C1250 D2R 50 Hz 60 Hz

Fuel consumption Standby Prime Standby Prime


kVA (kW) kVA (kW) kVA (kW) kVA (kW)
Ratings 1400 (1120) 1256 (1005) 1588 (1270) 1400 (1120)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 21.9 40.4 58.4 77.4 20.1 36.7 52.6 68.9 27.5 45.8 65.4 87.2 23.5 41.5 58.6 76.9
L/hr 83 153 221 293 76 139 199 261 104 173 248 330 89 157 222 291

Engine Standby Prime Standby Prime


Engine Manufacturer Cummins
Engine Model KTA50G3
Configuration 4-Cycle; 60° Vee; 16-Cylinder Diesel
Aspiration Turbocharged and Aftercooled
Gross engine power output, kWm 1227 1097 1380 1220
Bore, mm 159
Stroke, mm 159
Rated speed, rpm 1500 1800
Piston speed, m/s 7.9 9.5
Compression ratio 13.9:1
Lube oil capacity, L 151
Overspeed limit, rpm 1800 ±150 2100 ±150
Regenerative power, kWm 116 168
Governor type Electronic
Starting voltage 24 Volts DC

Fuel flow
Maximum fuel flow, L/hr 625
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature (°C) 60

Air
Combustion air, m3/min 104.8 96.3 110.4 104.8
Maximum air cleaner restriction, mm H2O 635

Exhaust Standby Prime Standby Prime


Exhaust gas flow at set rated load, m3/min 240.7 223.7 257.7 237.8
Exhaust gas temperature, °C 525 520 475 460
Maximum exhaust back pressure, mm Hg 51