Specification sheet

Diesel generator
set
QSK95 series
engine
3125 kVA - 3350 kVA 50 Hz
Data Center Continuous
Emissions regulated
Description
Cummins Power Generation commercial Control system - The PowerCommand® digital
generator sets are fully integrated power control is standard equipment and provides total
generation systems providing optimum genset system integration including automatic
performance, reliability and versatility for Data remote starting/stopping, precise frequency and
Center applications. voltage regulation, alarm and status message
display, AmpSentry™ protective relay, output
Features metering and auto-shutdown.
Cooling system - Standard and enhanced
Data Center Continuous (DCC) - Applicable
for supplying power continuously to a constant or integral set-mounted radiator systems, designed
varying electrical load for unlimited hours in a and tested for rated ambient temperatures,
data center application. simplifies facility design requirements for rejected
heat. Also optional remote cooled configuration
Uptime Compliant - Meets the requirement of for non-factory supplied cooling systems.
a Tier III and IV data center site by being rated to
Warranty and service - Backed by a
run for unlimited hours of operation when loaded
to 'N' demand for the engine generator set. comprehensive warranty and worldwide
distributor network.
Cummins® heavy-duty engine - Rugged 4-
NFPA - The generator set accepts full rated load
cycle, industrial diesel delivers reliable power, low
emissions and fast response to load changes. in a single step in accordance with NFPA 110 for
Level 1 systems.
Alternator - Several alternator sizes offer
selectable motor starting capability with low
reactance windings, low waveform distortion with
non-linear loads and fault clearing short-circuit
capability.

50 Hz Emissions compliance Data sheets


Model kVA (kW) EPA and TA Luft 50 Hz
2g TA Luft NAD-5830-DC
C3500 D5e 3125 (2500)
Tier 2 NAD-5938-DC
C3750 D5e 3350 (2680) Tier 2 NAD-5986-DC

Note: All ratings include radiator fan losses.

power.cummins.com
©2015 Cummins Power Generation Inc. | NAS-5829b-DC-EN (8/15)
Generator set specifications
Governor regulation class ISO 8528 Part 1 Class G3
Voltage regulation, no load to full load ± 0.5%
Random voltage variation ± 0.5%
Frequency regulation Isochronous
Random frequency variation ± 0.25%
Emissions to EN 61000-6-4
EMC compatibility
Immunity to EN 61000-6-2

Engine specifications
Bore 190 mm (7.48 in)
Stroke 210 mm (8.27 in)
Displacement 95.3 litres (5815 in3)
Configuration Cast iron, V 16 cylinder
Battery capacity 6 x 1400 amps minimum at ambient temperature of -18 °C (0 °F)
Battery charging alternator 140 amps
Starting voltage 24 volt, negative ground
Fuel system Cummins Modular Common Rail System
On engine triple element, 5 micron primary filtration with water
Fuel filter separators, 3 micron/2 micron (filter in filter design) secondary
filtration
Fuel transfer pump Electronic variable speed priming and lift pump
Breather Cummins impactor breather system
Air cleaner type Unhoused dry replaceable element
Lube oil filter type(s) Spin-on combination full flow filter and bypass filters
Standard cooling system High ambient cooling system (ship loose)

Alternator specifications
Design Brushless, 4 pole, drip proof, revolving field
Stator Optimal
Rotor Two bearing, flexible coupling
Insulation system Class H on low voltage and medium, Class F on high voltage
Standard temperature rise 125 ºC standby / 105 ºC prime
Exciter type Optimal
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform total harmonic distortion < 5% no load to full linear load, < 3% for any single harmonic
Telephone influence factor (TIF) < 50 per NEMA MG1-22.43
Telephone harmonic factor (THF) <3
Anti-condensation heater 1400 watt

Available voltages
 220/380  254/440  3464/6000  5775/10000
 230/400  400/690  3637/6300  6060/10500
 240/415  1905/3300  3810/6600  6350/11000
Note: Consult factory for other voltages.

Generator set options and accessories


Engine Alternator Control panel Generator set
 400 V thermostatically controlled  80 C rise  Multiple language support  Battery
coolant heater for ambient  105 C rise  Ground fault indication  Battery charger
above 4.5 C (40 F)  125 C rise  Remote annunciator panel  LV and MV entrance box
 Heavy duty air cleaner  150 C rise  Paralleling and shutdown alarm  Spring isolators
 Redundant fuel filter  Differential current transformers relay package  Factory witness tests
 Air starter Cooling system  Floor mounted pedestal installed  IBC and IEEE seismic
 Redundant electric starting  Enhanced high ambient cooling control panel certification
 Eliminator oil filter system system (ship loose) Warranty
 Lube oil make up  Remote cooled configuration  3, 5 or 10 years for standby
 Coalescing breather filter including parts (labor and travel
optional)
 2 or 3 years for prime including
parts, labor and travel
Note: Some options may not be available on all models - consult factory for availability.

power.cummins.com
©2015 Cummins Power Generation Inc. | NAS-5829b-DC-EN (8/15)
PowerCommand® 3.3 – Control System
Engine data
 DC voltage
 Engine speed
 Lube oil pressure and temperature
 Coolant temperature
 Comprehensive FAE data (where applicable)
Other data
 Genset model data
 Start attempts, starts, running hours, kW hours
 Load profile (operating hours at % load in 5% increments)
An integrated microprocessor based generator set control  Fault history
system providing voltage regulation, engine protection, alternator
 Data logging and fault simulation (requires InPower)
protection, operator interface and isochronous governing. Refer
 Air cleaner restriction indication
to document S-1570 for more detailed information on the control.
 Exhaust temperature in each cylinder
AmpSentry – Includes integral AmpSentry protection, which
provides a full range of alternator protection functions that are Standard control functions
matched to the alternator provided. Digital governing
Power management – Control function provides battery  Integrated digital electronic isochronous governor
monitoring and testing features and smart starting control  Temperature dynamic governing
system. Digital voltage regulation
Advanced control methodology – Three phase sensing, full  Integrated digital electronic voltage regulator
wave rectified voltage regulation, with a PWM output for stable  3-phase, 4-wire line-to-line sensing
operation with all load types.  Configurable torque matching
Communications interface – Control comes standard with AmpSentry AC protection
PCCNet and Modbus interface.
 AmpSentry protective relay
Regulation compliant – Prototype tested: UL, CSA and CE
 Over current and short circuit shutdown
compliant.
 Over current warning
Service - InPower™ PC-based service tool available for detailed
 Single and three phase fault regulation
diagnostics, setup, data logging and fault simulation.
 Over and under voltage shutdown
Easily upgradeable – PowerCommand controls are designed
 Over and under frequency shutdown
with common control interfaces.
 Overload warning with alarm contact
Reliable design – The control system is designed for reliable
 Reverse power and reverse var shutdown
operation in harsh environment.
 Field overload shutdown
Multi-language support
Engine protection
Operator panel features  Battery voltage monitoring, protection and testing
Operator/display functions  Overspeed shutdown
 Displays paralleling breaker status  Low oil pressure warning and shutdown
 Provides direct control of the paralleling breaker  High coolant temperature warning and shutdown
 320 x 240 pixels graphic LED backlight LCD  Low coolant level warning or shutdown
 Auto, manual, start, stop, fault reset and lamp test/panel lamp  Low coolant temperature warning
switches  Fail to start (overcrank) shutdown
 Alpha-numeric display with pushbuttons  Fail to crank shutdown
 LED lamps indicating genset running, remote start, not in  Cranking lockout
auto, common shutdown, common warning, manual run  Sensor failure indication
mode, auto mode and stop  Low fuel level warning or shutdown
Paralleling control functions  Fuel-in-rupture-basin warning or shutdown
 First Start Sensor System selects first genset to close to bus  Full authority electronic engine protection
 Phase Lock Loop Synchronizer with voltage matching Control functions
 Sync check relay  Time delay start and cool down
 Isochronous kW and kVar load sharing  Real time clock for fault and event time stamping
 Load govern control for utility paralleling  Exerciser clock and time of day start/stop
 Extended Paralleling (baseload/peak shave) Mode  Data logging
 Digital power transfer control, for use with a breaker pair to  Cycle cranking
provide open transition, closed transition, ramping closed  Load shed
transition, peaking and base load functions.  Configurable inputs and outputs (20)
Other control features  Remote emergency stop
 150 watt anti-condensation heater
 DC distribution panel
 AC auxiliary distribution panel
Alternator data
 Line-to-neutral and line-to-line AC volts
 3-phase AC current
 Frequency
 kW, kvar, power factor kVA (three phase and total)
 Winding temperature
 Bearing temperature

power.cummins.com
©2015 Cummins Power Generation Inc. | NAS-5829b-DC-EN (8/15)
Do not use for installation design
This outline drawing is for reference only. See PowerSuite Library for specific model outline drawing number.

Dim “A”* Dim “B”* Dim “C”* Set Weight* Set Weight*
Model mm (in.) mm (in.) mm (in.) dry kg (lbs) wet kg (lbs)
C3500 D5e 7902 (311) 3028 (119) 3663 (144) 29526 (65092) 31194 (68771)
C3750 D5e 7902 (311) 3028 (119) 3663 (144) 29526 (65092) 31194 (68771)

* Weights and dimensions represent a set with standard features and alternator frame P80X.
See outline drawing for weights and dimensions of other configurations.

Codes and standards


Codes may not be available with all model configurations – consult factory for availability.
This generator set is designed in facilities
This generator set is available with CE
certified to ISO 9001 and manufactured in
certification.
facilities certified to ISO 9001 or ISO 9002.
All models are CSA certified to product class This generator set has been designed to
4215-01.
ISO8528 comply with ISO8528 regulation.

Engine certified to Stationary Emergency U.S. The engine used in this generator set complies
EPA New Source Performance Standards, with TA Luft Standards of 2g/nm3
U.S. EPA 40 CFR 60 subpart IIII Tier 2 exhaust emission (4.8g/bhp-hr) NOx at prime rating corrected to
levels. 5% oxygen content and measured in
accordance with ISO 8178.

Cummins Power Generation

Europe, CIS, Middle East and Africa Americas Asia Pacific


Manston Park Columbus Ave. 1400 73rd Avenue N.E. 10 Toh Guan Road #07-01
Manston, Ramsgate Minneapolis, MN 55432 USA Singapore 608838
Kent CT12 5BF United Kingdom Phone 763 574 5000 Phone 65 6417 2388
Phone 44 1843 255000 Fax 763 574 5298 Fax 65 6417 2399
Fax 44 1843 255902

Warning: Back feed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s electrical system
except through an approved device or after building main switch is open.

©2015 Cummins Power Generation Inc. All rights reserved.


Cummins Power Generation and Cummins are registered trademarks of Cummins Inc. PowerCommand, AmpSentry, InPower
and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names
may be trademarks or service marks of others. Specifications are subject to change without notice. power.cummins.com
NAS-5829b-DC-EN (8/15)