Tue Jan 08 2013 11:36:45 Settings (Enabled Features) PAGE 1

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR

SR489 SETUP
PREFERENCES
Default Message Cycle Time 2.0 s
Default Message Timeout 300 s
Parameter Averages Calc. Period 15 min
Temperature Display Units Celsius
Waveform Trigger Position 25 %
Waveform Memory Buffer 8 x 28 Cycles

MESSAGE SCRATCHPAD
First Scratchpad Message 2x2.5MW MASLI SMAL HYDRO PROJECT
Second Scratchpad Message Text 2
Third Scratchpad Message Text 3
Fourth Scratchpad Message Text 4
Fifth Scratchpad Message GE MULTILIN 489 Generator Relay

COMMUNICATION
Ethernet IP Address 1. 1. 1. 1
Ethernet Subnet Mask 255.255.252. 0
Slave Address 254
Computer RS485 Baud Rate 9600 baud
Auxiliary RS485 Baud Rate 9600 baud

SYSTEM SETUP
CURRENT SENSING
Phase CT Primary 750 A
Ground CT 1 A Secondary
Ground CT Ratio 750 :1

VOLTAGE SENSING
VT Connection Type Wye
Transformer Ratio 30.00 :1
Neutral Voltage Connection No

GEN. PARAMETERS
Generator Rated MVA 3.125 MVA
Generator Rated Power Factor 0.80
Generator Voltage Phase-Phase 3300 V
Generator Nominal Frequency 50 Hz
Generator Phase Sequence ABC

SERIAL START-STOP
Serial Start/Stop Initiation Off

DIGITAL INPUTS
BREAKER STATUS
Breaker Status Breaker Auxiliary a

GENERAL PURPOSE
GENERAL A
Assign Digital Input (A) Input 1
Input Name (A) Input A
Asserted Digital Input State (A) Closed
Block Input From Online (A) 0s
General Input A Control Off
Pulsed Control Relay Dwell Time (A) 0.0 s
Control Relay A No Relays
General Input A Control Events Off
General Input A Alarm Off
Alarm Relays A Relay 5
General Input A Alarm Delay 5.0 s
General Input A Alarm Events Off
General Input A Trip Unlatched
Trip Relays A Relay 1
General Input A Trip Delay 5.0 s

DUAL SETPOINTS
Active Setpoint Group(Dual Setpoints) Group 1
Edit Setpoint Group(Dual Setpoints) Group 1

OUTPUT RELAYS
Tue Jan 08 2013 11:36:45 Settings (Enabled Features) PAGE 2

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR

1 TRIP
R1 Trip All Resets

2 AUXILIARY
R2 Auxiliary All Resets

3 AUXILIARY
R3 Auxiliary All Resets

4 AUXILIARY
R4 Auxiliary All Resets

5 ALARM
R5 Alarm All Resets

6 SERVICE
R6 Service All Resets

MONITORING
TRIP COUNTER
Trip Counter Alarm Off

BREAKER FAILURE
Breaker Failure Alarm Off

CURRENT DEMAND
Current Demand Period 15 min
Current Demand Alarm Off

MW DEMAND
MW Demand Period 15 min
MW Demand Alarm Off

MVAR DEMAND
Mvar Demand Period 15 min
Mvar Demand Alarm Off

MVA DEMAND
MVA Demand Period 15 min
MVA Demand Alarm Off

PULSE OUTPUT
Positive kWh Pulse Output Relays No Relays
Positive kWh Pulse Output Interval 10 kwh
Positive kvarh Pulse Output Relays No Relays
Positive kvarh Pulse Output Interval 10 kvarh
Negative kvarh Pulse Output Relays No Relays
Negative kvarh Pulse Output Interval 10 kvarh
Pulse Width 200 ms

TRIP COIL MONITOR


Trip Coil Monitor Alarm Off

VT FUSE FAILURE
VT Fuse Failure Alarm Off

GEN. RUN HOURS


Initial Gen. Running Hour 0h
Gen. Running Hour Alarm Off

PROTECTION
CURRENT ELEMENTS[SETPOINT GROUP 1]
OVERCURRENT ALARM[SETPOINT GROUP 1]
Overcurrent Alarm Off

OFFLINE O/C[SETPOINT GROUP 1]


Offline Overcurrent Trip Off

INADVERTENT ENERG.[SETPOINT GROUP 1]


Inadvertent Energize Trip Off
Tue Jan 08 2013 11:36:45 Settings (Enabled Features) PAGE 3

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR

PHASE OVERCURRENT[SETPOINT GROUP 1]


Phase Overcurrent Trip Off
Voltage Lower Limit 10 %

NEGATIVE SEQUENCE[SETPOINT GROUP 1]


Negative Sequence Alarm Latched
Negative Sequence Alarm Relays Relay 5
Neg. Sequence Alarm Pickup 15 % FLA
Negative Sequence Alarm Delay 15.0 s
Negative Sequence Alarm Events On
Negative Sequence O/C Trip Latched
Negative Sequence O/C Trip Relays Relays 1-2-3-4
Neg. Sequence O/C Trip Pickup 20 % FLA
Neg. Sequence O/C Constant k 1
Neg. Sequence O/C Max. Time 10 s
Neg. Sequence O/C Reset Rate 0.0 s

GROUND O/C[SETPOINT GROUP 1]


Ground O/C Alarm Off
Ground O/C Trip Latched
Ground O/C Trip Relays Relays 1-2-3-4
Ground O/C Trip Pickup 0.25 x CT
Ground O/C Curve Shape ANSI Normally Inv.
Ground O/C Curve Multiplier 0.10
Ground O/C Curve Reset Instantaneous

PHASE DIFFERENTIAL[SETPOINT GROUP 1]


Phase Differential Trip Off

GROUND DIRECTIONAL[SETPOINT GROUP 1]


Ground Directional MTA 0°
Ground Directional Alarm Off
Ground Directional Trip Off

HIGH-SET PHASE O/C[SETPOINT GROUP 1]


High-Set Phase O/C Trip Latched
High-Set Phase O/C Trip Relays Relay 1
High-Set Phase O/C Pickup 5.00 x CT
High-Set Phase O/C Delay 0.00 s

VOLTAGE ELEMENTS[SETPOINT GROUP 1]


UNDERVOLTAGE[SETPOINT GROUP 1]
Undervoltage Alarm Off
Undervoltage Trip Off

OVERVOLTAGE[SETPOINT GROUP 1]
Overvoltage Alarm Latched
Overvoltage Alarm Relay Relay 5
Overvoltage Alarm Pickup 1.10 x Rated
Overvoltage Alarm Delay 3.0 s
Overvoltage Alarm Events On
Overvoltage Trip Latched
Overvoltage Trip Relay Relay 1
Overvoltage Trip Pickup 1.15 x Rated
Overvoltage Trip Delay 3.0 s
Overvoltage Curve Reset Rate 0.0 s
Overvoltage Curve Element Definite Time

VOLTS/HERTZ[SETPOINT GROUP 1]
Volts/Hertz Alarm Latched
Volts/Hertz Alarm Relay Relay 5
Volts/Hertz Alarm Pickup 1.10 X Nominal
Volts/Hertz Alarm Delay 3.0 s
Volts/Hertz Alarm Events On
Volts/Hertz Trip Latched
Volts/Hertz Trip Relay Relay 1
Volts/Hertz Trip Pickup 1.15 X Nominal
Volts/Hertz Trip Delay 3.0 s
Volts/Hertz Trip Reset Rate 0.0
Volts/Hertz Trip Element Curve #1
Tue Jan 08 2013 11:36:45 Settings (Enabled Features) PAGE 4

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR

PHASE REVERSAL[SETPOINT GROUP 1]


Phase Reversal Trip Latched
Phase Reversal Trip Relay Relays 1-2-3-4

UNDERFREQUENCY[SETPOINT GROUP 1]
Block Underfrequency from Online 1s
Voltage Level Cutoff 0.50 x Rated
Underfrequency Alarm Latched
Underfrequency Alarm Relay Relay 5
Underfrequency Alarm Level 47.50 Hz
Underfrequency Alarm Delay 3.0 s
Underfrequency Alarm Events On
Underfrequency Trip Latched
Underfrequency Trip Relay Relay 1
Underfrequency Trip Level 1 47.00 Hz
Underfrequency Trip Delay 1 3.0 s
Underfrequency Trip Level 2 46.00 Hz
Underfrequency Trip Delay 2 1.0 s

OVERFREQUENCY[SETPOINT GROUP 1]
Block Overfrequency from Online 1s
Voltage Level Cutoff (overfrequency) 0.70 x Rated
Overfrequency Alarm Latched
Overfrequency Alarm Relay Relay 5
Overfrequency Alarm Level 52.50 Hz
Overfrequency Alarm Delay 2.0 s
Overfrequency Alarm Events On
Overfrequency Trip Latched
Overfrequency Trip Relay Relay 1
Overfrequency Trip Level 1 53.00 Hz
Overfrequency Trip Delay1 3.0 s
Overfrequency Trip Level2 53.50 Hz
Overfrequency Trip Delay2 1.0 s

NEUTRAL O/V (FUND)[SETPOINT GROUP 1]


Neutral Overvoltage Alarm Off
Neutral Overvoltage Trip Off

NEUTRAL U/V (3RD)[SETPOINT GROUP 1]


Neutral Undervoltage Alarm Off
Neutral Undervoltage Trip Off

LOSS OF EXCITATION[SETPOINT GROUP 1]


Enable Voltage Supervision Yes
Voltage Level 0.70 x Rated
Circle 1 Trip Latched
Circle 1 Trip Relay Relay 1
Circle 1 Diameter 18.0 Ohm sec
Circle 1 Offset 1.9 Ohm sec
Circle 1 Trip Delay 3.0 s
Circle 2 Trip Latched
Circle 2 Trip Relay Relay 1
Circle 2 Diameter 22.8 Ohm sec
Circle 2 Offset 1.9 Ohm sec
Circle 2 Trip Delay 3.0 s

DISTANCE[SETPOINT GROUP 1]
Fuse Failure Supervision Off
Zone 1 Trip Off
Zone 2 Trip Off

POWER ELEMENTS[SETPOINT GROUP 1]


REACTIVE POWER ALARM[SETPOINT GROUP 1]
Block Mvar Element from Online 1s
Reactive Power Alarm Off

REACTIVE POWER TRIP[SETPOINT GROUP 1]


Block Mvar Element from Online 1s
Reactive Power Trip Latched
Reactive Power Trip Relays Relay 1
Positive Mvar Trip Level 1.40 X Rated
Tue Jan 08 2013 11:36:45 Settings (Enabled Features) PAGE 5

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR

REACTIVE POWER TRIP[SETPOINT GROUP 1] (continued from last page)


Negative Mvar Trip Level 0.75 X Rated
Positive Mvar Trip Delay 10.0 s
Negative Mvar Trip Delay 1.0 s

REVERSE POWER ALARM[SETPOINT GROUP 1]


Block Reverse Power from Online 10 s
Reverse Power Alarm Latched
Reverse Power Alarm Relays Relay 5
Reverse Power Alarm Level 0.05 x Rated MW
Reverse Power Alarm Delay 10.0 s
Reverse Power Alarm Events On

REVERSE POWER TRIP[SETPOINT GROUP 1]


Block Reverse Power from Online 10 s
Reverse Power Trip Latched
Reverse Power Trip Relays Relay 1
Reverse Power Trip Level 0.05 x Rated MW
Reverse Power Trip Delay 10.0 s

LOW FORWARD POWER ALARM[SETPOINT GROUP 1]


Block Low Fwd Power From Online 0s
Low Forward Power Alarm Off

LOW FORWARD POWER TRIP[SETPOINT GROUP 1]


Block Low Fwd Power From Online 0s
Low Forward Power Trip Off

RTD TEMPERATURE[SETPOINT GROUP 1]


RTD TYPES[SETPOINT GROUP 1]
Stator RTD Type 100 Ohm Platinum
Bearing RTD Type 100 Ohm Platinum
Ambient RTD Type 100 Ohm Platinum
Other RTD Type 100 Ohm Platinum

RTD #1[SETPOINT GROUP 1]


RTD#1 Application Stator
RTD#1 Name
RTD#1 Alarm Off
RTD#1 Trip Off

RTD #2[SETPOINT GROUP 1]


RTD#2 Application Stator
RTD#2 Name
RTD#2 Alarm Off
RTD#2 Trip Off

RTD #3[SETPOINT GROUP 1]


RTD#3 Application Stator
RTD#3 Name
RTD#3 Alarm Off
RTD#3 Trip Off

RTD #4[SETPOINT GROUP 1]


RTD#4 Application Stator
RTD#4 Name
RTD#4 Alarm Off
RTD#4 Trip Off

RTD #5[SETPOINT GROUP 1]


RTD#5 Application Stator
RTD#5 Name
RTD#5 Alarm Off
RTD#5 Trip Off

RTD #6[SETPOINT GROUP 1]


RTD#6 Application Stator
RTD#6 Name
RTD#6 Alarm Off
RTD#6 Trip Off
Tue Jan 08 2013 11:36:45 Settings (Enabled Features) PAGE 6

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR

RTD #7[SETPOINT GROUP 1]


RTD#7 Application Bearing
RTD#7 Name
RTD#7 Alarm Off
RTD#7 Trip Off

RTD #8[SETPOINT GROUP 1]


RTD#8 Application Bearing
RTD#8 Name
RTD#8 Alarm Off
RTD#8 Trip Off

RTD #9[SETPOINT GROUP 1]


RTD#9 Application Bearing
RTD#9 Name
RTD#9 Alarm Off
RTD#9 Trip Off

RTD #10[SETPOINT GROUP 1]


RTD#10 Application Bearing
RTD#10 Name
RTD#10 Alarm Off
RTD#10 Trip Off

RTD #11[SETPOINT GROUP 1]


RTD#11 Application Other
RTD#11 Name
RTD#11 Alarm Off
RTD#11 Trip Off

RTD #12[SETPOINT GROUP 1]


RTD#12 Application Ambient
RTD#12 Name
RTD#12 Alarm Off
RTD#12 Trip Off

RTD-ALARMS[SETPOINT GROUP 1]
Open RTD Sensor Alarm Off
RTD Short/Low Temp Alarm Off

THERMAL MODEL[SETPOINT GROUP 1]


THERMAL SETUP[SETPOINT GROUP 1]
Enable Thermal Model No

OVERLOAD CURVES[SETPOINT GROUP 1]


Select Curve Style Standard
Standard Overload Curve Number 4

CURRENT ELEMENTS[SETPOINT GROUP 2]


OVERCURRENT ALARM[SETPOINT GROUP 2]
Overcurrent Alarm Off

OFFLINE O/C[SETPOINT GROUP 2]


Offline Overcurrent Trip Off

INADVERTENT ENERG.[SETPOINT GROUP 2]


Inadvertent Energize Trip Off

PHASE OVERCURRENT[SETPOINT GROUP 2]


Phase Overcurrent Trip Off

NEGATIVE SEQUENCE[SETPOINT GROUP 2]


Negative Sequence Alarm Off
Negative Sequence O/C Trip Off

GROUND O/C[SETPOINT GROUP 2]


Ground O/C Alarm Off
Ground O/C Trip Off

PHASE DIFFERENTIAL[SETPOINT GROUP 2]


Phase Differential Trip Off
Tue Jan 08 2013 11:36:45 Settings (Enabled Features) PAGE 7

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR

GROUND DIRECTIONAL[SETPOINT GROUP 2]


Ground Directional MTA 0°
Ground Directional Alarm Off
Ground Directional Trip Off

HIGH-SET PHASE O/C[SETPOINT GROUP 2]


High-Set Phase O/C Trip Off

VOLTAGE ELEMENTS[SETPOINT GROUP 2]


UNDERVOLTAGE[SETPOINT GROUP 2]
Undervoltage Alarm Off
Undervoltage Trip Off

OVERVOLTAGE[SETPOINT GROUP 2]
Overvoltage Alarm Off
Overvoltage Trip Off

VOLTS/HERTZ[SETPOINT GROUP 2]
Volts/Hertz Alarm Off
Volts/Hertz Trip Off

PHASE REVERSAL[SETPOINT GROUP 2]


Phase Reversal Trip Off

UNDERFREQUENCY[SETPOINT GROUP 2]
Block Underfrequency from Online 1s
Voltage Level Cutoff 0.50 x Rated
Underfrequency Alarm Off
Underfrequency Trip Off

OVERFREQUENCY[SETPOINT GROUP 2]
Block Overfrequency from Online 1s
Voltage Level Cutoff (overfrequency) 0.50 x Rated
Overfrequency Alarm Off
Overfrequency Trip Off

NEUTRAL O/V (FUND)[SETPOINT GROUP 2]


Neutral Overvoltage Alarm Off
Neutral Overvoltage Trip Off

NEUTRAL U/V (3RD)[SETPOINT GROUP 2]


Neutral Undervoltage Alarm Off
Neutral Undervoltage Trip Off

LOSS OF EXCITATION[SETPOINT GROUP 2]


Enable Voltage Supervision No
Circle 1 Trip Off
Circle 2 Trip Off

DISTANCE[SETPOINT GROUP 2]
Fuse Failure Supervision Off
Zone 1 Trip Off
Zone 2 Trip Off

POWER ELEMENTS[SETPOINT GROUP 2]


REACTIVE POWER ALARM[SETPOINT GROUP 2]
Block Mvar Element from Online 1s
Reactive Power Alarm Off

REACTIVE POWER TRIP[SETPOINT GROUP 2]


Block Mvar Element from Online 1s
Reactive Power Trip Off

REVERSE POWER ALARM[SETPOINT GROUP 2]


Block Reverse Power from Online 1s
Reverse Power Alarm Off

REVERSE POWER TRIP[SETPOINT GROUP 2]


Block Reverse Power from Online 1s
Reverse Power Trip Off
Tue Jan 08 2013 11:36:45 Settings (Enabled Features) PAGE 8

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR

LOW FORWARD POWER ALARM[SETPOINT GROUP 2]


Block Low Fwd Power From Online 0s
Low Forward Power Alarm Off

LOW FORWARD POWER TRIP[SETPOINT GROUP 2]


Block Low Fwd Power From Online 0s
Low Forward Power Trip Off

RTD TEMPERATURE[SETPOINT GROUP 2]


RTD TYPES[SETPOINT GROUP 2]
Stator RTD Type 100 Ohm Platinum
Bearing RTD Type 100 Ohm Platinum
Ambient RTD Type 100 Ohm Platinum
Other RTD Type 100 Ohm Platinum

RTD #1[SETPOINT GROUP 2]


RTD#1 Application Stator
RTD#1 Name
RTD#1 Alarm Off
RTD#1 Trip Off

RTD #2[SETPOINT GROUP 2]


RTD#2 Application Stator
RTD#2 Name
RTD#2 Alarm Off
RTD#2 Trip Off

RTD #3[SETPOINT GROUP 2]


RTD#3 Application Stator
RTD#3 Name
RTD#3 Alarm Off
RTD#3 Trip Off

RTD #4[SETPOINT GROUP 2]


RTD#4 Application Stator
RTD#4 Name
RTD#4 Alarm Off
RTD#4 Trip Off

RTD #5[SETPOINT GROUP 2]


RTD#5 Application Stator
RTD#5 Name
RTD#5 Alarm Off
RTD#5 Trip Off

RTD #6[SETPOINT GROUP 2]


RTD#6 Application Stator
RTD#6 Name
RTD#6 Alarm Off
RTD#6 Trip Off

RTD #7[SETPOINT GROUP 2]


RTD#7 Application Bearing
RTD#7 Name
RTD#7 Alarm Off
RTD#7 Trip Off

RTD #8[SETPOINT GROUP 2]


RTD#8 Application Bearing
RTD#8 Name
RTD#8 Alarm Off
RTD#8 Trip Off

RTD #9[SETPOINT GROUP 2]


RTD#9 Application Bearing
RTD#9 Name
RTD#9 Alarm Off
RTD#9 Trip Off

RTD #10[SETPOINT GROUP 2]


Tue Jan 08 2013 11:36:45 Settings (Enabled Features) PAGE 9

UNIT 1 TG.489
C:\USERS\ADMIN\DESKTOP\
DEVICE DEFINITION
ORDER CODE: 489-P1-HI-A20-T
VERSION: 4.0X
SERIAL NUMBER: B3211623
DESCRIPTION: (NONE)
TEXT COLOR

RTD #10[SETPOINT GROUP 2] (continued from last page)


RTD#10 Application Bearing
RTD#10 Name
RTD#10 Alarm Off
RTD#10 Trip Off

RTD #11[SETPOINT GROUP 2]


RTD#11 Application Other
RTD#11 Name
RTD#11 Alarm Off
RTD#11 Trip Off

RTD #12[SETPOINT GROUP 2]


RTD#12 Application Ambient
RTD#12 Name
RTD#12 Alarm Off
RTD#12 Trip Off

RTD-ALARMS[SETPOINT GROUP 2]
Open RTD Sensor Alarm Off
RTD Short/Low Temp Alarm Off

THERMAL MODEL[SETPOINT GROUP 2]


THERMAL SETUP[SETPOINT GROUP 2]
Enable Thermal Model No

OVERLOAD CURVES[SETPOINT GROUP 2]


Select Curve Style Standard
Standard Overload Curve Number 4