Ahsan
Ahsan
Ahsan
Introduction:
Today we are going to discuss Types of Electrical Transformer which are the most costly
protection system of the electrical system. As all we know transformers are generally used to step up
and step down the voltage level. Since transformer working under several voltage levels, it’s also
require to have better protection in the transformers. There are the several type of transformer faults
occurs and it can mainly divide into Internal faults and through faults.Internal fault of the
transformers mainly happened due to the insulation breakdown of it.Insulation breakdown create
short-circuit conditions inside the transformers. This will cause hazard situations so we need to
special attention on this type of transformer fault.
Over heating
Protection Devices:
The following discusses protection devices typically delivered as a part of the power transformer
delivery.
2. Pressure Relay
4. Winding Thermometer
The power transformer protection as a whole and the utilization of the below presented protection
devices are not discussed here.
The Buchholz protection is a mechanical fault detector for electrical faults in oil-immersed
transformers. The Buchholz (gas) relay is placed in the piping between the transformer main tank and
the oil conservator. The conservator pipe must be inclined slightly for reliable operation.
Often there is a bypass pipe that makes it possible to take the Buchholz relay out of service.
The Buchholz protection is a fast and sensitive fault detector. It works independent of the number of
transformer windings, tap changer position and instrument transformers. If the tap changer is of the
on-tank (container) type, having its own oil enclosure with oil conservator, there is a dedicated
Buchholz relay for the tap changer.
A typical Buchholz protection comprises a pivoted float (F) and a pivoted vane (V) as shown in Figure 1.
The float carries one mercury switch and the vane also carries another mercury switch. Normally, the
casing is filled with oil and the mercury switches are open.
When the pressure in front of the piston exceeds the counter force of the spring, the piston will move
operating the switching contacts. The micro switch inside the switching unit is hermetically sealed and
pressurized with nitrogen gas.The simplest form of pressure relief device is the widely used frangible
disk. The surge of oil caused by a heavy internal fault bursts the disk and allows the oil to discharge
rapidly. Relieving and limiting the pressure rise prevent explosive rupture of the tank and consequent
fire.
Also, if used, the separate tap changer oil enclosure can be fitted with a pressure relief device.A
drawback of the frangible disk is that the oil remaining in the tank is left exposed to the atmosphere
after a rupture. This is avoided in a more effective device, the pressure relief valve, which opens to
allow the discharge of oil if the pressure exceeds the pre-adjusted limit.
The top-oil temperature may be considerably lower than the winding temperature, especially shortly
after a sudden load increase. This means that the top-oil thermometer is not an effective overheating
protection.
However, where the policy towards transformers’ loss of life permits, tripping on top-oil temperature
may be satisfactory. This has the added advantage of directly monitoring the oil temperature to
ensure that it does not reach the flash temperature.
4. Winding Thermometer:
The winding thermometer, shown in the figure below, responds to both the top-oil temperature and
the heating effect of the load current.The winding thermometer creates an image of the hottest part
of the winding. The top-oil temperature is measured with a similar method as introduced earlier. The
measurement is further expanded with a current signal proportional to the loading current in the
winding.
This current signal is taken from a current transformer located inside the bushing of that particular
winding. This current is lead to a resistor element in the main unit. This resistor heats up, and as a
result of the current flowing through it, it will in its turn heat up the measurement bellow, resulting in
an increased indicator movement.
The temperature bias is proportional to the resistance of the electric heating (resistor) element.
The result of the heat run provides data to adjust the resistance and thereby the temperature bias.
The bias should correspond to the difference between the hot-spot temperature and the top-oil
temperature. The time constant of the heating of the pocket should match the time constant of the
heating of the winding.
The temperature sensor then measures a temperature that is equal to the winding temperature if the
bias is equal to the temperature difference and the time constants are equal.With four contacts fitted,
the two lowest levels are commonly used to start fans or pumps for forced cooling, the third level to
initiate an alarm and the fourth step to trip load breakers or de-energize the transformer or both.
In case a power transformer is fitted with top-oil thermometer and winding thermometer, the latter
one normally takes care of the forced cooling control.
Thermometer Testing:
Every 3 to 5 years, and if trouble is suspected, do a thermometer testing. Suspend the indicator
bulb and an accurate mercury thermometer in an oil bath. Do not allow either to touch the side or
bottom of the container. Heat the oil on a hotplate while stirring and compare the two
thermometers while the temperature increases. If a magnetic stirring/heating plate is available, it is
more effective than hand stirring. Pay particular attention to the upper temperature range at which
your transformers normally operate (50 °C to 80 °C). An ohmmeter should also be used to check
switch operations.
The alarms and other functions should also be tested to see if the correct annunciator points
activate, pumps/fans operate, etc. If it is not possible to replace the temperature gage or send it to
the factory for repair, place a temperature correction factor on your data form to add to the dial
reading so the correct temperature will be recorded. Also lower the alarm and pump -turn-on
settings by this same correction factor.
Since these are pressure-filled systems, the indicator will typically read low if it is out of calibration.
Field testing has shown some of these gages reading 15 °C to 20 °C lower than actual temperature.
This is hazardous for transformers because it will allow them to continuously run hotter than
intended, due to delayed alarms and cooling activation.
If thermometers are not tested and errors corrected, transformer service life may be shortened or
premature failure may occur.