the step number and subcycle number are frozen.
Remark:
A valve failure as described in sections 10.1.3.1, 10.1.3.2 or 10.1.3.3 will result in a
switchover from 12 to 10-bed or 10 to 8-bed operation. When operating in 8-bed mode, such
a valve failure will however not result in an automatic shutdown immediately. Nevertheless
the malfunction will in time cause the adsorber to create a long long adsorption time after
which the unit will eventually go in shutdown. It is therefor important that the OVERRIDE
mode is not selected during normal operation.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 48 of 80
By : T. Cnop
7. START-UP
7.1 Before final connections (before first start-up) are made, it is important to verify that no dirt
remains in or can enter the unit. All lines have to be blown out so that all particles and
liquids are removed. It is important that no dirt enters the unit.
Before start-up of the unit, one has to make sure that the feed flow line has been blown
out so that all particles and liquids are removed. Before the instrument air-lines are
connected, they should be blown out, so that all dirt is removed to atmosphere.
Before hydrogen is allowed to the unit, it shall be purged with pure dry nitrogen. Dry
nitrogen is necessary to prevent an accumulation of water on the adsorbent during purge.
(Dew point MINUS 100 C). The oxygen concentration after purge has to be below 0.5
vol%. Nitrogen purge should always be done from TOP to BOTTOM.
7.2 Normal position of the process valves and control loops for nitrogen purge
- Close all valves through which gas can be vented to the atmosphere (sample connections,
vents, drains).
- Valves on instrument airlines should be open (one instrument air filter in use, isolation
valves of second instrument air filter closed).
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 49 of 80
By : T. Cnop
At Start-up:
Before crude hydrogen feed can be admitted to the POLYBED unit, all oxygen must be
purged from the unit with pure, dry nitrogen. The nitrogen purge pressure should be low;
however, upward-flow through the adsorber should be avoided. Nitrogen has to be tied into
the product line – purge is ALWAYS performed from TOP to BOTTOM.
Starting with adsorber V-31, open the N2 inlet valve. Valve UCV314 and a valve in the purge
gas line have to be opened in order to send the nitrogen-oxygen mixture to the atmosphere.
One has to make sure that all lines and headers are purged with nitrogen. This can be done
by temporarily opening a vent valve in the header lines together with valves XV312, UCV313,
XV315 and UCV316. Check the O2 concentration at these vents (< 0.5 vol%)
When the oxygen concentration is consistently less than 0.5 vol%, the nitrogen purge can be
stopped. A sample has to be taken of the bottom of every adsorber (in this example V-31).
Proceed with the other adsorbers V-32 through V-42 according to the same procedure. The
header lines do not need to be purged anymore.
Make sure that the tail gas drum is also purged with nitrogen before taking the unit in
operation.
If the POLYBED® unit is not going on stream with hydrogen feed right after nitrogen purge,
keep a positive nitrogen pressure (about 1 kg/cm²g) on the unit. This ensures that no oxygen
will enter the adsorbers during a cool night. This can be done by pressurising each vessel
after purge with nitrogen and closing UCV314…424.
IMPORTANT
Please note that one can only discharge a nitrogen-oxygen purge gas mixture to atmosphere.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 50 of 80
By : T. Cnop
At Shut-down:
After operating the PSA unit, the nitrogen purge has to be performed from TOP to BOTTOM
and DRY nitrogen has to be tied into the product line. This is important to push the front of
impurities downwards and to avoid irreversible deterioration of the adsorbent.
The N2-purge has to be continued till the H2-content of all the adsorber bottoms is below
0.5%vol and the CO-content is below the level of local health regulations.
The N2 purge gas mixture needs to be discharged to flare via the safety valve bypass valves.
The POLYBED Unit skid assembly has been leak-tested, prior to shipment. Before start-up,
the unit should be pressure tested as follows:
7.5 Start-up
The unit can be started by requesting start-up via the operator display and by setting the
start flag high. The unit then restarts in the same mode (12-, 10-, or 8-bed) as shown on
the display (last mode before shutdown) and in the subcycle and step number shown on
the display.
The operator can decide to restart in another subcycle by changing the subcycle number
on the display, while the unit is in shutdown. When the subcycle number is changed during
shutdown, the unit will switch to start of STEP 1 of the selected subcycle, the sequence
timer resets to zero and the subcycle time is calculated again.
At a restart, the unit will automatically switch to SWITCHOVER INHIBIT and OVERRIDE
mode.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 51 of 80
By : T. Cnop
On no occasion can the PSA-unit restart without operator intervention. This means that
e.g., when the unit is shutdown due to low instrument air pressure and the pressure is
restored later, the unit does not restart automatically, even when the operator had
initialised the restart before the deactivation of the shutdown. The last action required to
restart the PSA-unit is an operator action. For starting, operator should follow procedure
7.8.
After a computer system reload the program is in subcycle 1 step 1 and all timer outputs are
zero. The mode is MAN TIME and the unit is in 12-bed program and in SWITCHOVER
INHIBIT and OVERRIDE mode.
At a restart, the operator should always restart in the same subcycle as when the unit was
shutdown.
The change of subcycle number is intended for use after a cold start, since the subcycle
number then equals 1.
As soon as the operator requests START, the logic checks the following pressures:
1. The pressure of the adsorbers, coming in adsorption, should all be higher than "PT-301
- 2 kg/cm²”
2. The pressure of the adsorbers, coming on purge, should all be lower than 2 kg/cm²g.
3. The pressure of the adsorber coming on dump should be lower than Pdmax.
If any of the above conditions is not met, the unit will refuse to start and VERIFY
PRESSURES alarm will be generated.
The operator has then to take the necessary action to correct the pressure and ought to repeat
his attempt.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 52 of 80
By : T. Cnop
Crude hydrogen feed can only be allowed to the POLYBED unit, when the unit is free from
oxygen (concentration below 0.5 vol. % oxygen) – see §7.3.
The first purge gas will contain much nitrogen and will therefore not be suitable to be burned.
7.8.1 Make sure the feed gas header is at the same pressure as the adsorber to come into
adsorption (see §7.1.5.)
At the very first start-up the feed gas header pressure will be zero, since the adsorber
pressures are also zero. The unit has to be isolated on the feed side (hand isolation valve to
be closed).
7.8.2 The main product isolation valve should be closed, in order to arrive quickly at in-
specification product. It means that all the product gas, coming out of the adsorbers, is
used for repressurisation.
7.8.3 Make sure the feed, product and purge gas hand valves are closed. Set PY-3105 (purge
gas to flare) in AUTO with SP = 0.33 kg/cm²g. Select AUTO time mode with a low load
factor (KF = 800).
- Select subcycle 1.
- Open the feed valves UCV311…421 of all adsorbers and the product valve of adsorber V-
31 (XV 312 and UCV316).
- Slowly open the feed hand valve – pressure should not rise faster than 1 kg/cm² /min.
- As soon as a particular adsorber has reached its desired pressure (see Pressure
Sequence Chart), close its feed valve.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 53 of 80
By : T. Cnop
WARNING
For the same reason, no two purge valves (UCV314-424) of adsorbers, having a
difference in pressure of more than 2 kg/cm², should be opened simultaneously
If adsorbers show difference in pressure, first equalise pressures via the valves UCV313
to UCV423 in throttled position (<50%).
7.8.7 Immediately after start-up open the main feed valve gradually (if there are still pressure
differences between the adsorbers coming into adsorption and the feed system, open
the feed valve slowly).
7.8.8 It is to be noted that at start-up or after nitrogen purge, the equalisation steps will take
longer as a consequence of higher molecular weight and the equalisations will not be
fully finished. The equalisations will be finished properly as the hydrogen purity in the
product increases. As soon as the required adsorption pressure has been reached, take
out OVERRIDE mode.
7.8.9 The CO-content in the product should be checked. If as the CO-content is within
specification, the cycle time should be slowly lengthened (increase KF) and at the same
time product can be taken (open the product block valve).
7.8.10 Control the normal operation of the process valves during the initial sequencing of the
unit. Check the adsorber pressure profiles.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 54 of 80
By : T. Cnop
7.8.11 As soon as there are no more alarm messages, and the unit is in AUTO, the
SWITCHOVER INHIBIT mode can be taken out.
- Open FV-3204 slowly (FY-3204=MAN) until the valve to flare is completely closed.
- Adjust the setpoint of pressure control to flare PY-3105 to approximately 0.6 kg/cm²g.
The valve should remain closed during normal operation.
- Adjust the setpoint of FY-3204 until the minimum value of PT-3105 during a subcycle
equals SPW.
- Wait until the tail gas drum pressure PT-3105 has stabilised during a few subcycles to
be able to prepare a bumpless switch involving the control algorithm of the tail gas drum
pressure.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 55 of 80
By : T. Cnop
To maximise the efficiency of the unit, the following checks and adjustments should be made:
8.1.1.1 During the adsorption step the normal operating pressure of ca. 21.2 kg/cm²g should be
maintained in order to achieve the product purity. This pressure should be monitored for all
adsorbers.
8.1.1.2 Optimum performance is obtained when the purge gas pressure is at a minimum (design
value should be maintained in order to guarantee good unit performance). Operating at a
higher purge gas pressure will result in reduced capacity, reduced purity and recovery.
8.1.1.3 Optimum performance is obtained when both product filters are used in parallel
(minimal pressure drop). Operating the PSA unit with only one product filter on-line
should be limited to periods of maintenance.
An adsorber can adsorb a fixed amount of impurities and hence a fixed amount of feed flow
can be treated during one adsorption-regeneration cycle. When the subcycle time is
increased (increased KF) and feed flow is maintained, impurities will break through and
appear in the product and the product purity will decrease.
When the subcycle time is decreased (reduced KF), product purity will increase but hydrogen
recovery will suffer. The subcycle time has to be set to maximise product make which is still
conform to product specifications (i.e. H2 min 99.9 vol%). A too long subcycle time leads to
bad product purity, a too short subcycle time reduces the efficiency of the unit.
Every change of the subcycle time should be done with care, because a change in product
purity will only be seen with a certain time lag. If one adsorber has been too long on
adsorption step, the negative effect on product purity will appear several subcycles later when
the adsorber, which has received low quality purge gas, comes on the adsorption step.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 56 of 80
By : T. Cnop
Increasing the subcycle time results in a higher hydrogen recovery and a lower product purity.
Reducing the subcycle time does the opposite. If product purity is not acceptable and the
adsorption time is at its minimum, the only adjustment left is a REDUCTION OF THE FEED
RATE to the PSA unit.
When transmitter FT-3001 (feed flow) fails, the unit automatically switches to MAN mode.
During calibration of FT-3001, the operator ought to keep the unit in MAN mode and he ought
to keep the feed flow constant.
During calibration of PT-3105 (flow to burners) the operator needs to keep FY-3204 in AUTO
mode and maintain the feed flow and the subcycle time constant as much as possible.
When FT-3204 fails, FY-3204 switches to MAN while maintaining the last output.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 57 of 80
By : T. Cnop
The unit normally operates in automatic mode (AUTO). When the feed flow rate decreases
the capacity signal is reduced and hence the unit will run automatically on a longer subcycle
time. A maximal subcycle time about equal to the subcycle time at 30% capacity is
incorporated in the control.
If the feed flow decreases below 50286 Nm³/h, the subcycle time does no longer increase
and the hydrogen recovery will gradually decrease. Recovery of the unit can be maintained
between 30 and 100% capacity.
The POLYBED unit is designed to purify a feed gas in accordance with feed gas
specifications as given in the process flow diagram. Abnormal process conditions as e.g. high
feed flow temperature, lower hydrogen feed flow concentration, the presence of impurities
with a higher molecular weight and entrained liquids can adversely affect POLYBED unit
performance. Feed composition should be monitored to assure one is aware of possible
changes.
Operation at high temperature will reduce the capacity of the adsorbents to adsorb impurities
and can result in impure product. Operation with high impurity concentration in feed can result
in adsorbent overload and result in low product quality. High molecular weight impurities or
entrained liquids will be very strongly adsorbed by the adsorbent and may not be de-sorbed
from the adsorbent during the regeneration step. These heavy impurities will accumulate on
the adsorbent and reduce its capacity.
During periods of abnormal process conditions, the unit should be operated at SHORTER
cycle time as described in the next paragraph or, if necessary, at REDUCED capacity.
If the product purity is low during or after operation at abnormal process conditions, the unit
has to be operated with shorter cycle (increased purge).
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 58 of 80
By : T. Cnop
The capacity factor (KF) has to be reduced to achieve an immediate reduction in cycle time.
When the unit reaches product purity again the capacity factor can be reset to its original
value and the subcycle time will readjust. If the product purity decreases again it may be
necessary to run the unit consistently with shorter cycle times. Shortening the cycle time will
result in lower hydrogen recovery.
A valve failure will manifest itself by deviations of the adsorber pressure profiles. The process
valve should be repaired.
The position of the process valves is consistently monitored by the logic and in case a valve
does not open or close when required a valve failure alarm will be generated.
At the same time, the pressure profile of the adsorbers is monitored. If simultaneously with
the valve failure a pressure profile error occurs (Loop deviation, Equalisation deviation,
Isolation deviation) the unit will switch automatically from 12-bed to 10-bed operation, or from
10-bed to 8-bed operation, taking out the adsorber where the valve error was detected. The
automatic switchover can be inhibited by switching to SWITCHOVER INHIBIT mode.
Guidelines:
Whenever the feed conditions are changed (in this case the feed temperature) the CO
content in the product should be intensively monitored. If the CO content in the product is
too high, the KF value has to be lowered. Reference is made to sections 3.5.1 and 8.2.2
Attention should also be paid to the water content. If feed at 55°C is saturated with water,
the corresponding dew point of the purge gas will increase considerably. Water can
accumulate in the tail gas drum which should be drained.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 59 of 80
By : T. Cnop
We strongly recommend operating the unit in AUTO time mode. As such the capacity
dependence of the subcycle time is ensured. One has to be extremely careful when
using MANUAL time (preferably to be used only during start-up and when FT-3001
failed or has to be calibrated). See also § 3.5.2.
8.4 TROUBLESHOOTING
During steady conditions, purity and recovery of hydrogen should be satisfactory. The
pressure and flow indication of feed, product and tail gas can show some slight fluctuations,
but the pattern should be the same during each subcycle. If a deviation from the regular
pattern occurs, one should define exactly when it occurs.
When all valves of an adsorber are closed, the adsorber pressure should remain constant. If
the adsorber pressure changes during isolation then this is caused by a leaking valve. From
time to time one should verify adsorber pressure during isolation stages for all adsorbers.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 60 of 80
By : T. Cnop
There are three primary parameters linked to PSA performance. In general, it is possible to
trade off one against the other. Capacity is the quantity of feed the unit can process at mini-
mum adsorption time and produce on-specification product.
H2-recovery is the percentage of hydrogen contained in the feed that is recovered in the pro-
duct. It is a measure of the efficiency of the unit.
Product purity is the concentration of impurities in the product. Measurement of capacity and
product purity is quite straightforward.
Measurement of hydrogen recovery can be done in several ways, but requires great care to
obtain an accurate number. Recovery can be based on flows or compositions. Much more
accurate recovery numbers are obtained by using the composition-based calculations than
the flow-based calculation, but this method requires more analytical effort. The composition-
based method does not require any flow measurements at all to determine hydrogen
recovery, and recovery can be calculated based on several different components, providing
much more confidence in the result.
Fprod * Yprod − H
R=
Ffeed * Yfeed − H
The composition-based method can be calculated based on each different component, “i”, as
follows:
Yfeed − i − Yw − i Yprod − H
R= *
Yprod − i − Yw − i Yfeed − H
Note that the last part in the equation always refers to hydrogen.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 61 of 80
By : T. Cnop
Where:
R = H2-recovery
F = volumetric flow rate
Y = mol fraction
-H = hydrogen
-i = component i
W= tail gas
R (based on CO):
R (based on H2):
We advise to DAILY sample and analyse (by chromatograph) the gas streams to/from the
PSA unit, i.e. feed, product and purge gas during the first weeks following the start-up
(e.g. first 4 weeks). We advise to continue sampling and analysing on a WEEKLY basis
thereafter. Please note that the sample of the purge gas stream should be taken
DOWNSTREAM the tail gas drum.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 62 of 80
By : T. Cnop
A PSA is made to produce only high purity hydrogen. This means that the H2-product
purity SHOULD ALWAYS BE > 99,5.
When upstream refinery has an upset, this normally means that the feed hydrogen
concentration is worse, the KF factor should immediately be reduced to a low value (KF =
800).
Never operate the unit with the OVERRIDE and (switchover) INHIBIT function
continuously ON. These functions must be deselected after maximum 1 complete cycle
after start-up or switchover.
Purging the vessels is ALWAYS FROM TOP TO BOTTOM. Use the separate N2-purge
connection valves in the overhead piping. The purge gas can leave the vessel through the
bypass of the safety valve or the purge/dump valve (valves No. 4) If purging is done in a
different way, this will lead to IRREVERSIBLE DAMAGE of the adsorbent.
ALWAYS operate the PSA in AUTO mode. This means that TSC (subcycle time) is
automatically calculated based on the feed flow. The MANUAL mode is only to be used
when the feed flow signal is not available. In that case, make sure that this manual time is
short enough, because there is the risk to overload and damage the adsorbent since the
feed flow is not known.
Frequently check the H2-purity in the product (AT LEAST once per shift). If concentration
is below specification: H2 ≤ 99,9% then reduce the KF factor.
PRESSURISATION of a vessel (before start-up) is always done through the feed valves
(valves No. 1). Therefore, the operator has to make sure that the pressure in the feed
header (downstream feed battery limit block valve) is within 2 kg/cm² of the pressure in the
vessel. Otherwise, a risk of lifting the beds exists. For pressurisation open the feed valve
SLOWLY.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 63 of 80
By : T. Cnop
After a shutdown, the PSA can stay max. 2 or 3 days under process conditions (with
pressure in the vessels). If the shutdown takes longer the unit must be purged efficiently
with nitrogen (from top to bottom) and the vessels must be kept at a slight overpressure
with N2 (1 to 2 kg/cm²g).
When the unit goes in shutdown and will be restarted within 2 or 3 days (so it is still under
process conditions) the PSA must be started in the step and subcycle where it went in
shutdown! So when for example the PSA goes down in step 2.3, the PSA must be
restarted also in step 2.3 (with the correct pressures).
When the PSA was purged and put under a N2 atmosphere after a shutdown, the PSA
can be restarted in any subcycle. The subcycle switch is only accessible in shutdown.
Make sure that the pressures in the vessels correspond to the particular start up step as
indicated on the pressure and valve sequence chart.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 64 of 80
By : T. Cnop
9. SHUTDOWN
9.1 GENERAL
The unit can be stopped at any moment. The cycle freezes in the last step and all process
valves close. When the unit is restarted the sequencing starts where the unit stopped,
provided the operator did not manually change the subcycle.
For the case where the unit is to be shut down for up to one day, no special purging is
necessary. When the pressure is to be maintained in the unit, close product and feed hand
valves.
If the unit is shut down for an extended period, the residual impurities in the adsorber
vessel will diffuse toward the top of the vessel. Therefore, at a subsequent restart of the
unit, it will produce hydrogen of considerably lower quality for several cycles.
1. Shutdown up to 3 days
Operation before and/or after shutdown with reduced cycle time (reduce KF to 800)
for 4 hours.
After 4 hours, stop the unit and close isolation valves. Note the step during which the
unit was stopped.
- Close the feed isolation valve and continue to run the unit in AUTO; gradually the
pressure in the unit will decrease.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 65 of 80
By : T. Cnop
- Purge the unit with nitrogen from TOP to BOTTOM (see §7.3). Purge gas should
be evacuated via the safety valve bypasses.
- Pressurise the adsorbers with nitrogen (≈ 1 kg/cm²g) and close isolation valves.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 66 of 80
By : T. Cnop
10.1 SWITCHOVER FROM 12-BED TO 10-BED OPERATION AND FROM 10-BED TO 8-BED
OPERATION
10.1.1 General
In order to increase the reliability of the unit, it can be operated with a reduced number of
beds.
Switchover from 12- to 10-bed and from 10- to 8-bed can be done either automatically or
manually. It is impossible to switch immediately from 12- to 8-bed and vice versa. Automatic
switchovers will take place in case of an equipment malfunction. The with equipment
malfunction associated adsorber, is taken out of operation together with its associate.
At the moment of switchover, the unit switches to the appropriate subcycle in 10 or 8-bed
operation, as shown in Table 10.1, resp. Table 10.2.
All valves of the adsorbers taken out of operation go into closed position and the adsorbers
out of operation will be indicated on the control display where the adsorbers taken out of
operation change colour.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 67 of 80
By : T. Cnop
2 1 1 2 2 2 2*
3 2* 2 2 3 3 3
4 3 3* 3 3 4 4
5 4 4 4* 4 4 5
6 5 5 5 5* 5 5
7 5 6 6 6 6* 6
8 6 6 7 7 7 7*
9 7* 7 7 8 8 8
10 8 8* 8 8 9 9
11 9 9 9* 9 9 10
12 10 10 10 10* 10 10
The subcycles marked with * are the subcycles from which the logic will switchback from
10-bed to 12-bed operation (these points are also marked on the Pressure Sequence Chart
(B-H6265-003, sheet 1).
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 68 of 80
By : T. Cnop
In 10-bed operation, the adsorbers are renumbered from A to J depending on which pair of
adsorbers is taken out of operation. The renumbering table can be found on B-H6265-003,
sheet 2 and B-H6265-004, sheet 2.
SUBCYCLE A B C D E
10-BED &F &G &H &I &J
OUT OUT OUT OUT OUT
# #
1 8 1 1* 1* 1
2 1# 1# 2 2* 2
3 2 2# 2# 3 3*
# #
4 3* 3 3 3 4
5 4 4* 4 4# 4#
6 4# 5 5* 5 5#
7 5# 5# 6 6* 6
8 6 6# 6# 7 7*
9 7* 7 7# 7# 8
10 8 8* 8 8# 8#
The subcycles marked with * are the subcycles from which the logic will switchback from 8- to
10-bed operation (these points are also marked on the Pressure Sequence Chart (B-H6265--
003, sheet 2).
Switchovers marked # can only take place at the start of the subcycle when the pressure of
the adsorber starting providing gas for equalisations is still high enough (adsorption-pressure
– 2 kg/cm²). Else switchover is postponed till start of the next subcycle.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 69 of 80
By : T. Cnop
The operator touches the target "IN SERVICE" on the appropriate adsorber to be taken
out of operation and switches to "OUT SERVICE". The switchover occurs immediately.
On the display the adsorber contour turns from one colour into another and the unit
continues to run in the new mode of operation.
If the manual switchover is not urgent, it is best to wait with the execution of the switchover
command until the preferred moment is reached. These preferred moments (exitpoints)
are the same as the actual entrypoints were the switchback occurs (the entrypoints are
indicated on B-H6265-003)
In 12-bed operation it’s best to wait until the pair to be taken out has one adsorber on
adsorption and the other adsorber on purge. Eg. if the pair 33/39 has to be taken out, this
is best done at the beginning of subcycle 5 or subcycle 11.
In 10-bed operation, it’s best to wait until the pair to be taken out comes in the third
equalisation step (receiving/providing). Eg. if the pair B/G has to be taken out, this is best
done at the beginning of subcycle 5 or subcycle 10.
10.1.3.1 Both alarms “Valve Failure” and “Equalisation 1, 2 or 3 deviation” are present. The faulty
valve determines which adsorber is taken out.
10.1.3.2 Both alarms "Valve Failure" and either “Loop deviation repressurisation”,” Loop deviation
dump” or “Loop deviation purge” are present. The faulty valve determines which adsorber is
taken out.
10.1.3.3 One of the feed valves UCV311…421 or product valves XV312…422 is in alarm status. The
faulty valve determines which adsorber is taken out.
10.1.3.4 The signal of one of the transmitters PT-311…421 of an adsorber in operation drops below
3mA. The adsorber with the faulty transmitter is taken out.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 70 of 80
By : T. Cnop
10.1.3.5 When the alarm “Long repressurisation time” comes in and unit is in step 3, the adsorber,
which is in the re-pressurization step, is taken out.
When the unit is in inhibit mode the switchovers described under 10.1.3.1. to 10.1.3.3. will not
take place.
At every restart and at every switchover to 10-bed or to 8-bed as well as at every switchback
from 8- to 10-bed or from 10- to 12-bed, the logic automatically selects “SWITCHOVER
INHIBIT” mode. The operator can also select this mode manually. Under normal operating
conditions, the “SWITCHOVER INHIBIT” should not be selected.
Switchback from 8- to 10-bed operation or from 10- to 12-bed operation can only be done
manually via the operator display.
The operator can at any time move the cursor to the adsorbers to be taken again into
operation. When touching the “IN” touch target and pushing “ENTER”, the computer checks
the pressure of the adsorbers to come into operation. If the pressures meet the conditions
stated below, the logic will accept the switchover request from the operator. The indication “IN
SERVICE” starts to flash, indicating that the logic has accepted the switchback and that the
adsorber pair is waiting to be put back in operation. At the start of the appropriate subcycle
(entrypoint), the unit switches from 8- to 10- or from 10- to 12-bed operation (see tables 10.1
to 10.2).
10.2.1 At switchback to 12-bed, taking back into operation an adsorber pair (eg V-31 & V-37) the
pressure of one adsorber should be at adsorption pressure while the other adsorber pressure
should be lower than 1 kg/cm²g. Both conditions should be fulfilled.
For switchback to 12-bed mode, there are two possible switchback moments (see table 10.1
or the entry points indicated on B-H6265-003 sheet 1). The control logic will select the correct
subcycle.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 71 of 80
By : T. Cnop
Eg. when executing a switchback request for adsorbers V31 & V37 during subcycle 5 (in
10-bed mode), the control logic will wait until the beginning of subcycle 7 (10-bed mode) to
switch to subcycle 9 of 12-bed operation. Adsorber V31 has to be prepared at purge pressure
and V37 at adsorption pressure.
10.2.2 For switchback to 10-bed taking back into operation an adsorber pair, the pressure of one
adsorber should be higher than 8.8 kg/cm²g while the other should be lower than 1 kg/cm²g.
There are two possible switchback subcycles (see table 10.2 or the entry points indicated on
B-H6265-003 sheet2)
10.2.3 When the unit arrives in the next appropriate subcycle in 8-bed, resp. 10-bed operation
(indicated with * on Table 10.1, resp. Table 10.2), the unit automatically switches to 10-bed
operation, resp. to 12-bed operation at the start of step 1, into the subcycle indicated on
Table 10.1, resp. Table 10.2, provided the pressure of the adsorbers coming into operation
are in agreement with the above pressure conditions.
10.2.4 If not all pressure conditions for switchback are fulfilled, the request will be refused. The
adsorber with the pressure not in agreement with the switchback conditions will be indicated
on screen. At this moment, the operator should check and adjust the pressure(s) of the
adsorber(s) he wants to bring back on line. After adjusting the pressures, he ought to repeat
his request.
10.2.5 After the operator has made a request to take an adsorber back into operation, and before
the actual switchback is executed, he can still cancel the request before the actual
switchback to 10- or 12-bed has taken place. Therefore, he pushes the OUT-sign of the
adsorber.
10.2.6 If after the operator’s request to switchback to 10-bed, or 12-bed, a new switchover takes
place (from 10- to 8-bed) or the unit shuts down for whatever reason, the request for
switchback is cancelled automatically. The indication that the adsorber is waiting to be put
into operation will disappear, and the operator has to repeat his request if he later decides to
bring the adsorber back in.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 72 of 80
By : T. Cnop
When switching from 10- to 12-bed, one vessel of the adsorber pair will be put back in
adsorption. One has to make sure that the adsorber coming on adsorption is purged with H2
before it is repressurised to adsorption pressure in order to make sure that the product it
produces will meet the specification. The adsorber coming on purge should be
depressurised.
When switching from 8- to 10-bed, one adsorber will come back in equalisation 3 up
(receiving), as such it should be purged with hydrogen before repressurising it in order to
make sure that product will be within spec). The other adsorber will come on EQ3+PP1 and
should be pressurised to about 8.8 kg/cm²g..
When working on adsorber equipment, the adsorber should be isolated after purge with
BLOCK VALVES AND BLINDS.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 73 of 80
By : T. Cnop
10.3.1 Depressurisation
- Monitor the pressure of corresponding vessel until the pressure has dropped to the
required pressure (see pressure conditions for switchover).
10.3.2 Repressurisation
- Open product block valve of the adsorber one wants to repressurise in throttled position
- Open the product process valve of the adsorber in throttled position. (XV312…362 open
and UCV316…426 throttled)
- Repressurise till the required pressure (see pressure conditions section 10.2.) is reached.
Before exposing the adsorber internals of the idle adsorbers to air when valves need to be
repaired, it is required to purge the adsorbers till local safety and health regulations are met.
Purge procedure as per section 6.1.2. can be followed. Adsorbers have to be purged from top
to bottom to prevent impurities from migrating to the top layers (possibly causing deactivation
of the adsorbent material).
Before taking the adsorbers back in operation, air has to be purged from the adsorbers with
nitrogen, followed by a purge with hydrogen (product).
Purge gas should be evacuated to flare via the safety valve bypass valves.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 74 of 80
By : T. Cnop
10.3.3.2 Purge of the adsorber out of operation with hydrogen can be done by following procedure:
- Make sure the adsorber is totally isolated with its block valves.
- After depressurisation to flare, leave the safety valve bypass valve to flare open.
- Open the product process valve of the adsorber in throttled position. (XV312…362 open
and UCV316…426 throttled)
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 75 of 80
By : T. Cnop
Normally the POLYBED PSA unit operates unattended. Regular checks of process
conditions, process performance and mechanical operation are necessary to maintain
satisfactory performance of the unit.
4) Transmitters
Good transmitter performance is of prime importance. The end of providing purge
pressure should be regularly (normally once a year) checked by means of one common
calibrated manometer. This check can be done during operation. It is important that this
pressure is equal for all adsorbers (max. allowable deviation approx. 0.2 kg/cm²). Small
deviations are compensated for by the logic.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 76 of 80
By : T. Cnop
1) All operating check-points as listed in Section 9 shall be checked and adjusted when
necessary.
2) The hydrogen feed temperature should not exceed 40°C. Higher temperatures can
adversely affect the unit performance and result in the production of low purity product.
3) The hydrogen feed gas composition should be in accordance with the composition as
indicated in the Process Flow Diagram. High impurities content can adversely affect the
unit performance and result in the production of low purity control.
Refer to manufacturer’s specifications and guidelines supplied in the Maintenance Manual for
instructions on maintenance and repair of all valves and instruments.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 77 of 80
By : T. Cnop
12. SAFETY
Although the POLYBED PSA unit is designed to avoid any possible known hazards, the
operators must be aware of certain basic facts associated with safe plant operation. The
basic safety requirements outlined in the following paragraphs are intended for this
purpose but should not be regarded as a complete guide. The operators must depend on
their judgement at all times while watching for possible safety hazards and applying
necessary countermeasures.
12.2 HAZARDS
Hydrogen gas forms an explosive mixture in air when its concentration in air is between 4
and 75% by volume, and it can detonate when concentrations in the air range between 18
and 59%, subject to a source of ignition being available. Explosive or detonating air-
hydrogen mixtures are extremely dangerous when present in confined areas, pipes or
vessels. The speed of burning hydrogen gas in a confined space (especially small
diameter pipes) increases with the heat of reaction and may reach supersonic levels
causing detonation.
Note, however, that no detonation (unless set off by a detonator) will occur to an
unconfined mixture of hydrogen and oxygen in the air. Hydrogen is a colourless,
odourless, tasteless and non-toxic gas. However, it can cause asphyxiation when it
displaces the normal oxygen concentration in a confined area without proper ventilation.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 78 of 80
By : T. Cnop
Repairs may become necessary while the plant is in operation or when it is shut down for
brief or extended periods.
If the shutdown is for an extended period of time, or if equipment in the area of the
POLYBED PSA unit requires repairs, the unit should be purged with nitrogen and
maintained under a nitrogen atmosphere.
If the shutdown is for a brief period, the POLYBED PSA unit should be isolated from
other systems and maintained at about 1 kg/cm²g pressure. The isolation valves must be
closed to isolate the unit. Process valves alone will not isolate the unit.
Both the purging of the complete plant and the subsequent repair work must be carried out
with all necessary precautions to exclude the possibility of fire, explosion, or detonation
within the equipment. Normal air composition should prevail in working areas. Gas from
process streams should be vented only to the flare tack. Before starting actual repairs
check the atmosphere within and outside the equipment to be repaired.
Any plant section in which repair work is going to be performed must be positively isolated
from other sections of the plant containing combustible gases.
Closing valves is not sufficient - lines must be blanked.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 79 of 80
By : T. Cnop
In case of fire, determine its extent and origin as quickly as possible, then take steps to
shut off the supply of hydrogen or other fuels. Do not put out a flame unless the flow of
hydrogen has been stopped first because of the danger of re-ignition or explosion. Large
quantities of water should be sprayed on adjacent surfaces to cool the equipment and
prevent involvement in the fire. Combination fog and solid-stream nozzles are preferred to
permit widest adaptability in fire control. Small hydrogen fires have been successfully
extinguished using dry chemical extinguishers or with carbon dioxide, nitrogen and steam.
Re-ignition may occur if a metal surface adjacent to the flame is not cooled with water or
other means.
Water must be available in adequate volume and pressure for fire protection. Personnel
must be cautioned that hydrogen flames are practically invisible and may only be detected
by heat waves.
To further ensure the plant safety, normal safety measures should be applied, e.g. do not
permit the carrying of matches, or smoking, anywhere on the property, except in “safe”
areas that may be designated.
Pressure safety relief valves are installed on the feed side of each adsorber. They are
designed for fire conditions based upon API RP520. Safety valves are also installed on the
tail gas drum. Safety valves should be properly maintained.
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
PROJECT SPECIFICATION
UOP N.V., Noorderlaan 147, B-2030 Antwerp, Belgium Number Rev.
E-H6265-720 0
OPERATING MANUAL Sheet : 80 of 80
By : T. Cnop
REFERENCE DOCUMENTS
P & ID B-H6265-002
This information is proprietary and shall not be disclosed outside your organisation, nor shall it be duplicated, used, or disclosed for
any purpose other than as permitted under written agreement with UOP.
Operating Manual For Cryogenic Nitrogen
Generator
Unit - 96
Operation & Maintenance Manual
For
Capacity
Customer
This document contains confidential or proprietary information of BOC India Limited. Neither the
document nor the information therein is to be reproduced, distributed, used or disclosed, either in whole
or in part, except as specifically authorized by BOC India Limited.
A Member of BOC Group Page 1 of 49
Operation & Maintenance Manual for Cryogenic Nitrogen Generator
TABLE OF CONTENTS
Introduction.........................................................................................................................4
Designed for..........................................................................................................................................4
Product Specification ............................................................................................................................4
Stream Abbreviations: ..........................................................................................................................4
• 1.0 EQUIPMENT LIST: ......................................................................................................................5
1. INLET AIR FILTER 96-FS-01(10) A/B/C..................................................................5
2. AIR COMPRESSOR 96-K-01(11)A/B/C .....................................................................5
3. REFRIGERATION UNIT 96-M-01(15)..............................................................................5
4. MOISTURE SEPARATOR 96-B-01(69) ..............................................................................5
5.ADSORBER 96-B-02(16) A/B........................................................................5
6.PPU AFTER FILTER 96-FS-02(62) A / B....................................................................5
7.DE PRESSURIZATION SILENCER 96-M-04(64) .............................................................................5
8. PRODUCT NITROGEN SILENCER 96-M-06(16) ..............................................................................5
9. WASTE AIR SILENCER 96-M-05(12) ..............................................................................5
10. AIR EXCESS VENT SILENCER 96-M-07(11)……………………………………………………
11. AIR SEPARATION COLD BOX .........................................................................................................5
MAIN HEAT EXCHANGER 96-E-02(21)................................................................................5
DISTILLATION COLUMN 96-C-01(25) ...............................................................................5
REBOILER - CONDENSER 96-E–03(31) ...............................................................................5
EXPANSION TURBINE 96-M-02(35) ...............................................................................5
12. 100KL LIQUID NITROGEN TANK 96-T-01 A/B ………………………………………………………...
13. LIN ATMOSPHERIC VAPORISER FOR BACKUP 96-E-04A/B……………………………………...
14. ATMOSPHERIC PRESSURISATION COIL FOR TANK 96-E-06 A/B………………………………..
15. WASTE DISPOSAL DRUM 96-B-04(96)...............................................................................5
16. REGENERATION GAS HEATER 96-E-01(63) ...............................................................................5
17. THAWING HEATER 96-E-05(99)...............................................................................5
18. LIN PUMP 96-P-01………………………………………………………….
19.ANALYSERS .....................................................................................................................................5
O2 in N2 Analyzer AIT 1342 ........................................................................................................5
Moisture Analyzer AIT 1232 ........................................................................................................5
CO2 Analyzer AIT 1231 ........................................................................................................5
CONTROLLER LIST .............................................................................................................................6
CONTROLLER......................................................................................................................................6
FUNCTION / DESCRIPTION ................................................................................................................6
LOCATION ............................................................................................................................................6
1.0 Introduction
This document should to be kept always with the operator for the Nitrogen Generation Unit
Supplied by BOC India Limited, for IOCL Haldia.
Designed for
Product Specification
Purity Units
Nitrogen (N2) 99.99 Vol %
Oxygen <3 ( Normal) PPM (vol)
CO2 <3 (Max.) PPM (vol)
CO Trace
Other carbon compounds <5 PPM
Oil NIL
0
Dew Point -100 C at atm. Pr.
Stream Abbreviations:
The last part of the service code is fluid type. Examples are as follows:
5. ADSORBER 96-B-02(16)A/B
18 ANALYSERS
CONTROLLER LIST
LIC 1501 96-C-01(25) LEVEL CONTROL ( THRO LIQ.NITROGEN DRAWL) 96-C –01(25)
PIC 1602 GAN PRODUCT PRESSURE CONTROL WHEN PLANT IS SHUT 6”-GN-96-16-87-A3-1F
DOWN
The nitrogen plant cold box being automatically controlled from the plant control system, the
operator needs to do the following:
The control system prevents nitrogen being drawn off in excessive quantities, which would cause
the nitrogen to exceed purity limits.
The detail Control Strategy and Interlock description of the plant is attached in Appendix I.
Snapshots of the main cold box control scheme is given below
Gas Mode
∗ Selected by HS-1502
∗ PIC 1401 to go to auto and acts on turbine bypass valve PV-1401 with a predetermined
value says [4.43 barA].
∗ LV-1501 is driven closed by controller action and operator has no access.
∗ This mode is mutually exclusive to gas/liquid mode.
Gas/Liquid Mode
∗ Selected by HS-1503.
∗ Controller PIC 1401 must be in auto and PIC setpoint is changed to predetermined
value[says 5.37 barA]
∗ Controller LIC-1501 must be in Automatic, otherwise plant mode shifts to Gas Only.
∗ Column level is controlled by LIC-1501 acting on LV-1501 (Liquid Nitrogen)
∗ This mode is mutually exclusive to gas only mode.
∗ LAHH-1501 shifts cold box from Gas/Liquid Mode to Gas Only Mode i.e. the Turbine
bypass valve PV1401 opens and PIC 1401 remain in auto [PIC setpoint to be changed
by operator to maintain the flow as per requirement of gas mode and Turbine IGV
opening to be adjust suitably] and the LN product valve LV-1501 closes. The latter must
be taken to manual and shall be opened (if required).
∗ AAHH-1501 trips cold box from Gas / Liquid Mode to Gas Only Mode as explained
earlier and Gaseous Nitrogen Product valve FV-1502A closes and opens the Impure
Nitrogen Vent valve FV-1502B.
∗ There must be a positive pressure difference between the cold box and the liquid
nitrogen storage tank before gas/liquid mode is selected.
∗ The reflux for the column is obtained by condensing part of the gaseous nitrogen overheads
from the column in the Reboiler / condenser 96-E-03 (31) by evaporating Rich Liquid.
∗ The RL flow to 96-E-03 (31) is controlled by FIC1501 acting on FV1501 to maintain the
design waste gas flow rate.
∗ The maximum inlet pressure to the expansion turbine 96-E-03 (31) is controlled by the inlet
pressure controller PIC1401, acting on PV1401.
NOTE: Care should be taken to set up the expansion turbine flows/pressure, nozzle and speed
control valve as indicated in the Expansion Turbine as Cryostar’s Instructions.
In case of High Oxygen in Product Nitrogen above the permissible limit, then the alarm and trip
circuit is activated by the analyzer, AIT. 1501
Note: The alarm circuit will automatically switch the cold box mode from “Gas/Liquid” to “Gas
Only” after a pre-trip warning to operator.
When the oxygen content has fallen below the permissible limit, AIT 1501 will automatically open
FV 1502A and close valve, FV1502B, thereby restoring the gaseous nitrogen supply. To return
to liquid production, it is necessary to manually re-select "Gas/Liquid" production, once the cold
box operating parameters have stabilized.
Two controllers control the flow of gaseous nitrogen from the cold box.
∗ PIC Gaseous Nitrogen Pressure ex Cold Box - PIC 1502A maintains the distillation
column pressure at or above its set point. When there is drop in pressure of circuit, the valve
FV 1502A is throttled to maintain the pressure
Pressure controller PIC1502 is set at 7.9 kg/cm2 (g) (slightly lower than operating pressure).
∗ FIC1502A Gaseous Nitrogen flow ex Cold Box: If the demand for gaseous nitrogen is
more than the design rate, FIC 1502A throttles the gaseous nitrogen product valve FV
1502A.
Thawing
During Plant Thawing, ensure the Air Compressor and pre purification system is in operation
to provide thawing air to the cold box. In Thawing mode, V-21-1 is to be partially opened and
Nitrogen Product Valves FV-1502A and LV-1501 remain closed. But the Rich Liquid Valve
FV-1501 should be operable and the waste gas vent valve PV-1304 to atmosphere should
be operable and to be kept at 100% open.
Shutdown
On a plant trip all controllers will re-set to manual with control valves being driven to their fail
position.
Start-up
There is no automatic start-up sequence for the cold box.
All controllers will be in manual. The operator will then adjust each controller to its required
set point individually before selecting automatic mode from the relevant faceplate.
The plant start-up is a logical progressive sequence of starting up the individual units until the
complete plant is on stream.
The normal sequence of cold box start-up with a fully operational pretreatment system is as
follows:
The compressor has been prepared for start-up as per the manufacturer Ingersoll Rand (IR)
instruction as given in the compressor operation and maintenance manual.
Compressor Starting:
Compressor is started as per instructions given in the compressor operation and maintenance
manual.
The refrigeration unit has been prepared for start-up as per the manufacturer Kirloskar India ltd.
instruction as given in the Unit’s operation and maintenance manual.
ASSUMED CONDITIONS
Prior to starting the dryer Adsorbers, the Air Compressors and Refrigeration Unit must have
been checked out and placed in service (as described in the preceding sections). The air at
the battery limit shall be at design pressure.
The entire operation of the dryers is accomplished by 'Temperature swing Adsorption' (TSA).
∗ Ensure Both beds are at atmospheric pressure and cold box is isolated
∗ When the bed A/B is pressurized (after satisfying the PDI1302A interlock 0.2 bar), open
XV1303A or XV1303B
∗ Ensure the PPU line sequence is in a specific step required. If not, use the Step
Advance pushbutton to move to the correct step.
∗ Select the manual step selection then put the system in auto.
∗ Check the displays to make sure that the auto cycle timer is running and the PPU is
operating correctly. If the timer is off, the auto cycle is frozen and the alarm section
should be reviewed.
The operation of the TSA PPU Cycle is divided into seven (7) steps for each bed. The total
time required to complete all the steps is approximately 8 Hrs. The following description will be
specific for bed A. The same description would be valid for bed B (by replacing A's with B's).
5 Repressurization A 10 C C C C C O O C C OFF
7 Depressurization B 10 O C C C C C C C O OFF
Heating B ON
8 82 O C C O C C C O C (after 2
min.)
Heater off
9 10 O C C O C C C O C OFF
Cooling B
10 123 O C C C O C C O C OFF
Repressurization B
11 10 O C C C C O C C C OFF
ASSUMED CONDITIONS
Air is available from the air compressors, the purification system is up to the operating
pressure, and an adequately regenerated adsorber is on stream.
If the cold box has not been previously started up then it MUST be thoroughly dried out using
thawing air before attempting a start-up. A freeze fracture of equipment could result if water is
present within a cold box. The cold box should be thawed and dried out if it has been
shutdown for a prolonged period, or if repair work has been carried out, or if the process side
has been left open to atmosphere.
PROCEDURE
∗ Check that all the instrument air supply valves to all instruments and pneumatically
actuated valves are open.
∗ The cold box is isolated, i.e. inlet valve, V-21-1 and its bypass V-21-3 are closed.
∗ The thawing gas inlet valves, T35A/B-1, T31-1 and T25-4 are locked closed.
∗ Thawing gas outlet valves T35A/B-3 are closed.
∗ Nitrogen product start-up vent FV 1502A is closed.
∗ Liquid nitrogen product drain, D25-2, is closed.
∗ The process air regeneration valve may be partially open if the Adsorbers are already
being regenerated.
∗ Nitrogen product isolation valve, V-21-1B is closed.
∗ The turbine valves, XV1401A/B, T35A/B-3, V358A/B-1, and V35-2 are closed.
∗ The turbine is shutdown with no lube oil circulation.
∗ The oxygen analyzer isolation valve shall be closed.
∗ Ensure the rich liquid control valve FV1501 is closed and controllers FIC1501 and
PIC1401 are in manual with zero output signal.
∗ Ensure the gaseous nitrogen product control valve FV1502A is closed and controllers
FIC 1502A and PIC 1502A are in manual with zero output signal.
∗ Ensure liquid nitrogen off-take control valve, LV1501 is closed with the controller
LIC1501 in manual.
∗ Check that the column drain valve, D25-4, is closed.
∗ Turbine bypass control valve PV1401 is open with controller, PIC1401, and open in
"manual.
∗ The high-pressure system within the cold box is now fully isolated and ready for
pressurizing.
∗ Check cold box is in “Gas Only” mode of operation (HS1502).
∗ Activate the cold box control valves.
∗ With the controller in "manual" set the output signal to the waste gas vent valve PV1304
to 100% open.
∗ Open the cold box inlet by-pass valve V-21-3 and slowly pressurize the cold box column
maintaining a minimum pressure of 8.51 kg/cm2 (g) in the Adsorbers.
∗ When the column is fully pressurized, close V-21-3 and fully open the cold box inlet
valve V-21-1.
∗ Open the various control valves in many position and establish the flow through entire
cold box various circuits
A Member of BOC Group Page 13
Operation & maintenance manual for Cryogenic Nitrogen Generator
ASSUMED CONDITIONS
Air is available and the adsorber system is pressurized.
The cold box has been prepared for start-up and the distillation column has been pressurized
as per the instructions of Section 3.4.
• The lube oil heater 96-E-12 (35) A/B has been switched to start using HS 1407 A/B at least
2 hours prior to start-up.
• The lube oil pump motor has been running for at least 30 minutes.
START-UP PROCEDURE
Review the Cryostar’s manual prior to start-up.
• Open the turbine outlet valve, V-35A/B-2.
• Open brake temperature control valve (V-359-1) fully open and brake flow control (FCV-
1401) half open.
• Check nozzle position is set to 0% opening.
• Open the seal air supply valve V-358-1, if closed. Check the seal air pressure is at the
required pressure on PI 1402A/B. If not, adjust PCV 1402A/B until seal air pressure meets
the figure stated in the Cryostar’s manual.
• Start the oil pump from the local panel (HS1405 A/B). This should be left running for at least
a further 5 minutes in order to circulate warm lube oil. If the expansion turbine shutdown
during operation and was left cold then the warm lube oil should be circulated for a minimum
of 15 minutes or longer to ensure that the "cold end" bearing is not frozen with solid oil.
Once the lube oil pump has been started check the lube oil pressure and lube oil
temperatures.
• Check that PIC1401 is in manual with zero output. Place into automatic and set PIC1401 to
the required set point.
• Slightly open the rich liquid valve FV1501 (approximately 10%), using FIC1501 in manual.
Once a flow of waste gas is established then start the expansion turbine.
• Press turbine start HS1401A/B from DCS/Aux Console or HS 1404A/B from local, the turbine
inlet valve XV1401A/B will open, and the turbine by-pass valve PV1401 will close by the PIC
1401. The pressure increases on the turbine inlet on PT-1401. The turbine starts to rotate at
low speed (by nozzle leakage). Slightly open the nozzles by 2% increments to reach a speed
Set PIC1401 at the desired operating point and put the controller into automatic.
Note:
a) It may be necessary to open the inlet nozzles HV1401A/B if the normal operating
pressure is reached before the design flowrate on FIC1501.
b) The design flow rate on FIC1501 may not be achievable even with FV1501 fully open
during start-up when the cold box is in a warm condition.
The flow of waste gas when the expander is warm should be less than design. As the turbine
cools down, more and more waste gas will flow through the turbine until the design flow is
reached.
When the expansion turbine is close to its normal operating temperatures, adjust the waste
gas flow using FIC1501, the inlet nozzles using HIC1401A/B to achieve the correct operating
inlet pressure, and the oil brake speed control valve to achieve the correct turbine speed.
Continue to cool down the plant as Section 3.6. As the plant cools down, check that the
turbine inlet pressure is maintained at the desired level. This is necessary since, as the plant
cools down, the turbine can take more gas and there could be a reduction in turbine inlet
pressure. If necessary make adjustments to PIC1401 and/or FIC1501 and/or the expansion
turbine inlet nozzles, (HIC1401A/B).
Once a continuous waste gas stream is available from the cold box the adsorber regeneration
system can be started using waste gas from the cold box by setting up the appropriate
parameters on the waste gas control system including venting excess waste gas to
atmosphere via PV1234.
Turbine Trips
If any of the trip/interlock is activated, a red flag will appear against that item.
If all the interlocks and permissive are satisfied, "Ready to start" light will start flashing.
ASSUMED CONDITION
The turbine has been started up and has the correct inlet pressure registered on PIC1401.
PROCEDURE
Initially, when the plant is warm, the turbine throughput is small but as the plant cools down
the turbine will take more air so the rich liquid valve, FV1501, will adjust to maintain a
maximum turbine inlet pressure.
The cooling of the plant can be followed by watching temperature points, TI 1401 and TI 1402
(the turbine inlet and outlet), during this period. It is important that turbine inlet temperature
should not be allowed to fall lower than -172°C at any time, otherwise excessive cryogenic
liquid may form within the wheel and cause erosion. If necessary, reduce the inlet pressure
of the turbine by reducing the set point of PIC1401.
A few hours after start-up of the turbine, TI 1401 will have fallen to about -179°C. Liquid will
start to form in the column sump and pass into the rich liquid line.
The rich liquid valve FV1501 will slowly close to maintain the turbine inlet pressure and then
the maximum waste gas flow. Adjust controllers if necessary.
At this stage of the cool down, it is recommended that the oxygen analyzer AIT 1501 be
switched on.
Liquid air is evaporated in the condenser/evaporator to produce reflux for the distillation
column and to fill the distillation trays with liquid. Once the trays have been filled with liquid, a
level will start to appear in the column sump (LIC1501).
Allow the liquid level to slowly rise to approximately 50% on the scale. The level should not
be controlled any higher than 50% indication in order to leave adequate vapor space below
the column feed inlet branch connection.
Open the turbine bypass valve, PV1401 to approx. 60 per cent using controller, PIC, on
"manual".
Check that FIC1501 control the waste gas flow at the desired rate.
ASSUMED CONDITIONS
The cold box is cooling down.
The turbine has reached its operating temperatures and there is a liquid level in the column
sump.
Rich Liquid Valve FV1501 is partially open with the design waste gas flow established and
controllers FIC1501 and PIC1401 should be in automatic maintaining this flow rate.
The waste gas vent control system is operational and PV1304 is automatically venting excess
waste gas to atmosphere.
Gaseous Nitrogen Product valve, FV 1502A is closed and controllers FIC 1502A and PIC
1502A are in manual.
Nitrogen product vent valve, FV1502B, is closed and the blow-down valve, V-21-7B, is
closed.
Product off-take isolation valve, V-21-1B, is closed.
PROCEDURE
It is necessary to put the product analyzer on stream and obtain the correct purity before it is
possible to open the product off-take control valve, FV 1502A.
The oxygen analyzer is put on line as follows:
Open isolation valve for the analyzer AIT 1501.
Establish an adequate sample flow through the oxygen analyzer.
The alarm point of the nitrogen purity is set at 2ppm oxygen and the design point is set at 3
ppm oxygen.
Initially the oxygen content of the gaseous nitrogen is above the design value. When the
impurity falls below the design value, the product off-take valve, FV1502A, is automatically
energized and the Nitrogen Vent valve, FV1502B, closes. Controller, FIC1502A, should
therefore be left fully closed on "manual".
NOTE: If purity is slow to improve - open liquid nitrogen drain, D25-2, on the cold box until
liquid shows, then close D25-2. It may also be necessary to partially allow purging cold box
by impure nitrogen out of the product lines.
When the product impurity is finally below the design value, it is possible to commence
exporting gaseous nitrogen to the distribution line. This is accomplished as follows:
NOTE: If controller, PIC 1502A, is in manual with a zero output signal then FV 1502A will not
open as FX 1502A will select the low signal. Adjust the output of PIC 1502A to approximately
80%.
Open the final delivery isolation valve, V-21-1B.
Slowly open FV 1502A, using FIC 1502A in the manual mode, to meet the user demand but
do not allow the flow on FIC 1502A to exceed 2500 Nm3/h (gas only mode) otherwise the
product purity may be lost.
Adjust the set point of FIC 1502A to 2000 Nm3/h or the desired product flow rate, and put the
controller into "automatic".
Adjust the set point of PIC 1502A to 7.9 kg/cm2 (g) the required setpoint and switch the
controller to "automatic". Check the action of both controllers PIC 1502A and FIC 1502A to
ensure there is no interaction.
ASSUMED CONDITIONS
The cold box is on stream producing gaseous nitrogen only.
• The turbine inlet pressure, PIC1401, is reading a lower figure than Gas/Liquid Mode.
• LIC1501 is in manual with a zero output.
• FIC1501 is in automatic and the waste gas flow is at the correct value,
• The liquid Nitrogen storage tank is cold and partially full.
• Check that the liquid nitrogen tank inlet valve is closed.
• Check that the liquid nitrogen drain valve on the inlet line is closed.
• Liquid nitrogen product off-take control valve, LV1501 is closed.
• Pressure controller PIC1401 is set at about 4.6 kg/cm2 (g) and is in automatic.
PROCEDURE
• Change to gas/liquid production using selector switch HS1503.
• The turbine bypass valve PV1401 will now close and the turbine inlet pressure, PIC1401,
will rise to 4.6 kg/cm2 (g).
• Watch the turbine inlet temperature, TI1401, for some time. If the temperature falls below -
172°C, reduce the waste gas flow slightly on FIC1501.
• In Gas/Liquid Mode change the set points of FIC1501 and FIC 1502A to the desired set
values.
• Partially open LV1501 using LIC1501 in manual. Partially open liquid nitrogen drain valve
D25-2 to purge impure liquid nitrogen from the transfer line.
• Close drain valve D25-2 and open liquid nitrogen tank’s inlet valve depending on the tank
to be filled.
• Slowly open LV1501 to approximately 50%, put LIC1501 into automatic and observe the
action of the control valve output.
A Member of BOC Group Page 18
Operation & maintenance manual for Cryogenic Nitrogen Generator
• Controller, LIC1501, is now regulating the liquid off-take valve, LV1501, and liquid nitrogen
is passing to storage.
• A minimum pressure difference should be maintained between the top of the column and
the storage tank to allow liquid nitrogen to flow from the column to the storage tank.
NOTES: 1) When the cold box is on “Gas/Liquid” production, and the purity goes bad close to analyzer
alarm limit, the cold box will automatically change back to gas mode, closing valve, FV1502A.
“Gas/Liquid” production has to be manually re-selected when the cold box is in stable
operation. The nitrogen purity trip switches from “Gas/Liquid” to “Gas only”, closes FV1502A
and opens FV1502B.
2) If all the liquid nitrogen storage tanks fill to the high level alarm point, the cold box should
be switched back to "Gas Only" production manually.
3) Set point changes of controllers FIC1502A, FIC1501 and PIC1502A and PIC1401 must be
small and over a period of 10 - 15 minutes to ensure stability of cold box operation.
4) Controller LIC1501 is to be in automatic at all times in case the cold box trips to ‘Gas Only’
mode.
ASSUMED CONDITIONS
The cold box is on stream producing both gaseous and liquid nitrogen products.
The turbine inlet pressure, PIC1401 is 4.6 kg/cm2 (g) maximum.
The column base level controller, LIC1501, is controlling LV1501, the liquid nitrogen product
off-take valve.
Rich liquid controller FIC1501 is in automatic controlling the waste gas flow via FV1501.
The liquid nitrogen storage tank is operating normally.
PROCEDURE
Change controller LIC1501 to manual control and reduce the output signal to zero.
Select the "Gas Only" operation mode using selector switch 1502
Liquid nitrogen product off-take valve, LV1501 is now closed.
With LIC1501 in manual, gradually move PV1401 from a zero output to approximately 50%
output in order to decrease the turbine inlet pressure PIC1401 to the gas only mode pressure,
established during commissioning. This will decrease the turbine speed.
Gradually change the setpoints of FIC1501 and FIC1502A to the desired maximum Gaseous
Nitrogen Flowrate.
4.1 General
The routine operations to be performed on the plant are limited generally to the occasional
checking of plant conditions and the logging of operating parameters.
If, however, the setting is correct, the air supply pressure may be low due to insufficient air
from the air compressor or there might be too low a setting on FIC1502A. If this is the case,
then an adjustment in the settings of the air compressor or an increase in the setting of
FIC1502A should restore the position.
When operating at full throughput, the feed air pressure controls the column pressure. If this
pressure is too low, then the gaseous nitrogen will not condense in the Reboiler / condenser,
96-E-03 (31), to form the reflux necessary for stable column operation.
This problem would most likely occur in the "Gas/Liquid" mode. In the "Gas Only" mode the
rich liquid evaporation pressure is lower so 96-E-03(31) functions better.
This results in low reflux formation in the Reboiler / condenser, 96-E-03(31) and reduced
column performance.
Increase the waste gas flowrate using FIC1501 whilst in the "Gas/Liquid" mode, but ensure
that the maximum turbine inlet pressure is not exceeded.
This will generally be apparent from LIC1501 as the level of liquid will tend to drop and the
instrument will not control satisfactorily. In this case the flow on FIC1501 should be reduced.
Some time may elapse before the purity returns to normal.
The gaseous nitrogen produced for the operating mode is too high.
E. The set point of PIC 1401 is to high or the inlet nozzles of the expansion turbine
are in a "closed" position.
The operating pressure of waste gas is to too high so that gaseous nitrogen is not
condensed. Check the set point of PIC1501and nozzle settings of the expansion turbine.
The trays of the column may be fouled with solid deposits. In this case, the cold box requires
thawing out.
In general it should be pointed out that the plant will run satisfactorily providing there are as
few adjustments as possible made to the settings of the instruments.
Also the correct settings must be used for the correct operating mode.
The cryogenic liquid should not normally be drained from the cold box, however distillation
column level may be maintained 50%.
In order to prevent the ingress of atmospheric moisture it is better to leave the cold box
pressurized whilst shutdown.
If the plant has to be left pressurized for longer than say 24 hours, then the column pressure
will have to be vented to atmosphere to maintain the pressure below the design pressure of
10.5 kg/cm2 g.
Assumed Conditions
The plant is on stream, producing gas only.
Controllers LIC1501, FIC1501,FIC 1502A PIC1401and PIC1502A are on automatic.
Shutdown Procedure
• Put FIC1502A into "manual" and close FV1502A. The Gaseous Nitrogen flow will cease.
• Put PIC1502A into "manual" and reduce the output signal to zero.
• Put PIC1401 into “manual” and open the turbine by-pass valve PV1401, the turbine inlet
pressure and speed will fall.
• Stop the turbine using the stop switch HS1404A/B.
• Put FIC1501 into ‘Manual’ and close the rich liquid valve FV1501.
• Close the cold box inlet valve V-21-1
- Slowly close off the expander nozzles by decreasing the output of HIC1401A/B by 10% at
a time, until the output is 0%.
- Stop 96-M-02 (35) by pressing the stop button HS1401 A/B. Close V-35-2.
- Confirm that HV1401A/B is closed, and seal gas pressure / lube oil pressures are normal.
- Stop airflow to the ASU by slowly reducing the value of the controller FIC1501 and
nitrogen flow by closing FIC1502A.
- V-163-7 must be opened as necessary to meet the regeneration flow requirement.
- Close off the cold box purge valves.
- If the small shutdown, keep PPU and Refrigeration unit running. Continue the
regeneration of the PPU with air.
- If a total plant shutdown, stop nitrogen flow to customer and close V-21-2.
- Check the pressure in 96-C-02 (25) to confirm that there is no pressure build up in
columns.
The PPU removes carbon dioxide and the final traces of water from the inlet air. However,
under typical operating conditions small amounts of carbon dioxide and perhaps
hydrocarbons will pass through the PPU to the cold box. Eventually sufficient accumulation
will occur to warrant a complete derime.
ASSUMED CONDITIONS
THAW-OUT PROCEDURE
Drain off the column sump liquid using the drain valve, D25-4.
Open the valves, V-21-7B, FV1502B and V-21-6 on the waste gas line.
Thawing air temp should be lower than 50°C free from CO2 or water.
The control loops for FV1501 and LV1501, is in "Manual" position. The PV1304 should be
automatically driven 100% open.
Start a flow of thawing air from the PPU. The cold box equipment should now be warmed up
to near ambient temperature.
NOTE:
(i) As there is no seal air or lube oil circulation on the turbine, the inlet and outlet
isolation valves, XV 1401A/B and V-35A/B-2 must remain fully closed. No attempt
should be made to thaw out the turbine.
1) The feed air flow path through the main heat exchanger, 96-E-02(21), from the
column to the thawing gas outlet valve, V-21-7B.
2) The complete waste gas flow path from the column sump via FV1501, LV1501, and
the waste gas line via PV1304 or V-21-6.
4) The column and gaseous nitrogen product off-take line from the column sump to the
column overhead line to the main heat exchanger and the nitrogen product line via
FV1502B.
5) The column sump drain line via the drain valve, D25-4.
Continue passing thawing air through the cold box until the outlet temperatures at the
various vent points are hand warm.
The cold box is now fully thawed, the thaw-out operation should now be stopped as follows:
7 MISCELLANEOUS ACIVITIES
In the event of a power failure the air compressor motor and drives will shutdown including
the expansion turbine. On air compressor shutdown the cold box will shutdown:
2) Check that the cold box inlet valve, V-21-1 is fully closed.
If the power cannot be restored immediately, then the plant should be isolated and left cold.
Failure of the instrument power system will cause the Compressor, PPU and Cold Box to
safety trip.
On air compressor failure the Cold Box will shutdown in the same way as a power failure.
If the Turbine should seize then it has to be repaired using a spare expansion turbine
mechanical centre section (cartridge).
The following symptoms will indicate that the turbine has seized.
2) No temperature drop between the turbine inlet and outlet, ie: TI1401 and TI1402.
4) A falling column sump level. Controller LIC1501 will be moving to a fully closed
position.
Air Compressor
PDAH 1101A/B/C Suction Filter 55 mmWC
TAH1101 & 1106 A/B/C Air Compressor Motor Bearing DegC
TAHH1101 & 1106 A/B/C Air Compressor Motor Bearing DegC
TAH1102 to 1105 & 1107 Air Compressor Motor Winding DegC
to 1108 A/B/C
TAHH1102 to 1105 & 1107 Air Compressor Motor Winding DegC
to 1108 A/B/C
VAH1101/1102/1103 A/B/C Air Compressor -
VAHH1101/1102/1103 Air Compressor -
A/B/C
rd
TAH1111A/B/C Air Compressor 3 Stage 52 DegC
Suction
rd
TAHH1111A/B/C Air Compressor 3 Stage 55 DegC
Suction
nd
TAH1110A/B/C Air Compressor 2 Stage 52 DegC
Suction
nd
TAHH1110A/B/C Air Compressor 2 Stage 55 DegC
Suction
TAH1112A/B/C Air Compressor Discharge 52 DegC-
2
PAL1104 A/B/C and PAL Air Compressor discharge 8.7 kg/cm G
1105 pressure
2
PALL1106A/B/C Lube Oil to Air Compressor 1.5 kg/cm G
2
PAL1106A/B/C Lube Oil to Air Compressor 2.0 kg/cm G
TAH1126A/B/C Lube Oil Ex Air Compressor 45 DegC
TAHH1126A/B/C Lube Oil to Air Compressor 45 DegC
TAL1126A/B/C Lube Oil to Air Compressor 30 DegC
TALL1126 A/B/C Lube Oil to Air Compressor 20 DegC
PAL1106A/B/C Lube Oil to Air Compressor 2.0 Kg/cm2G
LAL1128A/B/C Lube Oil Tank -
Refrigeration Unit
TAH 1282 Air Outlet temp from chiller 15 DegC
TAL 1282 Air Outlet temp from chiller 8 DegC
TALL 1283 Air Outlet temp from chiller 8 DegC
DPAL 1284/1285 Pressure drop across CW flow
Cold Box
AAH1501 Oxygen in Nitrogen 4.0 ppm v/v
AAHH1501 Oxygen in Nitrogen 5.0 ppm v/v
LAL1501 Distillation Column 10%
LAH1501 Distillation Column 70%
LAHH1501 Distillation Column 85%
TAL1501 Waste Gas ex Cold Box 5°C
TALL1501 Waste Gas ex Cold Box 0°C
Utility
FAL1701 Cooling Water Supply 350 M3/hr
PAL1701 Cooling Water Supply 3.5 kg/cm2g
PAH1701 Cooling Water Supply 5.0 kg/cm2g
TAH1701 Cooling Water Supply 35
TAL1701 Cooling Water Supply 15
TAH1705 Cooling Water Return 45
TAL1705 Cooling Water Return 20
PAH1702 Instrument air supply 7.0
PAL1702 Instrument air supply 3.8
Cold Box
FIC1502 A/B Gaseous Nitrogen ex Cold Box Gas Only 2000 Nm3/h
Gas/Liq 1600 Nm3/h
FIC1501 Waste Gas ex Cold Box Gas Only 5200 Nm3/h
Gas/Liq 5200 Nm3/h
PIC1401 Expander Inlet Pressure Gas/Liq 4.6 Kg/cm2g
Gas Only to be confirmed
during Commissioning
LIC1501 Column Level - Gas Only 50%
LIC1501 Column Level - Gas/Liq 50%
PIC1502A/B Column Pressure 8.0 kg/cm2 G
A. Fail to start 1. Failure to clear shutdown or interlock devices. 1. Correct shutdown or interlock condition that is indicated by panel light.
2. No primary power to starter 2. Check voltage to starter. Check fuses.
3. No control panel power to compressor control panel or starter 3. Check voltage to panel/ starter. Check control transformer.
4. Loose or corroded connection or defective power cables. 4. Check connections. Clean, tighten and replace s necessary.
5. Defective motor starter or starting circuit. 5. Troubleshoot starter per manufacturer’s recommendation
B Inactive Prelube pump 1. Improper adjustment of prelube pump relief valve. 1. Adjust relief valve for correct pressure.
2. Pump not running 2. Troubleshoot pump starter. Check for proper voltage.
3. Defective motor 3. Repair or replace motor
4. Defective pump 4. Repair or replace motor
5. No seal air 5. Establish seal air
C High Oil temperature 1. Low or no water flow to oil cooler 1. Establish correct water flow
2. Higher water temperature than realized 2. Take necessary step to lower the water supply temperature.
3. Improper temp device setting 3. Calibrate instrument
4. Dirty or plugged oil cooler on water side 4. Clean cooler tubes.
D. Low oil Pressure 1. Improper adjustment of system pressure relief valve 1. Adjust system pressure relief valve for correct oil pressure
2. Leaking or pinched oil line. 2. Repair or replace oil line
3. Dirty oil filter 3. Replace with clean filter
4. Defective main oil pump 4. Repair or replace main oil pump.
E High Air temperature 1. Low or no water flow to oil cooler. 1. Establish correct water flow
F Low seal air pressure 1. Low instrument air pressure 1. See “Low instrument air pressure”
2. Improper adjustment of seal air pressure regulator 2. Adjust regulator to obtain correct seal air pressure
3. Worn seals 3. Replace seals
G Low Instrument air 1. No supply pressure, pinched or leaking air lines 1. Establish instrument air supply pressure.
pressure 2. Improper adjustment of air regulator 2. Adjust regulator to obtain correct instrument air pressure
H High Vibration 1. Low oil temperature 1. Allow warm up period for oil
2. Driver to compressor misalignment 2. Check and correct alignment
3. Worm coupling or spacer 3. Lubricate. Replace coupling and/or spacer
4. Rotor assembly unbalance due to foreign matter build up 4. Cleaning & balance check required
5. Damaged aero parts 5. Repair / replacement & balance check required.
A. Frost spot on cold box 1. Leaking flange or bonnet on valve 1. Locate and repair leak
2. Loose Insulation 2. Add or replace insulation material
3. Wet Insulation 3. Replace insulation material
4. Cold Box purge rate is too high 4. Reduce purge rate
B. Purity Problems 1. Analyzer out of calibration or defective 1. Calibrate and/or repair analytical equipment
2. Process upset 2. Check all process flows, pressures, temperatures and take corrective actions
D. 96-C-02(25) pressure 1. Insufficient liquid in the sump of 96-E-03(31) 1. Adjust liquid level to normal level
too high or unsteady 2. Build of non-condensable in 96-E-03(31) 2. Open or increase opening of the non-condensable purge valve.
E. High sump level in 96- 1. LV-1501 is partially closed 1. Check valve stroke signal and valve positioner
C-02(25)
2. Too much nitrogen reflux flow 2. Cut back on reflux nitrogen flow
74-EX-03(35) EXPANDER
A. High oil return 1. Insufficient cooling water 1. Increase water flow
temperature 2. Fouled oil cooler 2. Clean cooler
3. Bearing Problems 3. Replace bearings
C. Low Seal Gas 1. Restriction in gas supply 1. Make sure all valves are open
Pressure 2. Clogged filter 2. Replace filter
3. Insufficient supply pressure 3. Check source of supply
4. Worn Seals 4. Replace seals
The following is a list of basic safety recommendations, which should be followed. It is in no sense
comprehensive but rather attempts to illustrate hazards considered unique to low temperature air
separation plants. Overall safety regulations established by the organization in charge of plant operations
must always be adhered to, and above all, common sense and good judgment founded on successful
operation must be exercised.
• Sample gas and liquid carefully with good ventilation. Take samples only in the proper container,
which should first be inspected to insure that it is clean and safe for use. Wear gloves and
goggles or face shields while taking samples. Do not allow cryogenic liquid to contact equipment
or the bare skin.
• Extremely low temperatures encountered in the process can cause severe burns. Cryogenic
liquid must not be allowed to come in contact with the skin.
• Use particular care to avoid the accumulation of combustible materials. Degrease any surface
that it at all likely to come in contact with low temperature liquid oxygen or rich liquid. Do not
interchange pressure gauges, etc., from other service locations with those on the plant without a
complete degreasing.
• Use required personal safety equipment. Avoid loose clothing, particularly around moving
machinery. Keep guards in place on moving parts.
• Cryogenic liquid must never be admitted to warm equipment. The warm equipment would
generate large volumes of gas, which is undesirable, and the equipment could be seriously
damaged by the sudden change in temperature. Warm equipment should be cooled down with
cold gas before liquid is allowed to contact it.
• Some metals are greatly weakened and embrittled at low temperatures. Carbon steel for
example, must not be subjected to ultra low temperatures. Others should not be subjected to
shock or unusual stresses when cold. Aluminum, stainless steel, copper, and brass are preferred
for cryogenic service.
Rapid changes in temperature will shock metals and must be avoided.
• Water should not be brought in contact with cryogenic liquids, except in specially engineered
equipment.
• Switch and regenerate Adsorbers on schedule. Before regeneration, Adsorbers must be drained
free of liquid and the pressures completely relieved.
• Be mindful of pressure, temperature, and level limitation of all equipment. Operate valves
smoothly and deliberately. Do no jam close. Be familiar with the currently posted operational
instructions.
• Water must not be trapped in intercoolers or in any place where its temperature and pressure
may be increased without relief valve protection. Liquid discharging from relief valves must be
directed to the ground or other safe area.
• Safety valves must discharge well away from equipment and personnel.
• Admit no unauthorized or unbriefed personnel into the plant. Be aware of the location of all
personnel in the plant to ensure prompt evacuation in case of an emergency.
• Make regular, stringent inspections of all equipment and procedures to check equipment and
safety device service ability and to evaluate potential hazards.
• Be aware of the dangers of inhalation of toxic and inert gases. Use care in the vicinity of gas
vents.
• Those performing maintenance work should understand the difference between inert materials
such as nitrogen and the toxic materials such as chlorinated solvents. The former suffocates by
excluding oxygen and the latter are poisons by ingestion, digestion, and/or inhalation.
• Everyone having business in the plant must be aware of the nature of nitrogen. It is called
"stickstuff" in German which, translated literally, means "suffocation gas";.
• When working on the cold box, care should be taken to provide adequate ventilation, as local
pockets of nitrogen can be present in the insulation due to minor leaks in the equipment, and
high concentrations of nitrogen can, therefore, occur. It should always be remembered that the
only "Safe" oxygen concentration is that existing in atmospheric air. It is recommended that
whenever work is being performed inside a cold box, two persons be present, one inside the box
doing the work and one outside the box observing the conditions.
• Examine the cold box for leaks by approved methods. Confirm that it is purged satisfactorily.
• Elementary medical supplies should be available. This includes aspirin, band-aids, germicidal
soap, bandages, eyewash, etc.
• Instruct maintenance personnel in safety requirements. Allow no mechanical work, welding, etc.,
without proper authorization. Do not permit entry to vessels without proper purging, testing, and
ventilation.
• Area cleanliness rules apply at all times; they are indicative of efficient and safe operation.
Prevent the accumulation of combustible hazards and avoid all sparks and flames. Store oily
rags and water in closed cans.
• Confirm that no oil mist exists in the vicinity of plant process lines and that oil spills during
maintenance are immediately removed! Check insulation for signs of oil contamination after
maintenance. Replace insulation of doubtful conditions.
• Maintain compressors properly. Keep the after coolers free of fouling matter to keep discharge
temperature low. Check cooling water frequently. Check for excessive lubrication and oil
contamination.
• Ground all lines and equipment to avoid static electricity sparks. Tag all electrical lines and
equipment. Check before restoring service after repair work.
• Periodic check of safety equipment such as fire extinguisher, fire plugs and hoses should be
made.
All extinguishers should be maintained at full charge. After use, extinguisher should be recharged or
replaced immediately.
Water must be available in adequate volume and pressure for fire protection.
• In event of fire, large quantities of water should be sprayed on adjacent equipment to cool the
equipment and prevent involvement in the fire. Combination fog and solid stream nozzles are
preferable to permit widest adaptability in fire control.
INTRODUCTION:
The plant is provided with PLC control, which manifest all start up and trip
logics and is the main center of control system. Repeat signals from PLC to
the Customer’s DCS are provided to facilitate operation, monitoring and
control. However air compressor and refrigeration system are controlled by
the vendor local control panels with parameter monitoring facility in the DCS.
PPU sequence logics are repeated in the DCS and can be operated through
DCS.
a) Compressor controls
Compressor controls are performed in compressor control panel supplied by
vendor. Following parameter index indicates the controls available in the local
panel
Seria Parameter Read Alarm Trip Remarks
l No
1 Radial vibration each X X X
stage
2 High discharge Air X X X
rd
temp (inlet to 3
stage
3 High and low oil X X X
temp
4 Low seal air pressure X
5 Surge /unload X X
6 System air discharge- X Controlled by IGV
P through system -P set
point
7 Motor current X Can be Restricted
8 Control mode X
(modulate .auto
dual)
9 Compressor X
load/unload
10 System pressure set X
point
11 IGV and Antisurge X
Valve opening
12 Event logging X
13 Compressor X
ready/not ready
14 Start X
b) Refrigeration unit
Refrigeration unit is provided with thermostatic expansion valve, to regulate
temperature the air temperature. Further temperature control is achieved by
Loading, unloading of Refrigerant compressor cylinders. Temperature
Indicator (RTD) on Air from Chiller is provided. Based on this temperature
Refrigerant compressors are unloaded, loaded. All trips, start up interlocks,
parameter monitoring are available in the PLC control panel. Only start/stop
push buttons are in local push-button station
All parameters (lube oil DP, discharge-P, suction –P, Air outlet temp ex
chiller) running status of the unit and common alarm are configured in DCS (by
customer)
c) PPU
COLD BOX
• Product Purity
1. Product Pressure
2. Turbine inlet pressure
3. Mode change over
4. Product flow rate (LIN and GAN)
5. RL level
6. Waste gas flow rate
7. Waste gas pressure
8. Turbine IGV
PPU Area
Supply pressure
Section- 1:
Unless otherwise specified all the Running interlocks form part of startup interlocks Some
other parameters as required to be checked before startup by system are indicated. Once
started these will be bypassed and system goes by running interlocks.
1) AIR COMPRESSOR:
Interlocks are provided in Vendor’s Local control panel, functioning as per manufacturer’s
practice. Indicative description is furnished below
Local panel Push button HS 1201A/B to start the compressor (96-K-02 (15) A/B)
Local panel push button HS 1202 A/B to stop the compressor (96-K-02 (15) A/B)
Remote compressor A/B STOP/TRIP switch (HS 1203 A/B) available in Aux console
Startup Interlocks
96-M-01(015) Compressor Discharge pressure not high high
96-M-01(015) Compressor suction pressure not low low (start up delay relay)
Oil DP not Low
Cooling water to condenser not low ( DPS contact on )
Trip Interlock
96-M-01(015) Compressor Discharge pressure high high (PI 1283/1285)
96-M-01(015) Compressor suction pressure low low (PI 1282/ 1284)
Oil DP Low Low (PDI 1282)
In the event of above TRIP alarm is generated in PLC and displayed in DCS
and unit is tripped.
This Mode change over shall happen due to the following actions:
By Operator using remote switch HS-1502
LAHH 1501 (96-C-01(25) Level High High
Tank (96-TI-01 A/B) level LI 1601 A/B high high
AAHH 1501 (Oxygen Impurity in Product Nitrogen High High)
PPU trip
Turbine trip/stop YL 1401A/B
Turbine stop:
This interlock is located in PLC, its inputs are directly hardwired. This
interlock prevents the turbine to start due to following events:
QCV position feedback switch ZSL 1401 A is not Close
Seal gas pressure Low (PAL 1404 A)
IGV position feedback switch ZSL 1402 A not close
Lube oil pressure Low PAL 1403A
Turbine Lube Oil return Temp Low TAL 1403A
Lube oil pump not running YL 1403A
All trip interlocks healthy (except Low speed disabled for 30 sec during start)
• Pump start using Hand switch HS 1405 A from local control panel
• By HS 1403 A/B from Auxiliary console
Stop:
Lube oil tank level low (LSL 1401 A): Prevents Oil pump motor to start.
Seal Gas Pressure not Low Low PALL 1404A
Start:
By HS 1407A/B from Local control panel
Stop:
By HS 1407A from Local control panel
Trip interlock: I – 35 – 6A
This interlock is located in MCC; its inputs are directly hardwired. It puts OFF
the Oil heater or trips it if the following event exists:
Oil temperature of Lube oil tank High (TSH 1404 A): Heater is OFF
Oil temperature of Lube oil tank is not high (TSH1404A) subject to heater
switch is on condition: Heater is ON
Oil temperature of Lube oil tank High High (TSHH 1404 A): Heater is tripped.
This Interlock will be activated if the storage tank level LT 1601 A/B high high.
This Interlock will change the plant mode from mixed mode to gas mode.
1) Air compressor:
Air compressor trip signal is generated in LCP of machine and signal sent to
switch gear
In case of compressor trip following equipment’s trips (subject any 2 compressor
trips) and if only compressor trips the plant can run on turn down conditions
PPU trips
Ref unit trips
Regeneration heater trips (if dryer unit is in heating cycle)
Thawing heater Trips (in case of plant is under defrosting)
Turbine trips
2) PPU (I-16)
Heater Trips
5) COLD BOX
Action
De energises FSOV 1502A to close FV 1502A
The product vent valve FV1502 B opens and controls the flow and
discharge -P
Activates I-25 to shift the Plant to Gas Mode
7) TURBINE
Turbine Interlock:
When the plant is shut down & back up system is in line, then LIN from
the tanks is vaporized into GAN. To prevent Low temperature at the
vaporizer outlet, temperature monitoring is done by TE 1601 A/B/C. If
any two of the three elements registered a Low value, then interlock I –
14 takes following action