Geotechnical Investigation Report

The document provides details on a soil exploration conducted for a proposed 8-story hospital building in Tacurong City, Philippines. Three boreholes were drilled on site and standard penetration tests were performed at 1.5m intervals down to 20m depth. Soil samples collected from the boreholes underwent laboratory tests to determine properties such as moisture content, grain size, Atterberg limits, and soil classification. The results of the field exploration and laboratory tests are presented in a table and indicate the subsurface soil conditions on site.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
448 views40 pages

Geotechnical Investigation Report

The document provides details on a soil exploration conducted for a proposed 8-story hospital building in Tacurong City, Philippines. Three boreholes were drilled on site and standard penetration tests were performed at 1.5m intervals down to 20m depth. Soil samples collected from the boreholes underwent laboratory tests to determine properties such as moisture content, grain size, Atterberg limits, and soil classification. The results of the field exploration and laboratory tests are presented in a table and indicate the subsurface soil conditions on site.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 40



 

a.) INTRODUCTION

The assessment of the geotechnical conditions is based on the findings from the actual
field and laboratory test results which were conducted last June 22 - 30, 2019 by RAJ Plans,
Designs and Consultancy.

The purpose of this subsurface exploration package is for the proposed Eight (8) Storey
Hospital Building located along Lapu – lapu St., Poblacion, Tacurong City as per request of
Tacurong Doctors’ Hospital as per requirements for the application of building permit and
be able to determine the applicable foundation necessary for their proposed construction.

Inclusions on this report are the recommendations for allowable bearing capacity for the
design criteria of foundation and foundation system of the subsurface structure.

The objective of this soil exploration is to collect/gather samples in every 1.5 meter depth
interval for at least twenty meters (20m) depth from existing ground or at certain depth
where standard penetration test could no longer advance. Three boreholes sampling were
done within the building area where it shall be erected.

The Standard Penetration Test (SPT) classified as ASTM D-1586-67 is employed to determine
the in situ allowable soil bearing capacity at various depths for surfaced loaded footings of
various widths. It is also used to determine the allowable frictional stress capacity of soil
profile at every layer of various depths for a pile footing foundation. Soil sampling was
taken at regular interval 1.50 meters. Upon encountering a hard type soil formation, drilling
procedures through water jetting is employed and extraction of sample through core
drilling. Standard Penetration Test activity is taken out upon reaching a sandy layer or
water table level. Another methodology will be employed for a non-cohesive soil.

The extracted/collected soil samples were taken to the soil laboratory for various
laboratory tests in determining the necessary soil characteristics and properties.

B.) FIELD INVESTIGATION

The actual field activities consisted of drilling boreholes with Standard Penetration Test for
the boreholes. The boreholes were done by advanced wash boring to a specified boring
depths. A drill pipe was drilled to a specified depth by means of water jetting. Then the split
spoon sampler will be embed to a certain depth through an extension rod and will be
driven by a drop hammer. The Standard Penetration Tests were conducted at every 1.50
meters interval by driving the split spoon sampler of 1½” diameter and a length of 18” (45
centimeters) in three successive segments of 6” (15 cm) using a 140 lbs (64 kgs)free falling
drop hammer at a height of 30”.

The number of blows (drops of hammer) required to penetrate the three layers of 6” spoon
sampler are recorded. The number of blows of the last two segments (middle third – last

1

 

third of spoon sampler) are added to give the N-value (blows) of a particular 18” stretch, a
measure of density or consistency of the soil.

Soil samples were extracted through this spoon sampler. Upon reaching the water table
level on this particular site, hard strata are eminent, the spoon sampler experienced a
longer period to penetrate the entire 18” (45 cm) length and no soil sample retained in the
spoon sampler.

All collected/gathered soil samples were properly labeled and stored in a plastic container
to ensure any disturbances with proper care and handling. Then it was brought to soil
laboratory for a specific laboratory testing in determining the necessary results for bearing
capacity calculations.

Observation on the field condition:

The lot area has an adjacent three storey residential building. Sub-surface water is within
1.50 meter depth from existing ground. Texture of upper layer soil is composed of silty sand
or fine sands. Erosion is highly eminent during excavation.

C.) LABORATORY TESTING

Collected soil samples from every specific depth, the 1.50m interval were subjected to the
following laboratory tests in accordance with the procedures specified in the current ASTM
standard as described herein:

Moisture Content Determination as per ASTM D2216

The method in determining water (moisture) content of soil by weight. Moisture content of
soil is the ratio of the mass of pore water in a given soil mass to the mass of the solid
material particles, given in percentage.

Grain Size Analysis as per ASTM D422

Sieve analyses were performed to determine the gradational characteristics of the soil in
order to come up with soil classification information.

Atterberg Limit Test as per ASTM D4318 (for plastic material)

Atterberg Limits test of fined grained materials (i.e., silty or clayey) were performed to
come up with soil classification data and to determine moisture content at which the
behavior of soil changes.
2

 

Plastic Limit of Soils

The plastic limit of soil is the water content (percentage in weight) of the oven dried soil
after reaching the condition between the plastic and semi-solid states.

Plasticity Index of Soils

The plasticity index is defined as the difference between the liquid limit and plastic limits of
soil.

Liquid Limit of Soils

The liquid limit of soil is the water content (percentage in weight) of the oven dried soil after
reaching the condition between the liquid states and plastic states.

Soil Classification Tests as per ASTM D2487

This standard classifies soils from any geographic location into categories representing the
results of prescribed laboratory tests to determine the particle-size characteristics, the liquid
limit, and the plasticity index.

The various groupings of this classification system have been devised to correlate in a
general way with the engineering behavior of soils. This standard provides a useful first step
in any field or laboratory investigation for geotechnical engineering purposes.

D.) RESULTS OF FIELD AND LABORATORY TESTING

The result of the borehole is presented on the table:

3

 

FINAL BOREHOLE LOG AND SUMMARY OF T EST RESULT S

PROJECT: Tacurong Doctors Hospital Building HOLE NO. BH-1


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 13.5 m
EXPLORER: RAJ Plans, Design & Consultancy GROUND WATER LEVEL : 1.5 m
DATE OF BORING: June 22 - 26, 2019

N-values

SAMPLE TYPE

LOG SYMBOL
%RECOVERY
SAMPLE NO.

SPT GRAPH
DEPTH (m)

SPT DESCRIPTION

USCS
1/3 2/3 3/3 SPT 0 10 20 30 40 50 60 70
6" 12" 18" N 0

1.5 1 2 4 5 SS 75 X SP Loose , Gray, Poorly Graded Sand 9 1

3.0 2 3 4 5 SS 80 X SM Loose , Gray, Silty Sand with Gravel 9 2

4.5 3 4 5 5 SS 80 X SP-SM
Loose, Gray, Poorly Graded Sand
10 3
with Silt
6.0 4 5 8 8 SS 75 X SP Medium , Gray,Poorly Graded Sand 16 4

7.5 5 7 8 9 SS 70 X SP Medium , Gray, Poorly Graded Sand 17 5

9.0 6 10 12 15 SS 70 X SP Medium, Gray, Poorly Graded Sand 27 6

10.5 7 17 22 25 SS 65 X SW Dense,Gray, Well Graded Sand 47 7

12.0 8 22 25 28 SS 75 X SM Very Dense, Gray, Silty Sand 53 8

13.5 9 24 28 34 SS 60 X SW
Very Dense, Gray, Well-Graded Sand
62
with Gravel 9

SIEVE ANALYSIS LEGEND:


MOISTURE CONTENT

ATTERBERG
SAMPLE NO.

LIMITS %PASSING SIEVE NO. SPOON SAMPLE

LL PI 1½ 1 ¾ ½ ⅜ #4 #10 #20 #40 #100 #200 X WASH SAMPLE


% %
1 20.5 NP NP 100 100 100 100 100 100 90 76 63 29 4 Certified by :
2 23.6 39.5 8.0 100 100 100 100 100 98 74 56 43 28 13
3 31.5 NP NP 100 100 100 100 100 100 96 81 68 44 10 JULES HA NNA H O. CERB O

4 21.0 NP NP 100 100 100 100 100 100 99 86 30 1 0 LICENSED GEOLOGIST


5 26.0 NP NP 100 100 100 100 100 100 100 97 52 2 1
6 24.9 NP NP 100 100 100 100 100 100 100 98 89 10 1 Verified by :
7 31.1 NP NP 100 100 100 100 100 100 99 92 48 2 0
8 30.2 35.6 4.7 100 100 100 100 100 98 90 78 70 57 19 ROGER A . JUA N

9 18.0 NP NP 100 100 100 100 100 95 69 37 23 6 4 HEAD, RAJ Plans, Designs & Consultancy
4

 

FINAL BOREHOLE LOG AND SUMMARY OF T EST RESULT S

PROJECT: Tacurong Doctors Hospital Building HOLE NO. BH-2


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 13.5 m
EXPLORER: RAJ Plans, Design & Consultancy WATER LEVEL : 1.5 m
DATE OF BORING: June 22 - 26, 2019

N-values

SAMPLE TYPE
SPT GRAPH

LOG SYMBOL
%RECOVERY
SAMPLE NO.
DEPTH (m)

SPT DESCRIPTION

USCS
1/3 2/3 3/3 SPT 0 10 20 30 40 50 60 70
0
6" 12" 18" N

1.5 1 2 5 5 SS 80 X SP Loose , Gray, Poorly Graded Sand 10 1

3.0 2 3 5 5 SS 75 X SM Loose , Gray, Silty Sand with Gravel 10 2

4.5 3 3 5 6 SS 70 X SP-SM
Loose, Gray, Poorly Graded Sand
11 3
with Silt
6.0 4 5 8 9 SS 65 X SP Medium , Gray,Poorly Graded Sand 17 4

7.5 5 8 9 9 SS 70 X SP Medium , Gray, Poorly Graded Sand 18 5

9.0 6 10 13 16 SS 65 X SP Medium, Gray, Poorly Graded Sand 29 6

10.5 7 18 23 27 SS 70 X SW Dense,Gray, Well Graded Sand 50 7

12.0 8 23 26 30 SS 70 X SM Very Dense, Gray, Silty Sand 56 8

13.5 9 25 29 35 SS 65 X SW Very Dense, Gray, Well-Graded Sand 64 9

ATTERBERG SIEVE ANALYSIS LEGEND:


MOISTURE CONTENT

LIMITS %PASSING SIEVE NO. SPOON SAMPLE


SAMPLE NO.

LL PI 1½ 1 ¾ ½ ⅜ #4 #10 #20 #40 #100 #200 X WASH SAMPLE


% %
1 21.5 NP NP 100 100 100 100 100 100 91 78 66 30 2 Certified by :
2 22.9 38.4 7.7 100 100 100 100 100 99 77 59 44 28 14
3 31.4 NP NP 100 100 100 100 100 100 95 78 64 41 8 JULES HA NNA H O. CERB O

4 20.6 NP NP 100 100 100 100 100 100 94 86 30 3 1 LICENSED GEOLOGIST


5 26.1 NP NP 100 100 100 100 100 100 99 79 37 5 2
6 25.3 NP NP 100 100 100 100 100 100 99 97 84 10 1 Verified by :
7 31.6 NP NP 100 100 100 100 100 100 99 90 49 4 0
8 31.1 36.3 5.0 100 100 100 100 100 98 90 77 69 58 20 ROGER A . JUA N

9 17.5 NP NP 100 100 100 100 100 94 65 32 18 9 3 HEAD, RAJ Plans, Designs & Consultancy
5

 

FINAL BOREHOLE LOG AND SUMMARY OF T EST RESULT S

PROJECT: Tacurong Doctors Hospital Building HOLE NO. BH-3


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 13.5 m
EXPLORER: RAJ Plans, Design & Consultancy WATER LEVEL : 1.5 m
DATE OF BORING: June 22 - 26, 2019

N-values SPT GRAPH

SAMPLE TYPE

LOG SYMBOL
%RECOVERY
SAMPLE NO.
DEPTH (m)

SPT DESCRIPTION

USCS
0 10 20 30 40 50 60 70
1/3 2/3 3/3 SPT
0
6" 12" 18" N

1.5 1 2 5 5 SS 80 X SP Loose , Gray, Poorly Graded Sand 10 1

3.0 2 3 5 5 SS 75 X SM Loose , Gray, Silty Sand with Gravel 10 2

4.5 3 3 5 5 SS 80 X SP-SM
Loose, Gray, Poorly Graded Sand
10 3
with Silt
6.0 4 5 8 9 SS 70 X SP Medium , Gray,Poorly Graded Sand 17 4

7.5 5 8 9 9 SS 65 X SP Medium , Gray, Poorly Graded Sand 18 5

9.0 6 10 12 16 SS 70 X SP Medium, Gray, Poorly Graded Sand 28 6

10.5 7 19 23 27 SS 70 X SW Dense,Gray, Well Graded Sand 50 7

12.0 8 23 26 30 SS 80 X SM Very Dense, Gray, Silty Sand 56 8

13.5 9 26 30 35 SS 75 X SW Very Dense, Gray, Well-Graded Sand 65 9

ATTERBERG SIEVE ANALYSIS LEGEND:


MOISTURE CONTENT

LIMITS %PASSING SIEVE NO. SPOON SAMPLE


SAMPLE NO.

LL PI 1½ 1 ¾ ½ ⅜ #4 #10 #20 #40 #100 #200 X WASH SAMPLE


% %
1 21.3 NP NP 100 100 100 100 100 100 90 79 68 29 5 Certified by :
2 23.0 38.7 8.2 100 100 100 100 100 98 78 63 48 29 14
3 30.7 NP NP 100 100 100 100 100 100 94 78 62 39 9 JULES HA NNA H O. CERB O

4 21.6 NP NP 100 100 100 100 100 100 91 83 29 3 1 LICENSED GEOLOGIST


5 27.6 NP NP 100 100 100 100 100 100 98 81 51 5 2
6 26.0 NP NP 100 100 100 100 100 100 99 96 83 11 2 Verified by :
7 32.3 NP NP 100 100 100 100 100 100 98 88 50 5 0
8 33.4 36.7 5.0 100 100 100 100 100 97 89 75 65 56 18 ROGER A . JUA N

9 18.8 NP NP 100 100 100 100 100 96 66 31 17 8 2 HEAD, RAJ Plans, Designs & Consultancy
6

 

The result of the borehole is summarized on the table:

GWL: 1.50m
Depth (m) Soil Classification Remarks
(Relative Condition/Consistency)
1.5 – 4.5 SP, SM, SP-SM Loose
6.0 – 9.0 SP Medium
10.5 – 13.5 SW, SM Dense to Very Dense

E.) EVALUATION AND RECOMMENDATION

Settlement

Settlement behavior is directly influenced by the compressibility of the soil material. Fine
grained soils, like silts and clays have generally time-dependent deformation due to its low
permeability. Thus dissipation of excess pore water in the voids of fine-grained soils takes
considerable time and in consolidation it takes a long term.

Immediate settlement reveal on the granular or coarse materials like sand which results to
a very minimal vertical deformation due to its high elastic properties.

Thus the site has no issue on settlement.

Liquefaction and Seismic Design Criteria

The followings are the ground condition criteria in considering liquefaction potential:
SPT N-value is less than 15
Soil particle diameter at 50% passing is between 0.02mm and 2.0mm
Saturated soil material
Non-plastic (cohesionless)
Liquidity Index (IL) > 0

Thus the site has issue on liquefaction at the upper sandy layers.

Shallow Foundation

For local shear failure, Meyerhof’s Equation, the general bearing capacity equation is used
in obtaining the ultimate bearing capacity.

qult = (c*Nc*sc+dc) + (q*Nq*sq*dq) + (0.5*γs*B*Nγ*sγ*dγ)

7

 

Immediate settlement of foundations resting on the ground surface of an elastic material


of finite thickness is given as:

ΔHi = qB (1 - μ²)If
E

Bearing Capacity from Standard Penetration Test (SPT)

Allowable bearing capacity

qa = 0.41Ncor ρa
Ncor = cN cW N

EFFECTS OF WATER TABLEON BEARING CAPACITY

The unit weight of soil used in the equations for bearing capacity are effective unit weights.
With the rising water table, the subsoil becomes saturated and the unit weight of
submerged soil is greatly reduced. The reduction of this unit weight results in the decrease
in the ultimate bearing capacity of soil.

For a five storey building and above, the minimum recommended foundation be used in
designing is a combined footing foundation scheme. As on the site condition, the
designing engineer shall consider the effect of the erosion to the adjacent lot during
excavation.

For a less destructive construction methodology or to lessen the effect of erosion to


minimize damages to adjacent property, it is recommended to have a test pile drive of at
least 12 meter length concrete pile to determine the actual depth of a stable strata.

DEPTH OF FOOTING ALLOW. BEARING CAPACITY


m kPA
1.5 112.8
2 92.3
2.5 82.0
3 82.0
3.5 71.8
4 61.5
4.5 71.8
5 61.5
5.5 92.3
6 92.3
6.5 82.0
7 82.0

8

 

The values above are applicable for footing width which is smaller than 4.0 meters under
non-seismic conditions.

The above values has already incorporated a geotechnical factor of safety of at least 3.0
against shear failure and are controlled by the limiting settlement magnitude of not greater
to 25mm.

The following values of geotechnical parameters are supplied for further analyses.

Sand materials
Φ = 32.5° - 37.5°
μ = 0.20 – 0.40 (Poisson’s ratio)
Υ = 18 – 19 kN/m³ (unit wt of soil)
Es = 10,000 - 30,000 kPa (modulus of elasticity)
c = 0 kPa

F.) LIMITATIONS

The foregoing assessments and recommendations are based on the actual exploration
and laboratory tests results. Should there be any significant variation or other conditions
become evident in the soil stratification encountered during the implementation phase,
the undersigned shall be informed immediately so that necessary supplemental
recommendations shall be made in accordance to engineering principles and practices.
And it will be necessary to re-evaluate the recommendation of this report.

Engr. Roger A. Juan


CEO, RAJ Plans, Design
& Consultancy

9

 

PROJECT: Tacurong Doctors Hospital Building


LOCATION: Lapu-lapu St., Poblacion, Tacurong City
EXPLORER: RAJ Plans, Design & Consultancy
TEST REQUIRED : Moisture Content

MOISTURE CONTENT DETERMINATION WORKSHEET


SAMPLE ID: BH -1

SAMPLE DESIGNATION SS-1 SS-2 SS-3 SS-4 SS-5 SS-6 SS-7 SS-8 SS-9
No of Can BT XM DF XT HD TC TJ KL DQ
Weight of can & wet soil,g 86.2 110.3 95.7 89.1 101.5 109.8 119.8 123.8 76.6
Weight of can & dry soil,g 73 92.8 74.8 75.1 84.5 91.6 95.7 99.4 66.2
Weight of moisture, g 13.2 17.5 20.9 14 17 18.2 24.1 24.4 10.4
Weight of can, g 8.5 18.5 8.5 8.4 19.1 18.6 18.3 18.6 8.5
Dry weight of soil, g 64.5 74.3 66.3 66.7 65.4 73 77.4 80.8 57.7
Moisture Content % 20.47 23.55 31.52 20.99 25.99 24.93 31.14 30.20 18.02

SAMPLE ID: BH -2

SAMPLE DESIGNATION SS-1 SS-2 SS-3 SS-4 SS-5 SS-6 SS-7 SS-8 SS-9
No of Can SZ PK GV CK SX DX FW ND KJ
Weight of can & wet soil,g 88.7 84.2 96.4 91.2 85.8 83.4 71.3 123.4 152.8
Weight of can & dry soil,g 74.5 70.1 77.8 78.8 69.8 68.3 56.2 98.5 132.8
Weight of moisture, g 14.2 14.1 18.6 12.4 16.0 15.1 15.1 24.9 20.0
Weight of can, g 8.4 8.5 18.5 18.5 8.6 8.5 8.4 18.5 18.6
Dry weight of soil, g 66.1 61.6 59.3 60.3 61.2 59.8 47.8 80.0 114.2
Moisture Content % 21.48 22.89 31.37 20.56 26.14 25.25 31.59 31.13 17.51

SAMPLE ID: BH -3

SAMPLE DESIGNATION SS-1 SS-2 SS-3 SS-4 SS-5 SS-6 SS-7 SS-8 SS-9
No of Can R4 TX AV XG GS RC JH RB M6
Weight of can & wet soil,g 104.5 121.3 98.6 92.5 98.5 78.2 78.3 123.1 81.3
Weight of can & dry soil,g 89.4 102.1 77.4 77.6 81.2 63.8 61.3 96.9 69.8
Weight of moisture, g 15.1 19.2 21.2 14.9 17.3 14.4 17.0 26.2 11.5
Weight of can, g 18.5 18.5 8.4 8.5 18.6 8.5 8.6 18.5 8.5
Dry weight of soil, g 70.9 83.6 69.0 69.1 62.6 55.3 52.7 78.4 61.3
Moisture Content % 21.3 22.97 30.72 21.56 27.64 26.04 32.26 33.42 18.76

RE MARKS: This report is the result of test performed on the sample gathered.

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy
10

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-1 BH-1


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 1.0-1.5 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
40
PLASTIC LIMIT LIQUID LIMIT
NO.OF TRIALS 1 2 1 2 3 35

CAN NO. 30
NO. OF BLOWS REQUIRED 25-35 20-30 15-25 25

%MOISTURE
NO. OF BLOWS (LAB)
20
1 wt of can
15
2 wt of can + wet soil
10
3 wt of can + dry soil
4 wt of water (2-3) 5
5 wt of dry soil (3-1) 0
6 % moisture (4/5 x 100) 15 20 25 30 35
NO. OF BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.0 196.4 100 90
1 25.000 0.0 196.4 100 80
¾ 19.000 0.0 196.4 100
70
½ 12.500 0.0 196.4 100
% PASSING

60
⅜ 9.500 0.0 196.4 100
50
#4 4.750 0.00 196.40 100
#10 2.990 18.70 177.70 90 40

#20 1.495 28.90 148.80 76 30


#40 0.425 25.70 123.10 63 20
#100 0.150 65.60 57.50 29 10
#200 0.075 49.20 8.30 4 0
ORIGINAL DRY WEIGHT : 196.40 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SP Loose , Gray, Poorly Graded Sand

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy
11

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-3 BH-1


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 4.0-4.5 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
PLASTIC LIMIT LIQUID LIMIT
28
NO.OF TRIALS 1 2 1 2 3
CAN NO. 26
NO. OF BLOWS REQUIRED 25-35 20-30 15-25 24

%MOISTURE
NO. OF BLOWS (LAB)
1 wt of can 22

2 wt of can + wet soil 20


3 wt of can + dry soil
18
4 wt of water (2-3)
5 wt of dry soil (3-1) 16
6 % moisture (4/5 x 100) 15 20 25 30 35
NO. OF BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.0 176.5 100 90
1 25.000 0.0 176.5 100 80
¾ 19.000 0.0 176.5 100
70
½ 12.500 0.0 176.5 100
% PASSING

60
⅜ 9.500 0.0 176.5 100
50
#4 4.750 0.00 176.50 100
#10 2.990 7.50 169.00 96 40
#20 1.495 25.50 143.50 81 30
#40 0.425 22.90 120.60 68 20
#100 0.150 42.30 78.30 44 10
#200 0.075 61.30 17.00 10 0
ORIGINAL DRY WEIGHT : 176.50 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SP-SM Loose, Gray, Poorly Graded Sand


with Silt
Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

12

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-4 BH-1


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 5.5-6.0 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
PLASTIC LIMIT LIQUID LIMIT 30
28
NO.OF TRIALS 1 2 1 2 3
CAN NO. 26
29
NO. OF BLOWS REQUIRED 25-35 20-30 15-25 24

%MOISTURE
NO. OF BLOWS (LAB)
28
22
1 wt of can
2 wt of can + wet soil 20
3 wt of can + dry soil 27
18
4 wt of water (2-3)
5 wt of dry soil (3-1) 16
26
6 % moisture (4/5 x 100) 15 20 25 30 35
NO. OF BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.00 227.60 100 90
1 25.000 0.00 227.60 100 80
¾ 19.000 0.00 227.60 100
70
½ 12.500 0.00 227.60 100
% PASSING

60
⅜ 9.500 0.00 227.60 100
50
#4 4.750 0.00 227.60 100
#10 2.990 2.30 225.30 99 40
#20 1.495 28.70 196.60 86 30
#40 0.425 128.70 67.90 30 20
#100 0.150 65.30 2.60 1 10
#200 0.075 1.70 0.90 0 0
ORIGINAL DRY WEIGHT : 227.60 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SP Medium , Gray,Poorly Graded Sand

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

13

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-5 BH-1


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 7.0-7.5 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
30
PLASTIC LIMIT LIQUID LIMIT
NO.OF TRIALS 1 2 1 2 3
CAN NO. 29
NO. OF BLOWS REQUIRED 25-35 20-30 15-25

%MOISTURE
NO. OF BLOWS (LAB)
28
1 wt of can
2 wt of can + wet soil
3 wt of can + dry soil 27

4 wt of water (2-3)
5 wt of dry soil (3-1) 26
6 % moisture (4/5 x 100) 15 20 25 30 35
NO. OF BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.00 221.90 100 90
1 25.000 0.00 221.90 100 80
¾ 19.000 0.00 221.90 100
70
½ 12.500 0.00 221.90 100
% PASSING

60
⅜ 9.500 0.00 221.90 100
#4 4.750 0.00 221.90 100 50

#10 2.990 0.50 221.40 100 40


#20 1.495 5.90 215.50 97 30
#40 0.425 100.90 114.60 52 20
#100 0.150 110.40 4.20 2 10
#200 0.075 2.60 1.60 1 0
ORIGINAL DRY WEIGHT : 221.90 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SP Medium , Gray, Poorly Graded Sand

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

14

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-6 BH-1


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 8.5-9.0 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
PLASTIC LIMIT LIQUID LIMIT 2830

NO.OF TRIALS 1 2 1 2 3
CAN NO. 2729
NO. OF BLOWS REQUIRED 25-35 20-30 15-25

%MOISTURE
NO. OF BLOWS (LAB)
2628
1 wt of can
2 wt of can + wet soil
3 wt of can + dry soil 2527
4 wt of water (2-3)
5 wt of dry soil (3-1) 2426
6 % moisture (4/5 x 100) 1515 2020 2525 3030 3535
NO.OF
NO. OFBLOWS
BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.00 214.50 100 90
1 25.000 0.00 214.50 100 80
¾ 19.000 0.00 214.50 100
70
½ 12.500 0.00 214.50 100
% PASSING

60
⅜ 9.500 0.00 214.50 100
50
#4 4.750 0.00 214.50 100
#10 2.990 0.30 214.20 100 40
#20 1.495 3.30 210.90 98 30
#40 0.425 20.10 190.80 89 20
#100 0.150 169.40 21.40 10 10
#200 0.075 19.40 2.00 1 0
ORIGINAL DRY WEIGHT : 214.50 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SP Medium, Gray, Poorly Graded Sand

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

15

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-7 BH-1


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 10-10.5 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
PLASTIC LIMIT LIQUID LIMIT 2830
46
NO.OF TRIALS 1 2 1 2 3 44
CAN NO. 2729
42
NO. OF BLOWS REQUIRED 25-35 20-30 15-25 40

%MOISTURE
%MOISTURE
NO. OF BLOWS (LAB)
2628
38
1 wt of can
36
2 wt of can + wet soil
3 wt of can + dry soil 2527
34
4 wt of water (2-3) 32
5 wt of dry soil (3-1) 2426
30
6 % moisture (4/5 x 100) 1515 2020 2525 3030 35 35
NO.OF
NO. OFBLOWS
BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.00 249.70 100 90
1 25.000 0.00 249.70 100 80
¾ 19.000 0.00 249.70 100
70
½ 12.500 0.00 249.70 100
% PASSING

60
⅜ 9.500 0.00 249.70 100
#4 4.750 0.00 249.70 100 50

#10 2.990 2.30 247.40 99 40


#20 1.495 16.80 230.60 92 30
#40 0.425 111.00 119.60 48 20
#100 0.150 115.70 3.90 2 10
#200 0.075 2.90 1.00 0 0
ORIGINAL DRY WEIGHT : 249.70 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SW Dense,Gray, Well Graded Sand

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

16

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-8 BH-1


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 11.5-12 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
PLASTIC LIMIT LIQUID LIMIT 40
39
NO.OF TRIALS 1 2 1 2 3
38
CAN NO. DU PS FZ DQ NU
37
NO. OF BLOWS REQUIRED 25-35 20-30 15-25
36

%MOISTURE
NO. OF BLOWS (LAB) 31 23 17
35
1 wt of can 18.5 18.4 8.5 8.4 8.4 34
2 wt of can + wet soil 28.1 27.4 50.6 47.6 45.2 33
3 wt of can + dry soil 25.8 25.3 40.2 37.1 34.8 32
4 wt of water (2-3) 2.3 2.1 10.4 10.5 10.4 31
5 wt of dry soil (3-1) 7.3 6.9 31.7 28.7 26.4 30
6 % moisture (4/5 x 100) 31.51 30.43 32.81 36.59 39.39 15 20 25 30 35
7 Average Plastic Limit 30.97 NO. OF BLOWS

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.00 145.20 100 90
1 25.000 0.00 145.20 100 80
¾ 19.000 0.00 145.20 100
70
½ 12.500 0.00 145.20 100
% PASSING

60
⅜ 9.500 0.00 145.20 100
50
#4 4.750 3.60 141.60 98
#10 2.990 11.60 130.00 90 40
#20 1.495 16.20 113.80 78 30
#40 0.425 11.50 102.30 70 20
#100 0.150 19.50 82.80 57 10
#200 0.075 55.90 26.90 19 0
ORIGINAL DRY WEIGHT : 145.20 grams

LIQUID LIMIT (LL) : 35.6 P LAST IC LIMIT (P L) : 30.97 P LAST IC INDEX (P I) : 4.66

Soil Classification (USCS) : SM Very Dense, Gray, Silty Sand

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

17

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-9 BH-1


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 13-13.5 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
4630
28
PLASTIC LIMIT LIQUID LIMIT
NO.OF TRIALS 1 2 1 2 3
45
CAN NO. 2729
NO. OF BLOWS REQUIRED 25-35 20-30 15-25
44

%MOISTURE
NO. OF BLOWS (LAB)
2628
1 wt of can 43
2 wt of can + wet soil
3 wt of can + dry soil 2527
42
4 wt of water (2-3)
5 wt of dry soil (3-1) 4126
24
6 % moisture (4/5 x 100) 1515 2020 2525 3030 3535
NO.OF
NO. OFBLOWS
BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.00 162.80 100 90
1 25.000 0.00 162.80 100 80
¾ 19.000 0.00 162.80 100
70
½ 12.500 0.00 162.80 100
% PASSING

60
⅜ 9.500 0.00 162.80 100
50
#4 4.750 8.40 154.40 95
#10 2.990 42.20 112.20 69 40
#20 1.495 52.30 59.90 37 30
#40 0.425 22.30 37.60 23 20
#100 0.150 28.20 9.40 6 10
#200 0.075 2.10 7.30 4 0
ORIGINAL DRY WEIGHT : 162.80 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SW Very Dense, Gray, Well-Graded Sand


with Grav el
Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

18

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-1 BH-2


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 1.0-1.5 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
40
PLASTIC LIMIT LIQUID LIMIT
NO.OF TRIALS 1 2 1 2 3 35

CAN NO. 30
NO. OF BLOWS REQUIRED 25-35 20-30 15-25 25

%MOISTURE
NO. OF BLOWS (LAB)
20
1 wt of can
15
2 wt of can + wet soil
10
3 wt of can + dry soil
4 wt of water (2-3) 5
5 wt of dry soil (3-1) 0
6 % moisture (4/5 x 100) 15 20 25 30 35
NO. OF BLOWS
7 Average Plastic Limit 0.00

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.0 167.7 100 90
1 25.000 0.0 167.7 100 80
¾ 19.000 0.0 167.7 100
70
½ 12.500 0.0 167.7 100
% PASSING

60
⅜ 9.500 0.0 167.7 100
50
#4 4.750 0.00 167.70 100
#10 2.990 15.10 152.60 91 40

#20 1.495 22.20 130.40 78 30


#40 0.425 19.70 110.70 66 20
#100 0.150 61.20 49.50 30 10
#200 0.075 46.40 3.10 2 0
ORIGINAL DRY WEIGHT : 167.70 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SP Loose , Gray, Poorly Graded Sand

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy 19

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-2 BH-2


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 2.5-3.0 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
46
PLASTIC LIMIT LIQUID LIMIT
NO.OF TRIALS 1 2 1 2 3 44
CAN NO. AP KS WM FZ MC 42
NO. OF BLOWS REQUIRED 25-35 20-30 15-25 40

%MOISTURE
NO. OF BLOWS (LAB) 31 25 20
38
1 wt of can 8.5 18.5 18.4 8.5 8.5
36
2 wt of can + wet soil 16.7 26.5 43.6 36.6 31.5
3 wt of can + dry soil 14.8 24.6 37.5 28.8 24.5 34

4 wt of water (2-3) 1.9 1.9 6.1 7.8 7 32


5 wt of dry soil (3-1) 6.3 6.1 19.1 20.3 16 30
6 % moisture (4/5 x 100) 30.16 31.15 31.94 38.42 43.75 15 20 25 30 35
NO. OF BLOWS
7 Average Plastic Limit 30.65
31.88 38.07 43.98
TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)
Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.0 163.4 100 90
1 25.000 0.0 163.4 100 80
¾ 19.000 0.0 163.4 100
70
½ 12.500 0.0 163.4 100
% PASSING

60
⅜ 9.500 0.00 163.40 100
50
#4 4.750 2.20 161.20 99
#10 2.990 35.60 125.60 77 40
#20 1.495 28.80 96.80 59 30
#40 0.425 24.60 72.20 44 20
#100 0.150 26.70 45.50 28 10
#200 0.075 22.30 23.20 14 0
ORIGINAL DRY WEIGHT : 163.40 grams

LIQUID LIMIT (LL) : 38.4 P LAST IC LIMIT (P L) : 30.65 P LAST IC INDEX (P I) : 7.73

Soil Classification (USCS) : SM Loose , Gray, Silty Sand with Grav el

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

20

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-3 BH-2


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 4.0-4.5 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
PLASTIC LIMIT LIQUID LIMIT
28
NO.OF TRIALS 1 2 1 2 3
CAN NO. 26
NO. OF BLOWS REQUIRED 25-35 20-30 15-25 24

%MOISTURE
NO. OF BLOWS (LAB)
1 wt of can 22

2 wt of can + wet soil 20


3 wt of can + dry soil
18
4 wt of water (2-3)
5 wt of dry soil (3-1) 16
6 % moisture (4/5 x 100) 15 20 25 30 35
NO. OF BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.0 184.1 100 90
1 25.000 0.0 184.1 100 80
¾ 19.000 0.0 184.1 100
70
½ 12.500 0.0 184.1 100
% PASSING

60
⅜ 9.500 0.0 184.1 100
50
#4 4.750 0.00 184.10 100
#10 2.990 9.60 174.50 95 40
#20 1.495 30.20 144.30 78 30
#40 0.425 25.80 118.50 64 20
#100 0.150 42.30 76.20 41 10
#200 0.075 61.30 14.90 8 0
ORIGINAL DRY WEIGHT : 184.10 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SP-SM Loose, Gray, Poorly Graded Sand


with Silt
Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

21

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-4 BH-2


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 5.5-6.0 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
PLASTIC LIMIT LIQUID LIMIT 30
28
NO.OF TRIALS 1 2 1 2 3
CAN NO. 26
29
NO. OF BLOWS REQUIRED 25-35 20-30 15-25 24

%MOISTURE
NO. OF BLOWS (LAB)
28
22
1 wt of can
2 wt of can + wet soil 20
3 wt of can + dry soil 27
18
4 wt of water (2-3)
5 wt of dry soil (3-1) 16
26
6 % moisture (4/5 x 100) 15 20 25 30 35
NO. OF BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.00 154.20 100 90
1 25.000 0.00 154.20 100 80
¾ 19.000 0.00 154.20 100
70
½ 12.500 0.00 154.20 100
% PASSING

60
⅜ 9.500 0.00 154.20 100
50
#4 4.750 0.00 154.20 100
#10 2.990 9.60 144.60 94 40
#20 1.495 12.30 132.30 86 30
#40 0.425 86.80 45.50 30 20
#100 0.150 41.60 3.90 3 10
#200 0.075 2.50 1.40 1 0
ORIGINAL DRY WEIGHT : 154.20 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SP Medium , Gray,Poorly Graded Sand

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

22

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-5 BH-2


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 7.0-7.5 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
30
PLASTIC LIMIT LIQUID LIMIT
NO.OF TRIALS 1 2 1 2 3
CAN NO. 29
NO. OF BLOWS REQUIRED 25-35 20-30 15-25

%MOISTURE
NO. OF BLOWS (LAB)
28
1 wt of can
2 wt of can + wet soil
3 wt of can + dry soil 27

4 wt of water (2-3)
5 wt of dry soil (3-1) 26
6 % moisture (4/5 x 100) 15 20 25 30 35
NO. OF BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.00 181.40 100 90
1 25.000 0.00 181.40 100 80
¾ 19.000 0.00 181.40 100
70
½ 12.500 0.00 181.40 100
% PASSING

60
⅜ 9.500 0.00 181.40 100
#4 4.750 0.00 181.40 100 50

#10 2.990 1.00 180.40 99 40


#20 1.495 36.80 143.60 79 30
#40 0.425 75.90 67.70 37 20
#100 0.150 58.70 9.00 5 10
#200 0.075 5.30 3.70 2 0
ORIGINAL DRY WEIGHT : 181.40 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SP Medium , Gray, Poorly Graded Sand

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

23

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-6 BH-2


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 8.5-9.0 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
30
28
PLASTIC LIMIT LIQUID LIMIT
NO.OF TRIALS 1 2 1 2 3
CAN NO. 29
27
NO. OF BLOWS REQUIRED 25-35 20-30 15-25

%MOISTURE
NO. OF BLOWS (LAB)
28
26
1 wt of can
2 wt of can + wet soil
3 wt of can + dry soil 27
25
4 wt of water (2-3)
5 wt of dry soil (3-1) 26
24
6 % moisture (4/5 x 100) 15
15 20
20 25
25 30
30 35
35
NO. OF
NO. OFBLOWS
BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.00 191.20 100 90
1 25.000 0.00 191.20 100 80
¾ 19.000 0.00 191.20 100
70
½ 12.500 0.00 191.20 100
% PASSING

60
⅜ 9.500 0.00 191.20 100
50
#4 4.750 0.00 191.20 100
#10 2.990 1.20 190.00 99 40
#20 1.495 4.30 185.70 97 30
#40 0.425 24.50 161.20 84 20
#100 0.150 142.50 18.70 10 10
#200 0.075 15.90 2.80 1 0
ORIGINAL DRY WEIGHT : 191.20 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SP Medium, Gray, Poorly Graded Sand


0
Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

24

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-7 BH-2


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 10-10.5 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
30
28
46
PLASTIC LIMIT LIQUID LIMIT
NO.OF TRIALS 1 2 1 2 3 44
CAN NO. 29
27
42
NO. OF BLOWS REQUIRED 25-35 20-30 15-25 40

%MOISTURE
%MOISTURE
NO. OF BLOWS (LAB)
28
26
38
1 wt of can
36
2 wt of can + wet soil
3 wt of can + dry soil 27
25
34
4 wt of water (2-3) 32
5 wt of dry soil (3-1) 26
24
30
6 % moisture (4/5 x 100) 1515 2020 2525 3030 3535
NO.OF
NO. OFBLOWS
BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.00 190.20 100 90
1 25.000 0.00 190.20 100 80
¾ 19.000 0.00 190.20 100
70
½ 12.500 0.00 190.20 100
% PASSING

60
⅜ 9.500 0.00 190.20 100
#4 4.750 0.00 190.20 100 50

#10 2.990 2.80 187.40 99 40


#20 1.495 16.30 171.10 90 30
#40 0.425 78.40 92.70 49 20
#100 0.150 85.50 7.20 4 10
#200 0.075 6.30 0.90 0 0
ORIGINAL DRY WEIGHT : 190.20 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SW Dense,Gray, Well Graded Sand

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

25

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-8 BH-2


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 11.5-12 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
PLASTIC LIMIT LIQUID LIMIT 40
39
NO.OF TRIALS 1 2 1 2 3
38
CAN NO. ZT CW AK LU PX
37
NO. OF BLOWS REQUIRED 25-35 20-30 15-25
36

%MOISTURE
NO. OF BLOWS (LAB) 33 22 18
35
1 wt of can 18.5 8.5 8.5 8.5 18.4 34
2 wt of can + wet soil 25.2 18.2 56.7 57.3 53.5 33
3 wt of can + dry soil 23.6 15.9 44.8 44.0 43.6 32
4 wt of water (2-3) 1.6 2.3 11.9 13.3 9.9 31
5 wt of dry soil (3-1) 5.1 7.4 36.3 35.5 25.2 30
6 % moisture (4/5 x 100) 31.4 31.1 32.8 37.5 39.3 15 20 25 30 35
7 Average Plastic Limit 31.2 NO. OF BLOWS
32.6 37.6 39.2
TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)
Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.00 164.70 100 90
1 25.000 0.00 164.70 100 80
¾ 19.000 0.00 164.70 100
70
½ 12.500 0.00 164.70 100
% PASSING

60
⅜ 9.500 0.00 164.70 100
50
#4 4.750 2.70 162.00 98
#10 2.990 13.90 148.10 90 40
#20 1.495 21.40 126.70 77 30
#40 0.425 13.20 113.50 69 20
#100 0.150 17.80 95.70 58 10
#200 0.075 62.10 33.60 20 0
ORIGINAL DRY WEIGHT : 164.70 grams

LIQUID LIMIT (LL) : 36.3 P LAST IC LIMIT (P L) : 31.23 P LAST IC INDEX (P I) : 5.02

Soil Classification (USCS) : SM Very Dense, Gray, Silty Sand

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

26

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-9 BH-2


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 13-13.5 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
30
46
28
PLASTIC LIMIT LIQUID LIMIT
NO.OF TRIALS 1 2 1 2 3
45
CAN NO. 29
27
NO. OF BLOWS REQUIRED 25-35 20-30 15-25
44

%MOISTURE
NO. OF BLOWS (LAB)
28
26
1 wt of can 43
2 wt of can + wet soil
3 wt of can + dry soil 27
25
42
4 wt of water (2-3)
5 wt of dry soil (3-1) 26
41
24
6 % moisture (4/5 x 100) 15
15 20
20 25
25 30
30 35
35
NO. OF
NO. OFBLOWS
BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE
Size of Opening Retained Weight %
inches mm grams Passing Passing
1-½ 37.500 0.00 183.80 100
1 25.000 0.00 183.80 100
¾ 19.000 0.00 183.80 100
½ 12.500 0.00 183.80 100
⅜ 9.500 0.00 183.80 100
#4 4.750 11.40 172.40 94
#10 2.990 53.80 118.60 65
#20 1.495 59.90 58.70 32
#40 0.425 26.10 32.60 18
#100 0.150 15.30 17.30 9
#200 0.075 12.40 4.90 3
ORIGINAL DRY WEIGHT : 183.80 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SW Very Dense, Gray, Well-Graded Sand

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

27

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-1 BH-3


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 1.0-1.5 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
40
PLASTIC LIMIT LIQUID LIMIT
NO.OF TRIALS 1 2 1 2 3 35

CAN NO. 30
NO. OF BLOWS REQUIRED 25-35 20-30 15-25 25

%MOISTURE
NO. OF BLOWS (LAB)
20
1 wt of can
15
2 wt of can + wet soil
10
3 wt of can + dry soil
4 wt of water (2-3) 5
5 wt of dry soil (3-1) 0
6 % moisture (4/5 x 100) 15 20 25 30 35
NO. OF BLOWS
7 Average Plastic Limit 0.00

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.0 201.1 100 90
1 25.000 0.0 201.1 100 80
¾ 19.000 0.0 201.1 100
70
½ 12.500 0.0 201.1 100
% PASSING

60
⅜ 9.500 0.0 201.1 100
50
#4 4.750 0.00 201.10 100
#10 2.990 19.60 181.50 90 40

#20 1.495 23.20 158.30 79 30


#40 0.425 21.80 136.50 68 20
#100 0.150 78.50 58.00 29 10
#200 0.075 48.30 9.70 5 0
ORIGINAL DRY WEIGHT : 201.10 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SP Loose , Gray, Poorly Graded Sand


0
Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy 28

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-2 BH-3


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 2.5-3.0 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
46
PLASTIC LIMIT LIQUID LIMIT
NO.OF TRIALS 1 2 1 2 3 44
CAN NO. YH DF LZ SP VW 42
NO. OF BLOWS REQUIRED 25-35 20-30 15-25 40

%MOISTURE
NO. OF BLOWS (LAB) 33 24 19
38
1 wt of can 18.5 8.5 8.5 18.5 18.5
36
2 wt of can + wet soil 32.6 17.5 42.6 48.6 40.9
3 wt of can + dry soil 29.3 15.4 34.3 40.1 34.1 34

4 wt of water (2-3) 3.3 2.1 8.3 8.5 6.8 32


5 wt of dry soil (3-1) 10.8 6.9 25.8 21.6 15.6 30
6 % moisture (4/5 x 100) 30.56 30.43 32.17 39.35 43.59 15 20 25 30 35
NO. OF BLOWS
7 Average Plastic Limit 30.50
32.74 39.64 43.56
TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)
Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.0 174.8 100 90
1 25.000 0.0 174.8 100 80
¾ 19.000 0.0 174.8 100
70
½ 12.500 0.0 174.8 100
% PASSING

60
⅜ 9.500 0.00 174.80 100
50
#4 4.750 3.30 171.50 98
#10 2.990 35.50 136.00 78 40
#20 1.495 25.30 110.70 63 30
#40 0.425 26.30 84.40 48 20
#100 0.150 33.20 51.20 29 10
#200 0.075 26.20 25.00 14 0
ORIGINAL DRY WEIGHT : 174.80 grams

LIQUID LIMIT (LL) : 38.7 P LAST IC LIMIT (P L) : 30.50 P LAST IC INDEX (P I) : 8.20

Soil Classification (USCS) : SM Loose , Gray, Silty Sand with Grav el

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

29

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-3 BH-3


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 4.0-4.5 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
PLASTIC LIMIT LIQUID LIMIT
28
NO.OF TRIALS 1 2 1 2 3
CAN NO. 26
NO. OF BLOWS REQUIRED 25-35 20-30 15-25 24

%MOISTURE
NO. OF BLOWS (LAB)
1 wt of can 22

2 wt of can + wet soil 20


3 wt of can + dry soil
18
4 wt of water (2-3)
5 wt of dry soil (3-1) 16
6 % moisture (4/5 x 100) 15 20 25 30 35
NO. OF BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.0 196.5 100 90
1 25.000 0.0 196.5 100 80
¾ 19.000 0.0 196.5 100
70
½ 12.500 0.0 196.5 100
% PASSING

60
⅜ 9.500 0.0 196.5 100
50
#4 4.750 0.00 196.50 100
#10 2.990 12.70 183.80 94 40
#20 1.495 31.20 152.60 78 30
#40 0.425 30.20 122.40 62 20
#100 0.150 45.50 76.90 39 10
#200 0.075 59.30 17.60 9 0
ORIGINAL DRY WEIGHT : 196.50 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SP-SM Loose, Gray, Poorly Graded Sand


with Silt
Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

30

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-4 BH-3


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 5.5-6.0 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
PLASTIC LIMIT LIQUID LIMIT 30
28
NO.OF TRIALS 1 2 1 2 3
CAN NO. 26
29
NO. OF BLOWS REQUIRED 25-35 20-30 15-25 24

%MOISTURE
NO. OF BLOWS (LAB)
28
22
1 wt of can
2 wt of can + wet soil 20
3 wt of can + dry soil 27
18
4 wt of water (2-3)
5 wt of dry soil (3-1) 16
26
6 % moisture (4/5 x 100) 15 20 25 30 35
NO. OF BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.00 175.40 100 90
1 25.000 0.00 175.40 100 80
¾ 19.000 0.00 175.40 100
70
½ 12.500 0.00 175.40 100
% PASSING

60
⅜ 9.500 0.00 175.40 100
50
#4 4.750 0.00 175.40 100
#10 2.990 15.30 160.10 91 40
#20 1.495 13.80 146.30 83 30
#40 0.425 95.10 51.20 29 20
#100 0.150 46.40 4.80 3 10
#200 0.075 3.20 1.60 1 0
ORIGINAL DRY WEIGHT : 175.40 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SP Medium , Gray,Poorly Graded Sand

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

31

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-5 BH-3


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 7.0-7.5 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
30
PLASTIC LIMIT LIQUID LIMIT
NO.OF TRIALS 1 2 1 2 3
CAN NO. 29
NO. OF BLOWS REQUIRED 25-35 20-30 15-25

%MOISTURE
NO. OF BLOWS (LAB)
28
1 wt of can
2 wt of can + wet soil
3 wt of can + dry soil 27

4 wt of water (2-3)
5 wt of dry soil (3-1) 26
6 % moisture (4/5 x 100) 15 20 25 30 35
NO. OF BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.00 160.30 100 90
1 25.000 0.00 160.30 100 80
¾ 19.000 0.00 160.30 100
70
½ 12.500 0.00 160.30 100
% PASSING

60
⅜ 9.500 0.00 160.30 100
#4 4.750 0.00 160.30 100 50

#10 2.990 3.60 156.70 98 40


#20 1.495 27.40 129.30 81 30
#40 0.425 46.80 82.50 51 20
#100 0.150 74.30 8.20 5 10
#200 0.075 5.60 2.60 2 0
ORIGINAL DRY WEIGHT : 160.30 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SP Medium , Gray, Poorly Graded Sand


0
Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

32

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-6 BH-3


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 8.5-9.0 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
30
28
PLASTIC LIMIT LIQUID LIMIT
NO.OF TRIALS 1 2 1 2 3
CAN NO. 29
27
NO. OF BLOWS REQUIRED 25-35 20-30 15-25

%MOISTURE
NO. OF BLOWS (LAB)
28
26
1 wt of can
2 wt of can + wet soil
3 wt of can + dry soil 27
25
4 wt of water (2-3)
5 wt of dry soil (3-1) 26
24
6 % moisture (4/5 x 100) 15
15 20
20 25
25 30
30 35
35
NO. OF
NO. OFBLOWS
BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.00 185.20 100 90
1 25.000 0.00 185.20 100 80
¾ 19.000 0.00 185.20 100
70
½ 12.500 0.00 185.20 100
% PASSING

60
⅜ 9.500 0.00 185.20 100
50
#4 4.750 0.00 185.20 100
#10 2.990 1.40 183.80 99 40
#20 1.495 5.60 178.20 96 30
#40 0.425 24.60 153.60 83 20
#100 0.150 133.60 20.00 11 10
#200 0.075 17.20 2.80 2 0
ORIGINAL DRY WEIGHT : 185.20 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SP Medium, Gray, Poorly Graded Sand


0
Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

33

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-7 BH-3


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 10-10.5 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
30
28
48
PLASTIC LIMIT LIQUID LIMIT
NO.OF TRIALS 1 2 1 2 3 46
CAN NO. 44
29
27
NO. OF BLOWS REQUIRED 25-35 20-30 15-25 42

%MOISTURE
%MOISTURE
NO. OF BLOWS (LAB) 40
28
26
1 wt of can 38
2 wt of can + wet soil 36
3 wt of can + dry soil 27
25
34
4 wt of water (2-3) 32
5 wt of dry soil (3-1) 26
24
30
6 % moisture (4/5 x 100) 1515 2020 2525 3030 3535
NO.OF
NO. OFBLOWS
BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.00 206.60 100 90
1 25.000 0.00 206.60 100 80
¾ 19.000 0.00 206.60 100
70
½ 12.500 0.00 206.60 100
% PASSING

60
⅜ 9.500 0.00 206.60 100
#4 4.750 0.00 206.60 100 50

#10 2.990 3.20 203.40 98 40


#20 1.495 20.70 182.70 88 30
#40 0.425 78.60 104.10 50 20
#100 0.150 94.70 9.40 5 10
#200 0.075 9.20 0.20 0 0
ORIGINAL DRY WEIGHT : 206.60 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SW Dense,Gray, Well Graded Sand

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

34

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-8 BH-3


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 11.5-12 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
PLASTIC LIMIT LIQUID LIMIT 40
39
NO.OF TRIALS 1 2 1 2 3
38
CAN NO. FD KG LX ZP WM
37
NO. OF BLOWS REQUIRED 25-35 20-30 15-25
36

%MOISTURE
NO. OF BLOWS (LAB) 33 24 19
35
1 wt of can 8.6 18.4 18.5 8.5 18.5 34
2 wt of can + wet soil 18.5 28.4 56.1 47.5 66.4 33
3 wt of can + dry soil 16.1 26.0 46.8 36.9 52.8 32
4 wt of water (2-3) 2.4 2.4 9.3 10.6 13.6 31
5 wt of dry soil (3-1) 7.5 7.6 28.3 28.4 34.3 30
6 % moisture (4/5 x 100) 32.0 31.6 32.9 37.3 39.7 15 20 25 30 35
7 Average Plastic Limit 31.8 NO. OF BLOWS

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE PARTICLE SIZE
Size of Opening Retained Weight % (mm)
37.5 25.0 19.0 12.5 9.5 4.75 2.99 1.495 0.425 0.150 0.075
inches mm grams Passing Passing 100
1-½ 37.500 0.00 187.30 100 90
1 25.000 0.00 187.30 100 80
¾ 19.000 0.00 187.30 100
70
½ 12.500 0.00 187.30 100
% PASSING

60
⅜ 9.500 0.00 187.30 100
50
#4 4.750 5.60 181.70 97
#10 2.990 15.10 166.60 89 40
#20 1.495 26.20 140.40 75 30
#40 0.425 17.80 122.60 65 20
#100 0.150 18.20 104.40 56 10
#200 0.075 71.10 33.30 18 0
ORIGINAL DRY WEIGHT : 187.30 grams

LIQUID LIMIT (LL) : 36.7 P LAST IC LIMIT (P L) : 31.79 P LAST IC INDEX (P I) : 4.95

Soil Classification (USCS) : SM Very Dense, Gray, Silty Sand

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

35

 

PROJECT: Tacurong Doctors Hospital Building SAMPLE ID: SS-9 BH-3


LOCATION: Lapu-lapu St., Poblacion, Tacurong City DEPTH : 13-13.5 m
EXPLORER: RAJ Plans, Design & Consultancy QTY. REPRESENTED : NOT SPECIFIED
KIND OF MATERIALS: Soil Sample

NATURAL MOISTURE CONTENT (ASTM D 2216)/ATTERBERG LIMITS (ASTM D4318)


LIQUID LIMIT - PLASTIC LIMIT - LIQUID LIMIT
30
46
28
PLASTIC LIMIT LIQUID LIMIT
NO.OF TRIALS 1 2 1 2 3
45
CAN NO. 29
27
NO. OF BLOWS REQUIRED 25-35 20-30 15-25
44

%MOISTURE
NO. OF BLOWS (LAB)
28
26
1 wt of can 43
2 wt of can + wet soil
3 wt of can + dry soil 27
25
42
4 wt of water (2-3)
5 wt of dry soil (3-1) 26
41
24
6 % moisture (4/5 x 100) 15
15 20
20 25
25 30
30 35
35
NO. OF
NO. OFBLOWS
BLOWS
7 Average Plastic Limit

TEST ON SIEVE ANALYSIS OF SOIL (ASTM D-422)


Sieve Diameter Weight CUMULATIVE
Size of Opening Retained Weight %
inches mm grams Passing Passing
1-½ 37.500 0.00 213.40 100
1 25.000 0.00 213.40 100
¾ 19.000 0.00 213.40 100
½ 12.500 0.00 213.40 100
⅜ 9.500 0.00 213.40 100
#4 4.750 9.40 204.00 96
#10 2.990 63.20 140.80 66
#20 1.495 74.10 66.70 31
#40 0.425 31.20 35.50 17
#100 0.150 17.60 17.90 8
#200 0.075 13.80 4.10 2
ORIGINAL DRY WEIGHT : 213.40 grams

LIQUID LIMIT (LL) : NP P LAST IC LIMIT (P L) : NP P LAST IC INDEX (P I) : NP

Soil Classification (USCS) : SW Very Dense, Gray, Well-Graded Sand

Certified by : Verified by :

JULE S HANNAH O. CE RBO ROGE R A. JUAN


LICENSED GEOLOGIST HEAD, RAJ Plans, Designs & Consultancy

36

 

37

 