How To Calculate Transformer Size
How To Calculate Transformer Size
In this post, we’ll detail how to calculate the required KVA for a 3 phase transformer. Actually, The
calculation of KVA capacity for a Three Phase Transformer is based on Winding Voltage and Amperage
information. The simple formula to calculate the rating of three phase Transformers is:
KVA = (√3. V x I) /1000
Where: V is the voltage (volts) and I is the current (amps).
Calculate & Find the Rating of Single Phase & Three Phase Transformers in kVA
We know that, Transformer always rated in kVA. Below are the two simple formulas to find the rating of
Single phase and Three phase Transformers.
P = V x I.
kVA= (V x I) / 1000
P = √3. V x I
But Wait, A question is raised here… Look at the General nameplate rating of a 100kVAtransformer.
Did you notice something????Anyway, I don’t care what is your answer 😉 but lets me try to explain.
Here is the rating of Transformer is 100kVA.
But Primary Voltages or High Voltages (H.V) is 11000 V = 11kV.
And Primary Current on High Voltage side is 5.25 Amperes.
Also Secondary voltages or Low Voltages (L.V) is 415 Volts
And Secondary Current (Current on Low voltages side) is 139.1 Amperes.
In simple words,
Transformer rating in kVA = 100 kVA
Primary Voltages = 11000 = 11kV
Primary Current = 5.25 A
Secondary Voltages = 415V
Secondary Current = 139.1 Amperes.
Example:
the following figure presents a nameplate of a three phase transformer. It’s rating is 100 KVA. Using
the aforementioned formula, let’s confirm this rating:
(KVA)in = (KVA)out
x----------------------------------------------------------------------x
Find the phase voltage, or "Vphase," associated with the 3-phase system. Refer
to system specifications. For example, assume 4,000 volts, which is typical for
power in the megawatt range
Find the power factor, "pf," of the load powered by the megawatt power
distribution system. Refer to specifications of the load. A typical power factor for
3-phase loads is 0.8.
Find the total power delivered by the power distribution system in Megavolts-
amperes or "MVA." Use the formula MVA = MW/pf where MW is the megawatt
value of the system. For example, if MW is 20MW and pf is 0.8:
I=(KVA*1000)/(1.732*V)
for example-
LT Current=(1250*1000)/(1.732*415)=1250000/718.78=1739.057 Amp.
I=(KVA*1000)/V
X-----------------------------------------------------------------------X
KVA is calculated by multiplying the line to line maximum voltage & maximum phase current; then
multiplying this value with 1.732 in case of three phase ; lastly dividing the final value by 1000 for KVA
and 100,000 for MVA
KVA calculation
For three phase KVA= (V*I*1.732)/1000
MVA calculation-
For three phase MVA= (V*I*1.732)/100,000