Diesel generator
set
QSK95 series
engine
3125 kVA - 3350 kVA 50 Hz
Data Center Continuous
Emissions regulated
Description
Cummins Power Generation commercial Control system - The PowerCommand® digital
generator sets are fully integrated power control is standard equipment and provides total
generation systems providing optimum genset system integration including automatic
performance, reliability and versatility for Data remote starting/stopping, precise frequency and
Center applications. voltage regulation, alarm and status message
display, AmpSentry™ protective relay, output
Features metering and auto-shutdown.
Cooling system - Standard and enhanced
Data Center Continuous (DCC) - Applicable
for supplying power continuously to a constant or integral set-mounted radiator systems, designed
varying electrical load for unlimited hours in a and tested for rated ambient temperatures,
data center application. simplifies facility design requirements for rejected
heat. Also optional remote cooled configuration
Uptime Compliant - Meets the requirement of for non-factory supplied cooling systems.
a Tier III and IV data center site by being rated to
Warranty and service - Backed by a
run for unlimited hours of operation when loaded
to 'N' demand for the engine generator set. comprehensive warranty and worldwide
distributor network.
Cummins® heavy-duty engine - Rugged 4-
NFPA - The generator set accepts full rated load
cycle, industrial diesel delivers reliable power, low
emissions and fast response to load changes. in a single step in accordance with NFPA 110 for
Level 1 systems.
Alternator - Several alternator sizes offer
selectable motor starting capability with low
reactance windings, low waveform distortion with
non-linear loads and fault clearing short-circuit
capability.
power.cummins.com
©2015 Cummins Power Generation Inc. | NAS-5829b-DC-EN (8/15)
Generator set specifications
Governor regulation class ISO 8528 Part 1 Class G3
Voltage regulation, no load to full load ± 0.5%
Random voltage variation ± 0.5%
Frequency regulation Isochronous
Random frequency variation ± 0.25%
Emissions to EN 61000-6-4
EMC compatibility
Immunity to EN 61000-6-2
Engine specifications
Bore 190 mm (7.48 in)
Stroke 210 mm (8.27 in)
Displacement 95.3 litres (5815 in3)
Configuration Cast iron, V 16 cylinder
Battery capacity 6 x 1400 amps minimum at ambient temperature of -18 °C (0 °F)
Battery charging alternator 140 amps
Starting voltage 24 volt, negative ground
Fuel system Cummins Modular Common Rail System
On engine triple element, 5 micron primary filtration with water
Fuel filter separators, 3 micron/2 micron (filter in filter design) secondary
filtration
Fuel transfer pump Electronic variable speed priming and lift pump
Breather Cummins impactor breather system
Air cleaner type Unhoused dry replaceable element
Lube oil filter type(s) Spin-on combination full flow filter and bypass filters
Standard cooling system High ambient cooling system (ship loose)
Alternator specifications
Design Brushless, 4 pole, drip proof, revolving field
Stator Optimal
Rotor Two bearing, flexible coupling
Insulation system Class H on low voltage and medium, Class F on high voltage
Standard temperature rise 125 ºC standby / 105 ºC prime
Exciter type Optimal
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform total harmonic distortion < 5% no load to full linear load, < 3% for any single harmonic
Telephone influence factor (TIF) < 50 per NEMA MG1-22.43
Telephone harmonic factor (THF) <3
Anti-condensation heater 1400 watt
Available voltages
220/380 254/440 3464/6000 5775/10000
230/400 400/690 3637/6300 6060/10500
240/415 1905/3300 3810/6600 6350/11000
Note: Consult factory for other voltages.
power.cummins.com
©2015 Cummins Power Generation Inc. | NAS-5829b-DC-EN (8/15)
PowerCommand® 3.3 – Control System
Engine data
DC voltage
Engine speed
Lube oil pressure and temperature
Coolant temperature
Comprehensive FAE data (where applicable)
Other data
Genset model data
Start attempts, starts, running hours, kW hours
Load profile (operating hours at % load in 5% increments)
An integrated microprocessor based generator set control Fault history
system providing voltage regulation, engine protection, alternator
Data logging and fault simulation (requires InPower)
protection, operator interface and isochronous governing. Refer
Air cleaner restriction indication
to document S-1570 for more detailed information on the control.
Exhaust temperature in each cylinder
AmpSentry – Includes integral AmpSentry protection, which
provides a full range of alternator protection functions that are Standard control functions
matched to the alternator provided. Digital governing
Power management – Control function provides battery Integrated digital electronic isochronous governor
monitoring and testing features and smart starting control Temperature dynamic governing
system. Digital voltage regulation
Advanced control methodology – Three phase sensing, full Integrated digital electronic voltage regulator
wave rectified voltage regulation, with a PWM output for stable 3-phase, 4-wire line-to-line sensing
operation with all load types. Configurable torque matching
Communications interface – Control comes standard with AmpSentry AC protection
PCCNet and Modbus interface.
AmpSentry protective relay
Regulation compliant – Prototype tested: UL, CSA and CE
Over current and short circuit shutdown
compliant.
Over current warning
Service - InPower™ PC-based service tool available for detailed
Single and three phase fault regulation
diagnostics, setup, data logging and fault simulation.
Over and under voltage shutdown
Easily upgradeable – PowerCommand controls are designed
Over and under frequency shutdown
with common control interfaces.
Overload warning with alarm contact
Reliable design – The control system is designed for reliable
Reverse power and reverse var shutdown
operation in harsh environment.
Field overload shutdown
Multi-language support
Engine protection
Operator panel features Battery voltage monitoring, protection and testing
Operator/display functions Overspeed shutdown
Displays paralleling breaker status Low oil pressure warning and shutdown
Provides direct control of the paralleling breaker High coolant temperature warning and shutdown
320 x 240 pixels graphic LED backlight LCD Low coolant level warning or shutdown
Auto, manual, start, stop, fault reset and lamp test/panel lamp Low coolant temperature warning
switches Fail to start (overcrank) shutdown
Alpha-numeric display with pushbuttons Fail to crank shutdown
LED lamps indicating genset running, remote start, not in Cranking lockout
auto, common shutdown, common warning, manual run Sensor failure indication
mode, auto mode and stop Low fuel level warning or shutdown
Paralleling control functions Fuel-in-rupture-basin warning or shutdown
First Start Sensor System selects first genset to close to bus Full authority electronic engine protection
Phase Lock Loop Synchronizer with voltage matching Control functions
Sync check relay Time delay start and cool down
Isochronous kW and kVar load sharing Real time clock for fault and event time stamping
Load govern control for utility paralleling Exerciser clock and time of day start/stop
Extended Paralleling (baseload/peak shave) Mode Data logging
Digital power transfer control, for use with a breaker pair to Cycle cranking
provide open transition, closed transition, ramping closed Load shed
transition, peaking and base load functions. Configurable inputs and outputs (20)
Other control features Remote emergency stop
150 watt anti-condensation heater
DC distribution panel
AC auxiliary distribution panel
Alternator data
Line-to-neutral and line-to-line AC volts
3-phase AC current
Frequency
kW, kvar, power factor kVA (three phase and total)
Winding temperature
Bearing temperature
power.cummins.com
©2015 Cummins Power Generation Inc. | NAS-5829b-DC-EN (8/15)
Do not use for installation design
This outline drawing is for reference only. See PowerSuite Library for specific model outline drawing number.
Dim “A”* Dim “B”* Dim “C”* Set Weight* Set Weight*
Model mm (in.) mm (in.) mm (in.) dry kg (lbs) wet kg (lbs)
C3500 D5e 7902 (311) 3028 (119) 3663 (144) 29526 (65092) 31194 (68771)
C3750 D5e 7902 (311) 3028 (119) 3663 (144) 29526 (65092) 31194 (68771)
* Weights and dimensions represent a set with standard features and alternator frame P80X.
See outline drawing for weights and dimensions of other configurations.
Engine certified to Stationary Emergency U.S. The engine used in this generator set complies
EPA New Source Performance Standards, with TA Luft Standards of 2g/nm3
U.S. EPA 40 CFR 60 subpart IIII Tier 2 exhaust emission (4.8g/bhp-hr) NOx at prime rating corrected to
levels. 5% oxygen content and measured in
accordance with ISO 8178.
Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s electrical system
except through an approved device or after building main switch is open.