LC5296 LC5296-H 5006RN LC5248E User Manual PDF
LC5296 LC5296-H 5006RN LC5248E User Manual PDF
LC5296 LC5296-H 5006RN LC5248E User Manual PDF
ON-OFF CONTROLLER
LC5296
LC5296-H
5006-RN
LC5248E
INDICATOR
408 - M
1. INTRODUCTION .................................................................................................... 4
Foreword .............................................................................................................. 4
Notice ................................................................................................................... 4
Trademarks .......................................................................................................... 4
Product Ordering Code ........................................................................................ 4
List of Accessories ............................................................................................... 5
Safety Precautions ............................................................................................... 5
2. SPECIFICATIONS ................................................................................................ 6
2.1 Inputs............................................................................................................ 6
2.2 Display & Keys ............................................................................................. 7
2.3 Output Types ................................................................................................ 7
2.4 Communication Details................................................................................. 7
2.5 Power Supply ............................................................................................... 8
2.6 Environmental Conditions............................................................................. 8
2.7 Advance Feature ............................................................................................ 8
Notice
The contents of this manual are subject to change without notice as a result of
continuous improvements to the instrument’s performance and functions.
Every effort has been made to ensure accuracy in the preparation of this manual.
Should any errors or omissions come to your attention, however, please inform
MASIBUS Sales office or sales representative. Under no circumstances may the
contents of this manual, in part or in whole, be transcribed or copied without our
permission.
Trademarks
Our product names or brand names mentioned in this manual are the trademarks or
registered trademarks of Masibus Automation and Instrumentation (P) Ltd. (herein
after referred to as MASIBUS).
Adobe, Acrobat, and Postscript are either registered trademarks or trademarks of
Adobe Systems Incorporated. All other product names mentioned in this user's
manual are trademarks or registered trademarks of their respective companies.
Checking the Contents of the Package
Unpack the box and check the contents before using the product. If the product is
different from which you have ordered, if any parts or accessories are missing, or if
the product appears to be damaged, contact your sales representative.
Product Ordering Code
The Single Loop Controller unit has a nameplate affixed to the one side of the
enclosure. Check the model and suffix codes inscribed on the nameplate to confirm
that the product received is that which was ordered.
Ordering Code
Options Display
Model Input Auxiliary Power Supply
Output-1 Output-2* (Only in LC5296H)
LC5296 1 J U1 80-265VAC / 100-300VDC N None N None 5 0.56”
5006RN 2 K U2 18-36VDC 1 4-20mA 1 4-20mA 8 0.8”
LC5296H 3 T 2 0-20mA 2 0-20mA
LC5248E 4 R 3 1-5V 3 1-5V
5 S 4 0-5V 4 0-5V
6 Pt-100 5 0-10V 5 0-10V
C 4-20mA 6 RS485
D 0-20mA
E 1-5V
F 0-5V
G 0-10V
Output-2= 2nd Retransmission o/p is not possible in LC5296H & LC5248E model;
Only optional RS485 is possible in same.
List of Accessories
The product is provided with the following accessories according to the model and
suffix codes (see the table below). Check that none of them are missing or damaged.
Safety Precautions
The product and the instruction manual describe important information to prevent
possible harm to users and damage to the property and to use the product safely.
Understand the following description (signs and symbols), read the text and
Observe Descriptions.
DESCRIPTION OF SIGN
Loop Power Supply (For LC5296, LC5296-H, 5006-RN, 408-M, LC5248E Only)
Supply Voltage 24VDC (±1V) @26mA with Inbuilt Short Circuit
Protection
3.3 LC5248E
Front Bezel 48 x 48 mm
Panel Cutout 44 x 44 mm
Depth Behind The Panel 115mm
Weight 200g Approx.
Encloser Material ABS
Encloser Protection IP20
Terminal Cable Size 2.5 mm2
4. TERMINAL CONNECTIONS
4.1 LC5296 & 5006-RN
4.3 LC5248E
10 (NC1)
11 (LPS+) 24VDC Loop power supply Terminal 14 is ground Reference.
12 (D+)
Modbus-RTU Communication Output
13 (D-)
14 (NC2)
For Relay-2 potential free Contacts (Use 230V -2A load)
15 (NO2)
16 (C2) On-Off Control o/p.
NOTE:
All wiring must confirm to appropriate standards of good practice and local
codes and regulations. Wiring must be suitable for Voltage, Current and
temperature rating of the system.
Provide power from a single-phase instrument power supply. If there is a lot of
noise in the power line, insert an insulating transformer into the primary side
of the line and use a line filter on the secondary side. Do not place the primary
and secondary power cables close to each other.
For thermocouple input, use shielded compensating lead wires for wiring. For
RTD input, use shielded wires that have low conductor resistance and cause
no significant differences in resistance between the three wires.
Use repeater after each set of 32 instruments connected in RS-485
Communication.
Unused terminals should not be used as jumper points as they may be
internally connected, which may cause damage to the unit.
Unused control terminals should not be used as jumper points as they may be
internally connected, which may cause damage to the unit.
Use >250V-1Amp Cable for Power Supply.
Supply voltage must be below maximum voltage rating specified on the label
If cable has two parallel wires inside then isolation between them must be 2.5
KV.
5.1 Front Panel Description for LC5296, LC5296-H, 5006-RN & LC5248E
NOTE: Two different variant for LC5296-H are available with different PV
Display size.
LC5296-H with 0.56” Display & LC5296-H with 0.8” Display
Name of 5006RN
Symbol Function LC5296
Part LC5296-H
Increment Increment the Value of any
Key Parameter.
Decrement the Value of any
Decrement Parameter.
Key Shows Ambient value for T/C Input
in RUN mode.
Shows Set Point-1(ST-1), if pressed
in RUN mode.
In Sub Menu it can be used to get to
SET-1 Key the next Parameter.
(Menu / It is also used to save the
Enter Key) parameters to nonvolatile memory,
when user setting a proper data by
Increment and decrement key for
parameter configuration.
Shows Set Point-1(ST-2), if pressed
in RUN mode.
SET-2 Key
Also used to store modified
SetPoint-2 Value.
4 digital 0.56 inch RED Display
4 digital 0.8 inch RED Display
(LC5296_0.8”, 408-M Model)
Display process value.
PV
Display parameter name when user
(Present
PV set parameter.
Value)
Display Display Parameter Value when in
Edit mode. (For Single Display
Model Only)
Display error message when an
error occurs.
4 digital 0.4 inch GREEN
SV
Display set value.
(Set
SV Display parameter value of
Value)
Display parameter in process value field
when user set parameter.
Relay-1 ON when Relay-1 is energized &
RL1
Indication OFF otherwise.
Relay-2 ON when Relay-2 is energized &
RL2
Indication OFF otherwise.
TX ON when device is transmitting
Tx
Indication some Data (RS-485).
RX ON when device is receiving some
Rx
Indication Data (RS-485).
Name of
Symbol Function
Part
Increment the Value of any
Increment Parameter in edit mode.
Key Shuffle to next parameter in the
Sub Menu.
Decrement the Value of any
Parameter in edit mode.
Decrement Shuffle to previous parameter in the
Key Sub Menu.
Shows Ambient value for T/C Input
in RUN mode.
Shows different SET Points, if
pressed in RUN mode.
It is used to enter in the sub menu.
SET Key It’s used to enter in the edit mode.
(Menu / It is also used to save the
Enter Key) parameters to nonvolatile memory,
when user setting a proper data by
Increment and decrement key for
parameter configuration.
4 digital 0.40 inch RED Display
Display process value.
Display parameter name when user
PV
set parameter.
(Present
Value)
PV Display Parameter Value when in
Display Edit mode. (For Single Display
Model Only)
Display error message when an
error occurs.
For Thermocouple input type, Press Decrement key to show ambient temperature.
Parameter
(PV display) Se tt in g n a m e a n d De f au l t Sh o w s
de sc r i pt io n va l u e on l y i f
Symbol Name
Parameter
(PV display) Setting Name & Description Default Value Show if Only
Symbol Name
Set PV Input Type
tC j / tC t / tC K / tC r / tC s /
rtd1 / rtd.1 / 0-5v / 1-5v / 0-10
10 to 100
If Device
Supports
SRNO Unit ID for Modbus-RS485 Communication
Serial No. 1 RS-485
(srno) 1 to 247
Communica
tion
Set Modbus RS485 Communication Baud
Rate
If Device
Supports
BAUD 9600 / 19.2k / 38.4k 0
Baud Rate RS-485
(baud) (9600)
Communica
0 : 9600 (9600 bps)
tion
1 : 19.2K (19200 bps)
2 : 38.4K (38400 bps)
Relay Delay is amount of time (in sec), that
Relay 1 will wait before getting ON after
RD 1 Relay Delay
the ON condition occurs. 1 sec
(rd 1) (For Relay-1)
0 to 99 sec
Relay Delay is amount of time (in sec), that
RD 2 Relay Delay Relay 2 will wait before getting ON after
1 sec
(rd 2) (For Relay-2) the ON condition occurs.
0 to 99 sec
Retransmission-1 Output Type
This output is according to PV input.
Zero & Span acts as Min & Max value of
retransmission o/p scale respectively.
PASS
Password Set Device Password0 to 99 1
(pass)
VERS
Version Shows the Version of the Current Firmware -
(vers)
Pa r a me te r
(P V d i s pl a y ) Default
Setting Name & Description Show if Only
Value
Symbol Name
AMB
Ambient Ambient Adjustment - Input is TC
(Amb)
CALZ Calibration Zero for PV Input
Calibration Zero -
(Calz) (PV/SV Display : Current PV)
CALS Calibration Span for PV Input
Calibration Span -
(\Cals) ( PV/SV Display : Current PV)
Calibration Zero for Retransmission Output-1
PV/SV Display :
RTZ1 Retransmission-
For LC5296, LC5296-H(0.56”) & 5006RN -
(rtz1) 1 ZERO
For Current & Voltage: 0
For LC5296-H(0.8”)
If voltage:-0.000 & If Current:-4.000
Calibration Span for Retransmission Output-1
PV/SV Display :
RTS1 Retransmission-
For LC5296, LC5296-H(0.56”) & 5006RN -
(rts1) 1 SPAN
For Current & Voltage: 0
For LC5296-H(0.8”)
If voltage:-8.000 & If Current:-20.00
Calibration Zero for Retransmission Output-2
PV/SV Display :
if Device
RTS2 Retransmission- supports Dual
For LC5296, LC5296-H(0.56”) & 5006RN -
(rts2) 2 SPAN Retransmission
For Current & Voltage: 0
Output
For LC5296-H(0.8”)
If voltage:-8.000 & If Current:-20.00
NOTE:-
For Dual Display Device available option for parameter will be displayed on
SV Display in Edit Mode. For Single Display Device available option for
parameter will be displayed on PV Display in Edit Mode.
The retransmission output type is jumper selectable. Thus if current type or
voltage type output, will be decided by the position of the jumper.
User’s Manual Page 23 of 36
Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13
No need to feed input while calibrating Rx. o/p. just make the value in
calibration mode equal to the displayed value.
Examples:
For Thermocouple input type, Press Decrement key to show ambient temperature.
Parameter
(PV display) Default
Setting Name & Description Show if Only
Value
Symbol Name
Set PV Input Type
Input
Value Range
Type
0 TCJ1 -200 to 1200 °C
INPT 5
INPUT Type 1 TCJ.1 -199.0 to 999.9 °C
(INpt)
2 TCK1 -200 to 1372 °C
(RTD.1)
3 TCK.1 -199.0 to 999.9 °C
4 RTD1 -200 to 850 °C
5 RTD.1 -199.9 to 850.0 °C
6 0-5V -1999 to 1999
7 1-5V -1999 to 1999
*Use external 250ohms,0.1% for current
input
Automatically change to the Input Lower
Range with changing of Input Type
ZERO (Refer Above Table) -199.9
Zero
(zero) (If RTD.1)
Can be set to any value within the Input Range
& less the SPAN Value.
Automatically change to the Input Higher
Range with changing of Input Type
SPAN (Refer Above Table) 850.0
Span
(spaN) (If RTD.1)
Can be set to any value within the Input Range
& greater the ZERO Value.
Set position of Decimal Point on Display.
VERS
Version Shows the Version of the Current Firmware -
(vers)
Parameter
(PV display) Default
Setting Name & Description Show if Only
Value
Symbol Name
AMB
Ambient Ambient Adjustment - Input is TC
(Amb)
ZERO Calibration Calibration Zero for PV Input
-
(zero) Zero (PV/SV Display : PV)
Span Calibration Calibration Span for PV Input
-
(spaN) Span (PV/SV Display : PV)
NOTE:-
For Dual Display Device available option for parameter will be displayed on
SV Display in Edit Mode. For Single Display Device available option for
parameter will be displayed on PV Display in Edit Mode.
Examples:
Since the temperature crosses the set point to change the output stage, the process
temperature will be cycling continually, going from below set point to above, and
back below. In cases where this cycling occurs rapidly, and to prevent contactors
and valves from getting damaged, an on-off differential, or “hysteresis,” is added to
the controller operations. On-Off hysteresis prevents the output from “chattering” or
making fast, continual switches if the cycling above and below the set point occurs
very rapidly.
9. CALIBRATION PROCEDURE
The unit can be calibrated without opening it and without trim pots.
For Entering into the Calibration Mode, Please refer Menu Layout.
After applying appropriate Input from the calibrator source, press ‘INCREMENT’ OR
‘DECREMENT KEY’ to bring the actual process value on display.
Example:-
At zero calibration reading expected on the display is 100 and it shows 107, adjust
the process value to 100 by using ‘DECREMENT KEY’. Now press ‘SET’ to store the
calibration parameter in non-volatile memory. Similarly one can calibrate Ambient,
SPAN and retransmission parameters.
Example:-
10.1 Introduction
The unit can be connected in RS-485 communication data link either in multi drop or
repeat mode. Each unit must have unique Serial Number. Entire range of addresses
(1 to 247) may be used. Before starting any communication, choose a baud rate
compatible to the host computer. The serial protocol used is MODBUS RTU.
The error checking field contains a 16-bit value implemented as two eight-bit bytes. The error check value is the
result of a Cyclical Redundancy Check (CRC) calculation performed on the message contents.
TABLE – 8
Note: 1. Refer Menu Mode Description Table the value & Range of each
Parameter.
EX: Input Type (Applicable Range : 0 to 9):
Input Type Value
J-tc 0
T-tc 1
K-tc 2
R-tc 3
S-tc 4
Rtd 5
Rtd.1 6
0 – 5V 7
1 – 5V 8
0 – 10V 9
11. APPENDIX
11.1 Troubleshooting
If the operating display does not appear after turning on the controller’s power, follow
the measures in the procedure below.
If a problem appears complicated, contact our sales representative.
IMPORTANT
Take note of the parameter settings when asking the vendor for repair.
These units come with different Variants differing by various Output option
available.
There are Two (One for LC5296-H (0.56”)) Addon Card Slots available on
PCB of Signal Card. Among them One Slot is fixed for Retransmission
(Analog) Output. And the other Slot can be used for either Retransmission or
RS-485 Communication Card by appropriate Jumper setting shown in below
figure.
0E (SMD 0805) Resistor is used for shorting the Jumper.
LC5248E
Jumper setting for Communication
Current Output
Voltage Output