LC5296 LC5296-H 5006RN LC5248E User Manual PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 36

User’s Manual

ON-OFF CONTROLLER
LC5296
LC5296-H
5006-RN
LC5248E

INDICATOR
408 - M

Masibus Automation & Instrumentation Pvt. Ltd.


B/30, GIDC Electronics Estate,
Sector-25, Gandhinagar-382044, Gujarat, India
 +91 79 23287275-79  +91 79 23287281-82
Email: [email protected]
Web: www.masibus.com
Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13
Contents

1. INTRODUCTION .................................................................................................... 4
Foreword .............................................................................................................. 4
Notice ................................................................................................................... 4
Trademarks .......................................................................................................... 4
Product Ordering Code ........................................................................................ 4
List of Accessories ............................................................................................... 5
Safety Precautions ............................................................................................... 5

2. SPECIFICATIONS ................................................................................................ 6
2.1 Inputs............................................................................................................ 6
2.2 Display & Keys ............................................................................................. 7
2.3 Output Types ................................................................................................ 7
2.4 Communication Details................................................................................. 7
2.5 Power Supply ............................................................................................... 8
2.6 Environmental Conditions............................................................................. 8
2.7 Advance Feature ............................................................................................ 8

3. PHYSICAL SPECIFICATIONS & MOUNTING DETAILS ..................................... 9


3.1 LC5296 / 5006-RN ...................................................................................... 9
3.2 LC5296-H / 408-M ....................................................................................... 9
3.3 LC5248E ................................................................................................... 10

4. TERMINAL CONNECTIONS .............................................................................. 11


4.1 LC5296 & 5006-RN ................................................................................... 11
4.2 LC5296-H / 408-M ..................................................................................... 12
4.3 LC5248E ................................................................................................... 12
4.5 How to connect wires? .............................................................................. 13

5. FRONT PANEL DETAILS .................................................................................. 15


5.1 Front Panel Description for LC5296, LC5296-H, 5006-RN & LC5248E .... 16
5.2 Front Panel Description for 408-M............................................................. 17

6. MENU LAYOUT FOR LC5296, LC5296-H, 5006-RN, LC5248E ........................ 18


6.1 Run Time Indication/Function .................................................................... 19
6.2 Set Point Setting ........................................................................................ 19
6.3 Configuration Mode ................................................................................... 19
6.4 Calibration Mode ....................................................................................... 23

7. MENU LAYOUT FOR 408-M ............................................................................ 25


User’s Manual Page 2 of 36
Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

7.2 Menu Layout for 408-M .............................................................................. 25


7.3 Run Time Indication/Function ..................................................................... 26
7.5 Configuration Mode .................................................................................... 26
7.6 Calibration Mode ........................................................................................ 27

8. CONTROL FUNCTION ....................................................................................... 28


8.1 ON/OFF Control ........................................................................................ 28

9. CALIBRATION PROCEDURE ............................................................................ 29


9.1 Procedure for CAL-zero and CAL-span ..................................................... 29
9.2 Procedure for RET-zero and RET-span .................................................... 29

10. COMMUNICATION PROTOCOL–MODBUS RTU............................................ 30


10.1 Introduction .............................................................................................. 30
10.2 Parameter Address Details...................................................................... 30
10.3 Exceptional Response ............................................................................. 31

11. APPENDIX ........................................................................................................ 32


11.1 Troubleshooting ....................................................................................... 32
11.2 On-Off Logic ............................................................................................ 33
11.3 Retramission Output Table for Open /Over /Under Condition ................. 33
11.4 Jumper Settings for Add-on Card Selection & Retransmission ............... 34
11.5 Load connection ...................................................................................... 36

User’s Manual Page 3 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13
1. INTRODUCTION
Foreword
Thank you for purchasing ON-OFF Controller- LC5296-H / LC5296 / 5006-RN /
LC5248E and Indicator 408-M.
This manual describes the basic functions and operation methods. Please read
through this user’s manual carefully before using the product.

Notice
The contents of this manual are subject to change without notice as a result of
continuous improvements to the instrument’s performance and functions.
Every effort has been made to ensure accuracy in the preparation of this manual.
Should any errors or omissions come to your attention, however, please inform
MASIBUS Sales office or sales representative. Under no circumstances may the
contents of this manual, in part or in whole, be transcribed or copied without our
permission.

Trademarks
Our product names or brand names mentioned in this manual are the trademarks or
registered trademarks of Masibus Automation and Instrumentation (P) Ltd. (herein
after referred to as MASIBUS).
Adobe, Acrobat, and Postscript are either registered trademarks or trademarks of
Adobe Systems Incorporated. All other product names mentioned in this user's
manual are trademarks or registered trademarks of their respective companies.
Checking the Contents of the Package
Unpack the box and check the contents before using the product. If the product is
different from which you have ordered, if any parts or accessories are missing, or if
the product appears to be damaged, contact your sales representative.
Product Ordering Code
The Single Loop Controller unit has a nameplate affixed to the one side of the
enclosure. Check the model and suffix codes inscribed on the nameplate to confirm
that the product received is that which was ordered.

Ordering Code
Options Display
Model Input Auxiliary Power Supply
Output-1 Output-2* (Only in LC5296H)
LC5296 1 J U1 80-265VAC / 100-300VDC N None N None 5 0.56”
5006RN 2 K U2 18-36VDC 1 4-20mA 1 4-20mA 8 0.8”
LC5296H 3 T 2 0-20mA 2 0-20mA
LC5248E 4 R 3 1-5V 3 1-5V
5 S 4 0-5V 4 0-5V
6 Pt-100 5 0-10V 5 0-10V
C 4-20mA 6 RS485
D 0-20mA
E 1-5V
F 0-5V
G 0-10V
Output-2= 2nd Retransmission o/p is not possible in LC5296H & LC5248E model;
Only optional RS485 is possible in same.

User’s Manual Page 4 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13
Ordering Code
Model Input Auxiliary Power Supply

408-M 1 J U1 85-265 VAC / 100-300 VDC


2 K U2 18-36 VDC
3 T
4 R
5 S
6 Pt-100
C 4-20mA
D 0-20mA
E 1-5 V
F 0-5 V
G 0-10 V

List of Accessories
The product is provided with the following accessories according to the model and
suffix codes (see the table below). Check that none of them are missing or damaged.

No Item name Part number Qty Remarks


1 Mounting Clamps - 2

Safety Precautions
The product and the instruction manual describe important information to prevent
possible harm to users and damage to the property and to use the product safely.
Understand the following description (signs and symbols), read the text and
Observe Descriptions.

DESCRIPTION OF SIGN

User’s Manual Page 5 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13
2. SPECIFICATIONS
2.1 Inputs
Analog Input
Input Type Thermocouple, RTD (Pt100), Current, Voltage
Display Range Refer Table-2.1
Accuracy + (0.25% of Full Span + 1 degree) for T/C and RTD
input.
+ (0.1% of Full Span + 1 count) for Linear input.
ADC Resolution 16 bits
Display Resolution 0.1°C / 1 Count
Sampling Rate 5 Samples/Sec
CJC Error ±3.0 °C Max
Sensor open Detection All inputs except 0-5V, 0-10V
Sensor Burnout current 0.25uA
RTD excitation current 0.166mA (Approx)
Allowable wiring resistance for Maximum 15 ohms/wire (Conductor
RTD resistance between three wires should be equal)
NMRR > 40 dB
CMRR > 120 dB
Temp-co < 150ppm/°C
Input Impedance > 1MΩ (Voltage Input)
250Ω (Current Input)
Max Voltage 20VDC

Input type Range


PT100 (0.1ºC) -199.9 to 850.0 ºC
PT100 (1ºC) -200 to 850ºC
J -199.9 to 1200ºC
K -199.9 to 1372ºC
T -199.9 to 400ºC
R 0 to 1768ºC
S 0 to 1768ºC
*4-20mA /1-5VDC, -1999 to 9999
*0-20mA /0-5VDC (Field Scalable)
0-10VDC -1999 to 9999
(Field Scalable)
Table-2.1
*Use external 250ohms, 0.1% for current Input

User’s Manual Page 6 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

2.2 Display & Keys

Model Display Specification


PV Display 4-Digit, 7-Segment, Red, Character height of 0.56”
SV / Parameter
LC5296 4-Digit, 7-Segment, Green, Character height of 0.40”
Display
Status Indication Individual RED Led for Relay & Communication Status
4-Digit, 7-Segment, Red, Character height of 0.56”
PV / Parameter
LC5296-H or
Display2
4-Digit, 7-Segment, Red, Character height of 0.8”
Status Indication Individual RED Led for Relay & Communication Status
5006-RN PV Display 4-Digit, 7-Segment, Red, Character height of 0.56”
Status Indication Individual RED Led for Relay & Communication Status
408-M PV Display 4-Digit, 7-Segment, Red, Character height of 0.8”
LC5248E PV Display 4-Digit, 7-Segment, Red, Character height of 0.40”
SV / Parameter
4-Digit, 7-Segment, Green, Character height of 0.28”
Display1
Status Indication Individual RED Leds for Relay Status, Rx,Tx
NOTE:
1. LC5296-H is available with Two Different variant.
 LC5296-H with 0.8” PV Display.
 LC5296-H with 0.56” PV Display.

2.3 Output Types


Relay Output
Relays 2 (Not available in 408-M)
Type Single Change over
LC5296/LC5296-H/5006-RN : Three Terminals (C, NO, NC)
Rating 2A @ 230VAC / 30VDC

Retransmission Output (For LC5296, LC5296-H, 5006-RN Only)


Number of output 1 / 2 (Specified in Order Code)
Output According to Process Value
Output Signal 4-20mA / 0-20mA /1-5VDC / 0-10V DC
Load resistance
 For Current o/p < 500Ω.
 For Voltage o/p > 3KΩ.
Output accuracy ±0.25% of span

Loop Power Supply (For LC5296, LC5296-H, 5006-RN, 408-M, LC5248E Only)
Supply Voltage 24VDC (±1V) @26mA with Inbuilt Short Circuit
Protection

2.4 Communication Details


Communication (For LC5296, LC5296-H, 5006-RN, LC5248E Only)
Interface RS485 (2 Wire)

User’s Manual Page 7 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13
Protocol Modbus-RTU
Baud rate 9600, 19200, 38400 bps

2.5 Power Supply


Standard 85-265VAC/ 100-300VDC
Optional 18-36VDC
Power consumption <10 VA (LC5296/LC5296-H/5006-RN,408-M)
Data backup Non-volatile memory (can be written up to 100000 times)

Isolation (Withstanding voltage)


 Between primary terminals* and secondary terminals**:

At least 1500 V AC for 1 minute


 Between primary terminals* and grounding terminal:

At least 1500 V AC for 1 minute


 Between grounding terminal and secondary terminals**:

At least 1500 V AC for 1 minute


 Between secondary terminals**:

At least 500 V AC for 1 minute


* Primary terminals indicate power terminals and relay output terminals.
** Secondary terminals indicate analog I/O signal and Communication O/P.
Insulation resistance: 20MΩ or more at 500 V DC between power terminals and
grounding terminal.

2.6 Environmental Conditions


TEMPCO For Input to PV Display < 100ppm. FOR Display to
Retransmission and Control output < 100ppm
Humidity 20% to 95% RH (Non-Condensing)
Instrument Warm-up Time Approx. 15 minutes
Ambient temperature 0 to 55°C
Storage Temperature 0 to 80°C

2.7 Advance Feature

 Input scalability for linear input

User’s Manual Page 8 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

3. PHYSICAL SPECIFICATIONS & MOUNTING DETAILS


3.1 LC5296 / 5006-RN
Front Bezel 96 x 96 mm
Panel Cutout 92mm(+0.8) x 92mm(+0.8)
Depth Behind The Panel 65 mm with Terminal
Weight 300g Approx.
Enclosure Material ABS
Enclosure Protection IP20
Terminal Cable Size 2.5 mm2

Fig 3.1: Mounting Details for LC5296 / 5006-RN

3.2 LC5296-H / 408-M


Front Bezel 48 x 96 mm
Panel Cutout 45mm(+0.6) x 92mm(+0.8)
Depth Behind The Panel 75 mm with Terminal
Weight 250g Approx.
Enclosure Material ABS
Enclosure Protection IP20
Terminal Cable Size 2.5 mm2

User’s Manual Page 9 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

Fig 3.3: Mounting Details for LC5296-H(0.56”)

3.3 LC5248E
Front Bezel 48 x 48 mm
Panel Cutout 44 x 44 mm
Depth Behind The Panel 115mm
Weight 200g Approx.
Encloser Material ABS
Encloser Protection IP20
Terminal Cable Size 2.5 mm2

Fig 3.2: Mounting Details for LC5248E

User’s Manual Page 10 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

4. TERMINAL CONNECTIONS
4.1 LC5296 & 5006-RN

Fig 4.1: Terminal Connection Detail of LC5296 / 5006-RN

Terminal No. Description


2 (NC1)
 For Relay-1 potential free Contacts (Use 230V -2A load)
3 (NO1)
4 (C1)  On-Off Control o/p.
5 (NC2)
 For Relay-2 potential free Contacts (Use 230V -2A load)
6 (NO2)
7 (C2)  On-Off Control o/p.
8 (Earth) Earth Connection
9 (N/-)
Power Supply Input
10 (L/+)
11 (LPS+) 24VDC Loop power supply Terminal 14 is ground Reference.
12 For RTD Input Only (Three wire Compensation).
13 (TC+/ V+)
For Thermocouple, RTD & Linear Input
14 (TC- / V- / LPS-)
17 (Rx1+)
 For Retransmission-1 output
18 (Rx1-)
19 (Rx2+ / D+)  For Retransmission-2 output
20 (Rx2- / D-)  Modbus-RTU Communication Output

User’s Manual Page 11 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13
4.2 LC5296-H / 408-M

Fig 4.4: Terminal Connection Detail of LC5296-H(0.56”)

Terminal No. Description


1 (LPS+) 24VDC Loop power supply Terminal 4 is ground Reference.
2 For RTD Input Only (Three wire Compensation).
3 (TC+/ V+)
For Thermocouple, RTD & Linear Input
4 (TC- / V- / LPS-)
9 (L/+)
Power Supply Input
10 (N/-)

4.3 LC5248E

Fig 4.5: Terminal Connection Detail of LC5248E

Terminal No. Description


1 For RTD Input Only (Three wire Compensation).
2 (TC+/ V+)
For Thermocouple, RTD & Linear Input
3 (TC- / V- / LPS-)
4 (Rx1+)
 For Retransmission-1 output
5 (Rx1-)
6 (N/-)
Power Supply Input
7 (L/+)
8 (C1)  For Relay-1 potential free Contacts (Use 230V -2A load)
9 (NO1)  On-Off Control o/p.
User’s Manual Page 12 of 36
Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

10 (NC1)
11 (LPS+) 24VDC Loop power supply Terminal 14 is ground Reference.
12 (D+)
 Modbus-RTU Communication Output
13 (D-)
14 (NC2)
 For Relay-2 potential free Contacts (Use 230V -2A load)
15 (NO2)
16 (C2)  On-Off Control o/p.

Fig 4.6: Lead Termination Detail

4.5 How to connect wires?


Before carrying out wiring, turn off the power to the controller and check that the
cables to be connected are not alive because there is a possibility of electric shock.

NOTE:

 All wiring must confirm to appropriate standards of good practice and local
codes and regulations. Wiring must be suitable for Voltage, Current and
temperature rating of the system.
 Provide power from a single-phase instrument power supply. If there is a lot of
noise in the power line, insert an insulating transformer into the primary side
of the line and use a line filter on the secondary side. Do not place the primary
and secondary power cables close to each other.
 For thermocouple input, use shielded compensating lead wires for wiring. For
RTD input, use shielded wires that have low conductor resistance and cause
no significant differences in resistance between the three wires.
 Use repeater after each set of 32 instruments connected in RS-485
Communication.
 Unused terminals should not be used as jumper points as they may be
internally connected, which may cause damage to the unit.
 Unused control terminals should not be used as jumper points as they may be
internally connected, which may cause damage to the unit.
 Use >250V-1Amp Cable for Power Supply.
 Supply voltage must be below maximum voltage rating specified on the label
 If cable has two parallel wires inside then isolation between them must be 2.5
KV.

User’s Manual Page 13 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

Fig 4.7: RS485 Connection Details

User’s Manual Page 14 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

5. FRONT PANEL DETAILS

User’s Manual Page 15 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

5.1 Front Panel Description for LC5296, LC5296-H, 5006-RN & LC5248E
 NOTE: Two different variant for LC5296-H are available with different PV
Display size.
 LC5296-H with 0.56” Display & LC5296-H with 0.8” Display

Name of 5006RN
Symbol Function LC5296
Part LC5296-H
Increment  Increment the Value of any
 
Key Parameter.
 Decrement the Value of any
Decrement Parameter.
 
Key  Shows Ambient value for T/C Input
in RUN mode.
 Shows Set Point-1(ST-1), if pressed
in RUN mode.
 In Sub Menu it can be used to get to
SET-1 Key the next Parameter.
(Menu /  It is also used to save the  
Enter Key) parameters to nonvolatile memory,
when user setting a proper data by
Increment and decrement key for
parameter configuration.
 Shows Set Point-1(ST-2), if pressed
in RUN mode.
SET-2 Key  
 Also used to store modified
SetPoint-2 Value.
 4 digital 0.56 inch RED Display
 4 digital 0.8 inch RED Display
(LC5296_0.8”, 408-M Model)
 Display process value.
PV
 Display parameter name when user
(Present
PV set parameter.  
Value)
Display  Display Parameter Value when in
Edit mode. (For Single Display
Model Only)
 Display error message when an
error occurs.
 4 digital 0.4 inch GREEN
SV
 Display set value.
(Set
SV  Display parameter value of  
Value)
Display parameter in process value field
when user set parameter.
Relay-1  ON when Relay-1 is energized &
RL1  
Indication OFF otherwise.
Relay-2  ON when Relay-2 is energized &
RL2  
Indication OFF otherwise.
TX  ON when device is transmitting
Tx  
Indication some Data (RS-485).
RX  ON when device is receiving some
Rx  
Indication Data (RS-485).

User’s Manual Page 16 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

5.2 Front Panel Description for 408-M

Name of
Symbol Function
Part
 Increment the Value of any
Increment Parameter in edit mode.
Key  Shuffle to next parameter in the
Sub Menu.
 Decrement the Value of any
Parameter in edit mode.
Decrement  Shuffle to previous parameter in the
Key Sub Menu.
 Shows Ambient value for T/C Input
in RUN mode.
 Shows different SET Points, if
pressed in RUN mode.
 It is used to enter in the sub menu.
SET Key  It’s used to enter in the edit mode.
(Menu /  It is also used to save the
Enter Key) parameters to nonvolatile memory,
when user setting a proper data by
Increment and decrement key for
parameter configuration.
 4 digital 0.40 inch RED Display
 Display process value.
 Display parameter name when user
PV
set parameter.
(Present
Value)
PV  Display Parameter Value when in
Display Edit mode. (For Single Display
Model Only)
 Display error message when an
error occurs.

User’s Manual Page 17 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

6. MENU LAYOUT FOR LC5296, LC5296-H, 5006-RN, LC5248E

User’s Manual Page 18 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

6.1 Run Time Indication/Function

Following parameters can view or change during run time.

 For Thermocouple input type, Press Decrement key to show ambient temperature.

6.2 Set Point Setting

Parameter
(PV display) Se tt in g n a m e a n d De f au l t Sh o w s
de sc r i pt io n va l u e on l y i f
Symbol Name

ST-1 Set Point 1


Range Depending on PV
10 0 -
(st-1) sensor type selected

ST-2 Set Point 2


Range Depending on PV
20 0 -
(st-2) sensor type selected

6.3 Configuration Mode

Parameter
(PV display) Setting Name & Description Default Value Show if Only
Symbol Name
Set PV Input Type
tC j / tC t / tC K / tC r / tC s /
rtd1 / rtd.1 / 0-5v / 1-5v / 0-10

Value Input Type Range


0 TC J -199.9 to 1200 °C
1 TC T -199.9 to 400 °C
2 TC K -199.9 to 1372 °C
3 TC R 0 to 1768 °C
4 TC S 0 to 1768 °C
INPT
INPUT Type 5 RTD -200 to 850 °C TC K
(inpt)
6 RTD.1 -199.9 to 850.0°C
0-5 V/ 0-20
7
mA*
1-5 V / 4-20 -1999 to 9999
8
mA*
9 0-10 V

*Use external 250ohms,0.1% for


current input

Automatically change to the Input Lower


Range with changing of Input Type
ZERO (Refer Above Table) -200
Zero
(zero) (If TC K)
Can be set to any value within the Input
Range & less the SPAN Value.

User’s Manual Page 19 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13
Automatically change to the Input Higher
Range with changing of Input Type
SPAN (Refer Above Table) 1372
Span
(span) (If TC K)
Can be set to any value within the Input
Range & greater the ZERO Value.
Automatically change to the Input Lower
Range with changing of Input Type
INLO (Refer Above Table) 0 Only in
(inlo) (if 0- 10V) Linear input
Can be set to any value within the Input
Range & less the SPAN Value.
Automatically change to the Input Higher
Range with changing of Input Type
INHI (Refer Above Table) 10 Only in
(inhi) (if 0- 10V) Linear input
Can be set to any value within the Input
Range & greater the ZERO Value.
Set Type of Set Point l-on / H-on
TSP1 Type of 0
0 : L-ON (Lower ON)
(tsp1) Set Point-1 (L-ON)
1 : H-ON (Higher ON)
Refer ON-OFF Control on Page:30
Set Type of Set Point l-on / H-on
TSP2 Type of 0
0 : L-ON (Lower ON)
(tsp2) Set Point-2 (L-ON)
1 : H-ON (Higher ON)
Refer ON-OFF Control on Page:30
Set Control O/P & Retransmission state
when Input OPEN condition.

OPES OPEN Sensor down / up 0


(opes) Status (DOWN)
0 : DOWN
1 : UP
Refer Page:35
Set position of Decimal Point on Display.
0 / 0.0 / 0.00 / 0.000
DP
Decimal Point 0:0 0
(dp)
0.0 : 1
0.00 : 2
0.000 : 3
Set which Set Point to shown in SV display
in RUN mode while device is in Auto Mode
Available for
DISP Display Set
0 LC5296
(disp) Point ST-1 / st-2
only
0 : ST-1 (Set Point 1)
1 : ST-2 (Set Point 2)
BRHT Adjust Brightness of the 7-segment
Brightness 50
(brHt) Display.

User’s Manual Page 20 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

10 to 100
If Device
Supports
SRNO Unit ID for Modbus-RS485 Communication
Serial No. 1 RS-485
(srno) 1 to 247
Communica
tion
Set Modbus RS485 Communication Baud
Rate
If Device
Supports
BAUD 9600 / 19.2k / 38.4k 0
Baud Rate RS-485
(baud) (9600)
Communica
0 : 9600 (9600 bps)
tion
1 : 19.2K (19200 bps)
2 : 38.4K (38400 bps)
Relay Delay is amount of time (in sec), that
Relay 1 will wait before getting ON after
RD 1 Relay Delay
the ON condition occurs. 1 sec
(rd 1) (For Relay-1)
0 to 99 sec
Relay Delay is amount of time (in sec), that
RD 2 Relay Delay Relay 2 will wait before getting ON after
1 sec
(rd 2) (For Relay-2) the ON condition occurs.
0 to 99 sec
Retransmission-1 Output Type
This output is according to PV input.
Zero & Span acts as Min & Max value of
retransmission o/p scale respectively.

0-5v / 1-5v / 0-10 / 4-20 / 0-20


RT-1 Retransmission 0
0 : 0-5V
(rt-1) 1 Type (0-5V)
1 : 1-5V
2 : 0-10V
3 : 4-20mA
4 : 0-20mA

Voltage or Current is Jumper Selectable


from the Hardware.

User’s Manual Page 21 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

Retransmission-2 Output Type


This output is according to PV input.
Zero & Span acts as Min & Max value of
retransmission o/p scale respectively.

0-5v / 1-5v / 0-10 / 4-20 / 0-20 if Device


supports
RT-2 Retransmission 0
0 : 0-5V Dual
(rt-2) 2 Type (0-5V)
1 : 1-5V Retransmiss
2 : 0-10V ion Output
3 : 4-20mA
4 : 0-20mA

Voltage or Current is Jumper Selectable


from the Hardware.

Hysteresis Value (in °C) for Relay-1 during


ON-OFF type Control.

1 to 100 TC & RTD Input


HY-1 Hysteresis – 1 0.1 to 10.0 RTD.1 Input
1 to 100 Linear Input with DP=0 5
(Hy-1) (For Relay-1)
0.1 to 10.0 Linear Input with DP=1
0.01 to 1.00 Linear Input with DP=2
0.001 to Linear Input with DP=3
0.100

Hysteresis Value (in °C) for Relay-2 during


ON-OFF type Control.

1 to 100 TC & RTD Input


HY-2 Hysteresis – 2 0.1 to 10.0 RTD.1 Input
1 to 100 Linear Input with DP=0 5
(Hy-2) (For Relay-2)
0.1 to 10.0 Linear Input with DP=1
0.01 to 1.00 Linear Input with DP=2
0.001 to Linear Input with DP=3
0.100

PASS
Password Set Device Password0 to 99 1
(pass)

VERS
Version Shows the Version of the Current Firmware -
(vers)

User’s Manual Page 22 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

6.4 Calibration Mode

Pa r a me te r
(P V d i s pl a y ) Default
Setting Name & Description Show if Only
Value
Symbol Name
AMB
Ambient Ambient Adjustment - Input is TC
(Amb)
CALZ Calibration Zero for PV Input
Calibration Zero -
(Calz) (PV/SV Display : Current PV)
CALS Calibration Span for PV Input
Calibration Span -
(\Cals) ( PV/SV Display : Current PV)
Calibration Zero for Retransmission Output-1

PV/SV Display :
RTZ1 Retransmission-
For LC5296, LC5296-H(0.56”) & 5006RN -
(rtz1) 1 ZERO
For Current & Voltage: 0

For LC5296-H(0.8”)
If voltage:-0.000 & If Current:-4.000
Calibration Span for Retransmission Output-1

PV/SV Display :
RTS1 Retransmission-
For LC5296, LC5296-H(0.56”) & 5006RN -
(rts1) 1 SPAN
For Current & Voltage: 0

For LC5296-H(0.8”)
If voltage:-8.000 & If Current:-20.00
Calibration Zero for Retransmission Output-2

PV/SV Display : if Device


RTZ2 Retransmission- For LC5296, LC5296-H(0.56”) & 5006RN supports Dual
-
(rtz2) 2 ZERO For Current & Voltage: 0 Retransmission
Output
For LC5296-H(0.8”)
If voltage:-0.000 & If Current:-4.000
Calibration Span for Retransmission Output-2

PV/SV Display :
if Device
RTS2 Retransmission- supports Dual
For LC5296, LC5296-H(0.56”) & 5006RN -
(rts2) 2 SPAN Retransmission
For Current & Voltage: 0
Output
For LC5296-H(0.8”)
If voltage:-8.000 & If Current:-20.00

NOTE:-
For Dual Display Device available option for parameter will be displayed on
SV Display in Edit Mode. For Single Display Device available option for
parameter will be displayed on PV Display in Edit Mode.
The retransmission output type is jumper selectable. Thus if current type or
voltage type output, will be decided by the position of the jumper.
User’s Manual Page 23 of 36
Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13
No need to feed input while calibrating Rx. o/p. just make the value in
calibration mode equal to the displayed value.
Examples:

1. How to change Input Type?

LC5296/LC5248E LC5296-H / 5006-RN

2. How to change Set Point-1?

LC5296/LC5248E LC5296-H & 5006-RN

User’s Manual Page 24 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

7. MENU LAYOUT FOR 408-M


7.2 Menu Layout for 408-M

User’s Manual Page 25 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13
7.3 Run Time Indication/Function
Following parameters can view or change during run time.

 For Thermocouple input type, Press Decrement key to show ambient temperature.

7.5 Configuration Mode

Parameter
(PV display) Default
Setting Name & Description Show if Only
Value
Symbol Name
Set PV Input Type

tCj1 / tCj.1 / tCK1 / tCk.1 / rtd1 /


rtd.1 / 0-5v /1-5v

Input
Value Range
Type
0 TCJ1 -200 to 1200 °C
INPT 5
INPUT Type 1 TCJ.1 -199.0 to 999.9 °C
(INpt)
2 TCK1 -200 to 1372 °C
(RTD.1)
3 TCK.1 -199.0 to 999.9 °C
4 RTD1 -200 to 850 °C
5 RTD.1 -199.9 to 850.0 °C
6 0-5V -1999 to 1999
7 1-5V -1999 to 1999
*Use external 250ohms,0.1% for current
input
Automatically change to the Input Lower
Range with changing of Input Type
ZERO (Refer Above Table) -199.9
Zero
(zero) (If RTD.1)
Can be set to any value within the Input Range
& less the SPAN Value.
Automatically change to the Input Higher
Range with changing of Input Type
SPAN (Refer Above Table) 850.0
Span
(spaN) (If RTD.1)
Can be set to any value within the Input Range
& greater the ZERO Value.
Set position of Decimal Point on Display.

0 / 0.0 / 0.00 / 0.000


DP Input Type is
Decimal Point 0
(dp) 0:0 Linear
1 : 0.0
2 : 0.00
3 : 0.000
Adjust Brightness of the 7-segment Display.
BRHT
Brightness 50
(brHt)
10 to 100
Set Device Password
PASS
Password 1
(pass)
0 to 9999
User’s Manual Page 26 of 36
Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

VERS
Version Shows the Version of the Current Firmware -
(vers)

7.6 Calibration Mode

Parameter
(PV display) Default
Setting Name & Description Show if Only
Value
Symbol Name
AMB
Ambient Ambient Adjustment - Input is TC
(Amb)
ZERO Calibration Calibration Zero for PV Input
-
(zero) Zero (PV/SV Display : PV)
Span Calibration Calibration Span for PV Input
-
(spaN) Span (PV/SV Display : PV)

NOTE:-
For Dual Display Device available option for parameter will be displayed on
SV Display in Edit Mode. For Single Display Device available option for
parameter will be displayed on PV Display in Edit Mode.

Examples:

1. How to change Set Point 2. How to change Input Type

User’s Manual Page 27 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13
8. CONTROL FUNCTION
8.1 ON/OFF Control
ON/OFF Controller is the simplest form of temperature control device. The output
from the device is either on or off, with no middle state. An on-off controller will
switch the output only when the temperature crosses the set point. For heating
control, the output is on when the temperature is below the set point, and off above
set point.

Since the temperature crosses the set point to change the output stage, the process
temperature will be cycling continually, going from below set point to above, and
back below. In cases where this cycling occurs rapidly, and to prevent contactors
and valves from getting damaged, an on-off differential, or “hysteresis,” is added to
the controller operations. On-Off hysteresis prevents the output from “chattering” or
making fast, continual switches if the cycling above and below the set point occurs
very rapidly.

Figure 8.1: Typical Relay operation

High type (H-ON):


For High type of set value, once process value reaches up to set point + Hysteresis
value, relay will be ON after few seconds (as per relay delay) and it will be ON until
process value goes down to Set point.

Low type (L-ON):


For Low type of set value, once process value reaches down to set point –
Hysteresis value relay will be ON after nearly few seconds (as per relay delay) and it
will be ON until process value goes up toward Set point.

User’s Manual Page 28 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

9. CALIBRATION PROCEDURE

9.1 Procedure for CAL-zero and CAL-span


The instrument is factory calibrated for the specified range, but due to long term drift
of components, re-calibration may be necessary in some cases. For calibrating the
instrument a reliable source is required. This source should be at least ten times
accurate compared to the range of the instrument.

The unit can be calibrated without opening it and without trim pots.

For Entering into the Calibration Mode, Please refer Menu Layout.
After applying appropriate Input from the calibrator source, press ‘INCREMENT’ OR
‘DECREMENT KEY’ to bring the actual process value on display.

Example:-
At zero calibration reading expected on the display is 100 and it shows 107, adjust
the process value to 100 by using ‘DECREMENT KEY’. Now press ‘SET’ to store the
calibration parameter in non-volatile memory. Similarly one can calibrate Ambient,
SPAN and retransmission parameters.

9.2 Procedure for RET-zero and RET-span


(Applicable only for LC5296, LC5296-H, 5006-RN, LC5248E)
For calibrating the retransmission output, both retransmission zero and
retransmission span has to be calibrated. At a time there can be either one or two
retransmission output available. If only one retransmission is used, then calibrate
RTZ1 (retransmission 1 zero) and RTS1 (retransmission 1 span) and if there are two
retransmission outputs available, then calibrate RTZ2 (retransmission 2 zero) and
RTS2 (retransmission 2 span) for second retransmission. No need to feed input
while calibrating retransmission o/p. it is like calibrating using digital trim pot. Only
look at the output, display value has no significance with output generated.

Example:-

For LC5296, LC5296-H(0.56”), 5006-RN, LC5248E


At retransmission zero calibration, expected output is 4.00mA and it gives 4.153mA.
Then adjust the output value to 4.000 by using ‘DECREMENT KEY’. Now press
‘SET1’ to store the calibration parameter in non-volatile memory. Similarly one can
calibrate retransmission span.

User’s Manual Page 29 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13
10. COMMUNICATION PROTOCOL–MODBUS RTU

(Applicable only for LC5296, LC5296-H, 5006-RN, LC5248E)

10.1 Introduction
The unit can be connected in RS-485 communication data link either in multi drop or
repeat mode. Each unit must have unique Serial Number. Entire range of addresses
(1 to 247) may be used. Before starting any communication, choose a baud rate
compatible to the host computer. The serial protocol used is MODBUS RTU.

Function Code for Modbus

CODE NAME Function


01 Read coil status Use to read Relay and Digital output status
03 Read Holding registers Use to read PV, Control, RSP output etc
04 Read input registers Use to read programmable registers
06 Preset Single register Use to write programmable register

The error checking field contains a 16-bit value implemented as two eight-bit bytes. The error check value is the
result of a Cyclical Redundancy Check (CRC) calculation performed on the message contents.

10.2 Parameter Address Details

Sr. Absolute Access 5006-RN


Parameters Type LC5296
No. Address Type LC5296-H

PROCESS VALUE Read  


1 30001 Int
Only

NOTE: Process Value (PV) Error Conditions Value


OPEN : 32767
UNDER : 32765
OVER : 32766

Sr. Absolute Access 5006-RN


Parameters Type LC5296
No. Address Type LC5296-H
1 Input Type 40001 Int R+W  
2 Zero 40002 Int R+W  
3 Span 40003 Int R+W  
4 SET Type-1 40004 Int R+W  
5 SET Type-2 40005 Int R+W  
6 Open Sensor Status 40006 Int R+W  
7 Decimal Point 40007 Int R+W  
8 Display set point 40008 Int R+W  
9 Brightness 40009 Int R+W  
10 Serial Number 40010 Int R+W  
11 Baud Rate 40011 Int R+W  
12 Relay Delay -1 40012 Int R+W  
13 Relay Delay -2 40013 Int R+W  
14 Retransmission o/p Type -1 40014 Int R+W  
15 Retransmission o/p Type -2 40015 NA NA  
User’s Manual Page 30 of 36
Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

16 Hysteresis 1 40016 Int R+W  


17 Hysteresis 2 40017 Int R+W  
18 Pass word 40018 Int R+W  
19 Set Value 1 40019 Int R+W  
20 Set Value 2 40020 Int R+W  
21 INLO 40021 Int R+W  
22 INHI 40022 Int R+W  

10.3 Exceptional Response


CODE MEANING
Function code Invalid. It must be 01, 05, 03 or 06.The function code received in
01
the query is not allowable action for the slave.
Illegal address value. The data address received in the query is not an
02
allowable address for the salve.
Illegal data value. A value contained in the query data field is not an allowable
03
value for the salve.
When Master device write some parameters to Slave device, If slave device
06
busy then it will send 06 code to indicate slave device is busy.

TABLE – 8

Note: 1. Refer Menu Mode Description Table the value & Range of each
Parameter.
EX: Input Type (Applicable Range : 0 to 9):
Input Type Value
J-tc 0
T-tc 1
K-tc 2
R-tc 3
S-tc 4
Rtd 5
Rtd.1 6
0 – 5V 7
1 – 5V 8
0 – 10V 9

User’s Manual Page 31 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

11. APPENDIX
11.1 Troubleshooting

If the operating display does not appear after turning on the controller’s power, follow
the measures in the procedure below.
If a problem appears complicated, contact our sales representative.

IMPORTANT
Take note of the parameter settings when asking the vendor for repair.

User’s Manual Page 32 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

11.2 On-Off Logic

Relay type PV Relay LED


Hi-On PV > SP On On
PV < SP Off Off
Open sensor Up scale On On
Down scale Off Off
Low-On PV > SP Off Off
PV < SP On On
Open sensor Up scale Off Off
Down scale On On

11.3 Retramission Output Table for Open /Over /Under Condition


(Applicable only for LC5296, LC5296-H, 5006-RN)

RETRASMISSION VARIABLE SCALE ACTION OPEN OVER UNDER

4-20mA PV UP DIR 20.8 20.8 3.2

PV DOWN REV 20.8 3.2 20.8

PV UP REV 3.2 3.2 20.8

PV DOWN DIR 3.2 20.8 3.2

1-5V PV UP DIR 5.2V 5.2V 0.8V

PV DOWN REV 5.2V 0.8V 5.2V

PV UP REV 0.8V 0.8V 5.2V

PV DOWN DIR 0.8V 5.2V 0.8V

NOTE: -1. OPEN/UNDER/OVER condition is applicable to all input types except


0-5v / 0-20mA.

User’s Manual Page 33 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

11.4 Jumper Settings for Add-on Card Selection & Retransmission


Output Type

(Applicable only for LC5296 / LC5296-H / 5006-RN, LC5248E)

 These units come with different Variants differing by various Output option
available.
 There are Two (One for LC5296-H (0.56”)) Addon Card Slots available on
PCB of Signal Card. Among them One Slot is fixed for Retransmission
(Analog) Output. And the other Slot can be used for either Retransmission or
RS-485 Communication Card by appropriate Jumper setting shown in below
figure.
 0E (SMD 0805) Resistor is used for shorting the Jumper.

User’s Manual Page 34 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

LC5248E
Jumper setting for Communication

There are mainly Two types of Retransmission Output is available:


o Voltage (0-10VDC, 0-5VDC, 1-5VDC)
o Current (4-20mADC, 0-20mADC)
 This can be Settable by changing the Position of Shorting Link Jumpers on
Retransmission Add-on Card shown in below figure.

Jumper Setting for Retransmission card: m61Cao201

Jumper Setting for Retransmission card: m61Cao102

Jumper Setting for Retransmission card: m49Acp101

User’s Manual Page 35 of 36


Model: LC5296-H / LC5296 / 5006-RN / 408-M / LC5248E
Doc. Ref. no.:- m61C/om/101
Issue no. 13

Current Output

Voltage Output

11.5 Load connection

Electrical precautions during use

Electrical noise generated by switching of inductive loads can create momentary


disruption, erratic display, latch up, data loss or permanent damage to the
instrument. Use of snubber circuits across loads as shown above, is recommended.

User’s Manual Page 36 of 36

You might also like