CSD3 User Manual
CSD3 User Manual
User Manual
Important User Information Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Because of this difference, and also because of
the wide variety of uses for solid state equipment, all persons responsible for
applying this equipment must satisfy themselves that each intended application
of this equipment is acceptable.
In no event will Rockwell Automation Korea, Ltd. be responsible or liable for
indirect or consequential damages resulting from the use or application of this
equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with any
particular installation, Rockwell Automation Korea, Ltd. cannot assume
responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation Korea, Ltd. with
respect to use of information, circuits, equipment, or software described in this
manual.
Reproduction of the contents of this manual, in whole or in part, without
written permission of Rockwell Automation Korea, Ltd., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of
safety considerations.
Trademarks not belonging to Rockwell Automation Korea, Ltd. are property of their respective companies.
Table of Contents
Chapter 1
Before Using the CSD3 Servo Drive Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
How to Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Notation Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Manual Description Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Others . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Product Type and Each Part Name . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Name of Each Part of the Drive . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Model Number of the Drive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Drive Type (by capacity) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Name of Each Motor Part . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Model Number of the Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
Reducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
Chapter 2
Installation Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Servo Motor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Servo Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Chapter 3
Wiring Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Electric Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Name and Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Electric Circuit Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Using the Socket and Lever . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
I/O Signal (CN1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
I/O Connection Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
(CN1) Pin Arrangement . . . . . . . . . . . . . . . . . . . . . . . 3-9
(CN1) Input Signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Sequence Input Signal (allocation) . . . . . . . . . . . . . . . . . . . . . . . 3-11
General Input Signal (fixed) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
(CN1) Output Signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
Sequence Output Signal (Allocation) . . . . . . . . . . . . . . . . . . . . . 3-13
General Output Signal (fixed). . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
(CN1) Input Circuit and Interface . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
Pulse Command Input Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
Analog Voltage Input Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Chapter 4
Operator, Basic Setting and Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Startup Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
About Servo-ON Signal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Table for Parameter Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Operator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Name and Function of Each Part . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Icons for the Key Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Structure of the Entire Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Status Display Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Overview of the Parameter Setting Mode . . . . . . . . . . . . . . . . . . 4-9
Overview of the Monitor Mode . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Overview of the Operation Mode. . . . . . . . . . . . . . . . . . . . . . . . 4-11
Basic Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Overview of the Basic Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Control Mode Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Motor Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16
Main Power Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
Before Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
Startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
Check up Items during Startup . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25
Chapter 5
Function for Control Mode Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Sequence I/O (Input/Output) Signal . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
What is Sequence I/O Signal? . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Function of Output Signal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Input Signal Allocation Method . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Output Signal Allocation Method . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Notice for Signal Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Position Control Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
Standard Wiring Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10
Position Command Pulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
Position Command Pulse Setting . . . . . . . . . . . . . . . . . . . . . . . . 5-13
Electrical Specifications of Position Command Pulse. . . . . . . . 5-14
Electronic Gear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15
Position Error Clear (/PCLR) . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21
Pulse Command Inhibition</INHIB> Input . . . . . . . . . . . . . 5-21
Expansion of Electronic Gear Setting . . . . . . . . . . . . . . . . . . . . 5-22
The Second Group of Electronic Gear </GEAR> input . . . . 5-23
Position Completion Signal Detection </P-COM>, Approach
Signal Detection </NEAR> Output. . . . . . . . . . . . . . . . . . . 5-23
Output Width of Allowable Position Error. . . . . . . . . . . . . . . . 5-27
Input/Output Signal Timing diagram . . . . . . . . . . . . . . . . . . . . 5-27
Speed Control Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28
Standard Wiring Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-29
Speed Command Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-30
Zero Clamp </Z-CLP> Input. . . . . . . . . . . . . . . . . . . . . . . . . . 5-31
Rotation Direction Switch Input /C-DIR . . . . . . . . . . . . . . . . 5-32
Motor Rotation Start/Stop Input /START. . . . . . . . . . . . . . . . 5-33
Speed Coincidence Output Signal </V-COM> . . . . . . . . . . . . 5-34
Rotation Detection </TG-ON> Output . . . . . . . . . . . . . . . . . 5-35
Speed Limit Function and Speed Limit Detection </V-LMT>
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-36
Torque Control Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-38
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-38
Standard Wiring Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-39
Torque Command Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-40
Torque Limit and Torque Limit Detection </T-LMT> Output . . .
5-41
Multi-Step Speed Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-45
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-45
Standard Wiring Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-46
Multi-Step Speed Command Setting . . . . . . . . . . . . . . . . . . . . . 5-47
Combinational Control Mode and </C-SEL> Function . . . . . . . . 5-50
Chapter 6
Tuning by Gain Setting Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Before you Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Mark Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Gain Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Inertia Ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Gain Setting Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Automatic Gain Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Auto Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Off-line Auto Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Chapter 7
Applications Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Motor Suspension. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Servo Alarm (Refer to Chapter 8-6) . . . . . . . . . . . . . . . . . . . . . . . 7-2
Over Travel <P-OT>, <N-OT> . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Dynamic Brake. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
Motor Brake Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6
Change of Motor Rotation Direction . . . . . . . . . . . . . . . . . . . . . . . . 7-10
Regeneration Resistor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11
Regeneration Resistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11
External Regenerative Resistor . . . . . . . . . . . . . . . . . . . . . . . . . . 7-12
Regenerative Resistor Selection Standard . . . . . . . . . . . . . . . . . . 7-13
Setting for Smooth Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-16
Speed Limiting Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-18
Position Feedback to the Host Controller . . . . . . . . . . . . . . . . . . . . 7-21
Direction Change of Output Pulse . . . . . . . . . . . . . . . . . . . . . . . 7-21
Pulse Dividing Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-22
Analog Monitor Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-25
Use of Absolute Encoder. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-27
What is an Absolute Encoder? . . . . . . . . . . . . . . . . . . . . . . . . . . 7-27
Contact with the Host Controller . . . . . . . . . . . . . . . . . . . . . . . . 7-28
Battery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-28
Reset of Absolute Encoder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-30
Data Transmission of Absolute Encoder . . . . . . . . . . . . . . . . . . 7-32
Operation Mode Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-35
Things to Know First. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-35
Jog Operation (run-00) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-35
Off-line Auto Tuning Operation (run-01) . . . . . . . . . . . . . . . . . 7-36
Searching an Origin Pulse(run-02) . . . . . . . . . . . . . . . . . . . . . . . 7-38
Auto Adjustment of Speed Command Offset (run-03) . . . . . . . 7-38
Auto Adjustment of Torque Command Offset (run-04). . . . . . 7-39
Chapter 8
Inspection and Protection Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Functions Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
Inspection of Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
Inspection of Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
Part Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
Battery Inspection for absolute Encoder (7.9.3) . . . . . . . . . . . . . 8-3
Protection Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
Servo Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
Servo Alarm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-6
Confirmation before Requesting for A/S . . . . . . . . . . . . . . . . . 8-14
Appendix A
Parameter List Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Parameter List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Summary of Parameters . . . . . . . . . . . . . . . . . . . . . . . A-2
Parameter Group 0. . . . . . . . . . . . . . . . . . . . . . . . . . A-7
Parameter Group 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-15
Pr-1.14: Current Controller BW . . . . . . . . . . . . . . . . . . . . . . . . . A-20
Pr-1.15: Velocity Response Level . . . . . . . . . . . . . . . . . . . . . . . . A-21
Parameter Group 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-21
Parameter Group 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-25
Parameter Group 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-29
Parameter Group 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-32
Operation Mode Function List. . . . . . . . . . . . . . . . . . . . . . . . . . A-40
Monitor Mode Function List . . . . . . . . . . . . . . . . . . . . . . . . . . . A-42
Appendix B
Servo Drive Specification Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Servo Drive Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Outline Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Specification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
1. New Parameter
About This Publication This manual provides detailed installation instructions for mounting, wiring,
and troubleshooting your CSD3 Plus servo drive drive, and system integration
for your drive/motor combination with a Motion Card.
Who Should Use this This manual is intended for engineers or technicians directly involved in the
installation and wiring of the CSD3 Plus servo drive drive, and programmers
Manual directly involved in the operation, field maintenance, and integration of the
CSD3 Plus servo drive drive with a Motion Card.
If you do not have a basic understanding of the CSD3 Plus servo drive drive,
contact your local OE Max sales representative before using this product, for
information on available training courses.
Conventions Used in This The conventions starting below are used throughout this manual.
Manual • Bulleted lists such as this one provide information, not procedural steps
• Numbered lists provide sequential steps or hierarchical information
Additional Resources The following documents contain additional information concerning related
CSD3 Plus servo drive products.
Introduction This chapter describes the general matters and optional specifications that you
should know before using the OEMax CSD3 SERVO DRIVE.
Topic Page
Introduction 1-1
Safety Precautions 1-2
How to Use This Manual 1-3
Product Type and Each Part Name 1-6
Safety Precautions This user’s manual describes safety matters using the following marks.
Safety marks deals with the important matters. If the following marks and
contents of each mark are indicated in the contents of this user's manual, you
must be fully aware of them and follow them.
1. The following is a warning mark. This indicates general precautions.
4. General Precaution
• This user’s manual may contain some drawings with the cover or
protective shields removed for more detailed and clear explanation.
Make sure to reassemble the device before operation.
• Any modification of the product made by the user is not covered by the
guarantee of quality.
• Servo motor or Motor: Refers to the servo motor exclusively for the
CSD3 drive.
• Initial value: Refers to the value set at the factory before the shipment.
• Set value: Refers to the initial value or the value changed and set by the
users.
Notation Description
2. A figure box with both the top corners cut off diagonally represents a
circuit diagram. If CN1 for I/O signal or a connector attached to the
servo driver is on the left, it is the output of CN1 or servo drive.
Example Output
R1
CN1
0[V] Host controller
Example Input
5. The following figure shows a symbol used to show a twist pair wires to
prevent the noise generation.
Symbol Figure Description
Twist the wires where this symbol is located for the noise
P prevention.
6. The following figure shows a symbol used to show a shield pair wire to
prevent the noise generation.
Symbol Figure Description
Shield the wires where this symbol is located for the noise
FG
Shield prevention.
This manual is described in the view of users from the purchase to operation.
Describes the basic settings that Describes the function of the product
7 users should set. for each control modes. 8
Others
Each chapter or paragraph has a page called Before you begin before
description. For easier understanding of this manual, be fully aware of the
contents of this page called Before you begin in advance.
Product Type and Each Part Name of Each Part of the Drive
Name
The following figure introduces the name of each part of the servo drive.
Optional Connector
<CN4>
Drive Nameplate
AC main Power Input
Terminal
Rated Output Label
Control power input
Terminal I/O Signals
Connector <CN1>
1. DC Main Power Input terminal.
2. DC Reactor Connection Terminal
for suppressing high frequency
Encoder Cable
Regenerative Resistor Connector <CN2>
Terminal
Mounting Hole
(Top, Bottom)
Regenerative Resistor
(400 [W]or Higher Attached)
Heat Sink
Wiring Socket
(6P, 4P and 3P) 3 Part
The following figure describes the model name on the nameplate of the servo
drive.
C S D 3 0 1 B X 2
Design Sequence
Mark Rated Output
A5 50 [W]
01 100 [W]
02 200 [W]
04 400 [W]
10 1 [kW]
15 1.5 [kW]
Mark Voltage
B AC220 [V]
The table below shows the capacity of drive (rated output) and the capacity of
the applied motor.
Drive Model Name Drive Capacity Capacity of the Applied Motor
1 CSD3-A3BX1 (P) 30 [W] 30 [W]
2 CSD3-A5BX1 (P) 50 [W] 50 [W]
3 CSD3-01BX1 (P) 100 [W] 100 [W]
4 CSD3-02BX1 (P) 200 [W] 200 [W]
Break Cable
Encoder Cable
Encoder
Nameplate of the
Motor
Motor Frame
Motor Shaft
Mounting Hole
The following figure describes the model name of the motor on the
nameplate.
The nameplate is attached to the motor. Check the model on the nameplate.
R S M Z - 0 1 B A 1 A N M 3
Rated Output
Voltage
Encoder Type
Design Sequence
Option
Manufacturer
Shaft Specification
Rated Output
A3 A5 01 02 04 ~ ~ 10 ~ 50
30 [W] 50 [W] 100 [W] 200 [W] 400 [W] ~ ~ 1 [kW] ~ 5 [kW]
Voltage
A B C D
AC 110 [V] AC 220 [V] DC 24 [V] AC 110/220 [V]
Encoder Type
Motor Model: CSMT/R, RSMS/D/H/F/K/L/Q/Z
Resolution/1 Encoder Type Resolution/1 Encoder Type
Mark Mark
Rotation Rotation
Q 131072 Serial Absolute Type R 131072 Serial Incremental Type
Reducer
The following figure describes the model name of the reducer on the
nameplate.
V R S F - 2 5 C - 2 0 0 - S P T
Mark Reduction Ratio
03 1/3 Mark Backlash Grade Mark Applicable Motor Mark Applicable Motor
Capacity Model
05 1/5 B 0.7° 030 30 [W] SPT CSM Motor
09 1/9 C 050 30 [W]
15 1/15 D 0.5°
~
Installation
Installation This chapter describes matters to consider when installing the servo drive and
the motor. Refer to the appendix for numerical data on the drive, motor, and
various peripheral equipment necessary for the installation.
Topic Page
Installation 2-1
Servo Motor
Precautions
Refer to the following figures when installing a motor.
A motor is a precision part. Pay an extra attention to the encoder, motor shaft,
and bearing.
A shock is the major cause of degrading Do not connect the motor to the
the performance of the motor. power directly.
Do not apply continuous stress on the The servo motor can be mounted
wire. vertically or horizontally
The oil is applied to the shaft to The ground wire of the servo motor
prevent it from rusting. Remove it must be connected to the grounding
before installing the servo motor. terminal of the servo drive.
Coupling Assembly
Avoid excessive instantaneous shocks.
An excessive shock during
the coupling assembly
damages the encoder.
Load Connection
Align the connection shaft of motor and load each other.
After assembling coupling, measure the concentricity of
the motor shaft and the load shaft. By rotating it at
intervals of 90 degrees, measure 4 positions and adjust it
so that the difference between the maximum and minimum
value is less than 0.03 [mm].
Installation Environment
Item Installation Environment
Storing Temperature Store it within -20 ~ 60[].
Operating Temperature Use it within 0 ~ 55[]
Operating Humidity Use it below 90[%] RH at a place without condensation.
Use it indoors with well ventilation, at a place for easy checkup and
Operating Environment cleaning, and at a place without explosive gas.
Servo Drive
Precautions
• The most important thing to consider when installing the drive is the ambient
temperature.
• Follow the operational temperature and mount the servo drive vertically.
Servo drive less than 400W applies the natural <Fixing Bolt>
convective cooling, and the servo drive with more 400 [W] or less : M4xL10
than 1kW uses the cooling fan. To increase the 2 mounting holes at the top
cooling efficiency, install it vertically & bottom
1 [kW] or more : M5xL10
2~4 mounting holes
depending on the capacity.
More than
50 [mm]
Pane
More than
50 [mm]
1. Installation Environment
Item Installation Environment
Storing Store it within -20 to 80 [°C].
Temperature
Operational Use it within 0 to 55 [°C].
Temperature
Operational Use it below 90 [%] RH at a place without condensation.
Humidity
Install a separate cooling device at a place with high ambient temperature and
use it within the operational temperature.
Use it indoors with well ventilation, at a place for easy checkup and cleaning,
and at a place without explosive gas.
Wiring
Introduction This chapter describes the information on motor, host controller and other
wiring connected to the servo drive, along with the circuit diagram.
Topic Page
Introduction 3-1
Electric Circuit 3-3
I/O Signal (CN1) 3-8
(CN1) Input Signal 3-11
(CN1) Output Signal 3-13
(CN1) Input Circuit and Interface 3-15
(CN1) Output Circuit and Interface 3-19
Encoder Wiring (CN2) 3-21
Wiringthe Battery (BATT) 3-31
General Articles Wiring 3-32
Before You Begin Pay attention to the following precautions when wiring.
In this chapter, the circuit is divided into electric circuit and signal circuit for
easier and convenient explanation.
Be fully aware of the names of each terminal when reading this user’s manual.
Signal Circuit
Optional Connector
<CN4>
Electric Circuit
Battery Connector
<CN5>
AC Power Terminal
• The I/O signal connector CN1, encoder cable connector CN2, and
NOTE
battery connector CN5 are included only in the description of the
signal circuit.
• The description of other connectors are omitted.
The terminal symbol is printed on the wiring socket at the electric circuit
terminal of the drive. Observe the drive to identify and understand the
terminals on the following table, and then wire accordingly.
Terminal L1, L2, L3 AC Power Terminal
Single phase 200 to 230 [V] (50/60 [Hz])
400 [W] or lower L3 port must not be used.
400 [W] or higher 3 phase 200 to 230 [V] (50/60 [Hz])
• The main power and control power can be divided when connecting to the drive. Therefore, the
user can configure surrounding circuits when the main power is cut off in an emergency or when
the drive itself checks the status and cuts off the power.
• If the drive independently checks the status and only the main power is cut off, but not the control
power, the drive can display the cause of cut-off of the main power. The user can take appropriate
action after identifying the cause of cut-off of the main power.
• Refer to the Chapter 3 for the Electric Circuit Diagram of the power separation.
The main power can be input by selecting either terminals (L1, L2 and L3) for the AC main power
terminal, or the terminals (DC- and P1) for the DC main power terminal.
Refer to the Chapter 4-8 for the selection method.
The initial setting is the AC main power input through the terminals (L1, L2 and L3).
When using the AC main power through terminals (L1, L2, L3), the terminals (P1, P2) can be used to
connect the DC reactor for RF control.
P1
External Equipment
P2
Drive
• When using the DC main power terminal for the main power
NOTE
supply, refer to the Chapter 4-8 for information on the setting of
main power input selection.
• If the terminals DC-, P1 and P2 are not used for ‘DC main power
input’ or ‘DC reactor for RF control’, do not remove the short circuit
wire of the terminals (P1 and P2) which is short circuit when
delivered.
POWER
MCCB (Molded Case Circuit Breaker)
1MCCB MC (Magnetic Contactor)
NOISE
FILTER 1MC 1MC For more than one second, press
<1> the Push Button S/W which allows
SW1 OFF SW2 ON Relay 1 SUP the current to flow when pressed.
<1> <2> Connect this if the power needs to
<3>
<2> be cut-off.
Relay 1 Alarm Display Lamp
Attach a surge suppressor to
<3> the MC relay coil.
ENTER
1MC
CHARGE POWER
L1 U Servo Motor
L2 V
Do not connect this to the drive
L3 W
with less than 400 [W].
L1C
This section describes the usage of wiring socket and lever provided
with servo drive.
• The peeled wire can be used. (Keep the length of the peeled core wire less than
8 [mm].)
• The use of phenol terminal is recommended for the reliability of wiring.
• Use a lever for wires provided with the product.
The following figure shows the sequence of assembling wire at the socket.
• As shown in the figure, insert lever in the socket and press it.
• Insert wire into socket and release the lever.
• Pull it slightly to check if the connection between the socket and wire is normal.
wire
Terminal
R
<Compress with the Phenol
Terminal Compressor>
Socket
Lever
(Keep the lenght of the peelde wire less than 8 [mm].)
NOTE The lever is a small tool, used when wiring. Keep it for other
wiring jobs.
This is the circuit diagram of a connector for I/O signal. It is divided into
input on the left and output on the right.
The Backup battery for absolute value encoder can be connected to (CN5) and
(CN1 49, 25). It must be connected to one side only.
Specifications
Pin #
Symbol Wire Color Electrical Features
1 Red
+24 [V] IN External 24 [V] input for contact point input.
2 Yellow
3 DI#1 Blue
4 DI#2 White
5 DI#3 Pink Pin for sequence input signal.
(Terminal input)
6 DI#4 Orange
7 DI#5 Gray Refer to the Chapter 5 for details.
23 AM-CH2 Yellow 3 Points Analog monitor CH2. -10 [V] to +10 [V].
24 - - -
25 BAT- White 3 Points Absolute encoder battery GND.
26 - - -
27 AM-SG Orange 3 Points Analog monitor output GND.
28 AM-CH1 Gray 3 Points Analog monitor CH1. -10 [V] to +10 [V]
29 EA+ Red 4 Points Encoder signal output.
30 EA- Yellow 4 Points (line drive output).
</G-SEL> Use 2 group gain where the input is on, and use
existing gain where the input is off. Convert 2 All 6-27
Gain group conversion types of gain groups.
</P-TL> If signal is ON, limit forward torque by the All
Limit forward torque setting of [Pr-4.03].
5-41
</N-TL> If signal is ON, limit reverse torque by the All
Limit reverse torque setting of [Pr-4.04].
<P-OT> If load mechanical part reaches the forward
Prohibit forward limit, this prevents the motor from moving PSC
operation further to that direction.
7-2
<N-OT> If load mechanical part reaches the reverse
Prohibit reverse limit, this prevents the motor from moving PSC
operation further to that direction.
Converts the speed controller from PI controller
</P-CON> type into P controller type. PSC 6-21
P/PI control conversion Used to provide better response performance by
prohibiting the overshoot in transient response.
</C-SEL> Combinational Control
Used to convert control mode when used as
Control mode Mode Only
combinational control mode.
conversion Refer to 5.6
Power
Signal Name Symbol Function Mode Reference
As control power input for contact point
External power +24 [V]IN signal, +24 [V] power should be prepared ALL
input by users.
Emergency Stop
Signal Name Symbol Function Mode Reference
Connect and use an extra emergency stop
Emergency Stop E-STOP switch to quickly act upon emergency ALL 3-17
situation,
Position Command
Signal Name Symbol Function Mode Reference
PULS+
Receives position command by pulse
PULS- input. Can respond to both line drive
Pulse command P
SIGN+ output and open collector output of host
controller. 5-9
SIGN-
Battery Connection
Signal Name Symbol Function Mode Reference
BAT+ Supplies the external battery power when
Battery input ALL 7-27
BAT- the absolute encoder is used.
/P-COM (+, -)
(Positioning It is ON when the position error is within the set value P
Completion of output width of position completion signal, [Pr-5.00],
detection) 5-23
/NEAR (+, -) It is ON when the position error is within the setting
(Position approach value of output width of position approach signal, P
detection) [Pr-5.01].
/V-COM (+, -) It is ON when error between speed command and motor
(Speed coincidence rotation speed is within the set value of output width of PSC 5-29
detection) speed coincidence signal, [Pr-5.02].
/TG-ON (+, -) It is ON when the motor rotates at speeds higher than
(Rotation All 5-35
the set value of rotation detection level, [Pr-5.03].
detection)
/T-LMT (+, -)
(Torque limit It is ON when it reaches the set torque limit. All 5-35
detection)
/V-LMT (+, -)
(Speed limit It is ON when it reaches the set speed limit. All 5-36
detection)
BK (+, -) Signal for the control of brake mounted internally or All 7-6
(Breaker control) externally on the servo motor.
/WARN (+, -)
(Warning It is ON if a servo warning is detected, All 8-4
detection)
• In this manual, < > is applied to the names of sequence I/O signal.
NOTE
• ex) </SV-ON>, </P-COM>
Alarm code
Signal Name Symbol Function Mode Reference
AL1
Upon servo alarm generation, it outputs
AL2 the types of the servo alarm with the 3-bit.
Alarm code ALL 8-4
AL3 Maximum rating of open collector :
DC 30 [V], 20 [mA]
AL-SG
Analog Monitor
Signal name Symbol Function Mode Reference
AM-CH1 Motor speed and torque, etc. are
Analog Monitor displayed for monitoring.
AM-CH2 ALL 7-25
Output
AM-SG Output range : -10 [V] to +10 [V].
Encoder signal
Signal name Symbol Function Mode Reference
EA+
EA- Displays multiplied encoder signal A, B, C
pulse in the form of line drive.
Encoder Signal EB+
Output EB- According to the parameter setting, the
drive can logically invert output of A, B ALL 7-21
EC+ pulse.
EC-
Servo alarm
Signal name Symbol Function Mode Reference
SALM+ It is displayed if the servo alarm is
Monitor Output ALL 7-25
SALM- generated.
(CN1) Input Circuit and Describes the connection circuit for input from the host controller to the servo
drive.
Interface
The drive receives the pulse output of host controller by position command in
position control mode.
• Host controller can output pulse in line drive or open collector type.
Select either of the two for use.
• Refer the Chapter 5-9 for the servo drive setting according to the
selection.
Input pin of CN1 that uses line drive and open collector output.
PULS +, PULS- (11, 12) SIGN +, SIGN- (13, 14) PCLR +, PCLR- (15, 16)
Line Drive
Vcc
Line Drive
R1 i 150[˟] 4.7[k˟]
P VF
By using the example at the bottom, set the value of Pull Up resistor R1 so that
the input current i is within 7 [mA] to 15 [mA].
Vcc of the Host Controller 24 [V] ± 5 [%] 12 [V] ± 5 [%] 5 [V] ± 5 [%]
R1 2.2 [kW] 1 [kW] 180 [W]
The drive receives analog voltage output of the host controller with speed, speed of
torque control mode and torque command.
• Input impedance of speed and torque commands is about 5 [M ].
• Maximum allowable voltage range of input signal is -10 [V] to +10 [V].
Input pin of CN1 that uses analog voltage output of the host controller
Speed command V-REF, V-REF SG (19, 20) Torque command T-REF, T-REF SG (21, 22)
V-REF -
12[V] 2[k˟] +
A/D
1000:1 P V-REF SG
CN1
Host Controller 0[V]
T-REF -
12[V] 2[k˟] +
A/D
P T-REF SG
1000:1
CN1
Host Controller 0[V]
Relay or open collector output of the host controller is used for the sequence input
circuit.
Relay Circuit
i +24[V]IN 3.3[k˟]
DC24[V] 50[mA]
or Higher P
CN1
Sequence Input Signal
Host Controller (DI#1 to DI#7)
This drive has a built-in circuit for the emergency stop situation.
• To quickly respond to the equipment failure or dangerous situation, it receives
the emergency stop signal from #10 pin of CN1.
• Emergency stop input can be done by the relay contact output of host
controller and installing a separate switch.
#10 pin of CN1 assigned below is used as the input pin only for the emergency
stop.
Normal Operation
External Power 24[V]
+24[V] IN 1/2
E-STOP 10
E-STOP Switch
E-Stop
External Power 24[V]
+24[V] IN 1/2
E-STOP 10
E-STOP Switch
CN
Install a host controller 1
or a separate switch.
• You can check the status of emergency stop signal through the
NOTE
monitor mode describe in the Chapter 7-50.
(CN1) Output Circuit and There are 3 types for the servo drive output circuits. Design the input circuit at
the host controller suitable for the each output circuit.
Interface
Line Drive Output
Output signal (EA+, EA-, EB+, EB-) that converted the encoder serial data
into 2 phase (A phase and B phase) pulse, zero point pulse signal (EC+, EC-)
and S phase rotation amount signal (PS+, PS-), are output to line drive circuit.
It is used to configure the position control loop from the host controller.
Receive the pulse signal with the line receiver circuit in the host controller.
Set R1 value to 330 [Ω].
P R1
CN1
0[V] Host Controller
DC 5 to 12 [V]
Photo-Coupler
P
0[V]
CN1
0[V] Host Controller
DC 5 to 12 [ V ]
Line Receiver
P
0[V ]
CN1
0[V]
Host Controller
DC 5 to 12 [ V ]
Relay
P
DC 5 to 24 [V]
Relay
P
CN1 0[V]
Host Controller
DC 5 to 12 [V]
Line Receiver
P
CN1 0[V]
Host Controller
The table below shows the pin arrangement for each encoder.
DRIVE MOTOR
CSMT
CSM CSMS/D/H/K RSMS/D
RSMQ CSMR
CSMT RSMS/D/H RSMH/F
RSMZ RSMQ
PIN CSMR RSMF/K/L RSMK/L
FUNCTION RSMZ
NO.
17bit 17bit
9 wire 15 wire 9 wire 9 wire 15 wire
ABS. ABS. ABS. Serial Serial
INC. INC. INC. INC. INC. Abs./Inc. Abs./Inc.
1 E0 [V] 8 14 14 11 14 G G G 8 G
2
3 A 1 1 1 1 1 A A A
4 /A 2 2 2 2 2 B B B
5 B 3 3 3 3 3 C C C
6 /B 4 4 4 4 4 D D D
7 C 5 5 5 5 5 E E E
8 /C 6 6 6 6 6 F F F
9
10 U 7 7 11 K K 4 K
11 RST 9 9 R
12
13 /U 8 8 12 L L 5 L
14 V 9 M
15 /V 10 N
16 W 11 P
17 /W 12 R
18 BAT+ 11 7 T 1 T
19 BAT- 12 8 S 2 S
20 E5 [V] 7 13 13 10 13 H H H 7 H
Frame 10 10
9 15 12 J J J 3 J
FG 15 15
The table below shows the terminal type and specifications of the encoder
cable.
<Encoder Cable>
CON A. CON B.
3 B 5 31 EB
P P
4 /B 6 32 /EB
5 C 7 33 EC
P P
6 /C 8 34 /EC
7 E5[V] 20
SG
P
8 E0[V] 1 27 0[V]
0[V]
9 FG 12 50 FG
5 C 7 33 EC
P P
6 /C 8 34 / EC
P P
8 / RX 13 36 / PS
9 RST 11
11 BAT + 18
SG
P
12 BAT - 19 27 0 [ V]
0[ V]
13 E 5 [ V ] 20 49 BAT +
P P
14 E0 [ V] 1 25 BAT -
DC 2.8 ~ 4.5 [ V]
15 FG FG
5 C 7 33 EC
P P
6 /C 8 34 / EC
P P
8 /U 13 36 / PS
9 V 14
10 P /V 15
11 W 16
SG
P
12 /W 17 27 0 [ V]
0[ V]
13 E 5 [ V ] 20 49 BAT +
P P
14 E0 [ V] 1 25 BAT -
DC 2.8 ~ 4.5 [ V]
15 FG FG
P P
D /B 6 32 / EB
E C 7 33 EC
P P
F /C 8 34 / EC
H E 5 [ V ] 20
SG
P
G E0[ V] 1 27 0[ V]
0[ V]
J FG FG
P P
D /B 6 32 / EB
E C 7 33 EC
P P
F /C 8 34 / EC
P
L /U 13
M V 14
P
N /V 15
P W 16
P
R /W 17
H E 5 [ V ] 20
SG
P
G E0 [ V] 1 27 0 [ V]
0[ V]
J FG FG
E C 7 33 EC
P P
F /C 8 34 / EC
P
L /U 13
R RST 11
T BAT+ 18
P
S WT
BAT-
A
AT 19
H E 5 [ V ] 20
SG
P
G E0 [ V] 1 27 0 [ V]
0[ V]
J FG FG
P P
L SD - 13 30 / EA
Up/Down
H E 5 [ V ] 20 counter
31 EB
G P P
E 0 [ V] 1 32 / EB
T BAT + 18 33 EC
P P
S BAT - 19 34 / EC
SG
27 0 [ V]
0 [ V]
49 BAT +
P
25 BAT -
DC 2 . 8 ~ 4 . 5 [ V ]
J FG FG
P P
4 /B 6 32 / EB
5 C 7 33 EC
P P
6 /C 8 34 / EC
P P
8 BAT - 19 36 / PS
9 RST 11
10 FG
SG
11 RX 10 27 0 [ V]
P 0[ V]
12 / RX 13 49 BAT +
P
13 E 5 [ V ] 20 25 BAT -
P DC 2 .8~ 4 .5[ V]
14 E0 [ V] 1
15 FG FG
P P
2 /A 4 30 / EA
Up/Down
counter
3 B 5 31 EB
P P
4 /B 6 32 / EB
5 C 7 33 EC
P P
6 /C 8 34 / EC
P
36 / PS
SG
27 0 [ V]
0[ V]
49 BAT +
P
10 E 5 [ V ] 20 25 BAT -
P DC 2 .8~ 4 .5[ V]
11 E0 [ V] 1
12 FG FG
P P
5 SD - 13 30 / EA
Up/Down
E 5 [ V ] 20 counter
7 31 EB
P P
8 E 0 [ V] 1 32 / EB
1 BAT + 18 33 EC
P P
2 BAT - 19 34 / EC
SG
27 0 [ V]
0 [ V]
49 BAT +
P
25 BAT -
DC 2 . 8 ~ 4 . 5 [ V ]
3 FG FG
<2>
<1>
Procedure
General Articles Wiring This part describes wiring to implement optimum performance of the servo
drive in wiring and noise.
Precautions
Electric Circuit
• Use a thick wire as earth wire if possible.
• Class 3 grounding is recommended. (Recommendation: grounding resistance
lower than 100Ω).
• Only 1 point must be grounded.
• Select ground phase and ground point considering the power conditions of
installation area. If the power is supplied by the ground phase, wire it so that L2
of AC main power input terminal (L1, L2, L3) becomes the ground phase.
• Use noise filter for the main power and control power.
• Electric circuit wiring and signal circuit wiring should be apart as much as
possible. (30 [cm] or more)
• Do not use same power with the electric ARC welding machine or discharge
processor equipment.
• The earth wire of the servo motor must be connected to the grounding
terminal of the drive. In addition, ground the grounding terminal of the drive.
• If the wiring is inside the metal pipe, ground the pipe with class 1 grounding.
Signal Circuit
• The host controller should be installed as closely as possible to the drive, and
the noise filter must be used.
• CN1 (I/O signal connector) and CN2 (encoder cable) should be twist pair wire
and batch shield wire. (Refer to the appendix for the Samsung's standardized
parts.)
• Note that the signal circuit wire is very thin, thus pay attention when handling
it.
• If the noise is generated at command input cable, ground 0 [V] line (SG) of the
input line before the usage.
Others
• Use the breaker or fuse for wiring to protect the servo drive.
• Make sure there is no continuous bending and stress to the wire.
• Use noise filter in radio noise.
• If used around residential area or the radio disturbance is concerned, install a
noise filter on the input side of power line.
• As the drive is for industrial use, there are no measures for radio disturbance.
• Attach a surge absorption circuit to the relay, solenoid, and coil of the magnetic
contactor.
The table below shows the capacity of servo drive and fuse.
The fuse capacity is the value when 100 [%] load is applied. When selecting the MCCB (breaker for
wiring) or fuse capacity, select the fuse capacity considering the load ratio.
Cut-off features : 200 [%]-2 seconds or more. 700 [%]- 0.01 second or more.
The high -speed cut-off fuse can not be used. As the power of the
NOTE
drive is condenser input type, the fuse may be blown even during a
normal situation if the high-speed cut-off fuse is used
Noise Protection
The high-speed switching device and microprocessor are used at the main
circuit of the servo drive. Thus, switching noise is affected by the connection
and grounding methods. Use the proper wiring and grounding method to
prevent any affects from the noise.
Use a wire of 3.5 [mm2] or thicker for the earth wire.
LINE FILTER
1
LINE
FILTER AV
P P P
2 R
L
1
L
2 CN1
L
3
L1C
U Servo Motor
L2C
V
Heat Sink
P
CN2 M
G
Ground Plate
One Point Grounding<Class 3 Grounding or Higher>
Earth Grounding
Extra caution is required when wiring the noise filter. The following figure
describes precautions when wiring the noise filter. If the wiring is wrong, the
performance of the noise filter falls.
• Separate the input and output wiring of the noise filter and do not tie
up them together.
Secondary
Primary
Filter
Secondary
Primary
Filter
Secondary
Secondary
Primary
Primary
Filter Filter
Separation of Separation of
Circuit Circuit
Secondary
Primary
Primary
Filter Filter
• Earth wire of noise filter should be solely attached in the earth plate.
Do not connect the earth wire of the noise filter to other earth wire
together.
Secondary
Secondary
Primary
Primary
Filter Filter
• If there is noise filter inside the case (panel), connect all of the earth
wires and earth wires of other equipment inside of the case to the
grounding plate. And then, ground them.
Secondary
Primary
Filter
ٻ
1MCCB
1MC
+24[V]
L1 CN1 Relay 1
SALM+ 45
L2
SALM- 46
L3
L1 CN1
SALM+ 45
L2
SALM- 46
L3
L1 CN1 0[V]
SALM+ 45
L2
SALM- 46
L3
y z {
AC 220 [V] Power
MCCB
Breaks the circuit if large
inruch current flows on
power line.
Noise Filter
Regenerative Magnetic
Resistor Contactor
ih{{
Battery
sX
sY
sZ juX
sXj Host
sYj Controller
u
wX
wY
iX
iY
|
Magnetic Contactor }
for the Motor Break ~
Control
juY Encoder Cable
Motor Cable
Brake Cable
Motor Brake
juZ
Control Power
Motor Break
Control Servo Motor Portable Operator
Introduction This chapter introduces the operator mounted on the servo drive. In addition,
it describes the basic setting of servo drive, and also an example for simple
startup.
Topic Page
Introduction 4-1
Before You Begin 4-2
Operator 4-6
Basic Setting 4-13
Startup 4-22
This part describes Servo-ON signal for the control of the servo drive.
What is Servo-ON?
Audio or TV can select and play music and display channel that the users want
from the moment the power switch is on.
However, the servo drive cannot run servo motor by simple applying the
power. To complete load the system and use the servo drive, Servo-ON signal
from the host controller is required.
Servo-ON signal should be applied and maintained from the host controller
for the servo drive to run the motor. In servo -OFF status, it cannot run the
motor.
• If the servo-ON signal is not applied after the • If the servo-ON signal is applied from the
power application, it is same as the servo host controller, the drive starts to apply
driver and motor being separated completely. voltage to the motor. At this time, if there is
no motor run command, the drive maintains
• This is a ready status to run the motor. the motor stopped.
Power Power
/SV-ON
Input of commands such as position, speed regarding servo-ON status and motor run.
• If the motor run command is input while the servo-ON signal of the host controller is maintained,
the drive can run the motor according to the command.
Power
/SV-ON
Input of command
such as position,
speed.
Motor
< Rotation >
• Refer to the Chapter 7-35 for the operation mode (run-00) to (run-02).
• Refer to the Chapter 8-6 for the information of the servo alarm.
• All parameter setting after Chapter 4-1 should be done for the
NOTE
Servo-ON status and Servo-OFF status.
• In this manual, ‘the servo drive status’ means whether the servo
drive is in servo-ON status or servo-OFF status.
Parameter Name
Parameter Setting Window Initial Value
0
Setting Value
1
Applicable Mode ALL Others Servo-OFF > Setting > Power Off & On > End
Table Description
• The setting window on the right of the parameter, is entered when the
ENTER key is pressed. The parameter must be set from the digit in
black color and the initial value shows the initial value of the parameter.
• <Setting value> Describes the value selectable by the user and the
selected value.
Others Description
Setting > End Set regardless of the drive status.
Servo-OFF > Setting > End Set it in Servo–OFF status.
Servo-OFF > Setting > Power Off & On > Set it in Servo-OFF status, and apply the power again.
Completion
The servo drive has a built-in operator for various status displays, parameter
setting, operation command, and monitoring.
• Distinguish the type of the servo drive according to the front design of
the operator.
• The following figure shows the front side of the operator on the servo
drive.
7 2
All-In-One
6 MODE
SET 3
5
ENTER 4
CHARGE POWER
Main Power Check and Checks if the main power is applied, and if the capacitor of
5 Discharge Check Lamp the main circuit is discharged after the main power cut-off
Moves the digit of 7-segment LED display and functions as
6 Top, Bottom, Left/Right Key the UP/DOWN of the number.
As shown in the figure below, the servo drive is divided into 4 types of control
modes:
• The mode displayed after the power ON is the status display mode.
• Be fully aware of the following 4 mode types and read the following.
Power
Connection
Monitor Mode
• All parameter setting after Chapter 4-1 should be done for the
NOTE
Servo-ON status and Servo-OFF status.
• In this manual, ‘the servo drive status’ means whether the servo
drive is in servo-ON status or servo-OFF status.
Row
Display 1
Row
Display 2
Row
Control Mode Status Point Display Display 3
Display Description
Description
Point It is on if the power is applied.
Display
Refer to the reference pages on the right for more information on the row
display.
Description Reference
When using as a position mode, if the difference between load position
and position command is smaller than [Pr-5.00] value, the servo drive 5-23
can display (</P-COM> position completion detection) signal. It is on
Row when </P-COM> signal is displayed.
Display 1 When using as a speed mode, if the difference between motor speed
and speed command is smaller than [Pr-5.02] value, the servo drive can 5-29
display (</V-COM> speed coincidence detection) signal. It is on when
</V-COM> signal is displayed.
Row When the rotation speed of the motor is higher than the setting value of
rotation detection level [Pr-5.03], the servo drive can display (</TG-ON> 5-35
Display 2 rotation detection) signal. It is on when </TG-ON > signal is displayed.
Row It is on when Z-pulse output of the encoder is detected.
Display 3
• The Parameter sets and saves various functions to make drive suitable
for equipment.
• There is a parameter that can be always set regardless of the status of the
drive, and those that must be in certain status of the drive when setting
them. Be careful to set parameter in reference to the contents in the
Chapter 4-2.
From To
• The table below shows the brief contents of each item in the monitor
mode.
From To
• The item of the monitor mode, whose value is more than 6 digits,
NOTE
is not displayed at once by the 6-digit 7-segment LED display.
• Refer to the Chapter 7-50 for details on how to check such items.
• The table below shows the brief functions of each item in the operation
mode.
From To
Refer to the Chapter 7-35 for details of operation mode and key button
NOTE
manipulation.
Basic Setting This section includes the introduction of the control mode and the basic
setting.
As shown below, the basic setting uses three parameters to set 3 types.
Basic Setting Parameter Setting
Motor setting
Motor type setting
2 Motor capacity (rated output) setting
Encoder type setting
y z t W X i h X h u r y
Motor Type Rated Output Encoder Type
GG
• The drive has another drive exclusively for the position control. For this
drive, there is no need for a separate control mode selection. (Refer to
the Chapter 1-7)
• The table below shows the control mode types. Refer to the chapter 5
for function for each control mode.
Precautions
The following are the precautions in setting associated control mode.
• If the setting is correctly entered, the setting window blinks once when
MODE/SET key is used to save the data. However, if wrong setting is
entered, it does not blink nor is saved.
Motor Setting
Select a motor to connect to the servo drive and set three items of the motor.
C S M T 0 1 B A 1 AN T 1
Motor Type Rated Output Encoder Type
Motor Type
Motor types of the servo motor are indicated in 4 digits, and the code starts
with CSM for all motors. Thus, the first 3-digit, CSM, is omitted in the display
of the motor.
CSMS RSMH
Rated output (capacity) and display of the motor are shown below.
Display Capacity Display Capacity Display Capacity
Encoder Type
In encoder type setting, serial absolute encoder whose encoder type is Q and E
type transmit encoder data to the drive and automatically performs setting as it
is connected to the drive.
The encoder type display is shown below.
Number Number
of Pulse/
Display Encoder Type Display of Pulse/ Encoder Type
1 1 Rotation
Rotation
Full
2048
2048 9wire Inc. Absolute
Motor Series: RSMS/D/H/F/K/L
Compact
2048 10000 15wire Inc.
Absolute
Precautions
Setting sequence is in order of motor model, rated output (capacity), and
encoder type. The encoder type is classified into group 1 and group 2,
according to motor model, and an encoder that corresponds to each motor
type is displayed. In addition, only the rated output of the motor that
corresponds to the type selected is displayed only.
A setting example of an encoder in the encoder type 1 is shown in the
following motor setting flowchart.
Find setting value from the setting items suitable for each digit.
to
sX
AC Main Power Input. sY
sZ
u
DC Main Power Input.
wY
For the use of DC voltage by connecting the
main power to the terminals N and P2
Set Parameter
to
Setting Range Initial value Unit Others Servo OFF > setting > completion
20 to 1000 20 [msec] Mode ALL
Set the time to process the temporary power down by the servo alarm.
If main power is not input within the set time, it generates temporary power down servo alarm
(E.AcoFF). Refer to the chapter 8.2.2.
The servo drive does not verify the status of temporary power down in
NOTE
case of using DC main power input terminal with input of main power
from [Pr-0.02].
• Setting is on the fourth digit of the setting window. Make sure to use the
correct digit.
End
Basic setting is all finished for the use of the drive. Reapply the power.
• To connect other motor type after completing the basic setting of motor
connected to the servo drive initially, or to change the parameter setting
at the basic setting, be sure to enter into corresponding parameter and
change it.
• Basic setting value is preserved even if the power is cut off or the
parameter is initialized (Refer to the Chapter 7-48). (But, the main power
input selection is initialized by the parameter initialization)
1. Be well aware of wiring in Chapter 3 and connect main power and control
power normally. In addition, by configuring emergency stop input circuit,
clear the emergency stop status.
2. Connect the motor and encoder properly.
3. Perform basic setting in reference to the Chapter 4-6
4. Do not connect the load to the motor for safety purposes. If the motor is
mounted on the equipment, remove coupling of the motor shaft so that
load may not move.
Startup
• The speed of the motor can be set from the drive for the jog operation.
• At startup 1, run the drive at the factory setting speed, 500 [rpm].
Turn Power On
The motor runs counter clockwise The motor runs clockwise w hile
w hile pressing the U P key. pressing the DOW N key.
Pree MODE/SET key and
clear JOG-OFF o peration.
• Start up the drive by changing the speed from the initial value, 500 [rpm]
to 1000 [rpm].
End
• If setting is wrong, the setting window does not blink when saving it by
pressing the MODE/SET key.
• You can see that the speed is changed from 500 [rpm] to 1000 [rpm].
NOTE • At first, the drive is not tuned suitable for the load or
motor.
You can check the servo motor status and the motion of the system whether
they occur noise or vibration or not during the jog operation.
If noise and vibration occur from the servo motor, perform off-line
NOTE
autotuning by referring to the Chapter 7-25. Then, you can run the
motor more smoothly in a stable condition.
Introduction This chapter describes the sequence input/output function of I/O signal
connector CNI and the function for each control mode.
Topic Page
Introduction 5-1
Sequence I/O (Input/Output) Signal 5-2
Position Control Mode 5-9
Speed Control Mode 5-28
Torque Control Mode 5-38
Multi-Step Speed Mode 5-45
Combinational Control Mode and </C-SEL> Function 5-50
• Input provides 16 functions and you can freely allocate input signal of
each function with 7 pins from CN1 No. 3 to CN1 No. 9.
• Output provides 8 functions and you can freely allocate output signal of
each function with three pairs of pins such as (41, 42), (43, 44) and (47,
48) of CN1.
Sequence I/O signal means the I/O signal of various functions that are
required for servo drive control by the host controller.
Sequence I/O signal is not to process input or output signal with the
designated pin of CN1, but to select the function that the user requires in
terms of circuit design of host controller and to directly allocate the selected
functions to the designated pin.
Therefore, the host controller can do the sequential control that fits to the
equipment to operate servo drive.
The following figure is sequence I/O part among 50 pins of CN1.
0 [ V] 2
41
DI # 1 3 DO # 1 +
P
42
DI # 2 4 DO # 1 -
43
DI # 3 5 DO # 2 +
P
44
DI # 4 6 DO # 2 -
47
DI # 5 7 DO # 3 +
P
48
DI # 6 8 DO # 3 -
DI # 7 9
• The sequence I/O signal name is indicated by < > in this manual.
NOTE
• ex) </SV-ON>, </P-COM>
Refer to the table below to allocate to CN1 pin by searching the function that
is suitable for your condition.
Setting Value
Input Channel No. Always DI#7 DI#6 DI#5 DI#4 DI#3 DI#2 DI#1 Always
CN1 Pin No. valid 9 8 7 6 5 4 3 invalid
• For example, if you want to put certain function to CN1 No. 5 pin, you
can find the related parameter of that signal and the position in the
setting window according to the table below and enter ‘3’ as the setting
value.
• If you want to make input signal ON all the time regardless to the
wiring, set ‘8’.
The following table is to arrange the parameter for each function and
7-segment number position in the setting window. Set so that the related
parameter of each signal and the number position in the setting window is not
in the wrong.
7-Segment 4th Position 3rd Position 2nd Position 1st Position
Enter ‘7’ in the 4th position in setting window of the parameter [Pr-0.05].
This is to use </P-CON> function and it means that the CN1 No. DI#7 pin is
used as an input pin.
Enter ‘3’ in the 3rd position in setting window of the parameter [Pr-0.08].
This is to use </G-SEL> function and it means that the CN1 No. DI#3 pin is
used as an input pin.
Enter ‘8’ in the 1st position in setting window of the parameter [Pr-5.09].
Refer to the table below to allocate to CN1 pin after searching the function
that is suitable for your condition.
Setting Value
Set the setting value as ‘0’ when the output of the related signal is not used.
The following table is to arrange the parameter for each function and
7-segment number position in the setting window. Set so that the related
parameter of each signal and the number position in the setting window is not
in the wrong.
7-Segment 4th Position 3rd Position 2nd Position 1st Position
Set ‘1’ in the 1st position in setting window of the parameter [Pr-0.09].
It is set to use </P-COM> function and it means that we will use CN1 No.
DO#1 pin as output pin.
Set ‘3’ in the 4th position in setting window of the parameter [Pr-0.10].
It is set to use </G-SEL> function and it means that we will use CN1 No.
DO#3 pin as output pin.
Sequence output signal is outputted when the situation that fits to the
NOTE
condition of each output. Therefore, related to sequence output signal
allocation, there is no setting value that is output always regardless of
wiring such as setting value '8' for input signal.
When you allocate the different functions to the same pin of CN1 as shown
below, the drive indicates servo warning in the status mode.
It is set to use </N-TL>function and it means that CN1 No. DI#4 pin
is used as an input pin.
In this case, when you reapply the power after completing the
Status Display Mode input allocation, the status display mode indicates servo warning
(Pin).
Check if you allocate more than two signals to the same pin of
CN1.
Through monitor mode in the 7-50, you can check if the sequence I/O
NOTE
signal is input.
E-STOP lamp (Emergency stop) uses the fixed input pin of CN1
NOTE
contrary to sequence input according to the allocation.
SALM +,- lamp (Servo alarm) uses the fixed output pin of CN1 in
contradiction to sequence output according to the allocation.
The position control mode is used when the position command pulse is
received from the host controller to move the load to a target position.
To operate the servo drive in position control mode, connect the position
command pulse signal to PULS and SIGN input pins, connect other necessary
input signals such as PCLR signal, and set as follows.
Set the position command pulse and signal type according to the host
controller output. [Pr-3.00]
Tune the servo drive by adjusting the gain according to the load condition.
The following figure illustrates the standard wiring example of position control
mode. You can set the sequence input/output signal, as you want if it is
necessary for the system configuration.
DC + 24 [ V]
+ 24 [ V] IN 1 28 Analog Monitor CH1
D/ A Output Range : -10 [V] to +10[V]
0 [ V] 2 23 Analog Monitor CH2
Sequence Input Circuit Output Range : -10[V] to +10[V]
27
AM-SG Alarm Code Output GND
Recommended Setup Furction 37
AL 1
Servo Alarm Code
Servo-ON / SV - ON DI # 1 3 38 Maximum Voltage: DC 30[V]
AL 2
Prohibit Forward Rotation P- OT Maximum Voltage: 20 [mA]
DI # 2 4 39
AL 3
Prohibit Reverse Rotation N- OT DI # 3 5 40
AL - SG Alarm Code Output GND
P-Control Conversion / P- CON DI # 4 6 29
EA +
Alarm Reset / A- RST P
DI # 5 7 30
EA -
Reverse Torque Limit / N - TL DI # 6 8 31 Encoder Phase A, B & C
EB +
Forward Torque Limit / P- TL P
DI # 7 9 32 (Line Receiver SN75175
EB - or MC3486)
33
EC +
P
E- STOP 10 34
EC -
Input for Pos ition Mode 35
PS + Absolute Encoder
P
PULS+ 11 36 Rotation Data
PS -
P
Connect to Line Position PULS- 12
17
drive of upper Command / Z - PULSE +
SIGN+ 13 Encoder Phase Z
level controller P
18 / Z - PULSE - OPEN Collector
or Open P
SIGN- 14
collector 45
SALM +
PCLR+ 15 P Servo Alarm
Position 46
Error Clear P SALM -
PCLR- 16
41
DO # 1 Position Completion
P
V- REF 19 42 Singal Detection
External Speed Limit DO # 1 -
-10[V] to +10 [V] P A/ D
V- REF SG 20 43
DO # 2 + Position Approach
P
44 Singal Detection
DO # 2 -
47
DO # 3 +
P Rotation Detection
BAT + 49 48
Back-up Battery DO # 3 -
For Absolute Encoder P
BAT - 25 24 26 50 Output Recommended
DC 3.6 [V] Channel Setup Function
X X X
Sequence Output
Circuit
• Host controller sends the position command with the pulse input and
sign input.
• To clear the position error to ‘0’, send the PCLR command. Refer to the
Chapter 5-21 for details on PCLR.
w| szR XX
Position Command Input
Pulse Input w
w| szT XY
zpn uR XZ
Pulse Input w
zpn uT X[ j uX
When the position control mode is used, there are line drive method and open
collector method as the input types of the host controller. The servo drive
supports two types of input.
The output of host controller
Connection ex.1: When it is line drive output (maximum allowable frequency
900 [kpps])
Cautions
In the figure above, when it is open collector method and TR1 of host
controller is ON, the servo drive identifies as low level input logic and if TR1 is
OFF, the servo drive identifies as high level input logic.
In addition, set the Pull Up resistor R1 value to be within 7 [mA] to 15 [mA] by
referring to the application example below.
Vcc of Host Controller 24 [V] ± 5 [%] 12 [V] ± 5 [%] 5 [V] ± 5 [%]
R1 2.2 [kW] 1 [kW] 180 [W]
NOTE • When you use open collector method for the output of
host controller, it is recommended to use 24 [V] for
Vcc. In doing so, the operation is stable even in the
environment with serious noise problem.
Set the position command pulse type for the host controller.
Positive Logic
Command Forward Direction Reverse Direction Input Setting
Pulse Form Operation Operation Multiplication Value
w|sz IsI
w|sz
CW + CCW -
zpnu
zpnu IoI
Pulse Train + -
Sign
`W⓸
Phase A + Duple
Phase B w|sz
zpnu
Quadruple
Negative Logic
CW + CCW -
Pulse Train + -
Sign
You can verify the data related to the position through monitor mode
NOTE
in the Chapter 7-50.
Maximum
Command Electrical Specification Allowable
Pulse Form Frequency
t1 t2 t3
CCW
T
CW
+ CW
CCW
Forward Operation Command Reverse Operation Command
t3 t7
Line Drive:
SIGN 900 [Kpps]
T
Pulse Train
+ Sign
PULS Open
t4 t1 t2 t5 t6 Reverse Operation Collector:
Forward Operation Command Command 200 [Kpps]
t1, t2, t3, t7 0.1 [us] t4, t5, t6 > 3 [us] τ 1.1 [us]
t1 t2
Phase A PHASE A
T
2 Phase
Pulse Train
of 90 Phase B
Difference PHASE B
(A, B Phase) Reverse Operation
Forward Operation Command Command
Electronic Gear
Electronic gear
The electronic gear is to set the amount of load movement per input
command pulse.
The following is the example of Encoder that generates 2048 pulses per
rotation.
• Encoder that the number of pulse is 2048, rotates once when the host
controller transfers 2048 pulses to the drive. Then, is it possible to make
a motor rotate once as transferring 1000 pulse (or other number of
pulse)? (Yes, it can)
• Let's suppose that the ball screw load is operated by the pitch (Unit of
load to be moved per rotation) with 15 [mm]. When the host controller
transfers 2048 pulses, the load moves 15 [mm]. For easier calculation, is
it possible to move one pitch (15 [mm]) with 1500 pulses? (Yes, it can)
• When you want to control the accurate angle using the servo drive, and
if you control 360 degree with 2048 pulses, the number of pulse and the
moving unit of the last mechanical part are different. So it is difficult to
calculate.
• Therefore, the electronic gear is set for easier calculation of the input
pulse of the host controller in respect to the distance or angle that is the
moving unit of last mechanical part.
• When you use the electronic gear, the host controller can control
without considering the number of pulse of the encoder or the
reduction ratio of mechanical part.
Reduction ratio
For the reduction ratio that is mentioned in electronic gear setting, refer to the
explanation below.
The reduction ratio that is mentioned in electronic gear setting is the rotation ratio of motor and end
mechanical part.
When the mechanical part rotates once while the motor rotates 5 times, then the reduction ratio is ‘5’.
When the device part rotates 5 times while the motor rotates once, then the reduction ratio is ‘0.2’.
Example 1
Ritch of ball Screw
(Linear Movement Distance Per Rotation) 10[mm]
• Ball screw is applied to the load above and the pitch is 10 [mm].
As a result, the ball screw rotates once with 10000 pulses, so the ball screw
with the movement pitch of 10 [mm] moves 1 [um].
Precautions
When you set up the denominator as 10000, the ball screw moves 1 [um] per pulse of the host
controller so that it shows better resolution than set with 1000.
If so, can you realize much better the resolution is if the denominator is set as 50000? No, you cannot.
The resolution of the encoder that is selected is 5000. So the electronic gear has to satisfy the
following formula because it is set according to the selected encoder.
Therefore, the example 1 above can make a motor rotate with maximum of 20000 pulses from the
host controller.
• This chapter explains the electronic gear setting for a belt load with the
reduction ratio.
Example 2
• For the ball screw in the example 1, you can easily recognize the pitch
through the ball screw specification, but you cannot find the load pitch
that consists of belt and pulley. Therefore, let's suppose that the distance
we want to move is 100 [um] per pulse from the host controller.
• Let's suppose that the number of pulse of the encoder is 2048 [pulse]
and the reduction ratio is ‘5’.
Rotate the pulley of the final mechanical part once with the 1570 pulses from the host controller.
In this case, the linear moving distance of the final load per pulse from host controller is 100 [um].
You can enter the numerator and denominator by reduction of fraction as the following.
Example 3
Desired rotation distance per one pulse
Rotation from host controller = 0.1 [degree]
Load
• Let's suppose the distance we want to rotate per command pulse from
the host controller is 0.1 [degree].
• Let's suppose that the number of pulse of the encoder 2048 [pulse] and
the reduction ratio is '3'.
Rotate the turntable load of the end mechanical part once with the 3600 pulses from the host
controller.
In this case, the rotation angle of the final load per pulse from host controller is 0.1 [degree].
The electronic gear is applied only when the position control mode is used.
You can easily adjust the distance or the angle of pulse command and load from the host controller by
setting the electronic gear.
You should check two things below when setting the electronic gear.
NOTE
• Check the number of pulse of encoder. Refer to the Chapter 4-7.
• Check the reduction ratio that is applied from shaft to the end
mechanical part.
Initial
Setting Range Unit Others Servo-OFF > Setting > End
value
Applicable
1 to 65535 Automatic [pulse] P
Mode
Initial
Setting Range Unit Others Servo-OFF > Setting > End
value
Applicable
1 to 65535 Automatic [pulse] P
Mode
The number of position command pulse of the host controller to rotate the load
(Load shaft) once
Setting value of the electronic gear should satisfy the following relationship.
• [Number of pulse per rotation of motor] x [Reduction ratio] x 4 [Setting value of Pr-3.02]
• If the relationship above is not formed, you can use it as pulse command but the resolution is not
guaranteed.
Maximum resolution is
If the setting value of [Pr-3.02] does not satisfy the relationship above,
• Reduce the distance or angle needs to be moved with one command pulse. (=reduce the
resolution)
• Use the high-resolution encoder, which outputs the number of pulse higher than the value set in
[Pr-3.02] divided by 4, or increase the reduction ratio.
If this signal is inputted, the position command, position error, and encoder
feedback counter (dIS-23) are cleared to '0'. If the position command pulse is
not inputted any more, the motor can be stopped from the current state. Input
the Position Error Clear (PCLR) signal to (15,16) pin of CN1.
In the parameter below, set the parameter for the signal trigger condition to
clear the error to '0' in position error clear input.
Select the trigger condition in the following parameter.
It clears in H level.
0 Position error maintains ‘0’ as long as the H level is "H"
maintained.
The position command counter can be stopped in the position control mode
by setting the pulse command inhibition</INHIB> by the sequence input
signal.
While </INHIB> input is ON, it is ignored even though the host controller
sends the position command pulse to the servo drive.
Therefore, it locks the servo status in the current position. If </INHIB>
signal is ON/OFF while the host controller continuously sends the position
commands, the following operation occurs according to the </INHIB> signal
status.
In the figure below, Td is about 10 [msec].
Position
Command
Position
Command
Counter Td Td
When the electronic gear ratio needs to be changed in position control mode,
the </GEAR> input can be used to switch from the first group of gear
parameters to the second group of electronic gear parameters in Pr-3.05 and
Pr-3.06. When the </GEAR> input is OFF, the first group of electronic gear
parameters in Pr-3.01 and Pr-3.02 will be used. The Details of the newly added
second group of electronic gear parameters are shown below.
Parameter
Parameter change the setting method of eletronic gear parameters Pr-3.01 and Pr-3.02
Name
0 - Change eletronic gear parameters only when Servo-OFF
Setting value 1 - Change eletronic gear parameters no matter what Servo-OFF or Servo-ON
Initial value 0
Mode P
Misc. Servo-OFF > Setting > Complete
Parameter
Parameter
between position feedback and position command is less than Setting value,
the position completion signal detection </P-COM> can be output.
Initial
Setting Range Unit Others Setting > End
value
Applicable
0 to 1000 10 [pulse] P
Mode
When the number of position error pulse is within the value above, position completion signal
detection </P-COM> signal is generated.
Initial
Setting Range Unit Others Setting > End
Value
Applicable
0 to 1000 20 [pulse] P
Mode
When the number of position error pulse is within the value above, position Approach Signal
detection </NEAR> signal is generated.
Other explanation
Position approach signal detection </NEAR> signal with position
completion signal detection </P-COM> signal is useful to reduce the
necessary operation at the position completion signal time. First, check the
approach signal and preparing the next sequence before the host controller
verifies the position completion signal detection signal. The setting of these
parameters above do not influence on the accuracy of final position decision.
Therefore, you can adjust timing to output </P-COM> signal and </
NEAR> signal by adjusting the number of position error pulse of [Pr-5.00]
and [Pr-5.01].
If the position completion signal detection </P-COM> signal is detected, the
segment LED in line indication 1 of status indication mode is on. However,
</NEAR> signal is not on.
Figure Explanation
Sequence output </P-COM> and </NEAR> signal output as shown below.
Position
Error
Pr-5.01
Pr-5.00
Time
0
/NEAR ON OFF ON
/P-COM ON OFF ON
G
Position Error
G
c Setting Value /P-COM Output
G
Position Error
c Setting Value /NEAR Output
When [Pr-5.00] is set with high value during the low-speed operation,
WARNING </P-COM> output signal remains ON.
Initial
Setting Range Unit Others Setting > End
Value
Applicable
0 to 65535 20480 [pulse] P
Mode
If position error is bigger than setting value, the position error overflow servo alarm (E.PoSEr) occurs.
Servo-On
Operation by the T1 T2
Drive
Position Command
Sign Input
Position Command
Pulse Input
T3
Position Command
Phase A
Position Command
Phase B
T1 T2 T3 T4 T5
The speed control mode is used to control the speed as inputting speed
command of analogue voltage type that is generated by the host controller to
servo drive even if the position control loop is formed in the host controller or
not.
In order to operate servo drive in speed control mode, connect the analog
speed command to the related input pin and set as the following.
Reset external speed command input gain in Servo-OFF state and run it
again as making Servo-On.[Pr-2.00]
If motor rotates even you command 0[V], adjust motor not to rotate using
speed command offset adjustment function.[run-03, run-05]
Use the zero clamp function to reduce the offset of host controller
command.[Pr-5.04]
Tune the servo drive by adjusting the gain according to the load condition.
The following figure illustrates the standard wiring example of the speed
control mode. You can set sequence input/output signal, as you want if it is
necessary for system configuration.
DC + 24 [ V]
Analog Monitor CH1
+ 24 [ V] IN 1 28 Output Range : -10 [V] to +10 [V]
Analog Monitor CH2
0 [ V] 2 D/ A 23 Output Range : -10 [V] to +10 [V]
Sequence Input Cir cuit
27 AM-SG Analog Monitor Output GND
Recommended Setup Furction Input Channel 37
AL 1 Servo Alarm Code
Servo-ON / SV - ON DI # 1 3 38 Maximum Allowable Voltage
AL 2 DC 30[V]
Prohibit Forward Rotation P- OT Maximum Allowable Current : 20 [mA]
DI # 2 4 39
AL 3
Prohibit Reverse Rotation N- OT DI # 3 5 40
AL - SG Alarm Code Output GND
P-Control Conversion / P- CON
DI # 4 6 29
EA +
Alarm Reset / A- RST P
DI # 5 7 30
EA -
Reverse Torque Limit / N - TL DI # 6 8 31 Encoder Phase A, B & C
EB +
P
Forward Torque Limit / P- TL DI # 7 9 32 (Line Receiver SN75175
EB - or MC3486)
33
EC +
P
E- STOP 10 34
EC -
35
PS + Absolute Encoder
P
36 Rotation Data
PS -
17
/ Z - PULSE + Encoder Phase Z
P OPEN Collector
18 / Z - PULSE -
45
SALM +
P
46
Servo Alarm
SALM -
Speed Command
Two pins of CN1 receive one command related to the speed control mode.
Host controller sends the voltage command of analog type.
Initial
Setting Range Unit Others Servo-off> Setting > End
value
Applicable
10.0 to 2000.0 500.0 [RPM/V] S
Mode
Set of speed command gain value [RPM] related to the analogue voltage 1 [V].
This setting is used as external speed limit function if the servo drive is not used in speed control
mode. For speed limit function, refer to the Chapter 7-18.
Therefore, If input voltage 6 [V] according to initial value, motor rotates 3000
[RPM] as the rated speed of motor, If input voltage 10 [V], motor rotates 5000
[RPM] as the maximum speed of motor. (Rated speed and maximum speed
can be different according to motor type.)
• Motor can rotate even though the speed command is not output or
NOTE
the host controller inputs speed command as 0 [V]. It is because of
the voltage offset between the host controller and the drive.
• The rotation of the motor can be prevented by offset using the
automatic adjustment of speed command offset (Run-03) or
manual adjustment (Run-05) function. Refer to the Chapter 7-35.
for the automatic (manual) adjustment of the speed command
offset,
• In addition, the rotation of motor can be prevented using the zero
clamp function in the Chapter 5-31.
Even though the analog speed command of the host controller is 0 [V], some
offset voltage can exist in servo drive input, resulting in slow rotation of the
motor. In this case, prevent the subtle rotation of motor according to offset
voltage using the zero clamp function.
</Z-CLP> is a sequence input signal. To use </Z-CLP> function, allocate
</Z-CLP> by referring to the sequence input/output signal in the chapter
5.1.
Set speed zero clamp level to the parameter below.
Initial
Setting Range Unit Others Setting > End
value
Applicable
0 to 5000 0 [RPM] S
Mode
Speed command that is below the value is ignored.
If you turn the signal on or off to the pin of CN1 where the zero clamp
function is allocated, the voltage command less than the zero clamp level
[Pr-5.04] or lower is ignored. When the speed command value is higher than
this level, the motor is accelerated to the command value.
In addition, if you set the sequence input as ‘8’ with the reference of the input
signal allocation method in the Chapter 5-7, the zero clamp function is always
valid and if it is set as ‘0’, the zero clamp function is not processed.
Analog Speed
Command
(External Input Voltage)
Pr - 5. 04
Time
0
/Z-CLP Input OFF ON
Actual Speed
Command
Pr - 5. 04
Time
0
R
Speed Command
Voltage
T
Normal Rotation
Motor Speed
Reverse Rotation
In some applications, the analog input used for speed command may not
support negative voltages (e.g. PLC 0-10V analog output). In this situation,
you can control the rotation direction using input </C-DIR>, which is also
used in Multi-step Velocity Control Mode (Pr-0.00 = C). When input </
C-DIR> is ON, the rotational direction of the motor will be inverted. For
example if the analog input speed command polarity is positive and </
C-DIR> is ON, then the analog input speed command will be interpreted as
negative. If the analog input speed command polarity is negative and </
C-DIR> is ON, then the analog input speed command will be interpreted as
positive.
Speed Command
Voltage
ON
/C-DIR
Motor Speed
With previous FW revisions, the motor begins to rotate when the speed
command is entered after Servo-ON in the Velocity Control Mode (Pr-0.00 =
S) or the Velocity Control Mode (Pr-0.00 = C). With the new FW, if the </
START> input is assigned to an input pin, the </START> contact point
input acts as an enable and can be used to control motor rotation start or stop.
Speed Command
Voltage
ON
/START
Motor Speed
G
(</START> is only configured to an input pin.)
The speed coincidence detection output is to indicate that the actual motor
speed matches up to command speed within the allowable error. Like position
completion output signal </P-COM> in position control mode, you can use it
as an inter-lock signal in the host controller.
</V-COM> is a sequence output signal. To use </V-COM> function,
allocate </V-COM> signal by referring to the sequence input/output signal
described in the Chapter 5-2.
Set output width of speed coincidence signal to the parameter below.
Initial
Setting Range Value Unit Others Setting > End
Applicable
1 to 1000 10 [RPM] ALL
Mode
If speed error is within setting value, speed coincidence detection </V-COM> signal is generated.
It indicates that the servo motor rotates at a speed higher than the set speed. It
can be used as one condition to check the motor status when you change the
control mode in mixed control mode, or before you change one sequence to
other sequence among sequences.
</TG-ON> is a sequence output signal. To use </TG-ON> function,
allocate </TG-ON> signal by referring to the sequence input/output signal in
the Chapter 5-2.
Set rotation detection level in order to set the appropriate constant to satisfy
the purpose such as control mode change or sequence conversion.
Initial
Setting Range Unit Others Setting > End
Value
Applicable
1 to 5000 20 [RPM] ALL
Mode
</TG-ON> signal is output if the motor rotates at a speed higher than the set value.
Rotation Speed
Actual Speed
Pr - 5. 03 Setting Speed
Time
0
If you set rotation detection level Pr-5.03 too low, </TG-ON> signal
NOTE
can be output even with small vibration.
You can limit the speed of servo motor within a set speed in order to avoid the
excessive operation of the load. Initial value is limited to 5000 [RPM] and you
can change the speed limit according to the parameter setting below.
Set speed level that you want to limit to the parameter below.
Speed Limit
Initial
Setting Range Unit Others Setting > End
Value
Applicable
1 to 5000 5000 [RPM] ALL
Mode
It limits the rotation speed of motor to keep below the speed of set value.
Even though you set the speed limit [Pr-2.12] as 1000 [RPM] and send analog
speed command related to 1500 [RPM] from the host controller, servo motor
runs in 1000 [RPM].
On this occasion, if the speed of motor reaches to speed limit as allocating
sequence output function speed limit detection </V-LMT>, you can generate
</V-LMT> signal to the allocated output pin.
</V-LMT> is sequence output signal. To use </V-LMT> function, allocate
</V-LMT> signal with reference to sequence input/output signal in the
Chapter 5-2.
Speed limit detection </V-LMT> output is ON when the following
conditions are satisfied.
The torque control mode is used to control the tension or the pressure of the
mechanical part by using the servo drive.
Enter the voltage related to the desired torque from the host controller.
Various setting values related to operation torque limit of motor are generally
applied to the position or the speed control mode.
In order to operate the servo drive in a torque control mode, connect the
analog torque command to the related input pin and set the required process
as shown bellow.
Select the sequence I/O function and allocate them. [Pr-0.05 to Pr-0.11]
Check if the motor rotates while slowly increasing the analog torque
command voltage.
If motor rotates even the command 0[V] is input, then use the torque
command offset adjustment function to adjust the motor to prevent the rotation.
[run-04, run-06]
Tune the servo drive by adjusting the gain according to the load condition.
If you set rotation detection level Pr-5.03 too low, </TG-ON> signal
NOTE
can be output even with small vibration.
The following figure illustrates the standard wiring example of the torque
control mode. The sequence input/output signal can be set according to needs
if it is necessary for the system configuration.
X X X
Sequence Output
Circuit
Torque Command
Two pins of CN1 receive one command related to torque control mode.
Host controller outputs the voltage command of the analog type.
Initial
Setting Range Unit Others Servo-off> Setting > End
Value
Applicable
0.0 to 100.0 33.3 [%/V] t
Mode
Set the gain of torque command value [%] related to analog voltage 1 [V].
Therefore, according to the Initial value, when the input voltage is 3 [V], 100
[%] torque that is rated torque of motor occurs. In addition, when input
voltage is 9 [V], 300 [%] torque that is maximum torque of motor occurs.
(Rated torque and maximum torque can be different according to motor type.)
Analog Input
Voltage [V]
It can limit the torque of servo motor and can set separately in
forward(reverse) direction.
Internal Limit
It means the drive limits itself according to the parameter setting regardless of
the external signal.
External Limit
It receives the external sequence input signal. In addition, it sets up the limit
value to the parameter that is different from internal limit, and torque is limited
according to sequence input signal.
If the internal torque limit is set, the limit value is always valid. However,
external torque limit setting is not always valid because it is controlled
according to sequence input signal. It can be difference between internal
torque limit and external torque limit.
Set the following two parameters for the internal torque limit.
Initial
Setting Range Unit Others Setting > End
Value
Applicable
0 to 300 300 [%] ALL
Mode
It limits positive torque in [%] unit related to rated torque.
Initial
Setting Range Unit Others Setting > End
Value
Applicable
0 to 300 300 [%] ALL
Mode
It limits negative torque in [%] unit related to rated torque.
Initial
Setting Range Unit Others Setting > End
Value
Applicable
0 to 300 100 [%] ALL
Mode
If </P-TL> is ON, it limits positive torque in [%] unit related to rated torque.
Initial
Setting Range Unit Others Setting > End
Value
Applicable
0 to 300 100 [%] ALL
Mode
If </N-TL> is ON, it limits negative torque in [%] unit related to rated torque.
Torque / P- TL Torque
Positive Torque OFF
(+) Pr - 4. 01
ON Pr - 4. 03
Speed Speed
Torque 0 0 Limited
Command Torque
0 0 Command
Speed ON Speed
(- ) Pr - 4. 04
Pr - 4. 02
Negative Torque
OFF Torque
Torque / N- TL
Cautions
</P-TL> and </N-TL> are sequence input signals. To use </P-TL> and </
N-TL> functions, allocate </P-TL> and </N-TL> signals by referring to the
sequence input/output signal in the chapter 5.1.
External limit of positive torque uses </P-TL> signal and that of negative
torque uses </N-TL> signal.
Torque limit by internal limit [Pr-4.01] and [Pr-4.02] are prior to external
torque limit </P-TL> and </N-TL> signal.
More explanation
Internal limit is used to limit maximum value of operation torque of motor(or
output torque) within set range to protect the load system or the object on
work.
Generally, the allowable torque limit of motor is as shown in the figure below.
Therefore, torque limit in the speed over rated speed is achieved within the
momentary operation range as shown in the figure. In high speed range,
torque limit according to current motor speed is automatically processed inside
Servo drive. If the values of [Pr-4.01] and [Pr-4.02] are set as shown in the
following figure, torque of motor is limited as the lined area in the figure.
Momentary Allowable
Momentary Continuous
Maximum Torque Allowable Area
Torque Limit
Setting Value
Rated Torque
Rotation Speed
Rated Maximum
Speed Speed
Initial
Setting Range value Unit Others Setting > End
Applicable
0 to 300 300 [%] ALL
Mode
Both forward and reverse rotation are limited by the same setting value.
• Internal and external torque limits can be set separately when the
NOTE
rotation direction of the motor is forward and reverse.
• However, for torque limit by over travel </P-OT> and </N-OT>
signal input, torque is limited by one setting value of rotation
prohibition torque [Pr-4.05] regardless of rotation direction of
motor.
Select sequence I/O function for multi-step speed control and allocate
them. [Pr-0.05 to P-0.11]
Tune the servo drive by adjusting the gain according to the load condition.
41
DO # 1
P Speed Coincidence /TG-ON
42 Detection
DO # 1 -
43
DO # 2 +
P Rotation Detection /T-LMT
44
DO # 2 -
47
DO # 3 +
P Speed Limit Detection /V-LMT
Back-up Battery for BAT + 49 48
DO # 3 -
Absolute Encoder P
Back-Up Battery BAT - 25 24 26 50 Output Recommended
Channel Setup Function
DC 3.6[V]
X X X
Sequence Output
Circuit
Multi-step speed control mode does not have external signal input pin for each
control mode unlike position, speed and torque control mode and can be
operated only by sequence input. Therefore, sequence input signal has input
signal that is exclusive for multi-step control mode and exclusive input signals
are as follows.
</C-DIR>
It is input signal to determine rotation direction of motor. If </C-DIR> signal is
OFF, motor rotates forward, and if it is ON, motor rotates reverse.
</C-DIR> Signal Motor Rotation Direction
1 OFF 0 Forward Rotation
2 ON 1 Reverse Rotation
Speed Command 1 0 0 1
Speed Command 2 0 1 0
Speed Command 3 0 1 1
Speed Command 4 1 0 0
Speed Command 5 1 0 1
Speed Command 6 1 1 0
Speed Command 7 1 1 1
Initial V alue
P arame te r [rpm]
You can control the rotation direction of motor differently to forward and reverse as
approving </C-DIR> sequence input for each speed that is designated to each speed
parameter.
</C-SP4>
In Multi-step Speed Mode (Pr-0.00 = C), </C-SP4> can be used to change
the motor speed using analog speed input voltage without changing the
control mode. When </C-SP4> is ON and <C-SP1>, <C-SP2>, and
<C-SP3> are all OFF, the motor speed is controlled by analog speed input.
The </Z-CLP> input and zero clamp function are all available. If the </
C-SP4> input is ON and any one of <C-SP1>, <C-SP2>, and <C-SP3>
inputs is ON at the same time, the motor speed is controlled by the
corresponding contact inputs.
Speed command
voltage
/C-SP1,2,3
ON
/C-SP4
Motor Speed
G
• If you do not change the rotation direction, you do not need to use
NOTE
</C-DIR> input.
• In addition, you do not need to use all </C-SP1>,</C-SP2> and </
C-SP3>, and can adjust change level using only </C-SP1> or both
</C-SP1> and </C-SP2> according to your needs.
• If you ser up '8' when you allocate sequence input signal as
described in sequence input/output signal in the Chapter 5-2, you
can always use valid input signal.
• </START> input can be used.
( Pr- 2. 07)
When acceleration/
( Pr- 2. 06) deceleration time is set
( Pr- 2. 08)
Forward ( Pr- 2. 05)
Operation
0[ rpm] 0[ rpm] 0[ rpm]
Reverse
Operation ( Pr- 2. 11)
( Pr- 2. 09)
( Pr- 2. 10)
/ C - DIR 0 1
/ C - SP 3 0 0 0 0 1 0 1 1 1 0
/ C - SP 2 0 0 1 1 0 0 0 1 1 0
/ C - SP 1 0 1 0 1 0 0 1 0 1 0
Speed
Command 1 2 3 4 5 6 7
Combinational Control Position control mode, speed control mode, torque control mode and
multi-step speed control mode described are called the basic control modes.
Mode and </C-SEL> The servo drive provides combinational control mode function to combine
Function basic control modes to meet the user's condition.
Combinational control mode uses two basic control modes.
Speed-Position
Torque-Speed
Torque-Position
Multi-Step Speed
+Position
Multi-Step Speed
+Speed
Multi-Step Speed+
Torque
Each basic control mode is already described before. If Servo is ON, the
current control mode is flashed and if the control mode is converted by
</C-SEL> signal, the alphabet of the control mode is flashed.
Status Display Mode </C-SEL> is sequence input that is used only for combinational control
mode.
As described before, mixed control mode uses two basic control mode. If you
use two-control mode and one mode is working, other control mode input is
ignored.
For example, when the speed control mode is used, position command pulse
or analog torque command is ignored and only when the control mode is
converted by </C-SEL> signal, the related input will be valid.
Introduction This chapter explains the servo drive setting that can achieve its optimum
performance to satisfy different load system as controlling servomotor.
Topic Page
Introduction 6-1
Before you Begin 6-2
Gain Setting Configuration 6-7
Automatic Gain Setting 6-7
Manual Gain Setting 6-11
Position, Speed, Torque Related Gain Setting 6-14
Tip to get fast response 6-20
Tunning Icon
Maximum
Gain Setting Parameter \WW
Setting Value
Initial Setting
Gain Name and Unit Sytem Gain Value
\W
[10Hz] Minimum
W Setting Value
Gain Introduction
As the audio system has equalizer to adjust the audio quality, the drive also
requires adjustment to achieve the optimum performance for each load.
Equalizer adjustment is not essential for the audio system, but the adjustment
is important fact that is directly connected to performance for servo drive.
You should adjust servo drive to satisfy load condition in order to achieve
optimum performance for each control.
In addition, the adjustment made to the motor that is connected to drive, to
achieve the optimum performance through gain setting, is called Tuning.
It is the same as the Bandwidth of overall speed control System Gain [Hz]
loop of the servo drive.
1000
0
IMPORTANT In case of BX2 Rev.B servo drive, the system gain is limited to
10Hz at its minimum to guarantee a proper level of motion
characteristics when velocityresponse level [Pr-1.15] is set too
low. For more information about velocity response level, refer to
peterkang.
<Applicable Gain> They are four gains that <Others> They are four parameters with
with separate functions. supplementary function that is required for tuning.
XWW
1000
W W W W 0
Inertia Ratio
Setting Unit
Setting value of Inertia Ratio uses the unit, [times]. For example, if the motor
inertia is same as the load inertia, the Inertia Ratio is 1 [time] and the setting
value is ‘1’.
The setting value of the Inertia Ratio is determined by the following formula.
Load Inertia
Inertia
Ratio Load Inertia
Setting Parameter
Inertia Ratio
Initial
Setting Range Unit Others Setting > End
Value
Applicable
0.00 to 60.00 1.00 [Times] ALL
Mode
It can be automatically set by off-line auto tuning function in the Chapter 7-36.
60 26
0
0
Speed Loop
Speed Loop Integration
Proportion Gain Gain [Nm/S]
[Nm/S]
Gain Setting Configuration This chapter explains the overall configuration (Position, Speed, Torque)
related to the gain setting.
The following diagram will help you understand the gain configuration related
to position, speed and torque.
Starting point for position mode gain setting
• Position mode using the position pulse command of host controller includes all gains
related to speed and torque from starting point to the servo motor as shown in the figure
below.
• Servo drive first generates the speed command using the position command of the host
1 controller, speed command generates the torque command and finally, it transfers the
torque command to the servo motor. Therefore, when you use the position mode, the gain
can be set properly.
• If gain related to position control is set properly but the gain related to torque or speed is
not set properly, the optimum tuning cannot be achieved.
Starting point for speed mode gain setting
• Speed mode using speed command of the host controller includes all gains related to
torque from starting point to the servo motor as shown in the figure below.
• Servo drive first generates torque command using speed command of the host controller
2 and finally, it transfers the torque command to the servo motor. Therefore, when you use
the speed mode, the gains related to speed and torque can be set properly.
• If gain related to speed control is set properly but gain related to torque is not set properly,
the optimum tuning cannot be achieved.
Starting point for torque mode gain setting
• Torque mode using torque command of host controller includes all gains related to torque
3 from starting point to servo motor as shown in the figure below.
• You can adjust gains related to torque in torque mode.
<SERVO DRIVE>
wTXUXZ
wTXUXZ
z
o¡ o¡
There are two functions, which automatically detects the load status inside
servo drive.
• Off-line-auto-tuning
• On-line-auto-tuning
Tuning function
IMPORTANT BX1 and BX2 servo drives automatically detect and set only
load inertia ratio.
However, BX2 Rev.B servo drive automatically detects and sets load
inertia ratio, friction coefficient, and resonant frequency.
Two basic gains are automatically set based on the detected data.
Tuning mode
There are two tuning modes.
• Inertia identification
• Inertia identification and resonance frequency
The tuning mode during Run-01 execution is set by autotuning mode setting
[Pr-0.03.N0]. For more information, refer to PeterKang.
• For Operation method for off-line auto tuning, Refer to Off-line Auto
Tuning Operation (run-01) on page 7-36.
After autotuning, max. bandwidth is determined, and the system gain [Pr-1.00]
is determined by [Pr-1.15].
Parameter
Explanation of the relationship flow between off-line auto tuning and gain
• When you run off-line auto tuning, drive automatically Inertia Ratio
[Pr-0.04] of load system and automatically set two basic gains as being
suitable for Inertia Ratio. Therefore, it is recognized that the response
quality of servomotor is improved at the same time.
The response performance of the drive is increased than prior to the auto tuning.
YWWW XWWWW
XWW XWW
W W Set the 2 basic gains automatically using
the data detected by the tuning.
Speed Loop Speed Loop
Proportion Integration
Gain Gain
<Automatic Setting of the basic gain>
XWWWW
Flowchart of the relationship between the off-line auto tuning and gain Start
Overview
On-line Auto Tuning is used when load is continuously changed during the
operation. It continuously changes the gain value according to load state in
order to maintain the regular response quality of system even though load state
is changed.
Precautions
Do not use On-line Auto Tuning for the cases below if possible, and we
recommend using the Off-line Auto Tuning or manual gain setting.
• When fine or large change is made to the Inertia ratio during the load
operation.
• If Inertia ratio is changed in two types during load operation, you do not
need to change. In this case, refer to the Chapter 6-27.
• When big torque does not occur during load operation because
acceleration/deceleration time is long or maximum rotation speed or
torque limit is set low.
9 On-line Auto
Tuning If this value is not ‘0’, use On-line Auto Tuning function.
Coefficient
[-] The higher you set the value, the more delicately it responses to load
0 change and respond quickly.
If load is quickly changed, you need to set the On-line Auto Tuning coefficient
high, but it can be momentarily unstable in the load environment that the
vibration is large. So, pay extra caution.
If the response quality of control loop is decreased during On-line Auto
Tuning, increase the value of system gain [Pr-1.00] and if noise or vibration
occurs, reduce that value.
For system gain [Pr-1.00], refer to the Chapter 6-12.
The following figure illustrates whole structure and procedure of Manual Gain
Setting.
60 26 20 300 1000
0 0 0 0 0 Perform fine adjustment
from each basic gain.
200
0 0 0 0
Perform fine adjustment
from each applicable gain.
Position Machine Position Position
Command Filter Resonance Feedforward Feedforward
Cutoff Frequency Suppression Gain [%] Filter Cutoff
[Hz] Filter [Hz] Frequency [Hz]
100 1000
0 0 0
Use other functions fro
tuning.
Slection of Auto P Control Minimum
Adjustment on Speed Conversion Position Error to Speed Bias
Loop Integration Standard Value Add Speed Bias [rpm]
Value [N/A] [Variable] [pulse]
Check the motion of the load system and if appropriate tuning is not done, repeat the above steps.
The following figure illustrates the flowchart that Inertia Ratio and system gain
set basic gain as being interlocked. Adjust to make the optimum tuning as
making Inertia Ratio and system gain refer to each other whenever Inertia
Ratio is changed or the system gain is adjusted.
500
5 basic gains are set for
the system gain.
interlocked 50
0
Setting Range 0.00 System Gain 3 basic gains are set for
Inertia Ratio to 60.00 [Times] [10Hz] the inertia ratio.
Inertia Ratio
Initial
Setting Range Unit Others Setting > End
Value
Applicable
0.00 to 60.00 1.00 [Times] ALL
Mode
Torque
[dB] [dB]
Torque Servo
Command Speed Motor
[Hz] [Hz]
10000 10000
[Hz [Hz
~ 0
]
0
]
10000
When load system is resonant in the specific frequency range, it
suppressed vibration by load resonance.
0 If it is appropriately set, you can increase other gain more. So you can
considerably improve the stability and response quality of the whole
Machine
system.
Resonance
Suppression If it is not properly set, vibration or noise can occur.
Filter [Hz]
If load system uses belt or chain, rigidity is low so that you cannot expect the
fast response. In addition, if you excessively increase speed control or position
control related gains, it can be oscillated. For those loads, it is difficult to set
the value of torque command filter [Pr-1.04] within about 100 [Hz].
Speed related gain includes speed command filter, speed loop proportional
gain and speed loop integration gain.
The following figure is related to speed in Gain Setting Diagram.
Speed Control Related Gain
Speed Command
Speed Limit Filter Cutoff Speed Loop Proportion Gain
Frequency
Spee
2000
[dB]
d
Speed Pr-2.12 60
KP Torque
Command Tim 0 Command
e
[Hz] [Nm/S]
2000
• The higher the value is set, the better response of speed
Speed Loop control loop is.
60
Proportion
0 Gain[Nm/S] • Set as high as you can within the limit that vibration does
not occur.
• If position control related gain of host controller is set high more than
necessary or in the environment where the noise is too big, reduce the
value of speed command filter [Pr-1.05].
Position related gain includes position FF gain, position FF filter and position
loop proportional gain.
The following figure is related to position in Gain Setting Diagram.
Position Control Related Gain
700
Pr -1.13
0 [ Hz ]
20
[ Hz ] Pr -1.13
0
• Increase the value of [Pr-1.03] again up to the level that vibration noise
does not occur in over response.
For position feed forward (FF) diagram, refer to the Chapter 6-18. Position FF
makes differentiation factor on position command in position control mode
approved in speed command through feed forward method. Therefore, over
response characteristics is improved so that you can reduce position output
time.
The related parameter to set is as follows.
Position Feed forward Gain Function
100
The higher the value is set, the better position control response
Position performance.
0 Feed
forward
Gain [%]
If you use it with On-line Auto Tuning, the system can be unstable.
WARNING
450
If position error is more than setting value of bias standard width
[Pr-1.13], much bigger speed command that adds the setting value is
Speed
sent.
0
Bias
[rpm] It is valid only when the value of [Pr-1.13] is not ‘0’.
As reference, if you set the value of [Pr-1.12] too high or the value of
NOTE
[Pr-1.13] too low, vibration can occur.
When you control speed or position, if you set speed loop integration gain
[Pr-1.02], it responds to the delicate command so that you can accurately
control and make the error in the normal state '0'.
However, if you increase speed loop integration [Pr-1.02] to increase response
quality, overshoot occurs in speed response as over response and as a result,
position completion time can be increased. Therefore, you can reduce position
completion time as setting instantly integration gain as '0' and suppressing
overshoot if necessary. In that case, speed control loop is changed from 'PI
controller' type to 'P controller' type.
There are two methods to change speed control loop from 'PI controller' type
to 'P controller' type.
OFF PI Controller
/P -CON Input
ON PI Controller
The following figure illustrates the conversion of 'PI controller' and 'P
controller' using</P-CON> input in speed control loop (speed controller).
Host Controller
Logical Decision
/ P - CON
Initial
Setting Limit Unit Others Setting > End
value
Applicable
0 to 3,000 100 Variable P, S, C
Mode
Initial Setting value is operates as ‘P controller’ type when torque command exceeds 100 [%].
Speed Speed
Speed Speed
Command Command
Speed Speed
Response Response
(Pr -1.11)
(Pr - 1.11)
• Initial torque bias approves motor toward the direction against initial torque that relates to
downturn when approving initial Servo-ON signal in order to prevent downturn by gravity when
controlling vertical shaft load.
• If you set initial torque bias appropriately against the strength that load drops, you can prevent the
downturn of vertical load during initial operation.
• If you control the vertical shaft load, use the motor that has built-in brake or install brake.
Initial
Setting Limit Unit Others Setting > End
value
Related
-100 to 100 0 [%] ALL
Mode
• If you set this value as the value not ‘0’, as soon as you do Servo-ON, control is started and the
value of torque command is started from Setting value of parameter.
• Since torque to maintain the current state occurs from the beginning, you can prevent the
phenomenon that load drops.
• Therefore, you can suppress overshoot of speed response so that you can reduce position
completion time.
• If you set value of initial torque bias [Pr-4.06] too high, load can
WARNING temporarily goes up.
• Be careful to make appropriate setting.
</G-SEL> Function
As shown in the figure below, two different conditions of load can be repeated.
For example, robot moves a object to other position and return to the original
position without any load after laying a object down.
If those movements are repeated too fast, On-line Auto Tuning is not
smoothly performed. In addition, if you operate different load condition with
the same gain, the response quality in one side is degraded.
In this case, you can effectively use sequence input </G-SEL> function.
Current Gain
With Rotation
1
Load
OFF
< /G -SEL > Input
ON
Without Rotation
2 Load
Gain2 Group
Therefore, if you use as dividing different loads into current gain and 2nd
group gain, you can satisfy the response quality of both different load
conditions.
</G-SEL> is sequence input signal. To use </G-SEL> function, allocate </
G-SEL> signal with reference to sequence I/O signal in the Chapter 5-2.
When you use </G-SEL> function, you cannot use On-line Auto Tuning.
WARNING
Applications
Introduction This chapter describes the contents that the users should know in terms of
fragmentary application function, operation mode and monitor mode when
using the servo drive.
Topic Page
Introduction 7-1
Motor Suspension 7-2
Motor Brake Control 7-6
Change of Motor Rotation Direction 7-10
Regeneration Resistor 7-11
Setting for Smooth Operation 7-16
Speed Limiting Function 7-18
Position Feedback to the Host Controller 7-21
Analog Monitor Output 7-25
Use of Absolute Encoder 7-27
Operation Mode Function 7-35
Monitor Mode Function 7-50
Motor Suspension It describes the suspension of the motor except the stopping by normal
operation.
Overview
The general overview on the each situation when the motor is stopped is
explained.
With the exception of motor suspended by the normal operation, the servo
drive suspend its operation when the below situation occurs and result in
suspension of the motor.
Servo Alarm Occurrence Over Travel Occurrence
The motor can be stopped by 2 above factors in normal operation of the drive,
and the method of stopping the motor for each suspension factors may be set
in several forms.
• Allow the operation within the range so that the loading does not reach
the sensor during the operation.
• The servo drive stops the motor to protect the load system when the
signal from the sensor occurs due to the loading exceeding the operation
range by a certain error.
Loading
Forward Reverse
juX
Loading Side Operation Operation
• <P-OT> and <N-OT> are the sequence input signals. In order to use
the <P-OT> and <N-OT> functions, refer to the sequence input &
output signal in Chapter 5-2 and allocate the <P-OT> and <N-OT>
signals.
• The No. 4 pin of CN1 has the <P-OT> signal, and the No. 5 pin of
CN1 has the <N-OT> signal allocation as a factory setting.
The over travel signal is not the servo alarm signal but it is a signal for
NOTE
the protection of the load system. When the over travel signal is
inputted, the drive status display mode shows the characters that the
signal is inputted.
Refer to the content of status display mode in the Chapter 4-2.
The sensor signal to cope with over travel may be used in performing
NOTE
the zero return function described in the Chapter 7-38.
Refer to the Chapter 7-38.
Dynamic Brake
• If the motor cable is connected to the servo drive and if the power is not
supplied to the servo drive, the switch in the below figure is
short-circuited. This indicates that the DB is in operation.
• Also, the servo drive controls the DB switch according to the parameter
setting for the DB operation.
• The DB cannot be used while stopping the motor with normal torque
control. The normal torque control is done in servo-ON, but the DB is
only operated in servo-OFF.
Dynamic Brake
(DB)
Drive Servo Motor
DB stop
DB Stop is operating the DB to stop the motor during the run.
• If the load is movable by the gravity (e.g.: When applied in the vertical
axis control)
• The fall can be prevented when the power is off or the drive servo is off.
Thrusting Thrusting
due to due to
Gravity. Gravity.
• In order to use the motor brake, refer to the sequence input & output
signal in the Chapter 5-2 first and allocate the <BK> sequence output
signal.
• The signal for brake control is outputted with the allotted pin.
Circuit configuration
• The drive cannot use the high voltage and current that can directly
control the motor brake. Therefore, the motor brake cannot be
connected directly to the drive and used. And it is possible to control the
brake indirectly by configuring the external relay circuit.
• Refer to the indirect control circuit through the relay shown below.
• The output channel of CN1 can be adjusted by the user according to the
condition since the sequence output signal is used. The example below
is based on a factory setting.
[_ kvGJZT
Relay 1
Motor
Relay 1 Brake External circuit
juX
configuration of the motor
brake control
• After the allocation of the brake output signal, the detailed setting on
the brake control can be made in the below parameter.
Initial
Setting Range Unit Other Servo - Off > Setting > End
Value
Applicable
0 to 1000 0 10 [ms] ALL
Mode
The motor brake has to be released first if the motor brake is in operation when the drive is about to
start the motor. At this time, if the brake is released before servo-ON (or simultaneously), the vertical
load will immediately fall. The drive has to be servo-on first and to prevent the fall of the vertical
load, then release the brake.
This setting is used to secure the time from the servo drive becomes servo-ON to the release of the
motor brake.
/SV-ON command of
the host controller OFF ON
/SV-ON command
BrakeBrake execution of the servo OFF ON
standby time driver
Initial
Setting Range Unit Other Servo - Off > Setting > End
Value
Applicable
0 to 1000 0 10 [ms] ALL
Mode
The time between the receiving the servo-off command from the host controller to the actual
servo-off by the drive can be set.
This setting is used in securing the time for operating the motor brake while the host controller
commanded the servo-off.
/SV-ON command of
the host controller ON OFF
Initial
Setting Range Unit Other Servo - Off > Setting > End
Value
Applicable
0 to 1000 50 10 [ms] ALL
Mode
In order to stop the motor from the host controller, the servo-off command is outputted from the
drive.
At this time, the actual time when the motor brake is operated, can be set.
/SV-ON command of
the Host controller ON OFF
Waiting Time When
Outputting Brake Signal Motor Brake
After Servo OFF Released Operating
Initial
Setting Range Unit Other Servo - Off > Setting > End
Value
Applicable
0 to 1000 100 [rpm] ALL
Mode
The motor speed when the motor brake is operated, can be set.
/SV-ON command of
the Host controller ON OFF
The brake attached to the motor should not be used to stop the
NOTE
running motor. Use it to maintain the stop status of the motor
immediately before or after the stop.
• As shown on the right column, if the brake operates after the actual
servo-off is completed, it will temporarily be descended by the gravity in
case of vertical load.
• In order to prevent the fall by the gravity, set the time properly.
O X
Servo-Off Delay Time Brake Output Standby Time Servo-Off Delay Time Brake Output Standby Time
e c
Brake signal is outputted according to the priority among [Pr-5.07] and [Pr-5.08].
Other
• Even when the brake attached to the motor is not used, a separate brake
may be manufactured and installed by the user.
• When the rotation direction of the motor is wired differently than the
intent of user by the pulse input, the rotation direction of the motor can
be reversed by the below parameter setting without the separate wiring.
Regeneration Energy
• When stopping the running motor, the motor operates like a generator
and the resulting energy is called the regeneration energy.
Regeneration Resistor
• When the motor is continuously rotated by the strength of the load - for
example (- loading condition) or (when of operating the vertical axis
loading)
Precaution
Speed Speed
W Time W Time
Regeneration Regeneration
Resistor Resistor
i i
i
X i
X
Y Y
| |
} }
~ ~
The regenerative resistor that the user connects to the outside for load is called
external regenerative resistor. The following is the description when using the
external regenerative resistor.
General Specifications
The user may consume the regeneration energy generated in the load system
by increasing the rated power of regenerative resistor and installing the
external regenerative resistor if the rated power of mounted regenerative
resistor consumes small regeneration energy.
Precautions
• When the rated power is increased for regenerative resistor on the above
two methods, the following conditions have to be satisfied.
O P
without load speed
repetition
frequency
d 1+n
Setting
[Cycles/Min]
speed
• Contents necessary in calculation shall be referred to the below [Reference Figure 1] and
[Reference Chart 1].
• (n) is the inertia ratio.
• The maximum speed shall be referred to the motor specifications of the appendix.
Make sure to use the actual repetition frequency of the motor smaller
WARNING than the permitted repetition frequency calculated on the above
formula.
Speed
CommandT
Time
ڋ
M Setting Speed
Revolution
Speed
Time
ڋ Acceleration Area
ڟ گDeceleration Area
Regeneration Area
Torque
Time
ڋ
τs
Revolution X
Speed d {
X 60 [Cycles/Min]
CSMH/RSMH 14 7 4
CSMK/RSMK 54 76 40 14
CSMQ/RSMQ 46 61 30
CSMS/RSMS 43 27
CSMZ/RSMD 88 63
Motor Rated
Speed
Speed
Command
Motor Rated
Speed
Time
ڋ
Motor Rated
Actual
Motor Rated Speed
Acceleration Time
Speed
Speed
Motor Rated
Speed
Time
ڋ Acceleration Deceleration
Setting Time Setting Time
Acceleration Time
Initial
Setting Range Unit Other Setting > End
Value
Applicable
0 to 60000 0 [ms] ALL
Mode
Deceleration Time
Initial
Setting Range Unit Other Setting > End
Value
Applicable
0 to 60000 0 [ms] ALL
Mode
Rated Motor
Speed Speed Speed
Command Command
Motor Setting
Speed
Time
ڋ
Rated Motor
Acceleration/ Speed Speed
Deceleration
Time Setting Motor Setting
Speed
Time
ڋ
Rated Motor
S-curve Time Speed
Setting Speed
Motor Setting
Speed
Time
ڋ
S-curve Time Setting
Initial
Setting Range Unit Other Setting > End
Value
Applicable
0 to 5000 0 [ms] ALL
Mode
Caution
The total command performance time differs by the acceleration-deceleration
and S-curve operation time.
If the total consumed time for initial speed command is 10 seconds, the total
time of speed command time after the acceleration-deceleration time setting is
(10 seconds + Pr-2.03). Also, the total time (10 seconds + Pr-2.03 + Pr-2.04)
of speed command performance after the S-curve time setting.
Speed Limiting Function It describes the function to limit the rotation speed of the motor.
• Limit the speed through the independent setting of the servo drive
(Internal speed limit)
• Limit the speed through the command from the host controller
(External speed limit)
• Internal speed limit is operated by the value set by the user on the below
parameter. Therefore, when the faster speed command than the setting
value of below from the host controller, the servo drive is limited to the
setting value and operated.
Speed Limit
Initial
Setting Range Unit Other Servo-OFF > Setting > End
Value
Automat [rpm] Applicable
1 to 5000 ALL
ic Mode
It limits the rotation speed of the motor to operate under the setting value.
Initial value is automatically set with the maximum speed of the motor applicable together with the
setting the motor model at the basis setting of the chapter 4.2.
• The below figure is the input of function to allow the servo drive to
make the speed control by permitting the analog speed command at the
host controller when the servo drive is used as the speed mode. Refer to
the speed mode in the chapter 5.3.
• If, the user does not use the speed mode and operate with other control
mode (position, torque, multi-step speed), the below input can be used
as the function limiting the speed. The speed limit utilizing the speed
command input pin is referred to as external speed limit.
• When it is used as speed mode, the external speed limit function may
not be used and the speed may be limited by the internal speed limit.
When operated in speed mode, the analog speed command of host controller is executed
• Select the analog command voltage and speed to be limited, and set the
external speed limit value of the below parameter.
Initial
Setting Range Unit Other Servo-OFF > Setting > End
Value
Applicable
10.0 to 2000.0 500.0 [rpm/V] S
Mode
Set the speed command value [rpm] on analog voltage 1 [V], and limit it with the set speed.
Accordingly, when the input voltage is 6 [V] following the initial value, it is
limited to the rated speed of motor, 3000 [rpm], and limited to 5000 [rpm], the
maximum speed of motor when the input voltage is 10 [V].
Host Controller Servo drive controls the servo motor by using several information received
from the encoder. Also, the servo drive has the function to output the encoder
information to host controller. In this the chapter, it describes the output
function of encoder information.
90° of Phase
Encoder Difference
In forward rotation, the encoder Output
A Phase
0 output A phase have a lead of
90 ° over B phase. Encoder
Output
B Phase
Setting
Value 90° of Phase
Encoder Difference
Output
In forward rotation, the encoder A Phase
1 output B phase have a lead of 90 °
Encoder
over A phase. Output
B Phase
Overview
Servo drive may adjust the number of pulse of encoder through the dividing
circuit function before outputting to the host controller through the input
received from the encoder.
Numerator
Number of Output to Host
G G Encoder Pulse = Controller
Denominator
Servo drive receives 2048 pulse per 1 revolution from the encoder, but outputs
1000 pulse to the host controller.
CN2 CN1
29
EA+
30
EA-
31
EB+
Encoder of
32
A, B and C
EB- Phase
33
EC+
34
EC-
35 Absolute
PS+ EncoderRot
36
PS- ation Data
1000
2048 Pulses 1000 Pulses
2048
Setting
Set the pulse dividing circuit numerator and denominator from the below
parameter.
Initial
Setting Range Unit Other Servo-OFF > Setting > End
Value
Applicable
1 to 32768 Automatic [Pulse] ALL
Mode
Initial
Setting Range Unit Other Servo-OFF > Setting > End
Value
Applicable
1 to 32768 Automatic [Pulse] ALL
Mode
Even when the motor rotates at a fixed speed, the encoder output
NOTE
pulse may have jittering of 33 [usec] depending on the rotation speed.
Precaution
Servo drive may not output to the host controller for the number of pulse that
is more than the input pulse number. Accordingly, the below condition has to
be complied.
• The monitoring is possible from all control mode and has two channels.
27 AM-SG
CN1
Output Range: -10 [V] to +10 [V] Host Controller
Setting
Set the output type and range that the users want to confirm from the below
parameter.
Analog Monitor Output CH2
Selection and Scaling
Initial
Setting Range Unit Other Setting > End
Value
0-0001 to Below Applicable
3-0500 ALL
6-2500 Chart Mode
The types of output and unit chart showing the setting window.
Selection Setting
Setting Example Type Unit
No. Range
0 Speed Command 1 to 500 [rpm]
Selection No. 1 Torque Command 1 to 30 [%]
2 Position Command 1 to 5000 [pulse]
3 Speed Feedback 1 to 500 [rpm]
4 Torque Feedback 1 to 30 [%]
Setting Range: 5 Position Feedback 1 to 5000 [pulse]
6 Position error 1 to 2500 [pulse]
Monitoring Sample
• Set the monitoring type and input the setting value applicable to 1 [V]
output.
Monitoring Sample 1
Confirm the speed command of host controller through the analog monitor output CH1.
• The speed command confirmation of host controller applicable to monitor output 1 [V] is 500
[rpm].
• By outputting of maximum of 10 [V], the confirmation can be made up to 5000 [rpm].
• Accordingly, the confirmation range of entire speed command is -5000 [rpm] to 5000 [rpm].
[V]
10[V]
1[V]
[rpm]
500 5000
Monitoring Sample 2
Confirm the position command of host controller through the analog monitor output CH2.
• The position command confirmation of the host controller applicable to the monitor output 1 [V] is
1000 [pulse].
• By outputting of maximum of 10 [V], the confirmation can be made up to 10000 [pulse].
• Accordingly, the confirmation range of entire position command is -10000 [pulse] to 10000
[pulse].
[V]
10[V]
1[V]
[Pulse]
1000 10000
Use of Absolute Encoder It describes on the matters related to the absolute encoder, battery and other
absolute encoder.
• Absolute encoder does not accumulate the error by the noise during the
signal transmission.
• When the host controller needs the absolute position of load system in
the power cut off, the motor that is equipped with the absolute encoder
has to be used.
UVW CN2
Information
DC 3.6V
+ AAA -
When the motor equipped with the absolute encoder is used, the standard
connection with the drive and host controller is as below figure.
33 EC
P
34 /EC
27 SG 0[V]
0[V
49 BAT+ ]
P DC 3.6[V]
25 BAT-
50 FG
Battery
Battery
It describes the battery for absolute encoder information preservation.
• When the power of servo drive is cut off, the battery memorizes the
absolute position of the load system and helps maintain it.
• If the power of servo drive is cut off and discharged the battery power
to lower than the standard, the saved information in absolute encoder
may be damaged.
• The voltage of battery is not directly monitored from the drive but the
error is checked indirectly through the encoder. Prepare the low voltage
detection circuit as needed basis.
Battery Specification
The below figure is the specification of battery connected to CN5 of servo
drive.
MOLEX 5264-02
RED
When the voltage of battery for absolute encoder When the capacitor voltage of encoder inside is
is 3.2 [V] or less, ‘absolute encoder battery low about 2.7 [V] or less, the ‘low voltage alarm for
voltage warning’ occurs. At this time, the below inside of absolute encoder’ occurs. At this time,
warning characters are displayed in the status the servo drive stops the operation.
display mode.
When ‘low voltage alarm for inside of absolute
Replace the battery before having ‘low voltage encoder’ occurs, the saved information on
alarm for inside absolute encoder’ occurs with encoder may be damaged.
the low battery voltage in having the warning.
Connection Sequence
1. Prepare the proper battery for specification.
2. Open the battery cover.
3. Push it all the way in to the No. <1>
ڙڍڗ
direction.
4. Contact the connector to the No. <2>
ڙڌڗ direction.
5. Close the battery cover.
6. The polarity is consistent if the battery
specification is complied.
• When separate the drive and encoder cable after cutting off the power
and connected again.
Completed
This Chapter describes the sequence of drive receiving the data of absolute
encoder and sending it to the host controller. After sufficiently understand it,
and then design the host controller.
CN2 CN1
29
EA+
30
EA-
31
EB+ Encoder
32
EB-
A,B,C
33
EC+
34
EC-
Absolute
35
PS+ Encoder
36
PS-
Rotation
Data
• Data is structured with “multiple rotation data & 1 rotation data, and
alarm”.
Caution
• For the host controller not receiving the serial data output using the PS
(+, -), the data of absolute encoder is sent to the host controller in the
form of incremental pulse form through the output of EA and EB, the
incremental encoder output signal. From the absolute data, send the 1
rotation data first, then send the multi-rotation data. The host controller
multiplexes the received pulses by 4 times.
4. Receive the number of rotation data, and then receive 1 rotation data
transmitted after 100 [ms].
5. EA and EB of drive are operated in normal incremental encoder output
signal after the lapse of about 50 [ms] after transmitting the 1 rotation data
to which division ratio is applied.
PAO Serial data reception sequence
ON Initial Incremental
OF
Incremental
/ABS-DT Pulse
F Pulse
EA
EB
First understand the below content before reading the description of the
operation mode.
1. From the flow chart content, the content of display of status display mode
may be different from the actual condition.
2. The content displayed in the flow chart and the key operation sequence is
the same with the actual condition.
3. The black part of key button mark on the right means to press.
4. The upper left side with servo-ON, servo-OFF means the status of servo
drives status in setting.
5. It describes to the order from (run-00) to (run-12).
6. Before using the functions of operation mode, the content of each
functions and flow chart shall sufficiently understand and operate it.
SERVO-ON SERVO-OFF
When the status of drive is not maintained, the following content is displayed during the
performance or storage of each operation mode.
Function Description
By using the direction key of the operator, the motor can be made for forward
rotation or reverse rotation.
• The speed of the motor is determined with the setting value of [Pr-2.01].
Confirm the setting value of [Pr-2.01] in advance before operation and
adjust it for situation.
• The operation can be possible in the range of 0 to 5000 [rpm] and the
initial setting speed is 500 [rpm].
How to Operate
Refer the flow chart of the below and operate.
SERVO-ON SERVO-OFF Jog Operation Flowchart
Make run-00.
(Initial run-00)
Operation expiration by
pressing the ENTER key
Completion
Function Description
Refer the Chapter 6-7 for detailed description on off-line auto tuning.
Caution
Loading Tuning
G Operation G
Range e Operation G
Range
How to Operate
Refer to the below flow chart to operate.
SERVO-ON SERVO-OFF Flow Chart of the Off-line
Auto Tuning Operation
Running Motor! Execute the optimal tuning for the load. After the tuning, the setting
value is automatically stored.
Auto tuning automatically
completed
Completed
Coupling
Function Description
• When the analog speed voltage command is made to 0 [V], the motor
has to stop. But there is such a case that the motor slowly rotates.
Operation Sequence
• Connect the host controller to the CN1 and the speed voltage command
is made to 0 [V].
• At this time, if the motor is not rotating, it can be said that there is no
offset voltage. However, if the motor is slowly rotating, there is an offset
voltage occurring.
• Make automatic offset adjustment. The drive reads the voltage of adjustment as
0 [V] and stops the motor.
Other
How to Operate
Refer the below flow chart and operate.
SERVO-ON SERVO-OFF Flowchart of the Speed Command
Off-set Auto Adjustment
Completion
When the operation is made with torque control mode from the host
controller or combination control mode related to torque, it is a function to
automatically adjust with the offset voltage of the torque command.
Function Description
• When the analog torque voltage command is made to 0 [V], the motor
has to stop. But there is such a case that the motor slowly rotates.
Operation Sequence
• Connect the host controller to the CN1 and the torque voltage
command is made to 0 [V].
• At this time, if the motor is not rotating, it can be said that there is no
offset voltage. However, if the motor is slowly rotating, there is an offset
voltage occurring.
Other
How to Operate
Completion
• It is same function with the automatic adjustment and can make more
precise adjustment than the automatic adjustment of speed command
offset.
• Continue to press the direction key to slowly stop the motor with the
speed nearing to 0 [rpm]. Once 0 [rpm] is reached, release the direction
key to confirm that the motor has stopped.
• If the motor is still rotated slowly, confirm the motor completely stop by
pressing the direction key one in a while. It is not to adjust one
operation of direction key per 1 [rpm]. When the motor is completely
stopped, it is progressed as below.
Completion
• It is the same function with the automatic adjustment and can make
more precise adjustment than the automatic adjustment of torque
command offset.
• Continue to press the direction key to slowly stop the motor with the
torque nearing to 0 [%]. Once 0 [%] is reached, release the direction key
to confirm that the motor has stopped.
• If the motor is still rotated slowly, confirm the motor completely stop by
pressing the direction key one in a while. It is not to adjust one
operation of direction key per 0.1 [%]. When the motor is completely
stopped, it is progressed as below.
Completion
The offset current that may occur when sensing the current flow on the motor
is automatically adjusted.
Function Description
• Servo drive sense and control the current flowing on the motor. If the
actual current flowing on the motor is not accurately sensed, the control
may become difficult.
• Servo drive may automatically adjust the offset current that may occur in
sensing the current flowing on the motor.
Precaution
How to Operate
Refer to the below flow chart and operate.
SERVO-ON SERVO-OFF Current Feedback Offset
Adjustment Flow Chart
Completion
Servo drive may reset the servo alarm detected by the independent error
diagnostic function.
Function Description
• The drive monitor the system with the independent error diagnosis
function from the moment the power is connected. At this time, if there
is an error in the servo drive, it displays the servo alarm.
• User has to understand the content of alarm and resolve the causes of
alarm for a normal use of the drive.
• If an alarm occurs, find out the content of alarm and resolve it. After
that, reset it through the alarm-reset operation. When the content of
alarm is resolved with no further problems, the occurred alarm is no
longer displayed.
• Even if the reset is made, if the action taken is not sufficient or other
error occurs, the drive continuously displays the alarm content.
How to operate
Refer to the flow chart below and operate.
Completion
Alarm History
Servo drive may store the servo alarm that is detected by the independent
error diagnosis function.
How to Operate
Refer to the flow chart below and operate.
Completion
Function Description
• When the optimal tuning that is appropriate to the load system is made,
it is stored.
How to Operate
Completion
• When the </G-SEL> function of the Chapter 6-27 is not used, the
NOTE
main storage function is meaningless.
This function is to initialize the user parameter to the same status as the
factory setting values.
General Matter
For changing the below parameter, directly change from the parameter.
Control mode setting Sequence input & output
Pr-0.00 Pr-0.05 to Pr-0.11
(optional) signal
Electronic gear and Pulse
Pr-0.01 Motor setting Pr-3.01 to Pr-3.04 dividing circuit
Pr-0.04 Inertia ratio Pr-4.01, Pr-4.02 Internal torque limit
Rotation prohibition torque
Pr-4.05 limit
How to Operate
Refer to the flow chart below and operate.
SERVO-ON SERVO-OFF Parameter Initialization Execution Flowchart
Completion - Initialize by
pressing the MODE/SET key
Display for normal
execution
Completion
The dis-04 and dis-05 are displayed each upper and lower digits (each 5 digits, total 10 digits)
separately by left and right key in case of overflowing count data
When the sequence input & output, emergency stop and servo alarm signal are on, the applicable
displays of each position are lit.
12 11 10 9 8 7 6 5 4 3 2 1
7 6 5 4 3 2 1 3 2 1
The alarm that occurs most recently is the number 1 servo alarm occurrence.
If all 8 alarms are stored, the alarm occurring thereafter is stored as number 1 with the earliest alarm
(No. 8 alarm) is deleted.
Refer the Chapter 8-4 for the content of servo alarm.
Example of
Version Display
When the number of digits increase, you can use left or right key to display the upper significant bits
and low significant bits (5 digits each, total 10 digits)
• Refer to the below flow chart to confirm the content of each monitor
item.
• Use the upper and lower direction key to confirm the alarm history
(dis-16)
Status Display
Completion
Introduction In this chapter, the inspection and the protective function of servo drive are
described.
Topic Page
Introduction 8-2
Inspection 8-2
Protection Function 8-4
Inspection It describes the basic inspection, abnormality diagnosis and how to take action
of servo motor and drive. Also, it describes the protection function of drive
and action to take in times of alarm occurs as well as any action to take in times
of breakdown following the alarm code.
Inspection of Motor
Motor does not have a brush that causes mechanically abrasive part. A simple
inspection is sufficient as follow. By considering the use environment,
determine the appropriate inspection time.
Item Period Inspection and Repair Action
Vibration and Determine with Sense and It shall not be larger than
Daily Check
Noise Hearing normal times
Presence of
Eternal Foreign In Occurrence Cleaning with Vacuum Cleaner
Substance
Measure with Insulation Inquiry to the company if
Insulation 1 year resistance meter the measuring value is 10
Resistance 500 [V] 10 [MW] [MΩ] or less
Only for motor that has
OIL SEAL 5000 hours Oil Seal Replacement oil seal
Disassembly and
20000 hours
Overall Inspection (5 years) Inquiry to the Company worn-out part
replacement
In the event of disassemble the servo motor for repair or inspection, a care shall be taken for A/S not
available.
Inspection of Drive
Servo drive is equipped with electronic circuit. The dust and foreign substance
may cause the breakdown or malfunction that the dust shall be cleaned and
tighten the nuts on a regular basis (1-year).
Inspection
Item Inspection and Repair Action
Period
Cleaning of Main Once or more per Clean with compressed
Do not have dust or oil
Body and Board year air or fabric
Do not allow loosening of
Socket, Connector, Once or more per socket, connector, nut and Do not allow loosening
Nut year others
Abnormal Part on Once or more per There is no discoloration by
Main Body and Inquiry to the company
year heat, damage or open circuit
Board
In the event of disassemble for repair and inspection the servo drive, be careful that the A/S is not
available.
Part Inspection
Protection Function It describes the equipped protection function and actions taken in times of
abnormal operation in order to protect the servo drive and load system. The
protection function is classified into two types depending on the importance.
1. Servo warning: It displays a minimal abnormality that does not require the
suspension of operation when occurred.
2. Servo alarm: It displays the very serious abnormality that requires the
suspension of operation when occurred.
Servo Warning
External Battery
Indicator Low Voltage of Absolute Encoder
Cause It occurs when the voltage of external battery of absolute encoder is 3.2 [V] or less.
Action Understand the content of Chpater 7-27 and replace the battery.
In the event the Q, E Type Absolute Encoder is rotated forward or reverse over 32768 (H,
Cause J Type Absolute Encoder is for 4096) revolution, it is displayed.
Action Refer to Chpater 7-27 and reset the Absolute Encoder.
Cause There may be a time of motor rotating for over 100[RPM] when main power is ON.
It only occurs in the event of Absolute Encoder serial of Q, E Type. And when the
Action resolution of 1 rotation data is 17bit, it automatically disassembled.
When the external torque command is inputted with 300 [%] or more of the rated value,
Cause it is displayed.
When the torque command is inputted for 300 [%] or more of the rated value, the drive
is automatically limited at 300 [%].
Action Also, when lowering the external torque command to 300 [%] or less of the rated value,
it automatically disassembled.
When the external speed command is inputted with the maximum speed or more of the
Cause motor, it is displayed.
When the speed command is inputted with the maximum speed or more of the motor,
the drive is automatically limited at the maximum speed of motor.
Action Also, when the external speed command is lowered for less than the maximum speed
or less of the motor, it automatically disassembled.
When sequence input & output signal is duplicated and allotted to the same input and
output channel.
In mixed control mode, when the control mode conversion </C-SEL> sequence input
Cause signal is not allotted.
In multi-step control mode, when speed command </C-DIR>,</C-SP1>, </C-SP2>, </
C-SP3> sequence input signal is not allotted, it is displayed.
Resetting it by referring Clause 5.1 of sequence input & output signal.
Action After resetting, it is effective only when the power is re-allowed.
Cause It occurs when motor power is set higher than the drive rated output.
Action Use a motor suitable to the drive or set the torque limit below the drive capacity.
• When the servo warning occurs, the servo drive may display that the
servo warning occurs by the host controller through the sequence
output signal </WARN> function.
Servo warning can be conveyed to the host controller for the presence
NOTE
of servo warning through the sequence output channel.
Servo Alarm
For protection function by the self-diagnosis, there is the servo alarm that
displays the important errors.
• When servo alarm occurs, the 7-segment indicator displays the character
applicable to the servo alarm and stops the operation regardless of
current indication condition.
• Even when servo alarm occurs during the user setting and operating the
key button by the user, the drive displays the content of alarm
immediately.
• Servo drive may store the maximum of 8 alarm contents in the order of
occurrence of servo alarm. Also, the stored alarm can be confirmed
through the monitor mode (dis-16) of Chpater 7-50 and clear the stored
alarm by using the operation mode (run-09) of Clause Chpater 7-45.
Cause When having a defect in a internal part of servo drive or circuit, it is displayed.
Action Replaced the product and inquire to the company.
When it occurs at the time of inputting power, there is an error in control and main
Cause1 power circuit.
Action1 Confirm the presence of wiring and power and inquire to the company if normal.
If it occurs during the operation, it is displayed if the over current occurs in the motor or
Cause2 the internal temperature of device for motor drive is increased for over the permitted
temperature.
Confirm the presence of error in the power and adjust the acceleration or deceleration
Action2 time.
If it occurs when the power is ON, there is an error in the control and main power
Cause1 circuit.
Confirm the presence of error in wiring and power, and inquire to the company if
Action1 normal.
If it occurs during the operation, it is made when the rapid over current was flown on
Cause2 the motor. (when the current of 300[%] or more of rated current is flown to the motor for
2[ms] or more)
Confirm the presence of error in the power, and adjust the acceleration or deceleration
Action2 time.
It occurs when the over current is flown to the regeneration resistor due to the error in
Cause regenerative transistor and regeneration resistor.
Action Replace the servo drive or regeneration resistor.
In the event that current feedback offset adjustment (run-07) is made, it occurs when
Cause the offset current is ±5 [%] or more of rated current.
Action Confirm the motor condition and inquire to the company if it continues to occur.
It occurs when the torque feedback is operated at the maximum torque of 0.5 [sec] or
Cause more.
(Wiring error), (excessive inertia of load), (error in setting rated output of motor)
Confirm the wiring of motor cable.
Action Confirm the load condition and adjust the acceleration and deceleration time.
Confirm motor setting value by referring Chpater 4-6.
It occurs when the torque feedback is continuously operated for rated torque several to
Cause several tens [sec] or more at the rated torque or more.
Confirm the motor cable wiring.
Action Confirm the loading condition and adjust the acceleration and deceleration time.
Confirm motor setting value by referring Chpater 4-6.
It occurs when the heat sink temperature of servo drive exceeds approximately 95
Cause ±10[°C] at 55[°C] or higher ambient temperature.
It occurs when the cooling fan is not operated.
Ambient temperature of servo drive less than 55[°C] or lower.
Action Refer to the installation of Chapter 2 to comply with the user environment.
Cause It occurs when the encoder setting of motor setting [Pr-0.01] is wrong.
Action Reset the encoder by confirming the model name of the motor nameplate.
It occurs when the encoder cable is short-circuited or the power is not supplied to the
Cause encoder.
Action Confirm the wiring of encoder.
Cause It occurs when there is a communication error in the servo drive and absolute encoder.
Action Replace the motor when the wiring of encoder is confirmed and found no error.
It occurs when the internal recharging capacitor voltage of absolute encoder is 2.7 [V]
or less.
Cause It occurs when the battery for absolute encoder has defective connection or not
connected.
Confirm the connection of battery. Replace the battery and refer to the Chpater 7-44 to
Action reset the alarm.
It may occur with the motor rotates in high speed when the main power of servo drive
Cause is disconnected while normally operating and the encoder is operated with external
battery.
Action Turn off/on power or reset the alarm.
It occurs if the number of rotation data is changed when main power of the servo drive
Cause is ON.
Action Turn off/on power or reset the alarm.
Cause It occurs if 1-time rotation data is changed when main power of the servo drive is ON.
When the input voltage exceeds the rated voltage scope, when the regeneration
resistor is short-circuited
Cause When the transistor for regeneration is in error, when operation is made for over the
regenerative capacity
Use rated voltage, replacing the regeneration resistor, replacing the servo drive
Action Confirm whether the inertia of load is excessive.
Cause It occurs when the main input voltage is not within the scope of rated value.
Action Confirm the input voltage.
It occurs when the main power is disconnected or lowered due to the instantaneous
Cause power failure.
Confirm the power or main circuit wiring (noise filter, magnetic contactor ).
Action Adjust the instantaneous power failure maintenance time set [Pr-5.10].
Cause It occurs when the motor is rotated with a speed exceeding the maximum speed.
Confirm the wiring condition of encoder motor cable. Confirm whether there is any
Action problem in tuning. Confirm whether there is any problem in external speed (torque)
command input gain [Pr-2.00], [Pr-4.00].
It occurs when the position error is exceeding the permitted error for position when
Cause controlling the position [Pr-5.09].
Confirm the pulse input wiring of host controller. Confirm whether the pulse input
Action frequency is excessive or not. Reset the gain by referring Chapter 6. Confirm whether
the inertia of load is excessive.
Cause It occurs when the input pulse command frequency of host controller is high.
Confirm the types and frequency of input pulse.
Action
Line drive: 900[kpps] or less. Open collector: 200[kpps] or less
Indicator Emergency-Stop
Cause It occurs when the emergency-stop signal is inputted from the external.
Action Resolve the emergency stop situation and release the emergency-stop input.
It occurs when there is an error in between the portable operator and servo drive that
Cause is caused by the noise or connection cable error.
Action Connection without the noise environment and condition of connection cable.
Cause It occurs when there is an error in the memory that stores the user parameter.
Confirm and reset the recently set parameter and the rest shall be backed up.
Action If frequently occurring, refer the Chpater 7-48 to return to the initial value for
parameter.
It occurs when the setting value that exceeds the setting scope of parameter is
Cause inputted.
Set the parameter within the value of setting scope.
Action Refer to Chpater 7-48 and return to the initial value of the parameter.
Cause It occurs when there is an error in the memory that stores the parameter.
Initialize the parameter by referring to Chpater 7-48.
Action Replace the servo drive in the event of frequent occurrence.
Cause It occurs when the rated output volume (capacity) of servo drive is wrongly set.
Action Inquiry to the company.
In the event an error occurs in servo alarm that is not displayed, it describes
the cause and action.
• The chart below shows the diagnosis on errors when the alarm does not
occur.
Parameter List
Introduction In this chapter, the inspection and the protective function of servo drive are
described.
Topic Page
Introduction A-1
Parameter List A-2
Parameter Group 0
Initial
Parameter type Name LED No. Set range value
Configure motor - - -
/SV-ON 1 0~8 1
P-OT 2 0~8 8
Assign sequence input N-OT 3 0~8 8
signals
/P-CON 4 0~8 4
/A-RST 1 0~8 5
/N-TL 2 0~8 6
Assign sequence input /P-TL 3 0~8 7
signals
/C-SEL 4 0~8 0
/C-DIR 1 0~8 0
/C-SP1 2 0~8 0
Assign sequence input /C-SP2 3 0~8 0
signals
/C-SP3 4 0~8 0
Parameter Group 0
Initial
Parameter type Name LED No. Set range value
/Z-CLP 1 0~8 0
/INHIB 2 0~8 0
Assign sequence input /G-SEL 3 0~8 0
signal
Reserved 4 0~8 0
/ABS-DT 1 0~8 0
/START 2 0~8 0
Assign sequence input /C-SP4 3 0~8 0
signal
/GEAR 4 0~8 0
/P-COM 1 0~3 1
/TG-ON 2 0~3 2
Assign sequence /BK 3 0~3 3
output signal
/V-COM 4 0~3 0
/T-LMT 1 0~3 0
/V-LMT 2 0~3 0
Assign sequence /NEAR 3 0~3 0
output signal
/WARN 4 0~3 0
Servo ID - 1~255 1
Password - - -
Parameter Group 1
Initial
Parameter type Name LED No. Set range value
Parameter Group 2
Initial
Parameter type Name LED No. Set range value
External speed command input - 10.0~2000.0 500.0
gain
Parameter Group 3
Initial
Parameter type Name LED No. Set range value
Position command pulse type 1 0~6 0
Position command pulse type 2 0,1 0
Encoder output pulse direction 3 0,1 0
PCLR input selection 4 0~3 1
encoder
Electronic gear (numerator) - 1~65535 pulse
numbers
encoder
Electronic gear (denominator) - 1~65535 pulse
numbers
Position output pulse - 1~65535 2048
adjustment (numerator)
Parameter Group 4
Initial
Parameter type Name LED No. Set range value
External torque command input - 0.0~100.0 33.3
gain
Parameter Group 5
Initial
Parameter type Name LED No. Set range value
Position completion - 0~250 10
determinaion width
Parameter Group 0
Speed -position
control mode
Torque -position
control mode
Contact
speed-position
control mode
Contact speed-speed
control mode
Contact speed-torque
control mode
Motor configuration
C SMZ - 0 1 B A 1 A NM 1
Motor type Rated output Encoder type
Inertia ratio
Motor inertia
• If the rotor’s inertia is 3[ gf.cm.s ·] and the load’s
intertia is 30[ gf.cm.s ·], the inertia ratio is
10[times].
Load inertia • As for the rotor’s inertia table, please refer to the
motor specifications on the appendix.
Initial Other
Set range Units Setting > End
value details
Applicable
0.00 to 60.00 1.00 [times] ALL
modes
• When setting the inertia ratio, 2 basic gain parameters ([Pr-1.01], [Pr-1.02]) are set automatically
by referring to system gain [Pr-1.00].
• When off-line auto tuning [run-01] function is selected, the servo drive automatically senses the
inertia ratio and sets the inertia ratio [Pr-0.04] accordingly.
Detailed Refer to Chapter 6-3
description
Set values
• As shown on the table below, relevant functions are already assigned to sequence input
parameters and the number of digits of the related configuration window; the user enters
relevant function by selecting a value in the range of ‘1-8’ , excluding value ‘0’.
• For example, if a certain function is to be applied to Pin 5 of CN1, the parameter pertaining to that
signal should be looked up from the table below and the set value entered as ‘3’.
• If the input signal function is not to be used,enter ‘0’.
• If the input signal should be always ON regardless of wiring, enter ‘8’.
The table below is a summary of parameters for each function and the 7-segment digits displayed on
the configuration window. Be sure that the digits on the configuration window match the parameters
relevant to each signal.
Configuration window
of each parameter
Configuration example
Value ‘7’ is set at the 4th digit of the configuration window for
parameter[Pr-0.05].
This value has been set to use the </P-CON> function; it means that the
pin DI#7 of CN1 is to be used as input pin.
Applicable ALL Other details Servo-OFF>Configure>Reapply power>Completed
modes
Detailed Refer to Chapter 5-2
description
Set value
Configuration window
of each parameter
Configuration example
Value ‘3’ has been set as the 4th digit on the configuration window of
parameter [Pr-0.11].
This value is set to output the </NEAR> signal; it means that pin 47 and 48
of CN1 are to be used as output pins.
Applicable Other details Servo-OFF > Configuration>Reapply power >
ALL
modes Completed
Detailed Refer to Chapter 5-2
description
Servo ID
Initial Other
Set range Unit Setting>End
value details
Applicable
1~255 1 - ALL
modes
• Parameter for setting servo ID
• Fix this value to 1 if RS-232 is used.
Password
Password parameter for A/S usage. Unrelated to user; do NOT use this parameter.
Parameter
Parameter
Parameter
Default 1
Applicable modes All
Other Set>End
Parameter
0 - RAK_ASCII
Set values 1 - Modbus_RTU
Default 0
Applicable modes All
Other Set>End
Parameter Group 1
System gain
Initial Other
Set range Unit Setting > End
value details
Related
0~500 50 [Hz] ALL
modes
• A higher value results in higher position/speed/torque related gain values and higher
responsiveness. (However, excessive values can result in noise and vibrations)
• Conversely, lower values result in smaller gain and lower responsiveness; however, the whole
system’s stability is increased.
• Refers to the bandwidth of the entire speed control loop.
• When this value is changed, the gain values [Pr-1.01], [Pr-1.02], [Pr-1.03], [Pr-1.04], [Pr-1.05] are
set automatically according to the control mode while referring to the inertia ratio parameter
[Pr-0.04].
• The lower limit is 10Hz.
Detailed Refer to Chapter 6
description
Initial Other
Set range Unit Setting > End
value details
Applicable
0~10000 60 [Nms] PSC
modes
• Parameter which determines the responsiveness of speed control.
• Value changed simultaneously with change of inertia ratio[Pr-0.04] or system gain[Pr-1.00]
Detailed Refer to Chapter 6
description
Initial Other
Set range Unit Setting > End
value details
Applicable
0~60000 100 [Nms2] modes PSC
Initial Other
Set range Unit Setting > End
value details
Applicable
0~700 20 [Hz] P
modes
• Parameter which determines the responsiveness of position control
• Change set value according to rigidity of load
• Value changed according to system gain[Pr-1.00]
Detailed Refer to Chapter 6
description
Initial Other
Set range Unit Setting > End
value details
Applicable
0~10000 1000 [Hz] ALL
modes
• Suppresses hih frequency components of torque command
• Value changed according to system gain[Pr-1.00].
Detailed Refer to Chapter 6
description
Initial Other
Set range Unit Setting > End
value details
Applicable
0~10000 1000 [Hz] ALL
modes
• Sets low pass cutoff frequency of speed command to suppress high frequency components
• Value changed according to system gain[Pr-1.00]
Detailed Refer to Chapter 6
description
Initial Other
Set range Unit Setting > End
value details
Applicable
0~60000 0 [Hz] ALL
modes
Sets low pass cutoff frequency of position command to suppress high frequency components
Detailed Refer to Chapter 6
description
Initial Other
Set range Unit Servo OFF > Setting > End
value details
Applicable
0~10000 10000 [Hz] ALL
modes
• Torque commands around the set frequency are blocked to suppress vibrations at a specific
frequency band.
• If set to ‘0’, the vibration blocking filter function is not used.
• System gain can be increased further if the resonant frequency according to load is used
appropriately
• If value is not set according to load’s resonant frequency, vibration or noise will occur.
• This parameter is automatically set after auto tuning.
Detailed Refer to Chapter 6
description
Position FF gain
Initial Other
Set range Unit Setting>End
value details
Applicable
0~800 200 [%] ALL
modes
• Larger values result in faster position completion and smaller position tolerances at transient
response condition.
• Value can differ according to load’s type or rigidity; too large values result in vibration.
Detailed Refer to Chapter 6
description
Position FF filter
Initial Other
Set range Unit Setting>End
value details
Applicable
0~2500 200 [Hz] ALL
modes
• Valid if position FF gain[Pr-1.08] is not ‘0’.
• If a value other than ‘0’ set for [Pr-1.08] results in overshoot or vibration, set this value to ‘0’.
Detailed Refer to Chapter 6
description
Changes the speed controller from proportional integral(PI) to proportional(P) automatically during
transient response to suppress overshoot of speed response. Therefore, the position completion time
gets shorter in case of position control.
Set value Details
0 P/PI mode transition not used
If torque command exceeds torque value[%] set at [Pr-1.11], speed controller changes
1 from PI to P.
If torque command exceeds torque value[rpm] set at [Pr-1.11], speed controller
2 changes from PI to P.
If the position tolerance exceeds the position tolerance value[pulse] set at [Pr-1.11],
3 the speed controller changes from PI to P.
Default 3
Applicable Other
ALL Servo-OFF > Setting > End
modes details
Detailed Refer to Chapter 6-21
description
Initial Other
Set range Unit Setting>End
value details
Applicable
0~3000 100 [Variable] ALL
modes
• The unit is determined according to the value set at [Pr-1.10]
• Torque[%],speed[rpm],position[pulse]
• If the speed torque command or the position tolerance exceeds the value set in this parameter,
the speed controller changes from PI type to P type,
Detailed Refer to Chapter 6-21
description
Initial Other
Set range Unit Setting>End
value details
Applicable
0 to 450 0 [rpm] ALL
modes
• In order to shorten the position decision time, if the position tolerance is larger than the value of
[Pr-1.13], a speed bias equal to the value set here is applied.
Detailed Refer to Chapter 6-21
description
Initial Other
Set range Unit Setting>End
value details
Applicable
0 to 250 10 [pulse] ALL
modes
• Set to shorten position decision time; determines at above how many pulses of position tolerance
the bias should be applied.
Detailed Refer to Chapter 6-21
description
Parameter
Parameter
Parameter Group 2
Initial Other
Set range Unit Servo-OFF > Setting > End
value details
Applicable
10.0~2000.0 500.0 [rpm/V] S
modes
• Sets the speed command value[rpm] for the analog speed command input pin(Pin 19,20 of CN1)
• Speed command[rpm] = (Pr-2.00) [rpm/V] x Input voltage[V]
Detailed Refer to Sec. 5.3, Sec.7.6
description
Initial Other
Set range Unit Setting > End
value details
Applicable
0~5000 500 [rpm] ALL
modes
Sets speed for jog operation using (run-00)
This set value is applied on approach speed for homing(run-02).
Detailed Refer to Chapter 4-22, Chapter 7-35
description
Acceleration time
Deceleration time
Initial Other
Set range Unit Setting>End
value details
Applicable
0 to 60000 0 [msec] ALL
modes
• Acceleration/deceleration time and S-operation time are set for smooth operation.
• Acceleration time is the time needed for acceleration from ‘0’ speed to motor’s rated speed.
• Deceleration time is the time needed for deceleration from rated speed to ‘0’ speed.
Motor
rated speed Speed command
Motor
set speed
0
Actual
Motor deceleration
rated speed time
Motor Speed
set speed
0
Time
Acceleration Deceleration
set time set time
S-operation time
Initial Other
Set range Unit Setting > End
value details
Applicable
0 to 5000 0 [msec] ALL
modes
• S-operation time set for smooth operation
• Applied only when acceleration/deceleration time have been set. If value is set to ‘0’,S-operation
is not performed; if a value other than ‘0’ is set, S-operation is performed on acceleration/
deceleration.
Motor Speed
Speed rated speed
Command Command
Motor
set speed
Time
0
Motor
rated speed
Acceldecel Speed
time set
Motor
set speed
Time
0
Motor
S-curve Time rated speed
Setting Speed
Motor
set speed
Time
0 S-curve set time
Other
Set range Initial value Unit Setting > End
details
Applicable
-5000 to 5000 100 to 700 [rpm] C
modes
• Sets each contact speed commands for contact speed control mode
• The operation speed should be entered in advance into the relevant parameters as
below.
• In addition, sequence input signal </C-DIR> is used to change the rotation direction
of each speed command.
Speed command 1 0 0 1
Speed command 2 0 1 0
Speed command 3 0 1 1
Speed command 4 1 0 0
Speed command 5 1 0 1
Speed command 6 1 1 0
Speed command 7 1 1 1
Parameter Initial
value[rpm]
Limit speed
Initial Other
Set range Unit Servo-OFF>Setting>End
value details
Applicable
1~5000 5000 [rpm] ALL
modes
• Limits the operation speed to below this set value in all control modes. .
• There are two methods of speed limitation: limitation thorough this value and limitation through
speed command of upper level controller. Configure by referring to speed limit method selection of
[Pr-2.13].
• In addition, in torque control mode,the mode is changed automatically to speed control mode if
motor speed exceeds this value; speed control is performed using limit speed command.
• If the analog speed command exceeds motor’s maximum speed, the excessive speed command
warning “OSC: is issued.
• If excessive speed command warning is issued, the speed command is automatically reduced to
the motor’s maximum speed.
Detailed Refer to Chapter 7-18
description
Parameter Group 3
Select the pulse type of the higher level controller’s position command pulse.
Positive logic
Input Set
Pulse type Forward rotation Reverse rotation multiplier value
PULS PULS
Pulse train+Sign -
SIGN "H" SIGN "L"
X1 times
X4 times
Negative logic
PULS PULS
Pulse train+Sign -
SIGN "L" SIGN "H"
Sets the encoder’s pulse direction when the servo drive outputs encoder pulse to higher level
controller.
Set value Details
90 deg
Encoder
Phase A of encoder output leads 90 ° at output :Phase A
0 forward rotation
Encoder
output :Phase B
When this signal is input, the position error is cleared to ‘0’ so that, if no more position command
pulses are input, the moor can be halted at current condition. The position error clear(PCLR) input
signal is input at pins (15,16) of CN1.
Sets the signal’s trigger condition at position error clear input to clear the error to ‘0’.
Set value Details
Cleared at H level.
0 As long as H level is maintained, the error stays at (0). "H"
Initial Other
Set range Unit Servo-OFF>Setting>End
value details
Applicable
1~65535 2048 [pulse] P
modes
• By using the electronic gear function, the amount of motor rotation pr input command pulse can
be set arbitrarily.
• The following relationship has to be satisfied: No.,of pulses per 1 motor rotation x Reduction ratio
x 4 (Pr-3.02)
• Maximum resolution=1/ ([No.of pulses per 1 motor rotation] x [Reduction ratio] x 4)
Detailed Refer to Chapter 5-9
description
Initial Other
Set range Unit Servo-OFF > Setting > End
value details
Applicable
1 to 65535 2048 [pulse] ALL
modes
• Sets the number of pulses to be output through the servo drive’s encoder signal output (EA+, EA-,
EB+, EB-) for one motor rotation/
• At [Pr-3.03] , the numerator of the encoder’s output divider ratio is entered. Generally, the number
of pulses to be output at 1 motor rotation is entered.
• At [Pr-3.04], the denominator of the encoder’s output divider ratio is entered. Generally, the number
of pulses output from the encoder connected to the motor for 1 rotation is entered.
• For the encoder output division ratio, the relationship [Pr-3.03] £ [Pr-3.04] has to be satisfied.
Numera
tor No .,of output pulsesper Output to higher level
rotation = controlle r
Denomi
nator
(1)
The same function as Pr-3.01 or Pr-3.02. These are effective only when /GEAR input is ON.
Initial Other
Set range Unit Servo-OFF>Setting>End
value details
Applicable
1~65535 32768 [pulse] P
modes
• By using the electronic gear function, the amount of motor rotation per input command pulse can
be set arbitrarily.
• The following relationship has to be satisfied: No.,of pulses per 1 motor rotation x Reduction ratio
x 4 (Pr-3.02)
• Maximum resolution=1/ ([No.of pulses per 1 motor rotation] x [Reduction ratio] x 4)
Detailed Refer to Chapter 5-9
description
Parameter Group 4
Initial Other
Set range Unit Servo OFF>Setting>End
value details
Applicable
0.0~100.0 33.3 [%/V] ALL
modes
• Set the speed command value[%] for 1[V] on the analog torque command input pin(pin 21,22 of
CN1)
• Torque command[%] = [Pr-4.00] [%/V] x input voltage[V]
Detailed Refer to Chapter 5-38
description
Initial Other
Set range Unit
value details Setting > End
Applicable
0~300 300 [%] ALL
modes
Limits forward and reverse direction torque on motor separately. (internally limited)
Detailed Refer to Chapter 5-38
description
Initial Other
Set range Unit Setting>End
value details
Applicable
0~300 100 [%] ALL
modes
• The torque imposed on the motor is internally limited automaticaly by the values set on [Pr-4.01],
[Pr-4.02]. Additionally, it is also limited by the values set on [Pr-4.03], [Pr-4.04] when external </
P-TL>,</N-TL> signals are input through sequence input.
• The torque limit according to internal limit [Pr-4.01] and [Pr-4.02] takes precedence to external
torque limit </P-TL> and </N-TL> signals.
Torque / P- TL Torque
Forward
torque OFF
Pr-4.01 Pr-4.03
(+)
ON
Speed Speed
Torque 0 0
command
Speed 0 Speed 0
Pr-4.02 ON Pr-4.04
(-)
Reverse
torque OFF
Torque / N- TL Torque
Initial Other
Set range Unit Setting>End
value details
Applicable
0~300 300 [%] ALL
modes
• Limits the torque imposed on the motor if the motor is halted by overtravel(<P-OT>,<N-OT>) input
signal during rotation.
• Unlike external and internal torque limit, the torque limit value for overtravel input is same for
forward and reverse direction.
Detailed Refer to Chapter 5-38
description
Initial Other
Set range Unit Setting > End
value details
Applicable
-100~100 0 [%] ALL
modes
• Initial torque bias is a function to apply an initial torque equal to the load’s descent which occurs
when the servo-ON signal is applied in a direction opposite to the iitial torque descent direction
in order to prevent descent due to gravity when trying to control such vertical axis load.
• If the initial torque bias has been set properly according to the load’s descending power, the
descent of vertical load at initial stage of operation can be prevented.
If vertical load is controlled, use a motor with built-in brake or install a brake system.
Detailed Refer to Chapter 6-20
description
Parameter Group 5
Initial Other
Set range Unit
value details Setting > End
Applicable
0~250 10 [pulse] P
modes
• Set to output the position completion indication singal</P-COM>, a sequence output signal.
• Sets the position(pulse) error range to output the position completion indication signal when the
servo drive performs position(pulse) command according to the higher level controller’s
position(pulse) command
• When the position error comes within set range and the position pulse command frequency is
entered below 100[pps] the position completion detection signal(/P-COM> is output at the
assigned output pin.
Detailed Refer to Chapter 5-38
description
Initial Other
Set range Unit Setting > End
value details
Related
0 to 250 20 [pulse] P
modes
• Set to output the position approximation detection signal </NEAR> .which is a sequence output
signal.
• Sets the position(pulse) error’s range to output the position approximation detection signal when
the servo drive performs position(pulse) command according to position(pulse) command of
higher level controller.
• If position error is within set range and the input position pulse command’s frequency is below
100[pps] , the position completion detection signal</NEAR> is output to the assigned output pin.
Position
error
Pr-5.01
Pr-5.00
Time
0
/NEAR ON OFF ON
/P-COM ON OFF ON
Initial Other
Set range Unit Setting > End
value details
Applicable
0 to 1000 10 [rpm] S
modes
• Set to output speed match detection signal</V-COM> which is a sequence output signal.
• Sets the speed error range for output of speed match signal when the servo drive performs speed
command according to speed command of higher level controller.
• When the speed error is within set range and </V-COM> output is assigned to sequence output
signal, the speed match detection signal</V-COM> is output to assigned output pin.
Rotation
speed
Set
Pr-5.02 value
Actual speed
Time
0
Initial Other
Set range Unit Configure>Complete
value details
Applicable
1 to 5000 20 [rpm] ALL
modes
• Set to output rotation detection signal</TG-ON> which is a sequence output signal.
• </TG-ON>signal is output if the servo motor’s rotation speed exceeds set value.
• If value is set too small, rotation detection signal can be output even due to small vibrations.
Rotation
speed
Actual speed
Pr-5.03 Set value
Time
0
Detailed
description Refer to Chapter 5-28
Initial
Set range Unit Other details Configure>Complete
value
Applicable
0~5000 0 [rpm] S
modes
• Used if the motor shows slight operation even when setting analog speed command to ‘0’ at
speed control mode. The zero-clamp function ignores small speed commands to keep motor at
halted state.
• Small speed commands below set value are ignored; if speed command exceeds set value, motor
is accelerated to set speed.
• Zero clamp function is activated when sequence input signal </Z-CLP> is assigned and signal is
input into assigned input pin.
• If a value other than ‘0’ is set at Pr-5.04, automatical speed clamp is performed regardless of
</Z-CLP> input even if </Z-CLP> input is not assigned.
Analog speed
command(external
input voltage)
Pr-5.04
0 Time
/Z-CLP input OFF ON
Actual speed
command
Pr-5.04
0 Time
Initial Other
Set range Unit Servo-OFF>Setting>End
value details
Applicable
0~1000 0 10[ms] ALL
modes
/SV-ON command of
higher level controller ON
OFF
Brake release Servo driver executing
Wait time /SV-ON command OFF ON
Initial Other
Set range Unit Servo-OFF>Configure>Complete
value details
Applicable
0~1000 0 10[ms] ALL
modes
• The time from the drive’s receiving servo-OFF command from higher level controller to the drive’s
actually setting servo-OFF can be set.
• This parameter is used to set the delay time from the higher level controller’s command to set
servo-OFF to the drive’s activating the motor drive.
Initial Other
Set range Unit Servo OFF>Configure>Complete
value details
Applicable
0~1000 50 10[ms] ALL
modes
• Higher level controller issues Servo-OFF command to drive in order to halt motor.
• The time delay from this point to the motor brake’s actual operation can be set.
/SV-ON command of
upper level controller ON OFF
Initial
Set range Unit Other details Servo-OFF > Configure > Complete
value
Applicable
0~1000 100 [rpm] ALL
modes
The motor speed at the point the motor brake is activated can be set.
/SV-ON command of
upper level controller ON OFF
Motor brake
Inactive Operation
Initial Other
Set range Unit Configure>Complete
value details
Applicable
0~65535 20480 [pulse] P
modes
• If the difference between position command and actual position exceeds th set value, a position
error overflow servo alarm(E.PoSEr) is issued.
Detailed Refer to Chapter 5-9
description
Initial Other
Set range Unit Servo-OFF>Configure>Complete
value details
Reserved
Initial Other
Set range Unit Configure > Complete
value details
Refer to
0-0001 ~ Applicable
0-0500 table ALL
6-2500 modes
below
• The servo drive outputs analog monitoring signals which can be input into an oscilloscope so that
the user can monitor the control operation.
Detailed Refer to Chapter 7-25
description
Initial
Setting Limit Unit Others Setting > End
Value
0-0001 ~ Table Applicable
3-0500 ALL
6-2500 below Mode
Sets whether battery should be used when using serial absolute value encoder.
This parameter is not valid when using ordinary absolute value encoders.
If value is set to 1, the serial absolute value encoder is recognized as a serial incremental encoder;
therefore, in this case, the multirotation data from the absolute value encoder is not valid.
Set value Details
0 Battery used
1 Battery not used
Applicable ALL Other details Servo-OFF > Configure > Reapply power > Completed
modes
When high resolution encoder is used by activating speed monitor, the speed ripple occurring at low
speed operation can be reduced.
Initial value 0
Set value Details
0 Speed monitor is not used
1 Speed monitor is used
Applicable P,S,C Other details Servo-OFF > Configure > Reapply power > Completed
modes
When excessive speed error detection function is used, E.SPDER error shows up when the speed
error is out of tolerable speed error range.
Set value Details
0 Excessive speed error detection function is not used
1 Excessive speed error detection function is used
Applicable S, P Other details Servo-OFF > Configure > Reapply power > Completed
modes
Jog Operation
Homing
Alarm Reset
Parameter Initialiaztion
Introduction
Topic Page
Introduction B-1
Servo Drive Specification B-2
50 5 <165>
140 55
5
5
4.
All-In-One
Ø
2-
145
155
153
5
165 70
50 20 140 55
5
5
4.
All-In-One
Ø
2-
145
155
153
5
210 90
63 27 185 55
5
5
All-In-One
5.
Ø
2-
145
155
198
Specification
Basic Specification
2048/2500/5000/10000 P/R (Incremental/Absolute Type)
Feedback Method 131072 P/R (17bit Serial Incremental/Absolute Type)
Operation Temp./Humidity 0 to 50/90% RH or less
Storing Temp./Humidity -25 to 80/90% or less
Mounting Method Base Mounting Type
Speed Control Range 1:5000
Performance
SpeedTorque Control
Load ±0.01% or less (at rate speed or in load rate 0 to 100%)
Variation
Speed Voltage 0% (at rate speed or in supply voltage 170 to 253VAC)
Variation Variation
Temp. ±0.1% or less (at rated speed or in ambient temperature
Variation 25±25)
Frequency Bandwidth 550Hz
Torque Control Precision ±2%
Acceleration 0 to 60sec
/Decelertion Time
Feedforward
Control
Position
0 to 100%
Compensation
Positioning Completion 0 to 250[pulse]
width
CW+CCW, Pulse + Sign
Command Signal
Position Control
Rotation Direction
Speed
I/O Signal
Position Output Type Absolute Encoder Data
Feedback Open Collector Output : Z pulse
Dividing Ratio User Defined
Servo-On, Alarm Reset, Gain Group Change
Forward/Reverse Torque Limit, Homing
Forward/Reverse Rotation Limit
Sequence Input P/PI or control mode change
Multi-Step Speed Command
Zero-Clamp, Position Command Override
Absolute Encoder Data Transmission
Positioning Completion, Position Nearing
Speed Coincidence, Rotation Detection
Seauence Output Torque Limit Detection, Speed Limit Detection
Brake Control Signal, Warning
Emergency Stop H/W Emergency Stop Input
Dynamic Brake Operate in case of main power-off or alarm
Regenarative Resistor Built in 400W or more
Overcurrent, Overvoltage, Overload, Overspeed
Overregenertion, Overheat
Protection Temporary Power Down, Low Voltage, CPU Fault
Communication Fault
2CH D/A outputs for measuring commands or feedback,
Monitoring error
Communication RS-232C
OEMAX Controls
www.oemax.com Trademarks not belonging to Rockwell Automation Korea
are property of their respective companies.
www.oemax.co.kr
Publication CSD3P-UM001E-EN-P - February 2008 7 Copyright © 2008 Rockwell Automation Korea. All rights reserved.