DeltaV CHARM
DeltaV CHARM
DeltaV CHARM
November 2019
www.emerson.com/deltav 2
DeltaV Electronic Marshalling November 2019
The CIOC carrier is mounted to the top of a vertical DIN rail and Baseplate extenders and cables provide great flexibility to the
up to eight CHARM Baseplates are mounted below it, snapping CHARM installation in existing cabinets or in custom enclosures.
easily to the DIN rail as they are connected to each other. The Cables are redundant, each carrying 24V DC field power,
bus termination assembly is attached at the bottom. A standard 6.3V DC CHARM power, and one of the communication busses.
DIN-rail lock is used to keep the entire assembly in place.
Bus termination provides added robustness for the
A pair of CIOCs installs on the carrier and communicates over communication bus and is installed at the end of the
a redundant Ethernet network with up to four controllers, physical bus.
allowing great flexibility and ease of system expansion.
Label features are available to identify channel usage and
Communication modules are available for copper and
Baseplate identification to help with maintenance.
fiberoptic media.
CHARMs can be added to any existing baseplate position and
Each baseplate is ordered with 12 terminal blocks: standard
autosensed online. Additional CIOCs can be added online.
terminal blocks, fused injected power terminal blocks, or relay
output terminal blocks.
CHARM Types
Electronic Marshalling eliminates the need to partition the I/O
wiring to specific channels based on signal type. Simply connect A variety of analog and discrete CHARMs are available to meet
field signal multi-cores in an orderly fashion as desired. Install your specific requirements. The following CHARMs are available
the appropriate CHARM to complete the field circuit and the starting with v11.3.1:
signal is ready to be used by any one of four controllers. No
AI 4-20 mA HART
cross-wiring required.
RTD
Each CHARM acts as a circuit protection device and field
wiring disconnect. Signals are inherently current-limited to Thermocouple / mV
protect against wiring faults to ground. Each CHARM provides
AI 0-10V DC Isolated
surge protection to meet industry standards in the area of
EMC. Under extreme overvoltage conditions due to incorrect AO 4-20 mA HART
field wiring, the CHARM will act as a fuse to protect adjacent DI NAMUR
channels. Signal faults are thus isolated to the single CHARM.
DI 24V DC low-side sense (dry contact)
CHARMs can be partially ejected to a locked position that
disconnects the field wiring from the system to perform field DI 24V DC Isolated
maintenance actions or to remove power to a field device. DO 24V DC High Side
Activating the CHARM latch ejects the CHARM to the detent
position. Closing the latch locks the CHARM in place and DO 100mA Energy Limited
isolates the field wiring for field work. DO 24V DC Isolated
24V DC Power
DI 120V AC Isolated
DI 230V AC Isolated
DO V AC Isolated
www.emerson.com/deltav 3
DeltaV Electronic Marshalling November 2019
All CHARMs have a bi-color power/integrity LED that indicates Each baseplate has a local power bus that can be connected
the health of the CHARM. The indications provide clear, to 24V DC or 120/230V AC through the injected power input
actionable instruction to the maintenance personnel. terminals, located on the Address Plug terminal block. Both,
the fused-injected power Terminal Block, the 3-wire DI fused-
Green Solid: Normal Operation
injected power Terminal Block, and the 3-wire AI Fused Injected
Green Blink: Normal awaiting configuration Terminal block connect to this power bus to provide system
power to the field circuit through the isolated CHARM. You can
Red Blink: Fault detected on wiring
combine isolated and system powered circuits on the same
Red Solid: Internal Fault detected baseplate, however, all system powered channels on a baseplate
Discrete CHARMs have a yellow LED to indicate the state of the share the same power source.
field signal. (On = circuit is energized) The Relay Output Terminal Block is designed for high output
All CHARMs meet ISA 71.04-1985 severity level G3 (harsh) current applications and requires the DO 24V DC High-side
corrosion specifications. CHARM to drive the relay coil. The Relay Output Term blocks
provide a normally open and normally closed contact with the
24V DC based discrete input CHARMs support pulse counters following ratings:
with a maximum frequency of 10 KHz.
28.8V DC at 5 A switching current
www.emerson.com/deltav 4
DeltaV Electronic Marshalling November 2019
www.emerson.com/deltav 5
DeltaV Electronic Marshalling November 2019
Hardware Specifications
Common Environmental Specifications (all components)
Operating Temperature* -40 to 70°C (-40 to 158°F)**
Protection Rating IP 20
Operating Temperature -40 to 70°C (-40 to 158°F). Operating Temperature -40 to 60°C (-40 to 140°F).
www.emerson.com/deltav 6
DeltaV Electronic Marshalling November 2019
CHARMs.
www.emerson.com/deltav 7
DeltaV Electronic Marshalling November 2019
CHARM 3-wire DI Fused-Injected-Power Terminal Block. CHARM Relay Output Terminal Block.
CHARM 3-wire AI Fused Injected Power Terminal Block. CHARM Thermocouple / mV Terminal Block.
www.emerson.com/deltav 8
DeltaV Electronic Marshalling November 2019
Redundant Ethernet connections via replaceable IOPs Fiberoptic: 100BASE-FX with MTRJ connectors;
Full duplex operation;
Multimode - 2 km nominal distance.
Copper twisted pair: 10/100BASE-TX with RJ45 connectors;
Full duplex operation
100 m distance
Specifications for CHARM I/O Card (CIOC) and CHARM I/O Card 2 (CIOC2)
Number of I/O Channels 96 Channels, individually defined signal types
www.emerson.com/deltav 9
DeltaV Electronic Marshalling November 2019
LED Indicators
Green – Power Indicates DC power is applied
CHARM Baseplate
Number of Channels per Baseplate 12
Shield Connections 1 Screw Cage terminal per channel, plus 1 for cable shield
0.32 – 2.5 mm2 / 22 – 14 AWG
Gold plated connectors for shield continuity
Wire Strip Length 7 - 9 mm / 0.28 – 0.36 in
Color Black
www.emerson.com/deltav 10
DeltaV Electronic Marshalling November 2019
Color Black
Color Black
Color Black
Color Black
Color Black
*Actual Current draw is determined by type of CHARM and associated field devices.
**Actual Current draw through the Address Block Terminal Block is determined by the combined current draws through Injected-Power Terminal blocks on each CHARM Baseplate.
www.emerson.com/deltav 11
DeltaV Electronic Marshalling November 2019
Simplified Circuit and Connection Diagrams for AI HART CHARM 0/ 4 to 20 mA Two-Wire and Four-Wire transmitters.
www.emerson.com/deltav 12
DeltaV Electronic Marshalling November 2019
Simplified Circuit and Connection Diagrams for AI HART CHARM 0/ 4 to 20 mA with 3-wire AI Fused Injected Power Terminal Block.
www.emerson.com/deltav 13
DeltaV Electronic Marshalling November 2019
www.emerson.com/deltav 14
DeltaV Electronic Marshalling November 2019
www.emerson.com/deltav 15
DeltaV Electronic Marshalling November 2019
Simplified Circuit and Connection Diagram for Thermocouple/mV CHARM with Thermocouple/mV
Terminal Block.
www.emerson.com/deltav 16
DeltaV Electronic Marshalling November 2019
Input Impedance 10 MΩ
www.emerson.com/deltav 17
DeltaV Electronic Marshalling November 2019
www.emerson.com/deltav 18
DeltaV Electronic Marshalling November 2019
Fault detection capable with NAMUR sensor or with an optional Guaranteed short circuit: <100 Ω
field resistor pack* as shown on Option 2 in diagram below Guaranteed good status: 400 Ω to 40 kΩ
(Option 1 in diagram below is not fault detection capable) Guaranteed open circuit: >75 kΩ
*VS6904 End of Line Resistance Module can be used for option 2, see DeltaV SIS Conditioning Components PDS for more info.
www.emerson.com/deltav 19
DeltaV Electronic Marshalling November 2019
Fault detection capable with an optional field resistor pack* as Guaranteed short circuit: <100 Ω
shown on Option 1 in diagram below (Without resistor pack Guaranteed good status: 400 Ω to 40 kΩ
fault detection is not possible) Guaranteed open circuit: > 75 kΩ
*VS6904 End of Line Resistance Module can be used for option 1, see DeltaV SIS Conditioning Components PDS for more info.
Simplified Circuit and Connection Diagram for DI 24V DC low-side sense CHARM.
www.emerson.com/deltav 20
DeltaV Electronic Marshalling November 2019
Simplified Circuit and Connection Diagrams for DI 24 V DC Isolated CHARM with 3-wire DI Fused Injected-Power Terminal Block.
www.emerson.com/deltav 21
DeltaV Electronic Marshalling November 2019
Simplified Circuit and Connection Diagram for DO 24V DC High Side CHARM.
Simplified Circuit and Connection Diagram for DO 24V DC High Side CHARM with
CHARM Relay Output Terminal Block.
www.emerson.com/deltav 22
DeltaV Electronic Marshalling November 2019
Simplified Circuit and Connection Diagram for DO 100 mA Energy limited CHARM.
www.emerson.com/deltav 23
DeltaV Electronic Marshalling November 2019
www.emerson.com/deltav 24
DeltaV Electronic Marshalling November 2019
Simplified Circuit and Connection Diagrams for 24V DC Power Simplified Circuit and Connection Diagrams for 24V DC Power
CHARM with Fused Injected-Power Terminal Block – CHARM with Fused Injected-Power Terminal Block - powering 4-wire
powering 3-wire HART Transmitter connected to HART Transmitter connected to AI HART CHARM 0/ 4 to 20 mA.
AI HART CHARM 0/ 4 to 20 mA.
www.emerson.com/deltav 25
DeltaV Electronic Marshalling November 2019
Frequency 50/60 Hz
Simplified Circuit and Connection Diagrams for DI 120V AC Isolated CHARM with 3-wire DI Fused-Injected-Power Terminal Block.
www.emerson.com/deltav 26
DeltaV Electronic Marshalling November 2019
Frequency 50/60 Hz
Simplified Circuit and Connection Diagrams for DI 120V AC Isolated Plus CHARM.
Simplified Circuit and Connection Diagrams for DI 120V AC Isolated Plus CHARM with 3-wire DI Fused-Injected-Power Terminal Block.
www.emerson.com/deltav 27
DeltaV Electronic Marshalling November 2019
Frequency 50/60 Hz
Simplified Circuit and Connection Diagrams for DI 230V AC Isolated CHARM with 3-wire DI Fused-Injected-Power Terminal Block.
www.emerson.com/deltav 28
DeltaV Electronic Marshalling November 2019
www.emerson.com/deltav 29
DeltaV Electronic Marshalling November 2019
*For hazardous area installations, please refer to installation instructions from ASCO.
www.emerson.com/deltav 30
DeltaV Electronic Marshalling November 2019
IEC60079-0
CHARM I/O hardware requires:
IEC60079-15
SD Plus controllers with DeltaV v11.3.1 or later software
Marine Certifications: IACS E10
SX controllers with DeltaV v11.3.1 or later software
ABS Certificate of Design Assessment
SQ controllers with DeltaV v11.3.1 or later software
DNV-GL Marine Certificate
MD Plus controllers with DeltaV v14.3 or later software
Wurldtech:
MQ controllers with DeltaV v14.3 or later software
CIOC: Achilles Communications Certification
MX controllers with DeltaV v14.3 or later software
Level 1 (v.13.3.1)
PK controllers with DeltaV v14.3 or later software
Pending: CIOC2: Achilles Communications Certification
When assigning CHARMs to MD Plus and SD Plus controllers, Level 2 (v.14.3.1)
make sure to evaluate the Time Utilization Chart on the
controller in DeltaV Diagnostics to ensure the additional Hazardous Area/Location
communication load can be handled by the controller.
DeltaV Electronic Marshalling solutions can be installed
S-series and M-series controllers can be installed on the same
and used based on the following Standards: (see actual
DeltaV Area Control Network in v11 and beyond. PK controllers
certificates for exact product markings for each product)
can be installed on the same DeltaV Area Control network in
v14.3 and beyond. FM (USA)
Control modules can be assigned to any controller and inter- Installation and Field Circuits:
controller references are fully supported between different
Class I, Division 2, Groups A, B, C, D, T4
types of controllers.
cFM (Canada)
Certifications Installation and Field Circuits:
www.emerson.com/deltav 31
DeltaV Electronic Marshalling November 2019
www.emerson.com/deltav 32
DeltaV Electronic Marshalling November 2019
Ordering Information
CHARM I/O Cards and Carrier
Redundant CIOC, includes 2 CHARMs I/O Cards, (Order these with standard cabinets) SE6502
www.emerson.com/deltav 33
DeltaV Electronic Marshalling November 2019
Ordering Information
CHARM I/O Baseplate Extender and Terminator
www.emerson.com/deltav 34
DeltaV Electronic Marshalling November 2019
Ordering Information
High Voltage Instrumentation CHARMs
DO V AC Isolated SE4302T03
* 24V DC Power CHARM requires DeltaV v12.3 or later software to be able to configure and use the diagnostic Information.
** The DI 120V AC Isolated Plus CHARM requires a HotFix to be used with DeltaV v11.3.1 and v12.3.1.
Terminal Blocks
www.emerson.com/deltav 35
DeltaV Electronic Marshalling November 2019
www.emerson.com/deltav 36
DeltaV Electronic Marshalling November 2019
Emerson
North America, Latin America:
©2019, Emerson. All rights reserved.
+1 800 833 8314 or
+1 512 832 3774 The Emerson logo is a trademark and service mark of Emerson Electric Co. The DeltaV logo is
a mark of one of the Emerson family of companies. All other marks are the property of their
Asia Pacific: respective owners.
+65 6777 8211 The contents of this publication are presented for informational purposes only, and while
diligent efforts were made to ensure their accuracy, they are not to be construed as warranties
Europe, Middle East: or guarantees, express or implied, regarding the products or services described herein or their
+41 41 768 6111 use or applicability. All sales are governed by our terms and conditions, which are available on
request. We reserve the right to modify or improve the designs or specifications of our products
www.emerson.com/deltav at any time without notice.