AHU Ventilation Calculations


Design case
Zone Identification Standard Case: ASHRAE 62.1-2004 Ventilation Rate Procedure (Multiple Zone Recirculating Systems

Outdoor Air Outdoor Air Breathing Table 6-2 Zone Table 6-3
Zone Floor Rate Zone Zone Outdoor percentage
Table 6-1 Rate Zone Air Outdoor System 30 ‰
Area Required PerRequired Population Outdoor Distribution Air Intake supply Voz/30‰ of Maixmum
Zone Occupancy Airflow Ventilation of supply Fraction
(Az) Unit Area (Pz) Airflow Effectiveness Flow air supply air fraction
Category Per Person (Voz) Efficicncy air
(Ra) (Vbz) (Vot)
(Rp) (Ez) (Ev)

(m^2) (l/s/person) (l/s/m^2) (people) (l/s) (l/s) (l/s) (l/s) (l/s)


spacc 1(office) office 30 2.5 0.3 5 21.5 0.7 30.71 0.8 38.39 300 90 0.30 0.13 0.27
spacc 2(workstation work station 50 2.5 0.3 8 35 0.7 50.00 0.8 62.50 200 60 0.30 0.31 0.27
spacc 3(meeting room) meeting room 70 2.5 0.3 7 38.5 0.7 55.00 0.8 68.75 400 120 0.30 0.17 0.27

150 95 135.71 169.64 900

maximum fraction 0.27


Required
out door air

(l/s)
81
54
108

243