990-9814C EN Rev 2.1.2.3
990-9814C EN Rev 2.1.2.3
990-9814C EN Rev 2.1.2.3
990-9814C-001
Publication Date: 4/2018
APC by Schneider Electric Legal Disclaimer
The information presented in this manual is not warranted by APC by Schneider Electric to be authoritative,
error free, or complete. This publication is not meant to be a substitute for a detailed operational and site
specific development plan. Therefore, APC by Schneider Electric assumes no liability for damages, violations of
codes, improper installation, system failures, or any other problems that could arise based on the use of this
Publication.
The information contained in this Publication is provided as is and has been prepared solely for the purpose of
evaluating data center design and construction. This Publication has been compiled in good faith by APC by
Schneider Electric. However, no representation is made or warranty given, either express or implied, as to the
completeness or accuracy of the information this Publication contains.
Copyright, intellectual, and all other proprietary rights in the content (including but not limited to software, audio,
video, text, and photographs) rests with APC by Schneider Electric or its licensors. All rights in the content not
expressly granted herein are reserved. No rights of any kind are licensed or assigned or shall otherwise pass to
persons accessing this information.
Safety.....................................................................................................................1
Safety Information for the Rack Monitor 250 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Introduction ............................................................................................................2
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Document Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Additional Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Receiving Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Inventory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Additional Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
StruxureWare-certified . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Physical Description...............................................................................................5
Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Rear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
LED Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Link-RX/TX (10/100) LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Installation..............................................................................................................7
Install the Rack Monitor 250 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Toolless peg-mount installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Rack-mount installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Power cord and network cable connections . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Connect Sensors and Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Connect sensors to universal sensor ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Connect other sensors and devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Cascade devices to A-Link ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Wire the Modbus Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
4-wire (full duplex) connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
2-wire (half duplex) connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Quick Configuration .............................................................................................12
TCP/IP Configuration Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Device IP Configuration Utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
BOOTP and DHCP configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Local access to the command line interface . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Remote access to the command line interface . . . . . . . . . . . . . . . . . . . . . . . . . .14
Command line interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
.INI file utility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
How to Recover from a Lost Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Access the Rack Monitor 250 ..............................................................................17
Web User Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Telnet and SSH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Telnet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
SSH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
The addition of this symbol to a Danger or Warning safety label indicates that an electrical
hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards.
Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will result
in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, can result in death or
serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or
moderate injury.
NOTICE
NOTICE addresses practices not related to physical injury including certain environmental
hazards, potential damage or loss of data.
CAUTION
FALLING EQUIPMENT HAZARD
Do not create a hazardous condition due to uneven mechanical loading. For example, do not use
the appliance as a shelf.
Failure to follow these instructions can result in injury or equipment damage.
The Rack Monitor 250 includes six ports for connecting temperature and humidity sensors, and other
sensors including fluid detection sensors and third-party dry contact sensors. Using other ports on the
Rack Monitor 250, you can connect two door switch sensors, two rack door handles, a beacon, and
temperature and humidity sensors with digital display.
To expand your system, you can connect the Rack Monitor 250 to your building management system,
connect up to six NetBotz Rack Sensor Pod 150s and additional sensors, and use ports that provide
power to or allow control of other devices.
NOTE: The Rack Monitor 250 cannot be connected to or networked with any other NetBotz appliances.
It uses unique software that is not compatible with other NetBotz products.
Document Overview
The NetBotz Rack Monitor 250 Installation and Quick Configuration Manual describes how to install the
Rack Monitor 250, connect the provided temperature/humidity sensor and other additional devices, and
configure the network settings. After performing the quick configuration procedures in this manual, you
can access your system through its software interface, perform additional configuration tasks, and begin
monitoring the environment.
Additional Documentation
Unless otherwise noted, the following documentation is available on the applicable product page on the
APC by Schneider Electric website, www.apc.com. To quickly find a product page on the APC website,
enter the product name or part number in the Search field.
NetBotz Rack Monitor 250 User Guide – Includes details for using, managing, and configuring the
system with a NetBotz Rack Monitor 250 (NBRK0250).
Security Handbook – Describes security features for the APC Network Management Card and for
devices with embedded components of the Network Management Card.
Modbus Register Map – defines NetBotz Rack Monitor 250 (NBRK0250) Modbus datapoint registers for
communication with a building management system using the Modbus protocol.
Modbus Over Serial Line Specification & Implementation Guide – The Modbus standard. Available at
www.modbus.org.
Receiving Inspection
Inspect the package and its contents for shipping damage and see that the parts included in the
shipment match the parts listed in the inventory table. Immediately report any shipping damage to the
shipping agent. Report missing contents, damage, or other problems to APC by Schneider Electric or
your APC by Schneider Electric reseller.
The shipping and packaging materials are recyclable. Please save them for later use or dispose of them
appropriately.
aem0315c
Item Description Not Shown
NetBotz Rack Monitor 250 • USB A-USB mini B configuration cable
USB Coordinator (NBWC100U) for wireless sensor • Temperature and Humidity Sensor
network (installed in the Wireless port under a plastic (AP9335TH) and hardware kit
cover) • Wireless Temperature Sensor
1.8-m (6-ft) IEC-320-C13 to IEC-320-C14 power cord (NBWS100T) and hardware kit
• Basement mount hardware kit
1.8-m (6-ft) NEMA 5-15P to IEC-320-C13 power cord
• NetBotz 125 kHz Handle Kit
1/4-W, 150-ohm resistors (2) (NBHN125) (Only included with
1/4-W, 499-ohm resistors (2) NBACS125)
203-mm (8-in) hook and loop cable strap • NetBotz 13.56 MHz Handle Kit
(NBHN1356) (Only included with
203-mm (8-in) nylon tie wraps (2)
NBACS1356)
Mounting brackets for a standard 19-in rack (2)
A-Link terminator
8-32 x 1/4-in Phillips-head screws (4)
StruxureWare-certified
This product is certified for use in StruxureWare® for Data Centers systems.
aem0537a
Ch
Gnd
1+ 0-
TxD
Modbus
Wireless
Handle #1 Handle #2 4 5 6
!
Item Description
AC Line Inlet The input power connection; see “Specifications” on page 22 for voltage information.
Switched Outlet Provides power to a device at a total maximum amperage of 10 A. Activates a
connected device when configured events occur. (For example, a fan may be
connected to this outlet, and the outlet may be configured to turn on when a high
threshold violation occurs for a temperature sensor.)
Wireless Network USB port with NetBotz USB Coordinator (NBWC100U) installed. Used with included
Coordinator Wireless Temperature Sensor (NBWS100T) to monitor temperature. Additional
wireless sensors can be purchased separately.
Rack Access ports Ports for the door switch sensors on doors #1 and #2
Ports for the handle sensors (NBHN125 or NBHN1356) on doors #1 and #2
Beacon port Used for connecting an alarm beacon (AP9324).
Universal sensor Used to connect APC by Schneider Electric sensors and third-party dry contact
ports sensors. (See “Connect sensors to universal sensor ports” on page 9 for a list of
sensors.) Third-party dry contact sensors require a Dry Contact Cable (NBES0304).
USB port Used to connect USB devices to the appliance.
Voltage Output Provides 12 Vdc or 24 Vdc (75 mA) to a connected device.
Relay Output Used for connecting relay-controlled external devices.
10/100 Network Provides the connection to the network. Status and link LEDs indicate network
Port traffic. See “Status LED” on page 6.
A-Link ports Used to cascade NetBotz Rack Sensor Pod 150s (NBPD0150), or connect
Temperature/Humidity Sensors with Digital Display (AP9520TH). Provides
communications and power using standard CAT-5 cabling with straight-through
wiring.
NOTE: To cascade multiple devices, connect a supplemental power supply
(100–240 Vac/24 Vdc, part number AP9505i) to a NetBotz Rack Sensor Pod 150.
For details, see “Cascade devices to A-Link ports” on page 10.
Modbus RS-485 Provides the connection to a building management system using the
port Modbus protocol.
Console Port Used to connect the USB A-USB mini B configuration cable, when configuring initial
network settings.
NOTE: If you are unable to access the appliance using the console port, you may
need to install a serial-to-USB virtual COM port driver. The USB vendor is FTDI; the
driver type is VCP. Driver downloads are available on the FTDI Chip website.
Power LED Indicates whether the unit is receiving power (blue = receiving power; dark = not
receiving power).
Reset button Restarts the Rack Monitor 250 network management interface.
LED Descriptions
Status LED
This LED (light-emitting diode) indicates the status of the Rack Monitor 250.
Condition Description
Off One of the following situations exists:
• The Rack Monitor 250 is not receiving input power.
• The Rack Monitor 250 is not operating properly. It may need to be repaired
or replaced. Contact Customer Support at www.apc.com and
www.help.ecostruxureit.com.
Solid green The Rack Monitor 250 has valid TCP/IP settings.
Solid orange A hardware malfunction has been detected in the Rack Monitor 250. Contact
Customer Support at www.apc.com and www.help.ecostruxureit.com.
Flashing green The Rack Monitor 250 does not have valid TCP/IP settings.*
Flashing orange The Rack Monitor 250 is making BOOTP requests.*
Rapidly flashing A user initiated a LED blink test from the user interface.
green
Alternately flashing If the LED is flashing slowly, the Rack Monitor 250 is making DHCP†
green and orange requests.*
If the LED is flashing rapidly, the Rack Monitor 250 is starting up.
*If you do not use a BOOTP or DHCP server, see “TCP/IP Configuration Methods” on page 12 to configure the
TCP/IP settings.
†To use a DHCP server, see “BOOTP and DHCP configuration” on page 13.
Condition Description
Off One or more of the following situations exist:
• The Rack Monitor 250 is not receiving input power.
• The cable that connects the Rack Monitor 250 to the network is
disconnected or not functioning properly.
• The Rack Monitor 250 is turned off or not operating correctly. It may need
to be repaired or replaced. Contact Customer Support at www.apc.com or
www.help.ecostruxureit.com.
Solid green The Rack Monitor 250 is connected to a network operating at 10 Megabits
per second (Mbps).
Solid orange The Rack Monitor 250 is connected to a network operating at 100 Mbps.
Flashing green The Rack Monitor 250 is receiving or transmitting data packets at 10 Mbps.
Flashing orange The Rack Monitor 250 is receiving or transmitting data packets at 100 Mbps.
NOTE: Install the Rack Monitor 250 in an environment compatible with the environmental specifications
on page 30.
NOTICE
Use only the hardware provided when installing the brackets.
aem0049a
Rack-mount installation
1. Choose a location for the Rack Monitor 250 in the front or rear of the rack.
The Rack Monitor 250 occupies one U-space. A notched hole or a number 7
on the vertical rail of the rack denotes the middle of a U-space.
1U 6
5
ns0014a
aem0198b
3. Secure the Rack Monitor 250 to the rack,
using cage nuts and screws (not provided).
4. See “Power cord and network cable
connections” on page 8.
aem0208b
Power cord and network cable connections
CAUTION
UNEXPECTED EQUIPMENT OPERATION
• Before you energize the Rack Monitor 250, review the electrical specifications on page 31 to
avoid overloading the circuit providing power.
• Make sure you properly ground the Rack Monitor 250; plug it directly into a wall outlet or verify
the ground path if you connect it to a power strip.
Failure to follow these instructions can result in injury or equipment damage.
NOTE: The NetBotz Rack Monitor 250 is not a PoE compatible device. Do not connect a NetBotz Rack
Monitor 250 to a PoE (Power over Ethernet) switch.
Connect the appropriate power cord to the AC Line Inlet of the Rack Monitor 250.
1. Secure the power cord using the tie wraps.
2. Connect a standard network cable to the Rack Monitor 250.
3. Plug the power cord into a power source.
4. Use the hook and loop cable strap and the 25-mm (1-in) wide tie wrap to secure cables.
NOTE:
• Third-party dry contact sensors require the NetBotz Dry Contact Cable (NBES0304). To connect a
sensor to the cable, follow the instructions provided with the sensor and the instructions provided
with the cable.
• The length of a sensor cable can be extended using RJ-45 female-to-female couplings and
standard CAT5 cabling. See “System Specifications” on page 24 for maximum cable lengths.
Device Port/outlet
Alarm beacon AP9324 Beacon port*
Door switch sensors • Universal sensor ports
• NBES0302 • Rack Access ports: Door #1 and Door #2
• NBES0303 NOTE: When using both a handle kit and a door switch sensor,
connect the door switch sensor to a Rack Access Door port.
Handles Rack Access ports: Handle #1 and Handle #2
• NBHN125
• NBHN1356
Sensor Pod150 (NBPD0150) A-Link ports†
Temperature sensor A-Link ports†
AP9520TH
Wiring Closet Ventilation Unit Switched outlet*
ACF301
*See “Configure Outlet-controlled Devices” on page 21 for configuration details.
†See “Cascade devices to A-Link ports” on page 10 to cascade multiple devices.
NOTE: The Rack Monitor 250 is not compatible with the following:
– Door switch cable included with the NetBotz Rack Access PX-HID (AP9361)
– NetBotz Sensor Pod 180 (NBPD0180)
A-Link is an APC by Schneider Electric proprietary CAN (Controller Area Network) bus. Devices
compatible with A-Link are not Ethernet devices and cannot coexist on an Ethernet bus with other
networking devices, such as hubs and switches.
Before performing this procedure, follow the installation instructions provided with your NetBotz Rack
Sensor Pod 150s and sensors. If you cascade several devices, be sure you have a supplemental power
supply (Power Supply 100–240 Vac/24 Vdc—AP9505i) to connect to your system.
NOTICE
Do not use crossover cables.
aem0119b
power supply (AP9505i) to the 24 (NBPD0150)
-Link
VDC Input jack of one of the Rack
Sensor Pod 150s.
Temerature/
NOTE: The first time a NetBotz
Humididty
Rack Sensor Pod 150 receives
Sensor with
-Link
For details on Modbus register settings, see the Modbus register map document for your specific
Modbus-enabled device.
The Modbus standard specifies 150 ohm termination resistors at each end of a bus. Unless the bus is
very long and operating at high data rates, these resistors are not needed.
Busses under 2000 feet operating at 9600 baud, or under 1000 feet operating at 19,200 baud, should
not require termination.
aem0539a
2-wire (half duplex) connection diagram
aem0540a
You must configure the following TCP/IP settings before the Rack Monitor 250 can operate on a network:
• IP address
• Subnet mask
• Default gateway
If a default gateway is unavailable, use the IP address of a computer that is located on the same subnet
as the Rack Monitor 250 and that is usually running. The Rack Monitor 250 uses the default gateway to
test the network when traffic is very light.
NOTE: Do not use the loopback address (127.0.0.1) as the default gateway address. It disables the
network interface and requires you to reset TCP/IP settings to their defaults using a local serial login.
See the NetBotz Rack Monitor 250 User Guide on www.apc.com for more information about the
watchdog role of the default gateway.
System requirements. The Utility runs on Microsoft Windows 2000, Windows Server® 2003, Windows
Server 2012 and on both 32- and 64-bit versions of Windows XP, Windows Vista, Windows 2008,
Windows 7, Windows 8 and Windows 10 operating systems.
When installed, the Utility is available through the Windows “Start Menu” option.
A user configuration (.INI) file can function as a BOOTP or DHCP boot file. For more information, see the
TCP/IP configuration section of the Rack Monitor 250 User Guide on the APC by Schneider Electric
website, www.apc.com.
If neither of these servers is available, see “Device IP Configuration Utility” on page 12, “Local access to
the command line interface” on page 14, or “Remote access to the command line interface” on page 14
to configure the needed TCP/IP settings.
BOOTP. For the Rack Monitor 250 to use a BOOTP server to configure its TCP/IP settings, it must find a
properly configured RFC951-compliant BOOTP server.
In the BOOTPTAB file of the BOOTP server, enter the MAC address of the Rack Monitor 250, IP
address, subnet mask, and default gateway, and, optionally, a bootup file name. Look for the MAC
address on bottom of the Rack Monitor 250 or on the Quality Assurance Slip included in the package.
When the Rack Monitor 250 reboots, the BOOTP server provides it with the TCP/IP settings.
• If you specified a bootup file name, the Rack Monitor 250 attempts to transfer that file from the
BOOTP server using TFTP or FTP. The Rack Monitor 250 assumes all settings specified in the
bootup file.
• If you did not specify a bootup file name, you can configure the other settings of the Rack Monitor
250 remotely through its Web interface or command line interface; the user name and password
are both apc, by default.
DHCP. You can use an RFC2131/RFC2132-compliant DHCP server to configure the TCP/IP settings for
the Rack Monitor 250.
This section summarizes the Rack Monitor 250 communication with a DHCP server. For more detail
about how a DHCP server can configure the network settings for a Rack Monitor 250, see the Rack
Monitor 250 User Guide on www.apc.com.
1. The Rack Monitor 250 sends out a DHCP request that uses the following to identify itself:
– A Vendor Class Identifier (APC by default)
– A Client Identifier (by default, the MAC address of the Rack Monitor 250)
– A User Class Identifier (by default, the identification of the application firmware installed on the
Rack Monitor 250)
2. A properly configured DHCP server responds with a DHCP offer that includes all the settings the
Rack Monitor 250 needs for network communication. The DHCP offer also includes the Vendor
Specific Information option (DHCP option 43). The Rack Monitor 250 can be configured to ignore
DHCP offers that do not encapsulate the APC cookie in DHCP option 43 using the following
hexadecimal format. (The Rack Monitor 250 does not require this cookie by default).
Option 43 = 01 04 31 41 50 43
where
– the first byte (01) is the code
– the second byte (04) is the length
– the remaining bytes (31 41 50 43) are the APC cookie.
See your DHCP server documentation to add code to the Vendor Specific Information option.
The Rack Monitor 250 Web interface has options to use vendor-specific data to require the DHCP server
to provide an “APC” cookie. See the Rack Monitor 250 User Guide on www.apc.com for information.
After the Rack Monitor 250 has its IP address configured, you can use Telnet, without first using ARP
and Ping, to access that Rack Monitor 250.
1. Use the MAC address of the Rack Monitor 250 in the ARP command to define the IP address.
NOTE: Look for the MAC address on the bottom of the Rack Monitor 250 or on the Quality
Assurance Slip included in the package.
For example, to define 156.205.14.141 as the IP address of a Rack Monitor 250 with 00 c0 b7 63
9f 67 as its MAC address, use one of the following commands:
– Windows command format:
arp -s 156.205.14.141 00-c0-b7-63-9f-67
– LINUX command format:
arp -s 156.205.14.141 00:c0:b7:63:9f:67
2. Use Ping with a size of 113 bytes to assign the IP address defined by the ARP command. For the
IP address defined in step 1, use one of the following commands:
– Windows command format:
ping 156.205.14.141 -l 113
– LINUX command format:
ping 156.205.14.141 -s 113
3. Use Telnet to access the Rack Monitor 250 at its newly assigned IP address. For example:
telnet 156.205.14.141
3. Type reboot. The Rack Monitor 250 restarts to apply the changes.
8. Type quit or exit to log off, reconnect any serial cable you disconnected, and restart any service
you disabled.
For more information on the interfaces, see the NetBotz Rack Monitor 250 User Guide on
www.apc.com.
When you use a Web browser to configure Rack Monitor 250 options or to view the event and data logs,
you can use either HTTP or HTTPS:
• HTTP (enabled by default) provides authentication by user name and password but no
encryption.
• HTTPS provides security through Secure Sockets Layer (SSL); encrypts user names, passwords,
and data being transmitted; and authenticates the Rack Monitor 250 using digital certificates.
To access the Web user interface and configure the security of your device on the network:
1. Address the Rack Monitor 250 by its IP address (or DNS name if configured).
2. Enter the user name and password (by default, apc and apc for an Administrator).
3. To enable or disable HTTP or HTTPS, go to Configuration > Network > Web >Access.
For more information on selecting and configuring network security, see the Security Handbook. For
details on how to access the Security Handbook, see “Additional documentation” on page 2.
Telnet
Telnet provides authentication by user name and password, but not the benefits of encryption. To use
Telnet to access the CLI of the Rack Monitor 250:
1. At a command prompt, use the following command line, and press ENTER:
telnet address
As address, use the IP address of the Rack Monitor 250 (or DNS name if configured).
2. Enter the user name and password (by default, apc and apc for an Administrator, or device and
apc for a Device User).
The interface, user accounts, and user access rights are the same whether you access the CLI through
SSH or Telnet. However, to use SSH, you must first configure SSH and have an SSH client program
installed on your computer.
See the NetBotz Rack Monitor 250 User Guide on www.apc.com for more information on configuring
and using SSH.
SNMPv2c is also supported by the SNMPv1 interface and configuration settings. For more information,
see FAQ article FA156193: Go to www.apc.com, select Support > Resources and Tools > FAQs, then
enter the article number in the search bar.
SNMPv3
SNMPv3 uses a system of user profiles to identify users for GETs, SETs, and trap receivers. An SNMPv3
user must have a user profile assigned in the MIB software program to perform GETs and SETs, browse
the MIB, and receive traps. The default settings are no authentication and no privacy.
NOTE: To use SNMPv3, you must have a MIB program that supports SNMPv3. The Rack Monitor 250
supports MD5 or SHA authentication and DES or AES privacy (encryption).
To enable or disable SNMP access, you must be an Administrator. Go to Configuration > Network, and
use the Access option under SNMPv1 or SNMPv3.
Modbus
In the Rack Monitor 250 user interface, go to Configuration > Network > Modbus > serial (or TCP).
1. Check the box to enable access to the Modbus serial or TCP interface.
2. Set the connection parameters for the Modbus connection:
– For the TCP connection, specify a port number (502, or 5000 to 32768). Click Apply.
– For the serial connection, specify the parameters. The default serial connection settings are
9600 baud, 8 data bits, parity even, and 1 stop bit.
a. Set Parity to None.
b. Specify the Target Unique ID (1 to 247).
c. Click Apply.
NOTE: The Rack Monitor 250 sets the value for stop bits automatically based on parity according to the
Modbus standard. When parity is set to None, 2 stop bits are used.
The Rack Monitor 250 with the NetBotz 125 kHz Handle Kit (NBHN0125) supports the following 125 kHz
proximity cards:
• H10301 26-bit
• H10302 37-bit
• H10304 37-bit with facility code
• CORP-1000
The Rack Monitor 250 with the NetBotz 13.56 MHz Handle Kit (NBHN1356) supports the following
13.56MHz proximity cards:
• MIFARE Classic 4-byte UID
• MIFARE Classic 7-byte UID
• MIFARE DESFIRE
• MIFARE PLUS
• iClass
To view, modify, or delete registered users, go to Configuration > Device > User Access > Registered
Users.
For more information about configuring rack access, see the NetBotz Rack Monitor 250 User Guide on
www.apc.com.
The Rack Monitor 250 must be communicating on the network, and you must have access to its Web
user interface to configure the wireless sensor network.
For information, see “Access the Rack Monitor 250” on page 17.
The wireless sensors appear in the list as they join the network. Auto Join runs for five hours, or until you
end it manually.
When you remove one or more wireless sensors, you must commit the sensor list to reboot the wireless
network and allow it to reform. This can take several minutes.
The Wireless NetBotz USB Coordinator & Router (NBWC100U) is supported on the wireless sensor
network in Router mode.
The NetBotz Wireless Temperature Sensors (NBWS100T and NBWS100H) are supported on the
wireless sensor network in End Device mode.
Each wireless network must have one and only one Coordinator, connected only to the Wireless
port on the Rack Monitor 250. Routers are powered by an AC-USB adapter, not directly connected to
the Rack Monitor 250. End Devices are powered by batteries.
NOTE: Store the USB Coordinator and the Wireless Temperature Sensor in a safe place when not in
use. APC by Schneider Electric is not responsible for misplaced parts. You can purchase replacements
or extra USB Coordinators (NBWC100U) and Wireless Temperature Sensors (NBWS100T) from
www.apc.com.
NOTE: If the LED flashes red three times, then slowly flashes red, contact Technical Support.
Condition Description
Flashes green Normal. The network was formed successfully.
Off Forming a network.
or
Not communicating with the Rack Monitor 250. Reboot the
Coordinator.*
Solid red Unable to form a network. Reboot the Coordinator.*
*To reboot the Coordinator, remove the plastic cover and press and hold the reset button (the LED) for no more
than three seconds.
For more information, see the Quick Start Guides and Installation Manuals for your wireless devices, or
go to www.help.ecostruxureit.com.
Environmental
Elevation (above MSL)
Operating 0 to 3000 m (0 to 10,000 ft)
Storage 0 to 15 000 m (0 to 50,000 ft)
Temperature
Operating 0 to 45ºC (32 to 113°F)
Storage –15 to 65°C (5 to 149°F)
Humidity
Operating 0 to 95%, non-condensing
Storage 0 to 95%, non-condensing
Performance
Typical Rack Monitor 250 response time 200 mS
for dry contact sensor or door switch
sensor state changes
Wireless Compliance
• CE
• EMC Directive 2004/108/EC
• RED Directive 2014/53/EU
• Canadian ICES-003
• US FCC 47 CFR Part 15
• IC: 3351C-NBWC100U
• FCC ID:SNSNBWC100U
Beacon
Maximum length of cable 100 m (330 ft)
Handles
Maximum length of cable 100 m (330 ft)
Door switches
Maximum length of cable 100 m (330 ft)
Gap distance Less than 1 in. (2.54 cm) in air
†If several devices (NetBotz Rack Sensor Pod 150s [NBPD0150], and Temperature/Humidity
Sensors with Digital Display [AP9520TH]) are cascaded on the A-Link bus, a supplemental
power supply (Power Supply 100–240 Vac/24 Vdc—AP9505i) is required. The power supply
connects to the 24 VDC Input on a NetBotz Rack Sensor Pod 150. Go to
www.help.ecostruxureit.com for more information.
Terms of warranty
APC by Schneider Electric warrants its products to be free from defects in materials and workmanship
for a period of two years from the date of purchase. APC by Schneider Electric will repair or replace
defective products covered by this warranty. This warranty does not apply to equipment that has been
damaged by accident, negligence or misapplication or has been altered or modified in any way. Repair
or replacement of a defective product or part thereof does not extend the original warranty period. Any
parts furnished under this warranty may be new or factory-remanufactured.
Non-transferable warranty
This warranty extends only to the original purchaser who must have properly registered the product. The
product may be registered at the APC by Schneider Electric website, www.apc.com.
Exclusions
APC by Schneider Electric shall not be liable under the warranty if its testing and examination disclose
that the alleged defect in the product does not exist or was caused by end user’s or any third person’s
misuse, negligence, improper installation or testing. Further, APC by Schneider Electric shall not be
liable under the warranty for unauthorized attempts to repair or modify wrong or inadequate electrical
voltage or connection, inappropriate on-site operation conditions, corrosive atmosphere, repair,
installation, exposure to the elements, Acts of God, fire, theft, or installation contrary to APC by
Schneider Electric recommendations or specifications or in any event if the APC by Schneider Electric
serial number has been altered, defaced, or removed, or any other cause beyond the range of the
intended use.
USA—FCC
This device complies with part 15 of the fcc rules. operation is subject to the following two conditions: (1)
this device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
NOTE: The grantee is not responsible for any changes or modifications not expressly approved by the
party responsible for compliance. such modifications could void the user’s authority to operate the
equipment.
Canada—ICES
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the
following two conditions: (1) this device may not cause interference, and (2) this device must accept any
interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts
de licence. L'exploitation est autorisée aux deux conditions suivantes : (1) l'appareil ne doit pas produire
de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le
brouillage est susceptible d'en compromettre le fonctionnement.
IC: 3351C-NBWC100U
European Union
The wireless USB Coordinator with this product is in conformity with the requirements of EU Council
Radio Equipment Directive 2014/53/EU.
This product is in conformity with the requirements of EU Council Directive 2014/53/EU. This product may
cause radio interference in which case the user may be required to take adequate measures. APC by
Schneider Electric cannot accept responsibility for any failure to satisfy the protection requirements
resulting from an unapproved modification of the product.
Worldwide Customer Support
Customer support is available at www.apc.com or help.se-dmaas.com.
© 2018 APC by Schneider Electric. APC, the APC logo, NetBotz, StruxureWare, PowerNet, and
NetShelter are owned by Schneider Electric Industries S.A.S. All other trademarks are property of
their respective owners.
990-9814C-001 4/2018