We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF or read online on Scribd
You are on page 1/ 3
TECHNICAL DATA SHEET
LHS CABLE
1 | Make PatolUK
2 | Type Digital Heat Sensing Cable (non -electrically operated)
3._ | Voltage Rating Lov dc. Maximum
| Maximum Ambient Temperature 70 degrees Centigrade
5. | Minimum Alarm Temperature ‘80 degrees Centigrade
6. _ | Maximum Alarm Temperature ‘90 degrees Centigrade
7. | Number of Core 2 (Two)
&. | Maximum Conductor Resistance per Km at 20°C | 100 ohms per km
3. | Material
a) _ | Conductor Tinned copper coated steel
b) | Insulation Thermoplastic
) | Sheath Nylon
10. | Conductor Dia -Meter ‘O.9mm
Li. | Insulation material Thickness 035mm
12. | Approval UL Listed, File No. $24081
13. _ | Approximate Detection Time (Small Flame) ‘Approximately 5 seconds
14, | Paircolour Red / White
15. __| Interface with FDA panel Through Monitor Module
16._| installed Area Conveyor
17.__[ Quantity ‘8000
18. | Catalogue enclosed ‘Anx-8
NAME OF SUPPLIER TECHNICO NDIA PVT.LTD; P-137 LAKE TERRACE; KOLKATA 700029
LENT RELIENCE NDUSTRIES UNITED cy DATE KE APP
ORIGINATOR “TVSSENNRUPP INDUSTRIES INDIA
TONSULTANT BENT FREDERICK, MARIANO
PACKAGE FIRE PROTECTION SYSTEM (KADIRA)
TIPLDATA SHEET NO, TALPS6I-O2-FORTETOS ° | waonis na a
38 of 63[ANX-8
Patol Limited
LINEAR HEAT DETECTING CABLE (L.H.D.C.)
Digital Line Heat Detector & Fire Sensor
The Patol Digital Line Heat Detector is designed to provide early detection of fire conditions
and overheating in circumstances where other forms of detection would not be viable, either
due to inability to sustain the environmental requirements or through prohibitive costs.
Extensive single zonal lengths of the Line Heat Detector Cable (LHDC) may be installed with
the ability to trigger alarms for ‘hot spots’ occurring on very small sections of the overall cable.
The LHDC may be employed in a wide variety of applications but is particularly suited where
there is a harsh environmental condition, a physical or hazardous maintenance access
constraint to the protected area, and/or a requirement to cost effectively install detection in
close proximity to the risk(s)
The primary features of Patol's Line Heat Detector are:-
+ Early detection of hazards at temperatures well below flame point.
+ Rugged construction for use in harsh environments.
+ Ease of installation - wide range of fixings available.
¢ Compatible with many existing zone monitors / control equipments.
ced Alarm Trigger Temperature
+ Intrinsically Safe configurable for Hazardous Areas.
+ Compliant with industry standards (e.g. CEGB GDCD-187)
+ Extensive range of proven applications.
+ UL Listed
39.0163Patol Limited
LINEAR HEAT DETECTING CABLE
Digital Line Heat Detector & Fire Sensor passivaTeD
i STEEL =
sti The Linear Heat Detector comprises a
Priwcipeles wisted paic win core cab. Each core is of CONDUCTORS
passivated steel and has a special heat
reactive polymer insulation. The cable has an overall protective
jacket / sheath TEMPERATURE
The primary mechanism of heat (fie) detection is that inner core REACTIVE.
insulating polymer is specially formulated such that it plastiizes POLYMER.
at a specific temperature. The cable is constructed such that the INSULATION
twisted steel cores are in tension, and al the polymer trigger
temperature the conductors connect. This provides an alarm
signal to any associated monitoring device
The LHDC may be used as a simple switch to operate a relay OUTER
etc. However in most fie alarm installations the minimum PROTECTIVE
Fig
requirement is that the LHDC circuit is monitored for SHEATH
disconnections by means of an End of Line (EOL) device and an
appropriate Fire Alarm Channel or Address Loop interface unit.
Patol can provide more sophisticated monitoring schemes that
‘can discriminate and identify Zone / Area alarm initiations whilst
‘maintaining a single length of LHDC.
Applications HOC is versatie in that it can both
provide an alternative to point heat
detectors in conventional (space) protection situations, and it
may also be readily installed in very close proximity to monitored
hazards.
The detector is particularly suited to applications where harsh
environmental conditions preclude the use of other forms of
detection,
The low maintenance requirement of the detector provides a
unique solution to fire detection in areas that have access
restrictions due to either physical difficulties or personnel health
risk,
The cable may be installed in Hazardous Areas by means of
Intrinsically Safe Zener Barriers. When the protected area is
remote from the monitoring equipment ‘interpasing’ cables may
bbe employed. See Fig.2
Eo.
Cable Tunnels, Ducts & Mezzeninee
Escalator & Moving Walkways
Poto-Chem Storage Tank Rim Seale
Pint Shops & Spray Baths
Conveyors - esl, Wood Sulphur ete
Celing Voids & Ati Spaces
Road & Ral Tunnel Cumogewaye
Nie Reactr Plant Areas
Refgeratd Stores & Cold Reame
occa Conta & Suchet Cabinets
Warehouse High Rise Pale Racking
(Rigs & OF Shore Pitioms
Fume Cupboards & Glove Boxes
Gran Sis & Agricutra Storage
Read /Ral Voile Engine Comparmonts
‘Stoam Ppp Leaks & Trace Heating Fat
Product Lines Flanges, Va & Pumps
CCamuter oom Under Fier Cable Voie
ai IS BARRIER CONTROL.
LINE HEAT DETECTOR -LHDC JB __INTERPOSING CABLE
‘TERMINATOR Fig2 Sr Requrea ——* PANEL
enton The LHDC can be provided in a variety of constructional configurations that will
Ss Rage vest me requirements of both standard ang special applications. Two ofthe
most commonly employed types are defined in the following table.
LHOG Type | Min.Alarn | Max Alarm | Maximum | Size-Oval | Sheath | Sheath | Corel
PartNumber | Temperature | Temperature | Ambient | Min/Max | Material | Colour | Coloure
700-070 | 60°C voc | 45 [35-45mm | nylon | Black [Orange / Blue
7o0-080 | 80°C 90°C voc | 35-45mm | Nylon | Black | Red/White
UL Approval UL File No. 24081 UTHV Listed
Rectory Road, Padworth Common, Berkshire, UK. RG7 41D
Patol Limited tet: +44 0) 118 9701701 44 (0) 118 9701700
Web: www.patol.co.uk email : [email protected]
40.0163