LSC BUS en CATALOGO PDF
LSC BUS en CATALOGO PDF
LSC BUS en CATALOGO PDF
LS Cable & System has strived to become a global leader in the industry by implementing constant innovation since the establishment of the company.
While providing high-quality solutions to help our clients, LS Cable & System is accelerating efforts to be the top player of the global cable industry by securing
the top technologies in submarine cables and superconducting cables, as well as focusing on green business. Under the company vision
’Your No.1 Creative Partner,’ LS Cable & System dedicates its best effort to deliver only the top technology and service to its clients.
Superior Essex
JS Cable
• LG Electronics • LG Display
• LG Chemical • LG Telecom
• GS Caltex • GS Retail
• GS Engineering & Construction • GS Homeshopping
Power equipment, Power supply & transmission, Industrial IT,
Automation equipment, Electric Power Tools, RFID etc.
A New Beginning as a Total Solution Provider for Electric Power and Telecommunications
History was made when LS Cable & System, the de facto holding company of LS Group, transformed into LS Holding Company in July 2008 and started as a new
total-solution provider specialized in electric power and telecommunications. It was the optimized business decision to increase management efficiency of the
constantly expending business segments and to strengthen the responsible management system to foster a new growth engine to drive our business.
By separating investment and business segments, LS Holdings was able to discover a new growth engine to propel the group into a new phase of growth. The new
change of business provided an opportunity to the subsidiary companies to focus on their own operations and to strengthen their respective business expertise,
as well as successfully enhancing the competitiveness in the industry. LS Cable & System, as the holding company, is committed to providing continued support to
the subsidiary companies, while practicing responsible management.LS Cable & System endeavor to focus on our core business while strengthening its business
expertise and competitiveness as a global company.
LNG, CNG
Components, Machinery
Standing Tall as the Third Largest Cable Maker in the Global Cable Industry
In August 2008, LS Cable & System acquired Super Essex, the largest cable maker in North America, making LS Cable & System the third largest cable maker
in the global cable industry. By incorporating the staple product line of coils and communication wires of Superior Essex to the existing business structure
of power cables, optical fiber cables, and wires of the company, LS Cable & System has built an ideal cable product line. Securing the extensive experience
of production and distribution network of Superior Essex in the markets of North America and Europe has led to LS Cable & System’s emergence as a true
global enterprise.
Superior Essex In 1999, Superior Cable, which back then was a communication cable producer, made an acquisition of Essex Wire, a magnet wire producer,
and the combination formed Superior Essex. The company is the world’s largest maker of magnet wires and the largest maker of communication cables in
North America. The company is headquartered in Atlanta, Georgia, USA, where they manage 24 factories in a total of 9 countries, including the United States,
Canada, Mexico, Germany, the UK, Italy, and China.
LS Cable & System
Busduct System Solution
Buildings
The LS C&S Bus Duct system is easy to install, and ensures large capacity of
energy transmission while providing space efficiency which makes the bus
duct system ideal for high-rise buildings, office buildings, data centers and
apartment complexes.
Plants
The full lineup is consisting of NSPB that can cover up to 27kV as well as
CAST RESIN and SIB, and the lineup thus enables us to provide our clients
customized designs. The system is suitable for electrical rooms and power
lines, and it features a real time monitoring system using the temperature
and power monitoring system.
Data Center
The flexibility and expandability as well as easy maintenance property
of the bus duct system provides the best alternative to improve the existing
problems of the conventional power cable system of data centers,
which requires constant extension, reinstallation and capacity
modification of loads.
Apartment Buildings
Although the demands for more electricity for families are growing,
the space for EPS area has reduced. Due to the change,
the need for bus ducts and multi boxes have increased.
Hospitals
The stability of the power supply in the hospitals is perhaps the most vital element,
because its failure could threaten the safety of patients.
The Bus Duct system distributes larger capacity of electric power, and provides
stability of the loads which make it an ideal choice to satisfy the requirements of
systematization of hospital complexes and larger hospital equipments.
Airports
In order to secure the stable power supply of the airport, the bus duct system
provides the best customized solutions by installing high voltage bus ducts
at the transmission, transformation and power distribution lines, and by
installing low voltage bus ducts at the cargo, the control tower and general
commercial buildings.
Stadiums
The needs for a bus ducts system has been growing for its benefit such as
large capacity of power transmission, providing a stable power supply for
various loads and an eco friendly property as well as economical quality.
End Closer
Spring Hanger
Spring Hanger
Plug in Unit
Plug-in Box
Spring Hanger Horizontal Ducts
Plug in Unit
Spring Hanger Plug-in Box
Rigid Hanger
1
Plug-in Box
1
2
Plug-in Box
7
4
6
5 Switchgear
Electrical Room
TR Flanged
End Box Switchgear
Transformer
Outdoor Transformer
The LS Cable & System Bus Ducts are available in a wide range of products from low voltage LT-Way (25A~63A) to high voltage E-Series
(630A~7500A), and the products enable the supply of proper capacity of power for factories and the distribution system. Our products such
as the air insulated bus conducts with enhanced safety property and the cast resin bus ducts with resistance for high temperature, humidity
and dusty environment will satisfy various application needs and provide a customized engineering service.
Ez/Ex/EF-way
1 Sandwich Type (PET Film, Epoxy Coating, MICA)/AL
Extrusion Housing/Standard IP54/Joint Kit
- Designed for low voltage products below AC 1000V, and between
630A to 7500A.
- The most widely used conventional model.
Mini-way
2 Air Insulated Type/AL Extrusion Housing/Standard IP54/Joint Kit
- Designed for low voltage products below AC 1000V, and between
160A and 800A.
- Ideal for small distribution system with multi distribution loads
(Vertical areas of buildings, data centers, assemble factories)
LT-way
3 Flat Wire Type/Copper Conductor with PVC Extruded Insulation/AL
Extrusion Housing/Various Plug Types/Joint Brush
(Can be installed with a live wire)
- Designed for low voltage products below AC 690V, and between 25A and 63A
- Suitable for Light bulbs, FFU and distribution for small equipments
MS/Wind-way
4 Air Insulated Type/ Compact NSPB Type / One-Bolting Type
Designed for low voltage products below AC 1000V, and between
1000A and 5000A
- A Hybrid incorporating NSPB and sandwich type
- Ideal for ships, wind towers and chemical plants where stability is required.
NSPB-LV/MV
5 Air Insulated Type/Insulated conductors separated by phase/AL,
STS and Steel Housing/Indoor Type/Outdoor Type
- NSPB-LV : Designed for low voltage products below AC 1000V,and below 4000A
- NSPB-MV: Designed for high voltage products below AC 27kV, and below 4000A
- Suitable for plants where high stability is required.
CR-LV/MV
6 - Cast Resin Type/IP 68/Dielectric Epoxy Molding between Conductors
- CR-LV: Designed for low voltage products below AC 1000V, and between
630A and7500A.
- CR-MV: Designed for high voltage products below AC 27KV,
and below 5000A.
- The most safe bus duct suitable for plants where high stability is required.
7 SIB
Epoxy Vacuum Impregnation Dielectric Products/Suitable for phase
separation system
- Designed for high voltage products below AC 27kV and below 7500A
- The benefit of bus ducts and cables are incorporated as SIB.
- Suitable for high voltage products.
Why Busduct?
Easy Distribution of Loads
When supplying power using cables, each load has to be connected individually to cables which waste space,
and an additional distribution panel is also required.
On the other hand, bus ducts are separated from a single line at a plug box which simplifies the electric power system.
A MCCB can be installed at the plug box to effectively shut off fault current.
Labor Hours
Pulling and cable tray installation for cables can be difficult, and 1000
requires a longer construction period, therefore increases the 1500
cost. On the other hand, the bus ducts use a simple installation 2000
method to connect specific length of products, which requires a 2500
shorter installation period, and is economically friendly. 3000
4000
Cable
Ampere Busduct
Compact
The compact design of the bus duct system provides high space efficiency at up to 50% compared to the cables.
While cables require larger space to install multi lines as well as additional space for coiling areas, the bus ducts use
proper fittings to maximize space efficiency.
The space
R
Cable required reduces S
T
by 50%
Cable Tray
Adaptability to various installation
environment and convenience
The bus duct system is a power distribution system and can
be applied to various complex routes. The bus duct system
comes with various fittings such as elbows, off-set and tee,
and can transmit high capacity currents without electrical
and mechanical loss.
Easy maintenance
The design of the bus duct system makes it easy to detect
abnormalities during installations, and ensures easy main-
tenance. When humidity or dust causes a malfunction on
the system, the easy-to -maintain design allows replacing
only the damaged part.
Outstanding features of
EMC and EMI
Unlike cables, the bus duct system does not require a shield,
instead the housing itself performs as a shield which en-
hances the features of EMC and EMI.
Why LS Cable &System Bus
Global Top Tier
LS Cable & System has been a long-time leading cable maker of the bus duct market in Korea. With extensive experience and
product line competitiveness, the company provides total solutions for each application to satisfy the needs of its clients. Us-
ing its expertise in the electronic markets of large LCD monitors and semiconductors in Korea, the company has obtained PJT
sales records in 50 countries worldwide in Asia, the Middle East, CIS, and the US.
Full Line – up
LS Cable and System is the only global company that provides a full line-up of bus ducts, from low to high voltage and from
low to high capacity, to satisfy every need of its clients and provide an optimized solution for each PJT.
LT-way
MS/Wind-way
Mini-way
Ez / Ex / Ef-way
CR-LV/MV
SIB (MV)
NSPB -LV/MV
Total Solution
• Once PJT launches, our engineer will participate to guide the clients from the initial period in order to produce the best
system for our clients, and to respond quickly when the system is changed.
• Our engineers from each department provide full support in design, production, installation and testing at in-bound to
satisfy our clients.
• We operate the CS Team, a task force for the bus duct system, to make sure efficient after-sale service and maintenance
service are provided.
Process
• Product development
dD
eve
• System design
lopm
Busduct
Installa
Total Solution
tion
on
• Customer Service ua
/Q
cti
lity d u
• Product test and / CS Pro
installation support
• Production
• PJT management
Technical Excellence
Unparalleled Reliability Total Engineering Technology
• Provides standardized design, and owns numerous certifications • Provide the optimum design by experienced engineers
such as UL Certification, Quack Proof Certification, and Impact • Design following analysis and inspection of CAE
Resistance Certification • Unique and exclusive design program for the bus duct system
• The CS team, a task force for the bus duct system, • Design based on structure stability inspection
provides efficient after-sale service
• The excellent heat –radiating property of the aluminum housing
• Safe use in hazardous zones ensures large capacity of power transmission
• Manage the system using an independent temperature • Low Weight & Low cost
monitor sensor
• Easy installation
• Semi-permanent service life
• Deployable where access is difficult
• Used qualified insulation such as epoxy and PET film
• Automated epoxy insulation facility
for efficient insulation
• Unique joint kit connections
• Reduce electromagnetic
Eco friendly
• BPMS Electric Power Monitoring System
• Fully recyclable
• BTMS Temperature Monitoring System
• Halogen free
• Does not contain RoHS 6 hazardous substance
• No toxicity in fire & Fire-Retardant
• Non Explosive
Why LS C&S Bus Duct?
The Bus Duct Temperature Monitoring System
BTMS : Busduct Temperature Monitoring System
The bus duct is a large capacity power distribution system. The insulation of the duct has to stay stable when the Joule lines
occur during a power supply of the conductor. The rated current will be set by the insulation type, and the temperature rises.
These properties of the bus duct make it possible to monitor and manage abnormalities of the system by checking the
temperature of specific areas of the system.
The temperature monitoring system uses various temperature sensors such as optical fiber cable, IC electric chips and
thermo-graphic cameras. Specific areas like the entire system line, joints, plug-in boxes and cable connection can be
monitored at the central monitor room using various methods on request.
Smart box
통신 Unit
<감시 Program>
Ez/Ex/Ef-way
LS C&S Bus Duct System Catalogue
01 of 08
Contents
I. Introduction
- Overview 14
- Application 15
II. General Data 16
III. Component
- Feeder 22
- Flanged End 23
- Fittings 26
- Hanger 29
- Plug-In Unit 31
- Etc 33
IV. Technical Data
- Impedance 35
- Voltage Drop 36
- Temperature Rise 37
V. Install Information
- Joint Connection 38
VI. Certification & Specification 39
I. Introduction
Overview
The E-Series
The LS C&S E-Series Bus Duct is designed to carry voltage range below AC 1000V, and to carry the current range of 633A to 7500A.Joint kit connections
provide more space to connect which reduce the contact resistance to its minimum while connecting products. LS C&S Bus Duct comes with a
standard IP54rating; however, it can be upgraded to an indoor or outdoor IP65 rating on request.
Depending on each insulation property the system comes in three types; Ez-way when polyester film is used, Ef-way when mica film is used and EX-way
is used when epoxy powder is used.
Compact Size
LS C&S E-Series Bus Duct uses an effective heat radiating housing profile which allows the size of the conductors to be smaller than the
existing Bus Duct models. The light weight of the Bus Duct also allows easier installation, and requires less space.
Application
Introduction
Electrical Rooms
• The bus duct can be installed both horizontally and vertically
at the electrical room.
• The maximized safety features are earthquake-proof and
explosion-proof.
• Provides excellent space efficiency and easy installation
compared to cables.
Plants
• The bus ducts can be applied to a vast range of industries such as
semiconductor, display and petrochemical plants.
• The temperature and the power supply monitoring system allows
easy maintenance.
• The bus ducts provides high space efficiency, and allows
a significantly reduced installation period.
Plug-in Box
Elbow
Flanged End
End Cap
Gemeral Data
Joint Kit
Offset
Conductors Housing
The E-Series uses either copper conductors with The E-Series uses an effective heat –radiating aluminum
conductivity over 99%, or aluminum conductors housing profile which produces an excellent mechanical
with conductivity over 61%. strength and heat radiation. The aluminum housing can
be used as a protective conductor due to its high level
The connection of the conductors is tin-plated in conductivity and cross sectional areas. An optional optical
order to reduce contact resistance and to prevent fiber temperature sensor can be installed at the housing.
corrosion of the connection. (A silver plated option
is available.)
General Specifications
E-series bus duct uses insulation with a thermal class rating over130 C for each phase. A sandwich type design is applied to
the bus duct to protect the aluminum housing, and it can be used at the voltage range of AC 1000V or less, and the current
range between 630A to 7500A. It is designed to use a joint kit connection and general IP54 rating.
Optical Fiber(Optional)
Conductor(Copper / Aluminum)
Insulation
- Ex-way by EPOXY
(Class B 130oC / Class F 155oC)
- Ez-way by PET
(Class B 130oC / Class F 155oC)
- Ef-way by MICA (1200oC)
Gemeral Data
a disc spring allows even connection of the contact surface.
Number of DH bolts
Number of
1 2 4 6
D.H bolts
630, 800, 1000, 2500, 3200,
CU 5000 6300, 7500
1250, 1600, 2000 3600, 4000
Ampere
(A) 630, 800, 1600, 3200,
AL 5000, 6300
1000, 1250 2000, 2500 3600, 4000
! Precaution
Be sure to clean the interior of the connections prior to installation. Use caution not to twist the joint kit while inserting it, and after it is inserted.
An excessive pressure during installation may break the kit.
Make sure that the double-headed bolts and the red tags are intact.
If proper torqueses are not applied at the connection, it may cause heat during operation.
The 200%N type Bus Duct is a nonlinear load bus duct that generates harmonic current. Lately, the needs for non-linear loads at the power distribution
system of buildings are increasing due to the increase of office automation and computer facilities. The harmonic current produced by the system can
flow up to 200% of over current at phase N. The LS C&S 200% N type bus duct is safe to be used at the distribution system where the harmonic current
can be generated.
Plating/Coating
Plating Coating
Standard tin plating is applied at taps, plugs and connections In order to improve heat radiation and to prevent corrosion, as
of conductors using an electroplating method to maintain the well as to fit in with the surroundings, we treat the surface before
electrical characteristics and to prevent corrosion. Silver plating is applying polyester-epoxy (hybrid) power coating. A wide range of
available on request. color is available to meet the needs of our clients.
NEMA STANDARD : • IP54=NEMA 12, 12K, 13 • IP55=NEMA 3, 3X, 3S, 3SX • IP66=NEMA 4.4X • IP67=NEMA 6
* As the standard differs, it is a similar substitution, not 1:1 substitution.
Gemeral Data
The degree of protection against water of the LS C&S E-Series is a standard IP54; however, it can be adjusted from IP42
to IP65 depending on the environment and on request.
IP
Solid Particle Protection Liquid Ingress Protection
0 No Protection 0 No Protection
5 먼지로부터 보호됨
1m
4 모든방향의 스프레이로 8 장기간 침수되어
부터 보호됨 수압을 받아도 보호됨
6 먼지로부터 완벽하게
보호됨
IP Code
Degree of Protection
Bus Ducts Construction Type
(IP)
IP54 Feeder, Plug-in, Riser Drip-proof / Splash-proof
Flanged End
Flanged end is connected to either a transformer or a low-tension panel. Dimension details are listed below.
[Fig. E2-1]
Component
[Fig. E2-2] [Fig. E2-3] [Fig. E2-4] [Fig. E2-5]
Dimension(mm)
Ampere(A) Fig.
t W A B
630 41 ~
E2-2
800 62 ~
1,000 86 40
100 E2-3
1,250 108 50
1,600 164 60
E2-5
2,000 210 70
AL 6.35
2,500 (2)126 40 E2-4
3,200 (2)164 60
3,600 (2)184 60
130
4,000 (2)210 70 E2-5
5,000 (3)184 60
6,300 (3)210 70
630 41 ~
800 41 ~ E2-2
1,000 57 ~
1,250 73 40 100
E2-3
1,600 108 50
2,000 145 50 E2-4
CU 2,500 6.35 195 70 E2-5
3,200 (2)108 50 E2-3
3,600 (2)126 40
E2-4
4,000 (2)145 50
130
5,000 (2)195 70
6,300 (3)164 60 E2-5
7,500 (3)195 70
*T: Conductor thickness
Feeder
Construction Options
AA AA
WW WW
3434
H
HH
H
t
tt
t
[Fig. E1-1] [Fig. E1-2]
A
A
W
W
34 34
H
34 34
H
t
t
[Fig. E1-3]
Dimension(mm) Weight(kg/m)
Ampere(A) Fig.
t W A 3W 4W 4W+50%E 4W+100%E
630 41 107 7.58 8.43 8.79 9.15
800 62 128 8.83 10.09 10.63 11.17
1,000 86 152 10.92 12.14 12.89 13.64
E1-1
1,250 108 174 13.40 15.42 16.36 17.30
1,600 164 230 19.57 20.61 22.08 23.55
2,000 210 276 23.08 26.23 28.14 30.09
AL 6.35
2,500 (2)126 352 28.94 33.18 35.38 37.58
3,200 (2)164 428 34.86 42.44 45.29 48.14
E1-2
3,600 (2)184 468 38.31 45.40 48.59 51.78
4,000 (2)210 520 41.81 50.10 53.75 57.40
5,000 (3)184 686 57.74 68.43 73.22 78.01
E1-3
6,300 (3)210 764 64.03 73.61 81.51 89.41
630 41 107 11.91 14.44 15.65 16.86
800 41 107 11.91 14.44 15.65 16.86
1,000 57 123 14.65 18.25 20.58 22.91
1,250 73 139 17.65 22.04 24.60 27.16 E1-1
1,600 108 174 26.74 31.00 36.47 41.94
2,000 145 211 31.69 37.39 44.76 52.13
CU 2,500 6.35 195 261 42.69 54.59 60.25 65.91
3,200 (2)108 316 50.16 63.60 69.87 76.14
3,600 (2)126 352 57.55 73.16 80.41 87.66
E1-2
4,000 (2)145 390 64.82 82.72 91.17 99.62
5,000 (2)195 490 85.26 109.14 121.08 133.02
6,300 (3)164 626 108.91 139.27 154.65 168.02
E1-3
7,500 (3)195 719 126.89 162.81 179.83 196.85
* H : 107.5(3W+GE, 3W+50%E) / 115(4W+GE, 4W+50%E) / 125(4W+100%E)
Flanged End
Drilling Pattern for Flanged End
B D
A D
B D D
D
C1 25 25 C2 C1 25 25 C2 C1 25 25 C2
[Fig. E4-1]
Component
[Fig. E4-2]
Fittings
E-Series Bus Duct has a wide range of fittings to satisfy any layout of buildings. Elbow angles other than a ninety degree
angles are also available. Fitting designs are shown in the following figures, and they consist of the source-side and the
load-side. Offset or combination elbows can be used where standard elbows are not feasible.
(Dimensions for each fitting are shown in the following figures. Contact our design team for a minimum dimension.)
Elbow Offset
[Horizontal] [Horizontal]
[Vertical] [Vertical]
Combination
Dimension(mm)
Ampere(A)
X Y Z
630~1,250 500 500 500
1,600~3,200 600 600 600
AL
3,600~4,000 700 700 700
5,000~6,300 800 800 800
630~2,000 500 500 500
3,000~4,000 600 600 600
CU
5,000~6,300 700 700 700
7,500 800 800 800
Component
Tee
[Horizontal] [Vertical]
600 600
600
600 600 600
600
600
600 600
600 600
Vertical Tee
Dimension(mm)
Ampere(A)
X Y Z
630~1,250 500 500 500
1,600~3,200 600 600 600
AL
3,600~4,000 700 700 700
5,000~6,300 800 800 800
630~2,000 500 500 500
3,000~4,000 600 600 600
CU
5,000~6,300 700 700 700
7,500 800 800 800
Fittings
Expansion
The fitting is designed to allow a 60mmextension of a straight line.
Dimension(mm)
Ampere(A)
X Y
630~7,500 1,500 360
Reducer
A reducer is used to connect a large capacity bus duct and a small capacity bus duct.
It can be used for an economical setup to distribute loads.
Ampere(A) Dimension(mm)
Primary Secondary X
1,000 630~800
1,250 800~1,000
1,600 1,000~1,250
2,000 1,250~1,600
2,500 1,600~2,000
1,000
3,200 2,000~2,500
4,000 2,500~3,200
5,000 3,200~4,000
6,300 4,000~5,000
7,500 5,000~6,300
*Any change made to load distribution or to capacities follows inner line regulations. An overcurrent circuit
breaker can be installed on request.
Hanger
Vertical Mounting Hangers
Spring hangers are used to support the bus ducts between floors. The number of springs depends on the weight of the installed ducts and plug-in boxes.
A medium hanger should be installed if the height between the floors exceeds 4.5 meters, and the height of the installed spring hangers can be easily
adjusted. Rigid hangers (no spring type) are used on the lowest floor, and they can be used instead of spring hangers depending on the set up design.
Component
[Rigid Hanger] [Spring Hanger]
Rigid Hanger
Spring Hanger
* Hangers with more than 2 rows depending on the installation environment are also available on request.
Please contact the design team for further information.
Hanger
Horizontal Hangers
General Hangers
The standard installation method for these hangers is to install them horizontally at 1.5 meters intervals. They generally require 12mm diameter stud bolts.
[Flatwise] [Edgewise]
Hanger Rod Hanger Rod
Hanger Clamp
Hanger Clamp
Wall Bracket
Wall brackets can be installed on a wall where general hangers are not feasible.
[Flatwise] [Edgewise]
Plug-in Unit
Straight Lengths: Plug-in/Tap-off Intervals
This bus dust comes with an overcurrent blocking device (MCCB, fuse) in order to protect the wires while distributing loads.
The required minimum intervals of a plug-in(800A or less)and a tap-off(1000A, 1250A) are shown below. A length longer than
the required minimum intervals can be predestinated on request.
Plug-in Feeder
MCCB Frame Plug-in Hole Intervals(P)
(AF) (mm)
50, 65, 100 650
250 650
400 900 W
630, 800 1000
Component
1000, 1250 1300
D
Plug-in Box H
Plug-in Unit
Plug-in Box Attachment Specifications
Attachments such as CT, TD and PT can be installed in a plug-in box to control and to supervise the current,
voltage and wattage remotely.
Etc.
Wall Flange
A wall flange is used to seal the gaps produced during installation of bus ducts at the walls, ceilings and floor. The standard
dimensions of a wall opening should be 30mm larger than the external dimensions of the E-Series Bus Duct.
Component
Floor Openings
The standard dimensions of a floor opening should be 30mm larger than the external dimensions of the E-Series Bus Duct.
Etc.
The Required Minimum Distances from a Wall for Heat Dissipation
The required minimum distances between a bus duct and a wall, or a ceiling are shown below.
벽, 천정 벽, 천정 천정 벽
벽 벽 벽
100mm
100mm 100mm
접속부
접속부 접속부
P2 P1 P3
200
접속부 접속부
100 100
200
Technical Data
Impedance and Voltage Drop
The formula to measure the voltage drop of a bus duct is shown below. The impedance and voltage drop values for aluminum and copper
conductors are shown in the table below.
The values listed are measured between upper and middle lines at 60Hz. For a 50Hz installation, multiply the reactance (X) by 0.83.
Component
α = 0.5, Distributed load • F : Flanged End (panel connections)
(a place such as a vertical section) F P P P P P • P : Plug-in Unit
Technical Data
630 13.98 4.07 14.56 13.85 14.87 15.66 15.25
800 7.97 2.62 8.39 10.32 11.01 11.52 11.04
1,000 6.83 2.21 7.18 11.02 11.77 12.32 11.84
1,250 5.55 1.82 5.84 11.22 11.97 12.52 12.01
1,600 3.82 1.23 4.02 9.85 10.52 11.02 10.60
2,000 3.08 1.00 3.24 9.96 10.63 11.12 10.67
AL
2,500 2.40 0.80 2.53 9.74 10.39 10.86 10.40
3,200 1.91 0.61 2.00 9.82 10.48 10.98 10.56
3,600 1.72 0.55 1.81 9.99 10.67 11.18 10.74
4,000 1.54 0.50 1.62 9.93 10.60 11.09 10.64
5,000 1.15 0.37 1.21 9.24 9.87 10.34 9.94
6,300 1.02 0.33 1.08 10.41 11.11 11.63 11.16
630 7.49 4.07 8.53 8.90 9.21 9.30 8.18
800 7.49 3.84 8.42 11.07 11.50 11.67 10.38
1,000 5.49 2.99 6.25 10.35 10.72 10.82 9.52
1,250 4.39 2.45 5.03 10.44 10.78 10.86 9.50
1,600 3.10 1.71 3.54 9.40 9.72 9.80 8.60
2,000 2.40 1.35 2.76 9.17 9.46 9.53 8.32
CU 2,500 1.86 1.05 2.13 8.87 9.16 9.22 8.06
3,200 1.54 0.85 1.76 9.34 9.66 9.75 8.55
3,600 1.35 0.74 1.54 9.20 9.51 9.60 8.42
4,000 1.20 0.67 1.37 9.13 9.42 9.49 8.29
5,000 0.93 0.52 1.06 8.84 9.13 9.19 8.03
6,300 0.73 0.39 0.83 8.62 8.93 9.02 7.97
7,500 0.62 0.35 0.71 8.83 9.12 9.18 8.02
Technical Data
Short Circuit Strength
LS C&S Bus Duct has been tested under actual short circuit conditions according to IEC 61439-2 and 6 [(previous standard) IEC 60439-1 and 2]
at KEMA and ASTA. The result and the graph are shown below.
Temperature Rise
The temperature rise limit is an important property which determines the performance of bus ducts. The temperature rise limit of the bus duct is
designed that when a bus duct is operated with a rated current , the temperature limit values of the housing are within 55K as specified in IEC61439-2
and 6 [(previous standard) IEC 60439-1 and 2].
1 2 3 4 5
Technical Data
7 8
-Joint- 6
80
70
2
60 3
Temperature(℃)
50
40 4
7 8
30 5 6
9
20
10
0 1 2 3 4 5 6 7 8
Time(hr)
Classification 1 2 3 4 5 6 7 8 9
Ambient
Sensor Location Connection Conductor Housing
Temperature
Temperature Rise
58K 64K 60K 40K 32K 31K 31K 31K 24℃
Value
Joint Connection
Both parts should be aligned at the top and the bottom and the left and Using a torque wrench, slowly tighten the exposed bolt head of a double head
the right as well as horizontally and vertically. (This also applies to the joint bolt. The double head bolt head is designed to break off at 800~1000Kgf • cm.
connection of the horizontal and vertical ducts.) Make sure that the joint kit Continue tightening the exposed head until it breaks off.
is not tilted. (We recommend a jig tool for the installation.)
Once the exposed head and the red tag attached to it have been cut off, a red line should be visible, which means they are properly connected. Be sure
to check the distance from the housing, and the gaps between the conductors at the kit after the installation.
투명 캡
Before applying the connection cover, check the space between the Perform the last inspection of the connection.
end block and the holes of the connection cover. The red line should be
visible through the transparent cap.
Information
Intall
Certification &
Specification
Dust and Water Proof Certification Fire Proof Certification (Ef-way) Fire Sprinkler Certification (Ef-way)
(E-series)
ISO14001 OHSAS18001
Contents
I. Introduction
- Overview 14
- Application 15
II. General Data 16
III. Component
- Feeder 21
- Flanged End 22
- Fittings 24
- Hanger 26
- Plug-In Unit 27
- Etc 28
IV. Technical Data
- Impedance 29
- Voltage Drop 29
- Temperature Rise 30
V. Install Information
- Joint Connection 31
VI. Certification & Specification 32
I. Introduction
Overview
Mini-way
LSC&S Mini-way is an air insulation type bare conductor bus duct, and designed for low currents at AC 1000V or less or between 160A and 800A.
Each conductor is compounded with a class B rating insulating material (thermal class 130 C) and using a joint kit system
at the joint connections provides easy installation of feeders.
The mini-way comes with an IP54 rating and is water proof which reduces malfunction during operation caused by water leakage.
Easy Installation
The light weight of LS C&S Mini-Way enables easy trans-
portation and installation, and employing the joint kit
system provides easy installation of the feeders.
Excellent Performance
LS C&S Mini-Way follows the IEC standard, and has
designed the cross-section, conductor support and hous-
ing shape according to the regulations of temperature.
Therefore it has efficient voltage drop and high short
circuit strength.
Application
Introduction
Data Center
• Supply power to computer equipments at each rack in the
server room.
• Distribution boards or modular racks are not necessary.
• Consist of two lines of general use and emergency use.
Plug-in Hole
Plug-in Box
Joint Kit
Joint Kit
Gemeral Data
Elbow
Feeder
Conductors Housing
The Mini-Way uses either copper conductors with The Mini-Way uses an effective heat –radiating aluminum
conductivity over 99%, or aluminum conductors with housing profile which produces an excellent mechanical
conductivity over 61%. The connection of the conductors is strength and heat radiation. The aluminum housing can
tin-plated in order to reduce contact resistance and to be used as a protective conductor (PE) thanks to its high
prevent to corrosion of the connection. (A silver plated level conductivity and cross sectional areas.
option is available.)
General Concept
LSC&S Mini-Way is an air insulation type bare conductor bus duct, and it supports each phase with Class B rating insulating
material (thermal class 130 Celsius). It is designed for AC 1000V or less or between 160A and 800A. It also comes with a joint
kit system and standard IP54 rating.
Configration
[3W+GE] [4W+GE]
[3W+50%E] [4W+50%E]
[3W+100%E] [4W+100%E]
Grounding Capacity
The aluminum housing of the Mini-Way is designed to perform as a grounding conductor within the rated current. In
case 50~100% more grounding capacity is needed, an internal grounding conductor can be added without changing
the existing design.
Gemeral Data
Housing
[General Earth]
Housing
50% Earth
[50% Earth]
50% Earth
[100% Earth]
Note
The aluminum housing itself acts as a grounding conductor and improves heat-radiation of conductors. The light weight of the mini-way was possible thanks
to the innovated design to reduce the weight.
The degree of protection against water of the Mini-Way is a standard IP54; however, it can be adjusted up to IP65.
An additional sealing using high strength silicon is also available at the joint connections between the housing and the
connection cover on request.
IP
Solid Particle Protection Liquid Ingress Protection
0 No Protection 0 No Protection
Feeder
Although the standard length of the Mini-Way is 3 meters, it can be adjusted to the installation
environment on request.
Gemeral Data
Component
A A
t t
W
W
[3W] [4W]
Flanged End
The flanged end is connected to either a transformer or a panel.
Dimension details are shown below.
50
50
200
200
150
12
150
40
A A
A A A
20
W
[3W+GE] [4W+GE] [측면]
50
50
200
12
200
150
150
40
20
70 A A A W
70 A A
[3W+50%E] [4W+50%E] [측면]
Dimension(mm)
Ampere(A) A
t w
3W 4W
160 20
250 30
AL 400 6.35 50
630 70
800 95
100 100
160 20
250 30
CU 400 6.35 50
630 50
800 70
*t : thickness of a conductor
A
50
Component
D
Dimension(mm) Dimension(mm)
Ampere(A) Ampere(A)
A B C D A B C D
160 200 70 160 200 70
250 200 70 250 200 70
AL 400 220 340 80 370 CU 400 220 340 80 370
630 240 100 630 220 80
800 265 125 800 240 100
Fittings
E-Series Bus Duct has a wide range of fittings to satisfy any layout of buildings. Elbow angles other than 90 degrees are also
available. Fitting designs are shown in the following figures, and they consist of the source-side and the load-side. Offset
or combination elbows can be used where standard elbows are not feasible.(Dimensions for each fitting are shown in the
following figures. Contact our design team for a minimum dimension.)
Elbow
[Vertical] [Horizontal]
Y X
Y Y
X
Y
X
X
Y Y X
X Y
Y
Dimension(mm) Dimension(mm)
Ampere(A) Ampere(A)
X Y X Y
160 ~ 800 500 500 160 ~ 800 500 500 Y
X Y
X
X
Y
X X X
Y
Offset
Z
[Vertical] [Horizontal] Z
Z
Z Y Y
X X
X X
Y Y
Z Z
Z Z
Dimension(mm) Dimension(mm)
Ampere(A) Ampere(A)
X Y Z X Y Z
160 ~ 800 500 500 500 160 ~ 800 500 500 500
Tee
[Vertical] [Horizontal]
Z Z
Z Z
Y
Y H H
Y Y Y
X X X
X
Component
Dimension(mm) Dimension(mm)
Ampere(A) Z Ampere(A)
X Y Z X Y Z
Z
160 ~ 800 500 500 500 160 ~ 800 500 500 500
Y Z Z
Y Y Dimension(mm) Dimension(mm)
Ampere(A) Ampere(A)
X Y Z H H_AL H_CU
Y Y
160 ~ 800 500 500 500 160 134 134
Y Z
Y
Dimension(mm)
Ampere(A)
X Y Z
160 ~ 800 500 500 500
Hanger
Bus ducts installed on the ceilings, floors, walls and beams are usually supported by stud bolts, system channels, angles
and channels. Various types of hangers are available depending on the installation condition or environment. (Please con-
tact our design team for further information about hanger types and installation.)
Horizontal Hangers
Vertical Hangers
[Rigid Hanger]
Base Channel
[Spring Hanger]
Base Channel
Plug-in Unit
The position of the plug-in distribution location will be decided according to the installation environment and on
request. The standard length of the feeders is 3 meters, and a maximum of 8 plug-in holes can be made on a 3 meter
feeder. In order to secure the smooth access between the plug-in brushes and feeders, a guide pin has been attached
Guide Pin
Component
Plug-in Box
Attachments such as CT, TD and PT can be installed in a plug-in box to control and to supervise current, voltage and wattage remotely.
Etc.
Wall Flange Floor Opening
Wall Open Size Wall Flange Fire Foam
Cut Out (out of scope) Floor Opening Size
W+160 Cut Out
W+60
W+60 30 W 30
W+10 30
H+160
H+10
H+60
H H+60
30
Glass Wool
(out of scope)
A wall flange is used to seal the gaps produced during installation of bus ducts at the walls, • W : The width of the product (165mm)
ceilings and floors. • H : The height of the product
(It is decided by a rated current.)
• W : The width of the product (165mm)
• H : The height of the product (It is decided by a rated current.)
250mm Beam
100
250mm Beam
100
벽 벽
벽벽
Wall,
ceiling
100 100
Joint
Joint Point
Point
100
100
JointPoint
Joint Point
천정
천정 벽 벽
천정
천정 벽벽
100
100100
200
200200
100
100 100
200
벽벽 100
벽 벽 100
벽 100
벽 100 벽벽
100
100
Technical Data
Impedance and Voltage Drop
The formula to measure the voltage drop of a bus duct is shown below. The impedance and voltage drop values for aluminum and copper conduc-
tors are shown in the table below.
The values listed are measured between the upper and middle lines at 60Hz. For a 50Hz installation, multiply the reactance (X) by 0.83.
Component
α = 0.5, Distributed load • F : Flanged End (panel connections)
(a place such as a vertical section) F P P P P P • P : Plug-in Unit
Technical Data
250 32 15.1 35.4 9.15 9.42 9.44 8.13
AL 400 15.3 13.8 20.6 10.74 10.76 10.42 8.19
630 6.7 8.0 10.5 11.38 11.11 10.41 7.32
800 5.0 6.5 8.2 11.28 10.95 10.16 6.92
160 82.2 20.9 84.8 9.17 9.56 9.73 8.75
250 35.1 17.6 36.3 9.64 9.80 9.68 8.04
CU 400 17.6 13.7 22.3 11.24 11.34 11.10 8.96
630 5.9 9.8 11.4 12.14 11.56 10.44 6.42
800 4.4 8.1 9.2 12.25 11.57 10.33 6.05
AL(kA) CU(kA)
Ampere (A)
1 sec. 3 sec. 1 sec. 3 sec.
160 10 6 10 6
250 10 6 10 6
400 25 15 25 15
630 30 17 30 17
800 40 23 40 23
Technical Data
Temperature Rise
The temperature rise limit is an important property which determines the performance of bus ducts. The temperature rise
limit of the bus duct is designed so that when a bus duct is operated with a rated current, the temperature limit values of the
housing are within 55K as specified in IEC61439-2 and 6 [(previous standard) IEC 60439-1 and 2].
1 2 3 4 5
7 8
-Joint- 6
80 2 3
1
70
60 4
Temperature(℃)
7 8
50
40 5
6
30
9
20
10
0 1 2 3 4 5 6 7 8
Time(hr)
Classification 1 2 3 4 5 6 7 8 9
Ambient
Censer Location Connection Conductor Housing
Temperature
Temperature Rise
75K 79K 80K 61K 39K 32K 52K 53K 23℃
Value
Joint Connection
1 2
Both parts should be aligned at the top and the bottom and the left and Using a torque wrench, slowly tighten the exposed bolt head of a
the right as well as horizontally and vertically. (This also applies to the joint double head bolt. The double head bolt head is designed to break
connection of the horizontal and vertical ducts.) Make sure that the joint off at 800~1000Kgf•cm. Continue tightening the exposed head until
kit is not tilted. (We recommend a jig tool for the installation.) it breaks off.
3 4
Technical Data
Once the exposed head and the red tag attached to it have been cut off, Be sure to check the distance from the housing, and the gaps between the
Information
a red line should be visible, which means they are properly connected. conductors at the kit after the installation.
Intall
5 6
Before applying the connection cover, check the space between the end Perform the last inspection of the connection. (Follow the instruction of
block and the holes of the connection cover. the installation manual for additional sealing according to the IP Code)
Refractoriness Certification Dust proof and Water proof TUV Eco Friendly Certification
Certification
Contents
I. Introduction
- Overview 14
- Application 15
II. General Data 16
III. Component
- Feeder 19
- Feed in Unit 22
- Flexible Fitting 23
- End Cover 24
- Hanger 24
- Plug In Unit 25
IV. Technical Data
- Impedance 26
- Voltage Drop 26
- Temperature Rise 27
V. Install Information
- Joint Connection 28
- Plug-in Unit Installation 28
VI. Certification & Specification 29
I. Introduction
Overview
About LT-Way
LSC&S LT-Way is designed for small capacity loads of 25 to 63A such as lamp circuits. It is also designed to blend in well with the existing facilities, while
providing the optimum power supply system. The LT-Way comes with the optimized cross sectional areas as well as stable design of conductors and
housing, which provide efficient heat-radiating property specified in IEC heat regulations. The LT-Way also comes with a high degree of protection with
standard IP54. The design can be applied in a special environment such as greenhouses and clean-rooms. Its adaptability to frequent alterations of a
layout makes it a perfect product.
Environmentally Friendly
The LS C&S LT-Way is an environmentally friendly product following the
RoHS regulation, and only uses components without hazardous substances.
Easy Installation
The light weight of LS C&S Mini-Way enables easy transportation
and installation, and employing the joint brush system makes
it easy to take apart and assemble. The plug-in load distribution
provides easier maintenance and installation compare to cables.
Application
Introduction
Major Supermarkets
Factory Production
Basement Parking
• Can be used as lighting system for basement parking space of
large buildings, apartments and commercial complexes.
Plug-in Hole
Plug-in Unit
Gemeral Data
Feeder
Flexible Fitting
Conductors Housing
The conductor uses over 99 percent pure copper flat The high strength aluminum housing can be used
wire consisting of 2 or 4 fibers. Elongated marks have as a protective conductor (PE) due to its high level
been etched in order to prevent slips when pressed. conductivity and mechanical strength. Variety of
The LT-Way comes with high molecule insulation coating options for the housing is available on request.
of a fire proof grade A rating. The intervals between
insulations have been designed for the optimum
functionality as specified in CAE (Computer Aided
Engineering).
Basic Structure
LT-Way comes with flat-wire, and suitable for small loads or lamp loads of 690V 25 to 63A. Each phase has been wrapped
with PVC, an electric insulation with an A rating (fire proof grade 105 Celsius) or higher, and the same rating insulation sup-
ports them.
Configration
Feeder
The standard length of feeders is either 3 meters or 1.5 meters,
and 5 plug-in holes can be applied on each side of a
3 meter feeder (maximum 10 holes).
For a 1.5 meter feeder, 3 plug-in holes can be applied
on each side (maximum 6 holes).
Gemeral Data
Component
1500
250 500 500 250
Ø
H
1500
375 750 375
3000
300 600 600 600 600 300
3000
500 1000 1000 500
3000
750 1500 750
Dimension(mm)
Ampere(A)
H W 외경Φ
25 1.8
CU 40 30 50
2.8
63
Feeder
A single housing can handle two lines (R, S, T, NX2), and the 3-phase 4-wire system supplies larger capacity than a single
phase which decrease the line imbalance.
Component
40 6 2 3000 2 LSLT F406232
2970
40 6 2 3000 3 LSLT F406233
40 6 2 3000 5 LSLT F406235
40 6 2 1500 2 LSLT F406212
1565
40 6 2 1500 3 LSLT F406213
25 6 2 3000 0 LSLT F256230
25 6 2 3000 2 LSLT F256232
2890
25 6 2 3000 3 LSLT F256233
25 6 2 3000 5 LSLT F256235
25 6 2 1500 2 LSLT F256212
1525
STD. Feeder 25 6 2 1500 3 LSLT F256213
(3Ph + N + PE)(Ph + N + PE) 40 6 2 3000 0 LSLT F406230
40 6 2 3000 2 LSLT F406232
3415
40 6 2 3000 3 LSLT F406233
40 6 2 3000 5 LSLT F406235
40 6 2 1500 2 LSLT F406212
1790
40 6 2 1500 3 LSLT F406213
25 8 2 3000 0 LSLT F258230
25 8 2 3000 2 LSLT F258232
3175
25 8 2 3000 3 LSLT F258233
25 8 2 3000 5 LSLT F258235
25 8 2 1500 2 LSLT F258212
1670
STD. Feeder 25 8 2 1500 3 LSLT F258213
(3Ph + N + PE) x 2 40 8 2 3000 0 LSLT F408230
40 8 2 3000 2 LSLT F408232
3860
40 8 2 3000 3 LSLT F408233
40 8 2 3000 5 LSLT F408235
40 8 2 1500 2 LSLT F408212
2010
40 8 2 1500 3 LSLT F408213
Feed in Unit
The feed in unit connects cables and the LT-Way. It can connect a maximum 10mm and is
used at the opening and ending points of source and load system.
69
90 347
69
90 271
Flexible Fitting
The flexible fitting rotates 180°, and used to adjust the height or bypass a route.
The fixing method is the same as the feeder, and the standard length is 0.5m and 1m.
53
33
500
105
1000
Component
605
End Cover
The end cover is applied at the end of a rail,
and the capacity for the covers is the same.
53
33 24
Capacity Source/Load Cat No.
A Source / Load No.
25 Source LSLT ES
53
25 Load LSLT EL
40 Source LSLT ES
93 40 Load LSLT EL
33
63 Source LSLT ES
63 Load LSLT EL
Hanger
General Type Direct Type
Maximum • The hangers are designed to install the bus ducts at buildings.
Product Install Method Load
• They can be either installed directly to the ceiling, or at the hanger rods.
kg
• The standard installation interval between hangers is 1.5 meters.
It is installed at the Caution) When the hangers are used to fix lamps, avoid the joint connections.
General Type 60
hanging bolt.
It is installed at the
Direct Type 60
fixing band.
Note
Please contact out design team if a special type of hangers (Tee or Reducer) are required due to the installation environment.
Plug-in Unit
The load distribution system can be either installed or removed with a live line. The unit is a double-sided
clamp to connect a conductor, and incombustible materials have been used for the insulation and plastic
Component
L1+N LSLT P10FU1
L2+N LSLT P10FU2
L3+N LSLT P10FU3
Fuse형 10/16A L1+L2 LSLT P10FU12
L1+L3 LSLT P10FU13
L2+L3 LSLT P10FU23
L1+L2+L3+N LSLT P10FU4
Technical Data
Impedance and Voltage Drop
The formula to measure the voltage drop of a bus duct is shown below. The impedance and voltage drop values for aluminum and
copper conductors are shown in the table below.
The values listed are measured between the upper and middle lines at 60Hz. For a 50Hz installation, multiply the reactance (X) by 0.83.
Copper(kA)
Ampere(A)
1 sec. 3 sec.
25 0.6 0.34
40 1.4 0.8
63 1.4 0.8
Temperature rise
The temperature rise limit is an important property which determines the performance of bus ducts. The temperature rise limit of the bus duct is
designed so that when a bus duct is operated with a rated current , the temperature limit values of the housing are within 55K as specified
in IEC61439-2 and 6 [(previous standard) IEC 60439-1 and 2].
1 2 3 4 5
7 8
Technical Data
-Joint- 6
80
70
60
Temperature(℃)
50 2
3 1
40 4
30
20 7 5
8 6
10 9
0 1 2 3 4 5 6 7 8
Time(hr)
Classification 1 2 3 4 5 6 7 8 9
Ambient
Censer Location Connection Conductor Housing
Temperature
Temperature Rise
46K 49K 46K 40K 15K 14K 15K 14K 12℃
Value
Joint Connection
1) Check the condition of the joint, and loosen the cross heads 2) Insert the end into the other as shown in the image below,
of the protection cover. and tighten the cross heads.
Caution) Don’t loosen the hexagon bolts for they fix the
products in place.
(O) (X)
(X)
(O)
! Caution
Make sure to clean the parts of the joint before installation. Proceed with caution since the joint can be damaged by impacts.
Be sure to keep them straight and steady to connect.
! Caution
Make sure the plug-in holes are clean before inserting the plug-in unit. Be sure to check the phase of unit and the plug.
Temperature Rise Test KERI Temperature Rise Test KERI Heat Resistant Performance
Certification Certification Certification
Information
Certification
Intall
Certification &
Specification
OHSAS 18001
Memo
Certification &
Specification
Contents
I. Introduction
- Overview 14
- Application 15
II. General Data 16
III. Component
- Feeder 21
- Fittings 21
- Flanged End 23
- Cable Junction Box 23
- Plug-In Unit 24
- Hanger 25
- Etc 28
IV. Technical Data
- Impedance 29
- Voltage Drop 29
- Temperature Rise 30
V. Install Information
- Joint Connection 31
VI. Certification & Specification 32
I. Introduction
Overview
The MS/Wind-Way is a hybrid type bus duct that combined the benefits of the sandwich type and the air insulation type.
The MS/Wind-Way is economic, and provides maximum stability. Compared to the existing power supply system
(cables), the MS/Wind-Way provides excellent economical efficiency, and provides stable supply of large capacity of
energy. It is simple to install, and has excellent space efficiency.
The MS/Wind-Way is suitable for inadequate or special environment such as; chemical or steel plants where the accident
rate due to powder coating is high; ships where durability against temperature, humidity and quack (shock vibration) is
required; and wind towers. The MS/Wind-Way and its routing system have been fully tested for the functionally.
[Product Size]
Comparison
• The hybrid type comes with the optimum
explosion proof design against harmful gas
in sealed areas.
Application
Introduction
Chemical Plants
• It is suitable for indoor and outdoor installation as well as
a place where high degree of protection is required.
• Petrochemical Plants
Ships
• It is suitable for areas exposed to high salinity such as
seawater.
• Electrical room of a ship
Wind Towers
• Areas where low frequency oscillation occurs by wind
• The generator and the transformer of a wind tower
Plug-in Hole
Plug-in Box
Joint
Gemeral Data
Elbow
Feeder
Conductors Housing
The MS-Way uses either copper conductors with The Mini-Way uses an effective heat–radiating aluminum
conductivity at over 99%, or aluminum conductors housing profile which produces an excellent mechanical
with conductivity at over 61%. The connection of strength and heat radiation. The aluminum housing can
the conductors is tin-plated in order to reduce contact be used as a protective conductor (PE) thanks to its high
resistance and to prevent corrosion of the connection. level conductivity and cross sectional areas.
Special Feature
Thesafety first designof the MS/Wind-Way makes it an idealoption for ships and wind towers. By separating the poxy
coated phase conductors, the Wind-Way obtained the epoxy and air insulation property.
Our design ensures electrical, structural and chemical stability. The MS/Wind-Way as well as the components and the
accessories such as feeders,fittings, plug-in boxes and hangers passed the rigorous ship classification, and obtained
certification form prestigious risk managing organizations.
*Ship classification: DNV, BV, LR, ABS, GL and KR
Electrical Stability
: The mechanical and heat stress caused by short
circuit should be taken into consideration when
accidents occurs.
100
Q Factor Limit
10
Q facto
Z-dir
1 Y-dir
X-dir
0.1
0 50 100 150
Frequency (Hz)
Gemeral Data
• Damp Heat • Dry Heat • Salt Mist • Cold
Explosion Proof Design ; IEC 60079, Creepage Distance / Spacing / Impact Resistance / IP54
• A 1000V bare conductor with equipment protection by increased safety ‘e’: The Creepage distance and spacing has been
designed as specified in IEC standards.
• Impact Resistance Design: Steal ball weight: 1Kg/Diameter 25mm/Drop Height 1meter
• IP54 : The Wind-Way and its joint connections are designed according to IP54.
The degree of protection against water of the LS C&S E-Series is a standard IP54; however, it can be adjusted from IP42
to IP65 depending on the environment and on request.
IP
Solid Particle Protection Liquid Ingress Protection
0 No Protection 0 No Protection
Feeder
Although the standard length of the mini-way feeder is 3 meters, it can be adjusted to the installation environment on request.
A A A
Gemeral Data
211
211
225
W W
W W
Dimension (mm)
Ampere(A) Weight(kg/m) Fig.
t W A
Component
1000 90 156 16
IP31 2200 160 226 22 W1-1
3200 250 316 28
1000 90 197 16.5
1250 98 205 19.5
1600 138 245 22.5 W1-2
AL 2000 10 185 292 31
2500 233 340 35
IP54
3200 160 463 38
3600 187 513 46
4000 212 563 49 W1-3
4500 243 652 52
5000 260 659 54
Fittings
MS/Mini-Way has a wide range of fittings to satisfy any layout of buildings. Elbow angles other than ninety degrees are also
available. Fitting designs are shown in the following figures, and they consist of the source-side and the load-side. Offset or
combination elbows can be used where standard elbows are not feasible. (Dimensions for each fitting are shown in the fol-
lowing figures. Contact our design team for a minimum dimension.)
Elbow
[Horizontal] [Vertical]
Dimension (mm)
Ampere(A)
X Y
1000~1600 600 600
2000~2500 600 600
AL
3200~3600 800 800
4000~5000 900 900
Fittings
Offset
[Horizontal] [Vertical]
Dimension (mm)
Ampere(A)
X Y Z
1000~1600 500 500 500
2000~2500 600 600 600
AL
3200~3600 800 800 800
4000~5000 900 900 900
Tee
[Horizontal] [Vertical]
Dimension (mm)
Ampere(A)
X Y Z
1000~1600 500 500 500
2000~2500 600 600 600
AL
3200~3600 800 800 800
4000~5000 900 900 900
Combination
Elbow
Dimension
Ampere
X Y Z
1000~1600 500 500 500
2000~2500 600 600 600
AL
3200~3600 800 800 800
4000~5000 900 900 900
Flanged End
Flanged end is connected to either a transformer or a panel. Dimension details are shown below.
Component
[Fig. W2-1] [Fig. W2-2] [Fig. W2-3] [Fig. W2-4]
Dimension (mm)
Ampere(A) Fig.
t W A B
1000 90 40 100
W2-1
1250 98 40 100
1600 138 40 100 W2-2
2000 185 70 100 W2-3
2500 233 60 100 W2-4
AL 10
3200 (2)160 60 130
3600 (2)187 70 130 W2-3
4000 (2)212 70 130
4500 (2)243 60 130
W2-4
5000 (2)260 70 130
Plug-in Unit
A plug-in unit can be installed at a distribution board
to distribute loads between 50 to 800A when a
distribution board is required at loads and lines.
Thanks to this beneficial factor, the size of the
distribution board is reduced, and the distribution
board can easily distribute loads at any location of
the system. As a result, the unit provides a flexible
approach to handle the flow of loads.
The preinstalled MCCB in the plug-in unit can
quickly shut off fault currents at a load; therefore,
can prevent the fault current from spreading to
the other loads.
It is recommended to use MCCB which has been
selected as a standard by the company, or other
certified products for the plug-in unit.
Hanger
Horizontal Hangers
The standard installation method for these hangers is to install them horizontally at 1.5 meters intervals. They generally require 12mm diameter stud bolts.
Hanger
Clamp
Component
Damper
Damper
Damper
Hanger
Hanger
Special Type for Ships
This special type is designed for ships, and it comes in U-shaped channel steel. The
special type requires two supports per each set.
STEP 1
Fix the hanger tightly at a designated location.
(maximum height=700mm, standard installation intervals=1.5m)
Max.
700mm
STEP 2
Place the product in the center of the hanger.
STEP 3
Use a clamp to apply bolting, and fix both sides as shown
in the image.
STEP 1
Install dampers and supports at the designated locations in accordance
with the layout as shown in the image.
STEP 2
Apply at two locations for each product as shown in the image.
Component
Vertical Load Type
STEP 1
Install dampers and supports at the designated locations in accordance
with the layout as shown in the image.
STEP 2
Apply at the lowest location of each section.
(Please contact our design team for detailed information.)
A-60 Approved
Bulkhead Insulation
Density 110kg/m3 Bulkhead
Furnace
Etc.
KVM Sealing Compound MANGANA Retaining Compound
or KVM 20mm Thickness
A-60 Approved
Bulkhead Insulation
Bulkhead and Deck Opening Size Density 120kg/m3 Bus Trunk Transit Thickness
6mm(steel)
Either bulkhead or deck can be penetrated while installing the product on a ship. The specifications of the opening size and the installation
method are shown below.(Please contact our) design team
Hi-Wool(120kg/m forRetaining
MANGANA detailed
Compound information for insulation
3 and compound installation.)
KVM Sealing Compound
Insulation or KVM 20mm Thickness
Furnace
Bulkhead
A-60 Approved
B
Bulkhead Insulation A A-60 Approved
Density 110kg/m3 Bulkhead Insulation
Bulkhead Density 110kg/m3
MANGANA Retaining Compound Bus Trunk Transit Steel Plate 6t MANGANA Retaining Compound 20mm Thickness
Furnace
20mm Thickness Bus Trunk Transit Steel Plate 6t
MANGANA Retaining Compound
or KVM 20mm Thickness KVM Sealing Compound
Deck
A-60 Approved
B A Bulkhead Insulation
B 3
Density 110kg/m Bulkhead
mpound Bus Trunk Transit Steel Plate 6t MANGANA Retaining Compound 20mm Thickness Furnace
MANGANA Retaining Compound Bus Trunk Transit Steel Plate 6t MANGANA Retaining Compound 20mm Th
Bus Trunk Transit Steel Plate 6t MANGANA Retaining Compound
KVM Sealing Compound 20mm Thickness
or KVM 20mm Thickness
t
t
KVM Sealing Compound
Hi-Wool(120kg/m3) MANGANA Retaining Compound KVMCompound
KVM Sealing Sealing Compound KVM Sealing Compound
Insulation or KVM 20mm Thickness
Furnace
B A
MANGANA Retaining Compound Bus Trunk Transit Steel Plate 6t MANGANA Retaining Compound 20mm Thickness
20mm Thickness Dimension (mm) Bus Trunk Transit Steel Plate 6t
Ampere(A)
t W A B
1000 Deck 90 320 W Bulkhead
t
1250A W
98 B 330
1600 138 370
2000 185 420
t
2500 233 470
AL KVM Sealing Compound 10 KVM Sealing Compound 330
3200 160 590
3600 187 640
4000 212 690
4500 243 750
5000 260 780
Note
The term for the upper and lower wall of a ship is called ‘deck’, and the deck needs to satisfy difficult conditions regulated by the classification society
in order to prevent flame spreads and flooding.
Technical Data
Impedance and Voltage Drop
The formula to measure the voltage drop of a busduct is shown below. The impedance and voltage drop values for aluminum and copper
conductors are shown in the table below.
The values listed are measured between upper and middle lines at 60Hz. For a 50Hz installation, multiply the reactance (X) by 0.83.
Component
α = 0.5, Distributed load • F : Flanged End (panel connections)
(a place such as a vertical section) F P P P P P • P : Plug-in Unit
Technical Data
1250 33.09 61.87 70.16 14.58 13.77 12.29 7.16
1600 24.51 48.78 54.59 14.41 13.54 12.01 6.79
2000 19.06 39.15 43.54 14.31 13.42 11.85 6.60
2500 15.65 32.62 36.18 14.83 13.90 12.26 6.78
3200 12.11 25.49 28.22 14.79 13.85 12.20 6.71
3600 10.38 21.95 24.28 14.30 13.39 11.79 6.47
4000 9.34 19.67 21.77 14.26 13.35 11.76 6.47
4500 8.33 17.44 19.33 14.25 13.35 11.77 6.49
5000 7.85 16.42 18.20 14.91 13.97 12.32 6.80
Ampere(A) 1000 1250 1600 2000 2500 3200 3600 4000 4500 5000
Shirt circuit (kA), 1sec. 46 72 90 98 126 135 150 150 150 150
Shirt circuit (kA), 3sec. 26 41 51 56 72 77 86 86 86 86
Temperature Rise
The temperature rise limit is an important property which determines the performance of bus ducts. The temperature rise limit of the bus duct is
designed that when a bus duct is operated with a rated current , the temperature limit values of the housing are within 55K as specified in IEC61439-2
and 6 [(previous standard) IEC 60439-1 and 2].
1 2 3 4
6 7
- Joint -
5
80
70
2
60 3
Temperature(℃)
50
40 4
6 7
5
30
8
20
10
0 1 2 3 4 5 6 7 8
Time(hr)
Classification 1 2 3 4 5 6 7 8
Ambient
Censer Location Joint Conductor Housing
Temperature
Temperature Rise Value 57K 63K 60K 40K 32K 33K 33K 22℃
Joint Connection
STEP 1
Check for any deformations or stains, and make sure the
bus ducts are aligned with the connecting direction. Insert
slowly towards the connecting direction.
STEP 2
Using a torque wrench, slowly tighten the exposed
bolt head of a double head bolt until it breaks off.
Technical Data
STEP 3
Once all the exposed double head bolts have been
cut off, place the top and bottom joint covers, and fix
them tightly with bolts.
Information
Intall
The double head bolts have been applied to the system for better connection. The double head bolt head and the red tag attached to it are designed
to break off at 800~1000Kgf•cm. Once the exposed head and the red tag attached to it have been cut off, the connected torque and the condition of
the connection will be visible for inspection. The highly reliable one-bolting connection system will provide electrical and mechanical stability of the
entire system to satisfy the needs of the clients.
Major References
Contents
I. Introduction
- Overview 14
- Application 15
- Customized Engineering 16
LV MV
II. General Data 21 26
III. Component
- Feeder 22 28
- Fittings 23 30
- Hanger 24 33
Overview
The NSPB
The design of the LS C&S NSPB Bus Duct improved the stability of the system by incorporating the epoxy coating and air insulation. The Bus Duct is
available from a low voltage of AC 1000V or less, up to a high voltage of 27kV. It is suitable for current capacities between 800A to 4000A.The bus duct
comes with a class B rating (130°C) insulation and its water proof quality is suitable for outdoors.
NSPB-LV
NSPB-LV
NSPB-MV
Switchgear
NSPB-MV
TR Flanged
End Box
TR Flanged
End Box
Transformer
Outdoor
Transformer
Introduction
Application
Large Buildings
Customized Engineering
The company provides a wide range of options including conductors, materials and design of housing as well as products
for various range of voltage (27kV or less) and current(between 800A and 4000A) to satisfy the needs of the clients and their
specifications.
01 Standard
The specialists of the company will provide the ideal size of the conductors and products through tests and analyses as specified in CAE to satisfy
specific needs of clients.
Configration
LV
•IEC 61439-6 [(previous standard) IEC 60439-20]
Busbar Trunking Systems
• IEEE C37.23 IEEE Standard for Metal-Enclosed Bus
IEC IEEE
전압 등급 1000V or less 0.635kVor less
Ambient 35℃ 40℃
•Housing : 55K •Housing : 40K
•Conductor : 70K •Conductor : 65K
Tempera-
The specifics can be adjusted according to the
heat resistance values of the insulations.
MV
• IEC 62271 High-voltage switchgear and controlgear
Part 200 : AC metal-enclosed switchgear and controlgear for rated
Voltages above 1 kV and up to and including 52 kV
• IEEE C37.23 IEEE Standard for Metal-Enclosed Bus
IEC IEEE
7.2(20) 4.760(19)
전압 등급 12(28) -
(내전압) 17.5(38) 15(36)
24(50) 27(60)
Ambient 35℃ 40℃
•Housing : 55K •Housing : 40K
•Conductor : 70K •Conductor : 65K
Tempera-
The specifics can be adjusted according to the
heat resistance values of the insulations.
Introduction
02 Conductor Materials
The NSPB Bus Duct uses either copper conductors with conductivity over 99%, or aluminum conductors with conductivity over 54%.
The connection of the conductors is tin-plated in order to reduce contact resistance and to prevent corrosion of the connection.
(A silver plated option is available.)
03 Conductor Insulations
The NSPB Bus Duct comes with standard epoxy coating, however, tube insulations is available on request. Epoxy coating is applied by automated
facility. The company performs rigorous testing on the products including exterior of the conductors, coating thickness, pin holes, impacts and
flexibilities to provide products that are highly safe.
Note
The optimized heat-radiating structure and size of the conductors are
chosen through simulation and actual measurement tests including
heat-radiating mechanism of the conductors, coating effects, housing
materials and the location of the grounding bar. (The size of the
conductors can be reduced when the conductors are aligned vertically
in comparison to horizontally aligned conductors.)
05 Housing Materials
High strength aluminum (50 type), STS, steel or materials with either the same or higher mechanical strength are used for housing of the NSPB Bus
Duct. Therefore, the mechanical strength and the heat-radiating property of the housing are excellent. The standard color of the coating is 5Y 7/1,
however, the company provides a wide range of color to satisfy the needs.
Note
The 3 types of current supply loss of metal materials are shown below.
1) Hysteresis loss (iron loss)
2) Eddy-current lose (induced current loss)
3) Copper loss.
These losses eventually increase loss resistance. Compared to the
characters of steel, a ferromagnetic body and high permeability, using
aluminum and STS decreases the loss from magnetic flux caused by time
variation of the current.
Customized Engineering
The company provides a wide range of options including conductors, materials and design of housing as well as products
for various range of voltage (27kV or less) and current(between 800A and 4000A) to satisfy the needs of the clients and their
specifications.
06 Insulation Support
Using insulations (LV: engineering plastic, MV: epoxy type) with dielectric
strength in correspondence with voltage ensures the insulation property
of the housing. In order to obtain the stable installation and sufficient
functionality of the conductors, the insulations are located at ideal
intervals based on analysis of CAE (Computer Aided Engineering).
Note
There are 3 types of air insulation bus ducts. (IEEE Std C37.23: IEE Standard for Metal-Enclosed Bus Standard) LS Cable and System provides the NSPB
type, however, other types are available to satisfy the needs, or for special environments. (Please contact out design team for further information.)
Introduction
07 Options
Grounding, Space heaters, Vents
Grounding
The standard aluminum housing of the NSPB is designed to perform
as a grounding conductor without additional conductors. (Additional
ground bars can be added on request. Please contact our design team
for further information.)
Space Heaters
A space heater can be applied for outdoor products to reduce dew
condensation. The heater is installed inside of the product during pro-
duction. A temperature sensor or a humidistat can be applied along
with the heater for better control. A space heater set is installed for each
feeder as the standard installation.
Drain Holes
(bottom)
NSPB-LV
Contents
II. General Data 21
III. Component
- Feeder 22
- Fittings 23
- Hanger 24
Ⅱ. General Data 06 / 07
Basic Structure
The NSPB-LV uses epoxy insulating material (thermal class 130 C) to separate the phases, and secure them using high
strength engineering plastic. It can be applied to 1000V or less, or between 800A and 4000A.
Gemeral Data
Structure
• Al / STS / SPCC
• Supporting Insulater
• CU or AL
Sectional View
Joint Cover
• Final Cover
Indoor Outdoor
Note
The NSPB is a hybrid type bus duct that combined the benefits of the epoxy insulation type and the air insulation type. Although it provides better
insulation stability, it is larger and the cost is higher than the E-Series (sandwich type). Therefore, they are suitable for large plants where the stability
is priority.
Feeder
Although the standard length of the LS C&S NSPB-LV Bus Duct is 2 meters, it can be adjusted to the installation environment
and on request.
w B
w B
t t
NL-1-1 NL-1-2
* Since the standards of the conductors differ, these are only for reference, and they
can be adjusted according to the installation site, or on request.
(For using aluminum conductors, please contact our design team for further information.)
Flanged End
The flanged end is used at a transformer or at a low-tension panel.
(Please, contact our design team for further information.)
Fittings
LS C&S NSPB has a wide range of fittings to satisfy any layout of buildings. Elbow angles other than ninety degrees are also
available. Offsets or tees can be applied where the standard elbows are not feasible. (Please contact our design team for
detailed information about the product length.)
Elbow
[Vertical] [Horizontal]
Component
Offset
[Vertical] [Horizontal]
Tee
[Vertical] [Horizontal]
Hanger
LS C&S NSPB can be installed using horizontal hangers, vertical hangers and wall brackets according to the installation
environment. (Please contact our design team for detailed information about installation.)
Horizontal
For horizontal installation, the NSPB requires two or more
supports for each product.
NSPB-MV
Contents
II. General Data 26
III. Component
- Feeder 28
- Fittings 30
- Flanged End 32
- Hanger 33
Ⅱ. General Data
Basic Structure
The NSPB-MV uses epoxy insulating material (thermal class 130 C) to separate the phases, and secure them using high strength
epoxy. It can be applied to 1000V or less, or between 800A and 4000A.
Structure (Vertical)
• Al / STS / SPCC
• Supporting Insulater
• Copper or Aluminum
Sectional View
Structure (Horizontal)
• Al / STS / SPCC
• Supporting Insulater
• Copper or Aluminum
Sectional View
Gemeral Data
도체 절연 및 접속
The conductors come with standard epoxy coating insulation. Tube insulation is also available on request. Use joint plates
to connect the parts, and cover them with boots as shown in the image below.
Joint Covers
For indoor installation, applying joint covers are sufficient; however, for outdoor installation, final covers should be applied additionally on top
of the joint covers. (Please contact our design team for further information.)
• Final Cover
Indoor Outdoor
w B
w B
t t
NM-1-1 NM-1-2
The standards of the conductors are only for reference, and they can be adjusted according to the installation environment,
or on request. (For using aluminum conductors, please contact our design team for further information.)
w
w
t B
t B
NM-2-1 NM-2-2
Component
[mm]
t W A B
800 6 50 670 330
1000 6 65 715 330
1250 10 65 715 335 NM2-1
1600 10 100 820 335
CU 6.35*41
2000 10 125 895 335
2500 10 110 850 355
3200 13 125 895 360 NM2-2
4000 15 150 970 370
The standards of the conductors are only for reference, and they can be adjusted according to the installation environment,
or on request. (For using aluminum conductors, please contact our design team for further information.)
Fittings
LS C&S NSPB has a wide range of fittings to satisfy any layout of buildings. Elbow angles other than ninety degrees are also
available. Offsets or tees can be applied where the standard elbows are not feasible. (Please contact our design team for
detailed information about the product size.)
Component
Offset (Alignment of the Conductors : Vertical)
Vertical Horizontal
Flanged End
The flanged end is used at a transformer or at a low-tension panel.
(Please, contact our design team for further information including the size and capacity.)
Vertically Aligned
Horizontally Aligned
Hangers
LS C&S NSPB can be installed using horizontal hangers, vertical hangers and wall brackets according to the installation
environment. (Please contact our design team for detailed information about installation.)
Horizontal Hangers
For horizontal installation, the NSPB requires two or more
supports for each product.
Component
Vertical Hangers Wall Bracket
An additional reinforcement design provides stability Once the angles and the channels are applied on walls,
for the vertical loading of the vertical feeders. they need to be fixed with bolts.
Technical Data
The short circuit strength of the LS C&S NSPB can be adjusted and produced in accordance with the request and
specifics of the clients.
15 36 95
1250~2000
50(65) 130(170)
2500~4000
27 60 125
* The numbers shown in the parenthesis of the short circuit current is the value of reinforcement products (optional).
[NSPB-LV] [NSPB-MV]
Technical Data
STEP 2.
• Apply the top and bottom joint covers,
and tighten the bolts securely.
• For the NSPB-MV, apply boots additionally after
joint plates have been connected as shown in
the image.
Information
Intall
[NSPB - LV] [NSPB - MV]
STEP 3.
• For outdoor installation, apply the top and bottom joint cover and reinforcement covers.
Apply silicone at both sides of the covers as shown in the image. (Torque = 120 kgf·cm)
Silicone Application
Steel-making plant and sintering plant of Hyundai Steel Korea Gas Corporation Substation 21 in Pyeongtaek
Co., Ltd. Investor : Korea Gas Corporation
Investor : Samsung Engineering Construction Period : 2010
Construction Period : 2008
Certification &
Specification
AKG2 (AL-KHALEEJ GAS) PROJECT PHASE II RAS LAFFAN PROJECT PHASE 6 & 7
Busduct Major
Memo
Certification &
Specification
Contents
I. Introduction
- Overview 14
- Application 15
- General Data 16
LV MV
II. General Data 20 33
III. Component
- Feeder 22 35
- Flanged End 23
- Fittings 24 36
- Terminal 37
- Hanger 26 38
- Etc 27 39
IV. Technical Data
- Impedance 28 40
- Voltage Drop 28 40
- Temperature Rise 29 41
V. Install Information 30 42
Overview
The CR-Way
The LS C&S CR-Way is available from a low voltage of AC 1000V or less, up to a high voltage of 27kV. It is suitable for current capacities between 630A
to 7500A (high voltage product 120~5000A). The epoxy resin molding performs as insulation and housing with an IP68 rating. The CR-Way is suitable
for plants and factories where large capacity of power is required. It is an ideal distribution wiring system for outdoors, humid and dusty areas and any
place where chemicals are frequently used.
Anticorrosion
The epoxy insulation of the CR-Way is highly resistant to erosion
and corrosion. Additional housing can be applied to maximize
Waterproof
The CR-Way comes with a standard IP68 rating, and is protected
completely against water and particles. It is safe to use in an inadequate
environment.
Fireproof
The CR-Way comes with fire resistance efficiency as a standard feature,
and it is designed to prevent flames from spreading.
Explosion Proof
The CR-Way is designed to be completely molded by insulation, and
this design ensures safety use of the product near inflammable steam
and gas, and dusty environment with an explosive atmosphere.
Introduction
Application
Plants & Factories
Ships
• Can be applied where salt concentration is
high including sea water
• Electrical room on a ship
Offset
Elbow
CR - LV
CR - MV
CR - MV
Gemeral Data
[01. Assembly of Molding Flasks and Booth Bars]
Epoxy Color
tank tank
The standard feature of the CR-Way comes with a standard IP68 rating. The CR-Way is suitable for humid and dusty
areas, chemical plants and areas where condensation may occur (exposed section between indoors and outdoors).
IP 6 8
Solid Particle Protection Liquid Ingress Protection
0 No Protection 0 No Protection
CR-LV
LS 전선 Busduct System Catalogue
06 of 08
Contents
II. General Data 20
III. Component
- Feeder 22
- Flanged End 23
- Fittings 24
- Hanger 26
- Etc 27
IV. Technical Data
- Impedence 28
- Voltage Drop 28
- Temperature Rise 29
V. Install Information 30
Ⅱ. General Data
Basic Structure
The CR-LV consists of conductors and epoxy resin. Since the resin performs as insulation and housing which provides protec-
tion to the interior structure, additional bus ducts or housing are not necessary.
For outdoor installation (sun exposure), a sun shade is used to prevent the epoxy resin from being exposed to direct sunlight.
• Sunshade(steel)
Configration
While other bus ducts with metal housing require grounding, the CR-LV does not require additional grounding because the epoxy resin insulation
itself performs as housing. (Additional grounding is available on request. Please contact our design team for further information.)
Joint Kit
The CR-Way uses a joint kit method.
Feature
Gemeral Data
Both joint plates of the joint kit and the conductors are tin plated. (A silver
plated option is available.) It prevents discoloration and corrosion of the joint
plates. In order to ensure easy maintenance and reliability, double -headed
bolts and visible labels are used to check the application, and a disc spring
allows an even connection of the contact surface.
! Precaution
Be sure to clean the interior of the connections prior to installation. Use caution not to twist the joint kit while inserting it, and after it is inserted.
An excessive pressure during installation may break the kit. Make sure that the double-headed bolts and the red tags are intact.
If a proper torque is not applied at the connection, it may cause heat during operation.
Feeder
Although the standard length of the LS C&S CR-LV Bus Duct feeder is 3 meters, it can be adjusted to the installation
environment, or on request.
2B+140
2B+140
B B 140 B
B WW B 140 B
WW
AA
AA
t
t
[Fig. CL1-2] [Fig. CL1-2]
3B+280
3B+280
B 140 B 140 B
B 140 B 140 B
WW
[Fig. CL1-3] AA
Dimension(mm) Weight(kg/m)
Ampere(A) Fig.
t W A 3W 4W 4W+50%E 4W+100%E
630 41 78 21.3 23.7 23.2 23.3
800 65 102 26.7 30.4 29.5 29.6
1000 86 123 32.4 37.8 36.3 36.4
1250 108 145 38.5 42.7 42.7 42.6 CL1-1
1600 164 201 53.5 59.4 59.3 59.4
2000 210 247 65.7 72.9 72.8 71.9
AL 6.35
2500 126 163 85.2 99.4 95.1 97.4
3200 164 201 106.3 118 118 118.4
3600 184 221 116.4 129.7 129.6 130.1
CL1-2
4000 210 247 124.7 138.6 139 139.3
5000 184 221 182.8 193.2 193.4 189.1
6300 210 247 192.6 214.8 215.3 214.4
CL1-3
630 41 78 26.5 30.1 30.9 31.8
800 41 78 26.5 30.1 30.9 31.8
1000 57 94 32.2 37.3 38.9 39.6
1250 73 110 38.3 44.6 46.4 47.7
CL1-1
1600 108 145 51.7 60.4 62.5 64.8
2000 145 182 66.3 77.5 80.2 83.4
CU 2500 6.35 195 232 85.7 100.3 104.2 108.4
3200 108 145 104.6 122.9 127.8 131.8
3600 126 163 118.6 139.5 145 151.4
CL1-2
4000 145 182 134.8 158.3 164.6 170.4
5000 195 232 173.5 203.9 214 220.5
6300 164 201 204.3 241.5 252.3 260
CL1-3
7500 195 232 261.2 309 324.1 334.5
* B : 3WGE=90mm, 4WGE/4WHE/4WFE=100mm
Flanged End
The flanged end is connected to either a transformer or a
panel. Dimension details are shown below.
[Fig. CL2-1]
Component
[Fig. CL2-2] [Fig. CL2-3] [Fig. CL2-4] [Fig. CL2-5]
Dimension (mm)
Ampere(A) Fig.
t W A B
630 41 ~
CL2-2
800 62 ~
1,000 86 40
100 CL2-3
1,250 108 50
1,600 164 60
CL2-5
2,000 210 70
AL 6.35
2,500 (2)126 40 CL2-4
3,200 (2)164 60
3,600 (2)184 60
130
4,000 (2)210 70 CL2-5
5,000 (3)184 60
6,300 (3)210 70
630 41 ~
800 41 ~ CL2-2
1,000 57 ~
1,250 73 40 100
CL2-3
1,600 108 50
2,000 145 50 CL2-4
CU 2,500 6.35 195 70 CL2-5
3,200 (2)108 50 CL2-3
3,600 (2)126 40
CL2-4
4,000 (2)145 50
130
5,000 (2)195 70 CL2-5
6,300 (3)164 60 CL2-5
7,500 (3)195 70 CL2-5
Fittings
Fittings including the elbow and tee are designed to adapt to any change made to the direction of the bus duct installation.
The same features have been applied to the fittings of the CR-Way, and the size specifications are shown below.
(The standard dimension of each fitting is the same as the dimension shown in the table below. Please contact our design
team for information about the minimum dimension.)
Elbow
[Vertical] [Horizontal]
Y
X
Y
Dimension(mm) Dimension(mm)
Ampere(A) Ampere(A)
X Y X Y
1단 500 500 1단 500 500
2단 500 500 2단 600 600
3단 500 500 3단 700 700
Offset
[Vertical] [Horizontal]
Z
Z X
Y
Y
Dimension(mm) Dimension(mm)
Ampere(A) Ampere(A)
X Y Y X Y Z
1단 500 150 500 1단 500 300 500
2단 500 150 500 2단 500 300 500
3단 500 150 500 3단 500 300 500
Tee
[Vertical] [Horizontal]
Y Y
Z Z
Component
X X
Dimension(mm) Dimension(mm)
Ampere(A) Ampere(A)
X Y Z X Y Z
1단 500 500 500 1단 500 500 500
2단 500 500 500
3단 500 500 500
Combination Expansion(optional)
Dimension(mm)
Ampere(A)
X Y Z
1단 500 300 500
2단 600 400 600
3단 700 500 700
Hangers
Both horizontal and vertical hangers are available for the CR-LV depending on the installation environment.
Horizontal
The standard horizontal installation method of the CR-LV requires two supports for each product. The standard 3 meter bus ducts are designed to be
installed at 1.5 meters intervals, and the space between the hangers should not surpass 2 meters at the most. (Please contact the design team for further
information.)
Hanger rod
Hanger clamp
Hanger bar
Vertical Hangers
For vertical installation of The CR-LV, install the vertical hangers first, and fix the bus ducts on the hangers for better support.
Rigid hanger
Base
Etc.
Wall Flange Floor Opening
Wall opening size Floor opening size
Cut out Cut out
W+160
W+60
W+60
W+10
W
W
H+160
H+60
H+10
H+60
H
Component
H
A wall flange is used to seal the gaps produced during • W : The width of the product
bus duct installation on the walls, ceilings and floors. • H : The height of the product
The company does not provide glass wool or fire forms.
The required minimum distances from a wall for heat dissipation and maintenance
벽, 천정 벽, 천정 벽
50mm
250mm BEAM
500mm
벽 벽
50mm
접속부
50mm
Technical Data
Impedance and Voltage Drop
The formula to measure the voltage drop of a busduct is shown below. The impedance and voltage drop values for aluminum and
copper conductors are shown in the table below.
The values listed are measured between the upper and middle lines at 60Hz. For a 50Hz installation, multiply the reactance (X) by 0.83.
Vd = I x 3(R cosθ + X sinθ) Vd = voltage drop[V] I = rated road amperes[A] R = resistance[Ω] X = reactance[Ω] / cos = power factor / sim = reactive factor
Actual load current Actual length of the line (m)
실제 전압 강하 = α x Vd x x
Rated load current 100m
Ampere(A) 630 800 1000 1250 1600 2000 2500 3200 3600 4000 5000 6300 7500
1sec 40 40 50 50 50 80 80 80 100 100 100 130 130
AL
3sec 23 23 29 29 29 46 46 46 58 58 58 75 75
CU
1sec 40 40 50 50 50 80 80 80 100 100 100 130 -
3sec 23 23 29 29 29 46 46 46 58 58 58 75 -
Temperature Rise
The temperature rise limit is an important property which determines the performance of bus ducts. The temperature rise limit of the
bus duct is designed so that when a bus duct is operated with a rated current , the temperature limit values of the housing are within
55K as specified in IEC61439-2 and 6 [(previous standard) IEC 60439-1 and 2].
Technical Data
1 2 3 4 5
7 8
- Joint - 6
80 2 3
1
70
60 4
Temperature(℃)
7 8
50
40 5
6
30
9
20
10
0 1 2 3 4 5 6 7 8
Time(hr)
Classification 1 2 3 4 5 6 7 8 9
Ambient
Censer Location Joint Conductor Exterior of Epoxy
Temperature
Temperature Rise
69K 62K 65K 63K 52K 51K 44K 50K 21.4℃
Value
CR – LV (Joint Kit)
1 Before connecting the bus ducts, be sure to align them at the top and the bottom and the
left and the right as well as horizontally and vertically. (This applies for joint connection of
the horizontal and vertical ducts.) Make sure that the joint kit is not tilted. Be sure that the
surface is clear of particles before connecting them.
Check List
• The alignment of the bus ducts.
• The surface of the joint must be clear of dust or particles.
2 Using a torque wrench, slowly tighten the exposed bolt head of a double head bolt. Connect
the bus ducts temporally first, and check the function of the insulation (100MΩ or higher)
by checking the insulation resistance. Make sure the insulation is working normally before
breaking off the double-head bolt head. The double-head bolt head is designed to break off
at 800~1000Kgf•cm, therefore tighten the exposed head until it breaks off. Once the exposed
head and the red tag attached to it have been cut off, the state of the joint connection should
be visible, which means they are properly connected.
Check List
• Check the connection of the joint: The head of the double-head bolt and the red
tag should be cut off.
3 Assemble the ducts using a molding flask and rubber packing. Spray plenty of release
agent inside of the molding flask when the assembly is finished.
Check List
• Assembling the molding flask
• Spraying the release agent
• Assorting the vertical type and horizontal type
4 While assembling the molding flask, be sure to position the rubber packing of the mold-
ing flask at 40 mm from the block end. Make sure there are no gaps between the rubber
packing and the bus ducts.
Check List
• The location of the rubber packing: 40mm from the block end
5 Be sure to keep the ambient temperature at 25°C or higher before mixing the epoxy resin and
filler. When mixing the epoxy resin in a cool environment, be sure to cover the mixing container
to keep warm. It is to maintain the temperature of the container at 25°C or higher. In order of
filler, epoxy resin and hardener, add them into the mixing container, and mix it for 15 minutes
using a hand drill. (Please contact our design team for information about how to maintain the
temperature of the container when mixing the epoxy resin in a cool environment.)
Check List
• The ambient temperature: 25° C or higher
• Mix filler, epoxy resin and hardener for 15 minutes
Pour the mixture into the molding flask. Maintain the ambient temperature at 25° C. When
6 molding in a cool environment, cover the molding flask to keep warm to maintain the
temperature at the molding flask. Remove foams on the surface of the mixture for about
1 hour. Mold only three joints out of a total of four, and continue molding the entire line
following the same procedure. Wait for 8 hours, and check the function of the insulation
by checking the insulation resistance. When it is normal, finish molding the remaining
joint. (Please contact our design team for information about covering the container when
molding the epoxy resin in a cool environment.)
Check List
• Ambient temperature: 25°C or higher
• Removing foams on the surface of the mixture for 1 hour
7 Remove the mixture form the molding flask, and polish the rough surface with
sandpaper.
Check List
• When to remove the molding flask: 8 hours after the molding
Information
• Polishing the surface with sandpaper
Intall
Check List
• Final inspection of the joint
Contents
II. General Data 33
III. Compenent
- Feeder 35
- Fittings 36
- Terminal 37
- Hanger 38
- Etc 39
IV. Technical Data
- Impedence 40
- Voltage Drop 40
- Temperature Rise 41
V. Install Information 42
Ⅱ. General Data 06 / 07
Basic Structure
The CR-MV is compact in comparison with the air insulated types. It is completely covered with epoxy insulation
molding and provides high stability. The CR-MV is designed for 27kV or less, and 1250A up to 5000A.
The standard IP68 rating of the CR-MV is suitable for the exposed section of both indoor and outdoor installation,
and inadequate environments including humid areas.
Gemeral Data
[The Bus Duct with No Housing]
7.2kV 이하 The Bus Duct with No Housing The Bus Duct with Housing
7.2kV 초과 The Bus Duct with Housing The Bus Duct with Housing
Note
Either aluminum or copper conductors will be applied. Housing will be applied for both outdoor types and the bus ducts over 10kV for grounding
and shielding.
Basic Structure
In comparison with other NSPB type bus ducts for high voltage (27kV or less), the conductors and joints of the CR-MV
are completely molded with epoxy resin which provides a standard IP68 rating. The CR-MV is suitable for inadequate
environments including chemical plants, areas prone to flood, an exposed section of indoor and outdoor installation
and areas where condensation may occur.
[CR-MV] [NSPB-MV]
Installation Location Special Plant (chemical plants, humid areas) General plants
In addition to the regular, design and in-site test that the company performs
for all the products, the CM-MV has also been tested for partial discharge
tests to inspect the interior foams to provide stability.
Using mobile defoamers to remove foams from joint moldings at construction
sites provides quality as good as factory-manufactured moldings.
Feeder
Although the standard length of the LS C&S CR-MV Bus Duct feeder is 3 meters, it can be adjusted to the installation
environment, or on request. The housing is only applied for indoor installation and products with 10kV or higher.
C
A
C
A t
t
W
B D
W B D
W
Component
A
t
A
t
W
B
W B
W
7.2kV 17.5kV
Conductor
Ampere(A) weight (kg/m) weight
A B C D A B C D
t W Indoor Outdoor (kg/m)
1250 4 89 113 119
1600 6 98 122 127
100 130 315 150 335
2000 8 103 127 132
2500 12 114 138 143
CU
3200 10 157 183 199
160 190 375 210 395
3600 12 166 192 207
4000 10 247 278 286
130 300 485 320 505
5000 12 276 500 260 292 315 540 299
1250 5 83 107 113
100 130 315 150 335
1600 9 86 110 115
2000 8 87 111 116
160 190 375 210 395
AL 2500 12 89 113 118
3200 6 124 151 166
3600 8 130 300 485 126 152 230 505 167
4000 10 193 225 232
* Further discussion is required with our design team for product with 17.5kV or higher.
Fittings
Fittings including the elbow and tee are designed to adapt to any change made to the direction of the bus ducts. The same
features have been applied to the fittings of the CR-MV, and the size specifications are shown below. (Please contact our
design team for detailed information of the dimension.)
Elbow
[Vertical] [Horizontal]
Offset
[Vertical] [Horizontal]
Tee
[Vertical] [Horizontal]
Combination
Terminal
Terminals are connected to the transformers or low-tension panels. The types of products are shown below. (Please contact
our design team for detailed information of the dimension.)
[Type1] [Type2]
Component
[Type3] [Type4]
[Type5] [Type6]
Hangers
Both horizontal and vertical hangers are available for the CR-MV depending on the installation environment.
Horizontal
The standard horizontal installation method of the CR-MV requires two supports for each product. The standard 3
meter bus ducts are designed to be installed at 1.5-meter intervals, and the space between the hangers should not
Hanger rod
Hanger clamp
Hanger bar
Vertical Hangers
For vertical installation of The CR-MV, install the vertical hangers first, and fix the bus ducts on the hangers for
better support.
Etc.
Wall Flange Floor Opening
Wall opening size Floor opening size
Cut out Cut out
W+160
W+60
W+60
W+10
W
W
H+160
H+10
H+60
H+60
H
Component
A wall flange is used to seal the gaps produced during installation • W : The width of the product
of bus ducts at the walls, ceilings and floors. The company does not • H : The height of the product
provide glass wool or fire forms.
벽, 천정 벽, 천정 벽
50mm
250mm BEAM
500mm
벽 벽
50mm
접속부 50mm
Technical Data
Impedance and Voltage Drop
The formula to measure the voltage drop of a busduct is shown below. The impedance and voltage drop values for aluminum and copper
conductors are shown in the table below.
The values listed are measured between upper and middle lines at 60Hz. For a 50Hz installation, multiply the reactance (X) by 0.83.
Vd = I x 3(R cosθ + X sinθ) Vd = voltage drop[V] I = rated road amperes[A] R = resistance[Ω] X = reactance[Ω] / cos = power factor / sim = reactive factor
Actual load current Actual length of the line (m)
실제 전압 강하 = α x Vd x x
Rated load current 100m
Temperature Rise
The temperature rise limit is an important property which determines the performance of bus ducts. The temperature rise limit of the bus duct
is designed so that when a bus duct is operated with a rated current, the temperature limit values of the housing are within 50K as specified
in IEC62271-Part 201.
Technical Data
1 2 3 4
6 7
- Joint - 5
80
70
60 2
Temperature(℃)
1 3
50 6 7
40
4 5
30 8
20
10
0 1 2 3 4 5 6 7 8
Time(hr)
Classification 1 2 3 4 5 6 7 8
Ambient
Censer Location Joint Conductor Housing
Temperature
Temperature Rise
51K 54K 51K 35K 35K 43K 43K 27℃
Value
1 Before connecting the bus ducts, be sure to align them at the top and the bottom and the
left and the right as well as horizontally and vertically. (This applies for joint connection of
the horizontal and vertical ducts.) Make sure that the joint kit is not tilted. Be sure that the
surface is clear of particles before connecting them.
Check List
• The alignment of the bus ducts.
• The surface of the joint must be clear of dust or particles.
2 Connect the bus ducts using the provided joint plates and bolts as shown in the image.
Check List
• Inspect the joint connection
3 Assemble the ducts using the molding flask and rubber packing. Spray plenty of release
agent inside of the molding flask when the assembly is finished.
Check List
• Assembling the molding flask
• Spraying the release agent
• Assorting vertical type and horizontal type
4 While assembling the molding flask, be sure to position the rubber packing of the mold-
ing flask at 40 mm from the block end. Make sure there are no gaps between the rubber
packing and the bus ducts.
Check List
• The location of the rubber packing : 40mm from the block end
5 Be sure to keep the ambient temperature at 25°C or higher before mixing the mixture.
When mixing in a cool environment, be sure to cover the mixing container to keep warm.
It is to maintain the temperature of the container at 25°C or higher. In order of filler, epoxy
resin and hardener, add them into the mixing container, and mix it for 15 minutes using a
hand drill. Pour the mixture into the provided vacuum chamber, and whisk it for 30minutes
to remove foams.
Check List
Vacuum Chamber
• The ambient temperature: 25° C or higher
• Mix filler, epoxy resin and hardener for 15 minutes
• Using mobile vacuum chamber to remove foams
6 Pour the mixture into the molding flask. Maintain the ambient temperature at 25° C. When
molding in a cool environment, cover the molding flask to keep warm to maintain 25°C
at the molding flask. Remove foams on the surface of the mixture for about 1 hour. Mold
only three joints out of a total of four, and continue molding the entire line following the
same procedure. Wait for 8 hours, and check the function of the insulation by checking the
insulation resistance. When it is normal, finish molding the remaining joint.
Check List
• Ambient temperature: 25°C or higher
• Removing foams on the surface of the mixture for 1 hour
7 Remove the mixture form the molding flask, and polish the rough surface with sandpaper.
Check List
• When to remove the molding flask: 8 hours after molding
Information
Intall
KEMA Certification (CR-LV) KEMA Certification (CR-MV) Short Circuit Test KERI Temperature Rise Test KERI
Certification (CR-LV) Certification (CR-LV)
Fireproof Certification (CR-LV) Wall Opening Fireproof Flame Resistance Structural Loading
Certification (CR-LV) Certification (CR-LV) Certification (CR-LV)
Certification &
Specification
Memo
Certification &
Specification
Contents
I. Introduction
- Overview 14
- Application 15
III. Component 18
V. Install Information 22
Overview
SIB
The LS C&S SIB (Solid Insulated Bus System) is a power distribution system with epoxy impregnated solid insulation. The SIB is an ideal product with the
benefits of bus ducts and cables combined. The SIB is suitable for high voltage (27kV or less) and high current (1000A to 7500A) by completely separating the
phases of the bus bars. By replacing the cables, the SIB provides space efficiency, and it also provides excellent short circuit strength and stability.
R S T
Large Capacity and Compact Size
The compact SIB can transmit larger capacity of power in comparison with the existing high voltage bus ducts.
The SIB uses only one bus bar for each phase to handle rated current sat up to 7500A, therefore, reducing inconveniency
of using several cables.
Excellent Stability
The epoxy vacuum impregnation of the SIB provides highly stable electrical performance. Thanks to the completely separated
phases, it is completely free of short circuit between phases, and the system also comes with excellent short circuit strength.
Joint Con-
Fitting
Feeder
Joint Con-
TR Flanged
End Box
Switchgear
Switchgear
TR Flanged
End Box
Transformer
Outdoor
Transformer
Application
Introduction
Transformer/Generator
• Limited areas where condensation may occur (the exposed
section between indoor and outdoor installation)
Gemeral Data
Ships
• Power distribution on ship
• Limited areas where high current needs to be transmitted
General Data
Joint Connection
The system is very easy to install. By implementing flexible
bars, the expansion joint can be applied to the system.
Manufacturing Process
The epoxy vacuum impregnation of the SIB provides highly stable electrical
performance.
1 preprocessing work
Gemeral Data
Sealing
loose cable 2
Fittings
The SIB has a wide range of fittings to satisfy 4 5
any layout of buildings.
Conductors Housing
The SIB uses either hollow or solid copper conductors The housing of the SIB is a flexible plastic tube, and the
with conductivity at over 99%, or aluminum conductors tube provides protections against environmental
with conductivity at over 54%. The conductor areas are elements including ultraviolet rays, humidity and
plated in order to provide stable power supply, and to external impacts.
prevent corrosion.
Insulation Joint
The SIB Bus has been wrapped in crepe-paper, and then The SIB uses flexible bars for connections. The design of
dried in a vacuum state before epoxy resin molding. the flexible bar provides a stable power supply, and the
Therefore, it provides excellent electrical performance. bar itself performs as an expansion joint. The system can
be shielded using insulating cylinders, and a standard
IP65 rating can be applied.
Basic Structure
Sectional View
Conductor
• Hollow or solid conductors
• Plated to provide a stable power
supply and to prevent corrosion
Ground Layers
Exploded View
Component
Feeders
The maximum length of the feeder is 7 meters, and the
feeder is designed for 27kV or less, or up to 7000A.
Either aluminum or copper conductors are available.
Fittings
The SIB has a wide range of fittings to satisfy any
layout of buildings.
Component
Single-Curve Type Double-Curve Type Double-Curve Type
Support
Thanks to aluminum compressive members, the
supports are very light, and the self assembly
structure design ensures easy installation.
Long-Term Durability
Design and Evaluation
Quailty Test
The LS C&S SIB has been tested and certified as specified in the
international standards (IEC 60137) by KEMA. The company
performed an additional long-term over current test at an actual
testing ground by applying current and voltage in accordance
with IEC 60502-4 to secure a long term reliability of the system.
⑨
⑩
⑤
④
⑥
⑦ ⑧
Specifics 1 2 3 4 5
GIS connector
Description Outdoor Termination Sleeve Indoor busbar Gas Tank
Termination
Specifics 6 7 8 9 10
Support and AC Internal Pressure
Description Current Transformer Cubicle CT Controller
Structure Testing Device
Joint Connection
STEP 1
Check for any deformation or stain on the surface of the connectors.
Align them at the top and the bottom and the left and the right as
well as horizontally and vertically.
STEP 2
Connect the provided flexible bars as shown in the image. In order to
maintain the electric field of the internal equipotential of the joint box,
connect the springs of the joint box with the connecting terminal.
(Please contact the design team for detailed instructions.)
STEP 3
Push the joint box until it is positioned at the center to support the
joint box. Install clamps and connect the grounding.
STEP 4
Install rubber bellows, and fix one of the bellows using STSties. Add
moisture absorbent through the other bellow before fastening it
with STS ties.
Information
Intall
Certification &
Specification
Contents
I. Introduction
- Overview 14
- Application 15
II. Component
- DTS 16
- MPTS 19
- IR-Ts 22
I. Introduction
Overview
About BTMS
The temperature sensors of the Bus Duct Temperature Monitoring System (BTMS) measure bus duct temperatures in real time to check the abnormality
of the lines to prevent accidents. Therefore, the BTMS is the optimum monitoring system for bus ducts.
Why BTMS?
The standard evaluation method to check the stability of the bus duct and other power distribution system is the evaluation of a permissible tempera-
ture and temperature change of the insulation materials. The permissible temperature is also used by international standards such as IEC to evaluate the
stability. Therefore, any abnormality of a product can be detected just by checking the temperature change.
BTMS Benefit
1) Easy Maintenance: Real time monitoring of the entire system including inaccessible areas
2) Unmanned Monitoring System: Minimize the size of the supervision staff for periodic inspection
Temperature(℃)
04 Proportional Measurement ▵T
Alarm
(Comparison to Temperature Differences)
For bus ducts with two or more stacks, an alarm will be set off if the tempera-
ture differences of the stacks are higher than the set value.
Ex. A-stsck : 55℃, B-stack : 65℃ Distance(m)
Application
S
• DTS (Optical Fiber Cable Sensor)
Introduction
• MPTS (Digital Temperature Sensor)
S
S
S
S
S
• IR-Ts (Infrared Temperature Sensor)
Feature DTS (Optical Fiber Cable Sensor) MPTS (Digital Temperature Sensor) IR-Ts (Infrared Temperature Sensor)
- Sequential temperatures
- Measure temperatures at multiple points - Measure temperature at a specific point
- Measure temperature by conducting
Monitoring - Proximity measurement of the points - Direct or proximity measurement
properties
- Identify the variation using data log - High-speed response
- High-speed response
-Suitable for long-distance sensor installation. -Economical due to temperature sensors and -Suitable for local or small-scale installation.
Economical -The cost of a measuring device is higher for communication modules. -The cost can be high, depending on the
Efficiency the optical fiber. -Harness module sensor type.
DTS
(Distributed Temperature System)
DTS Overview
1) Optical fibers are used as the temperature sensor for the DTS.
• Compact and lig ht weight
• The DTS does not get affected by EMC and EMI.
• Economical
2) Measure and monitor temperature of long distance section.
3) A self-diagnosis system as well as an auto adjusting system for optical attenuation of optical fibers.
4) The DTS collects and manages the temperature data. The computer based system ensures easy management of HMI and data.
Ias hav
(- )
∝ е kT
Is
Directional
Coupler
Optical Fiber Sensor
las : The illumination level Luminous
of the anti-stoke light Source
la : The illumination level of Raman Scattering Laser Light
the stoke light
Rayleigh Band
h : Planck constant
k : Boltzmann constant
Anti-Stokes Raman Stokes Raman
c : The speed of light Band Band
v : Frequency of incident Signal Processing
light
T : Temperature
Features of DTS
• DTS
− By channels (1,2,4,6ch) and distances (2,4,8,10,12km)
− Temperature sensing distance(1m) , Accuracy
• Industrial Computer
− Stability of industrial PC
− Fast and stable monitoring and data management
− High capacity HDD with 1 terabyte
• UPS (Optional)
− Provide stable power supply in case of power failure
Component
− Protect power supply of computer equipment
and peripheral devices
• GUI
− Objective and convenient screen layout
− Self data backup and organization system
(data analysis-detect, manage and predict problems)
DTS
Monitoring PC
Optical Fiber
General Function
• Monitoring temperature profile: Temperature vs. Distance graph
• Monitoring by zones, lines and loads: Up to 500 pre-designated points and statistical information
• Auto detection and warning system (when bidirectional measurement was applied) of optical attenuation and fiber cut
• Warning system: Data prints based on real time temperature measurement
• Warning signals can be interlocked with other systems
(Ex. Interlocking with fire signal)
DTS Application
[ Factory ]
[DTS Configuration Example] [Trend screen]
MPTS
(Multi-Point Temperature System)
MPTS Preview
• The MPTS measures temperature of a specific point by installing a digital temperature sensor at a specific point including the joint
connection of a bus duct.
• Each sensor is linked to a communication system to transmit the measured temperature in real time.
• Up to 80 points can be linked to a single communication line.
Component
by noise. The sensor is energy efficient, and suitable for measuring temperature in wide areas.
• Amplifier Circuit
- In order to amplify the weak signal of the sensor data, an amplifier circuit has been
installed in the sensor.
- Potential exterior noise during signal amplifications has been eliminated.
MPTS
The data collected by the sensor is gathered and saved at the data collection system, and monitored by a surveillance PC.
MPTS Setup
Configuration
No. Specifics Feature
1 Sensor Module Digital temperature sensor module with communication function
2 Data Collection Device Collecting and transmitting of the temperature data of the sensor module
MPTS Application
Drawing up a draft plane is easier thanks to the graphic configuration of HMI, and managing the points using the remote observation system
reduces the work loads.
Component
• Main Screen • Location Screen
–Displays the temperature monitoring points –Displays the locations of the temperature monitoring points
IR-Ts
IR-Ts Preview
The IR-Ts uses an infrared light noncontact temperature sensor to
measure and monitor the heat released from objects. The system is
suitable for dangerous environments including high voltage areas, or
areas where contact sensors are not feasible.
Feature
1) Compact and light weight
2) Can be installed at all directions
3) Applicable Temperature Range: -20°C~ 200°C
4) Real time temperature variation measurement and video (CCTV Camera)
5) Wire or wireless communication network system
IR-Ts (CCTV)
: Infrared Camera + CCTV
Installation
(Exterior image of the distribution board)
Photographic Measuring
1) Infrared Camera(IR Cam) 2) CCTV 3) Composite photograph of IR+CCTV
IR-Ts Configuration
*
*
*
Component
*
*
*
- PC-
*
*
*
- 16EA -
Yichang, China
Branches
Sydney Office Houston Office
Level 35, Suite 35.02 Northpoint 100 Miller St. North Sydney, NSW 2060 Australia 22126 Manor Estates Dr. Katy, TX77449, USA
Tel. +61-2-9460-0255 Tel: +1-713-202-8003
Jakarta Office
Graha Mustika Ratu, 11th Fl. Jl.Jenderal Gatot Subroto Kav.74-75, Subsidiaries
Jakarta Selatan 12870 Indonesia
Tel. +62-21-830-6733 LSCW
LS Industrial Park, Xin Mei Rd. National High-tech Industrial Development Zone
Singapore Office Wuxi, Jiangsu Province 214028 China
300 Beach Rd. #25-07 The Concourse Singapore 199555
Tel. +65-6342-9162~3 Tel : +86-510-8534-5943
Production : Automotive Wire & Cable, Bus Duct, Electroncic Wire & Cable, Tube, ACF,
Accessories for EHV Cable System
Abu Dhabi Office
#133, Al Bateen Towers C6, Bainunah St.34, Al Bateen,
P.O.Box 113 100, Abu Dhabi, U.A.E LSCT
Tel : +971-2-406-9856 East of Jing-jin Express, Yixingbu Entrance, Beichen Tianjin, China
Tel : +86-22-2699-7618
Riyadh Office Production : Magnet Wire
#7, 2nd Fl. Olaya St. B/D #28, Riyadh, Saudi Arabia
Tel : +966-1-201-3515 China R&D Center(Yichang)
#1 Tanjiahe Rd. Dianjun District, Yi-Chang City, Hubei Province 443004 China
Cairo Office Tel. 070-8650-2188
#36, El-Zeini Tower, 25 Misr Helwan Rd. Maadi, Cairo, Egypt
Tel. +20-19-966-2810 LSHQ
#1 Tanjiahe Rd. Dianjun District, Yi-Chang City, Hubei Province 443004 China
Johannesburg Office
3rd Fl. South Tower at Nelson Mandela Square,Corner 5th Ave. and +86-717-667-7777
Maude St. Sandton, Johannesburg, South Africa Production : Power Cable, Submarine Cable, Industrial Specialty Cable
Tel. +27-11-783-6320
LS-VINA(Haiphong)
Moscow Office South of Binh Bridge St. So Dau Precinct, Hong Bang Dt. Haiphong, Vietnam