Panasonic CS-E9CKP CS-E12CKP Service Manual Log PDF
Panasonic CS-E9CKP CS-E12CKP Service Manual Log PDF
Panasonic CS-E9CKP CS-E12CKP Service Manual Log PDF
CONTENTS
Page Page
1 Features 2 10 Installation And Servicing Air Conditioner Using R410A 46
2 Functions 3 11 Installation Instructions 57
3 Product Specifications 6 12 Servicing Information 66
4 Dimensions 10 13 Technical Data 75
5 Refrigeration Cycle Diagram 12 14 Exploded View 78
6 Block Diagram 13 15 Replacement Parts List 79
7 Wiring Diagram 14 16 Exploded View 80
8 Operation Details 16 17 Replacement Parts List 81
9 Operating Instructions 41 18 Electronic Circuit Diagram 82
www.ilmalämpöpumput.com
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
1 Features
• Product • Serviceability
− Microcomputer-controlled compressor operating − Washable Front Panel
frequency − Breakdown Self Diagnosis function
− Vertical and Horizontal Airflow Directions
− Five modes of operation selection • Environmental Protection
− Power Mode operation − Non-ozone depletion substances refrigerant (R410A)
− Delay ON Timer and OFF Timer
− Standby operation • Quality Improvement
− Remote Controller with illuminable buttons − Gas leakage detection
− Power Monitor Display LED − Deice operation
− Catechin Air Purifying Filter − Auto restart control
− Triple Deodorizing Filter
− Ionizer Mode Operation
− Quiet Mode Operation
www.ilmalämpöpumput.com
2
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
2 Functions
Remote Control
Illuminable
buttons
FAN SPEED
Indoor Fan Speed Selection
• Low
• Medium-
• Medium
OFF/ON • Medium+
I • High
Operation OFF / ON • AUTO Automatic Fan Speed
FAN
MODE TEMP
Operation Mode Selection
Room Temperature Setting
• a Automatic Operation • Temperature Setting (16°C to 30°C)
• HEAT Heating Operation
TIMER
• COOL Cooling Operation ON OFF
• DRY Soft Dry Operation Timer Operation Selection
• FAN Fan Operation • 24-hour, OFF / ON Real Timer Setting.
POWERFUL ∧
Powerful Mode Operation ∨
Time / Timer Setting
QUIET
Quiet Mode Operation OFF / ON • Hours and minutes setting.
SET
CANCEL
Ion Mode Operation OFF / ON Timer Operation Set / Cancel
• ON Timer and OFF Timer setting and
AIR SWING
cancellation.
www.ilmalämpöpumput.com
3
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Indoor Unit
Powerful Mode
Operation Indication Lamps (LED)
• For quick cooling or heating.
• POWER (Green) ...... Lights up during
MONITOR compressor operation. Quiet Mode
• (Green) ............ Lights up in Ionizer
Mode Operation. • To provide extra quiet operation.
• POWER (Green) ...... Lights up in
operation, blinks in Ionizer Control
Automatic Operation • Ionizer control for generate negative ion
Mode judging and Hot in discharge air.
Start operation.
• TIMER (Orange) .... Lights up in Timer Delay ON Timer and OFF Timer
Setting.
Blinks in Self
Diagnosis Control. Automatic Restart Control
• QUIET (Orange) .... Lights up in Quiet • Operation is restarted after power failure
Mode Operation. at previous setting mode.
• POWERFUL (Orange) ... Lights up when
Powerful Mode is Microcomputer-controlled Room
selected. Temperature Control
www.ilmalämpöpumput.com
4
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Outdoor Unit
Hot Start
Mininum Operation Frequency
Protection Control
Intake Air Temperature Control
www.ilmalämpöpumput.com
5
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
3 Product Specifications
Unit CS-E9CKP CU-E9CKP5
INTAKE
Air Volume Indoor Air (Lo) m3/min (cfm) Cooling; 6.5 (231) —
Heating; 7.1 (249)
Indoor Air (Hi) m3/min (cfm) Cooling; 9.9 (350) Cooling; 30.0 (1,060)
Heating; 10.6 (370)
www.ilmalämpöpumput.com
6
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
7
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
INTAKE
Air Volume Indoor Air (Lo) m3/min (cfm) Cooling; 7.3 (258) —
Heating; 9.2 (325)
Indoor Air (Hi) m3/min (cfm) Cooling; 10.9 (380) Cooling; 31.0 (1,090)
Heating; 11.8 (420)
www.ilmalämpöpumput.com
8
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
9
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
4 Dimensions
www.ilmalämpöpumput.com
10
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
11
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
12
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
6 Block Diagram
www.ilmalämpöpumput.com
13
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
7 Wiring Diagram
www.ilmalämpöpumput.com
14
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
15
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
8 Operation Details
www.ilmalämpöpumput.com
16
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
17
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
For normal start of operation, including Thermo-OFF, Deice-Resuming, and remote controller ON-OFF starts, the compressor
starts to operate at frequency no. 8, values of 30Hz and 32Hz for E9CKP and E12CKP respectively, for 60 seconds.
The frequency to be judged and instructed, however, starts to judge once the air conditioner operated and the judgment will
continue every 30 seconds until it is stopped by all kinds of compressor off conditions. This judgment is based on the internal
temperature sampling that involving internal setting temperature and intake air temperature.
From the internal sampling, the temperature different (intake air temperature - internal setting temperature) will be used to judge
the Zone on which the frequency to be instructed for the initial operation of compressor (refer to Table on Initial Frequency Zone).
After the initial operation, the instructed frequency will change or shift from initial frequency according to the judgment on
temperature different from sampling (refer to the Table on Shifting Frequency Zone).
www.ilmalämpöpumput.com
18
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Besides, the range of operation frequency will change according to the setting environment as listed below:
Condition: Freq. no. for E9CKP Freq. no. for E12CKP Remarks
MIN MAX MIN MAX
Cooling Mode 1 15 1 16 (a)
- if remote controller set 28°C & fan speed = 7 15 7 16 (a), (c)
Hi
- if remote controller set 28°C & fan speed = 5 15 6 16 (a), (c)
Me-, Me, Me+, Auto
- if remote controller set 28°C & fan speed = 4 15 5 16 (a), (c)
Lo
- if Powerful Mode ON 7 15 7 16 (a), (c)
Soft Dry Mode 4 7 4 8
Heating Mode 1 30 1 30 (b)
- if remote controller set 18°C & fan speed = 10 30 10 30 (b), (d)
Hi
- if remote control set 18°C & fan speed = 9 30 9 30 (b), (d)
Me-, Me, Me+, Auto
- if remote controller set 18°C & fan speed = 8 30 8 30 (b), (d)
Lo
- if Powerful Mode ON 10 30 10 30 (b), (d)
Remark:
(a) If frequency decreases from MAX, the following frequency performed will be depending to outdoor temperature, as given in below table
(for 30 seconds only) and then continues as normal rule.
(b) (If frequency increases from Freq. No. 17, the following frequency performed is as below (for 30 seconds only) and then continue as
normal rule.
(c) When temperature different (intake - setting) < -1.0 °C or Thermo-Off activated and only valid for 120 seconds; not applicable during Soft
Dry Mode, and Anti-freezing control.
(d) When temperature different (intake - setting) > +1.5 °C or Thermo-Off activated and only valid for 130 seconds.
www.ilmalämpöpumput.com
19
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
The frequency judgment will perform every 30 seconds. Nevertheless, the frequency is instructed to outdoor compressor after
every 90 seconds except when either one of the below conditions is met:
(a) The frequency judged changes from frequency number decreasing zones (Zone No. 0 or 1 or 2 or 3) to frequency number
increasing zones (Zone No. 5 or 6 or 7 or 8) and vice verse.
(b) The frequency judged falls on frequency shifting zone number 0 or 1 (shift to Frequency MIN) at Cooling mode operation.
(c) The frequency judged falls on frequency shifting zone number 4 (no shifting in frequency number) at Cooling mode
operation.
(d) The frequency judged falls on frequency shifting zone number 7 or 8 (shift to Frequency MAX) at automatic fan speed.
The instructed frequency is the value referred by the frequency number, which resulted from previous instructed frequency
number with the numbers of frequency numbers to be shifted, in Table on Frequency Number.
Time (s) 0 30 60 90 120 150 180 210 240 270 300 330
Zone (+/-) + + + + + +/- + - - +/- +
Freq. zone based on temp. diff. 8 7 7 6 6 6 4 5 3 1 4 5
Frequency shift Max Max +2 +2 +2 0 +1 -1 Min 0 +1
Freq. no. judged based on 15 30 30 17 17 17 15 16 14 5 4 6
previous
Freq. instruction (Y/N) & its Y (a) Y (a) Y (b) N N Y (c) Y (d) N Y (e) Y (f) Y (d) N
condition
Freq. control condition (g) (g) (h) (h) (i)
Instructed freq. 8 8 15 15 15 14 5 5 5
Operation freq. 8 8 15 15 15 15 15 15 14 5 5 5
Note:
(a) Starting frequency.
(b) Frequency judged falls on Zone 7 or 8 (shift to Frequency MAX).
(c) 90 seconds frequency instruction limit.
(d) Frequency judged falls on Zone 4 (no shifting).
(e) Frequency no. changes from no. increasing zones to no. decreasing zones.
(f) Frequency judged falls on Zone 0 or 1 (shift to Frequency MIN).
(g) Normal initial operation starts (60 s).
(h) Maximum frequency for normal cooling operation
(i) Minimum frequency for normal cooling operation.
www.ilmalämpöpumput.com
20
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
There are 31 fan speed numbers assigned for different fan speed operation at designed conditions, as shown in below table. The
fan speed can be set manually using remote control (5 speeds for cooling mode: Lo, Me-, Me, Me+, Hi; 5 speeds for heating: Lo,
Me-, Me, Me+, Shi) or let it automatically changes depending on the operation and its environment.
www.ilmalämpöpumput.com
21
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
The automatic fan speed for cooling operation is as shown in below patterns (a → b → c → → h) with each pattern 10 seconds.
The fan speed for each level (X or Y or Z) is as below table.
(a) During cooling operation, if all the following conditions occur, indoor fan speed will be shifted to Shi internally.
(i) Indoor intake air temperature 24°C.
(ii) Instructed frequency = 39 Hz (E9CKP) or 52 Hz (E12CKP).
(iii) Remote controller setting temperature = 16°C.
(iv) Remote controller setting fan speed = Hi.
(v) Outdoor air temperature 30°C.
(vi) Operation starts 30 minutes.
8.1.5. Heating Mode Indoor Fan Motor Operation (Anti Cold draft Control)
Indoor fan speed varies in accordance to indoor heat exchanger temperature, based on type of air volume and direction, as shown
below.
www.ilmalämpöpumput.com
22
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Note:
a. UP:
• If move from Lo or Lo-, the fan speed will be shifted to Maximum.
• If move from Maximum, the fan speed no change.
• Other than that, the fan speed will be increased one Fan Speed No.
b. DOWN:
• The fan speed will be decreased one Fan Speed No.
c. Fix:
• No change in fan speed.
d. Maximum:
• Fan speed will be increased to maximum auto fan speed.
Outdoor fan motor is operated with one fan speed only. It starts when compressor starts operation and it stops 30 seconds after
compressor stops operation.
www.ilmalämpöpumput.com
23
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
1. There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by vertical vanes).
2. Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger temperature
and intake air temperature) and manual (angles of direction can be adjusted using remote controller).
Vertical Airflow
Operation Mode Airflow Direction Vane Angle (°)
1 2 3 4 5
Heating Auto, with Heat Exchanger A 17
Temperature B 58
C 7
Manual 7 17 33 49 67
Cooling, Soft Dry and Fan, Ion Auto 7 ~ 37
Manual 7 17 25 33 41
Mode Judgment in Auto Auto 7
Manual 7 17 25 33 41
1. Automatic vertical airflow direction can be set using remote controller; the vane swings up and down within the angles as
stated above. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as
Figure 1 below. When the air conditioner is stopped using remote controller, the vane will shift to close position.
2. Manual vertical airflow direction can be set using remote controller; the angles of the vane are as stated above and the
positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote controller, the vane will shift
to close position.
Horizontal Airflow
1. Automatic horizontal airflow direction can be set using remote controller; the vane swings left and right within the angles as
stated below. For heating mode operation, the angle of the vane depends on the indoor heat exchanger temperature as
Figure 1 below.
Operation Mode Vane Angle (°)
Heating, with heat exchanger temperature A 55 ~ 125
B 90
Cooling, Soft Dry and Fan, Ion 55 ~ 125
www.ilmalämpöpumput.com
24
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
2. Manual horizontal airflow direction can be set using remote controller; the angles of the vane are as stated below and the
positions of the vane are as Figure 2 above.
Pattern 1 2 3 4 5
Airflow Direction
Patterns at Remote
Controller
Vane Angle (°) 90 55 70 110 125
This mode can be set using remote controller and the operation is decided by remote controller setting temperature, indoor intake
air temperature and outdoor air temperature.
During operation mode judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor are running for 20 seconds to detect
the indoor intake and outdoor air temperature. The operation mode is decided based on below chart.
Values of T1, T2, and T3 depend on remote controller setting temperature, as shown in below table. After the adjustment of T1,
T2 and T3 values, the operation mode for that particular environment and remote controller setting is judged and performed, based
on the above operation mode chart, every 30 minutes. Heating mode operation will be performed, however, if deice operation is
detected.
Remote Controller Setting Temperature (°C) T1 T2 T3
16 ~ 18 +10 +8 -5
19 ~ 22 +8 +7 -7
23 ~ 26 +7 +6 -7
27 ~ 30 +6 +5 -8
There is a temperature shifting on T1, T2, and T3 if the operation mode judged is changed from Cooling/Soft Dry to Heating or vice
verse.
Operation Mode change from Temperature shifts (°C)
Cooling/Soft Dry → Heating -2
Heating → Cooling/Soft Dry +2
www.ilmalämpöpumput.com
25
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
The operation mode chart for this example is as shown in below figure and the operation mode to be performed will depend on
indoor intake air temperature and outdoor air temperature at the time when the judgment is made.
Delay ON timer can be set using remote controller, the unit with timer set will start operate earlier than the setting time. This is to
provide a comfortable environment when reaching the set ON time.
Seventy minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 20 seconds to determine
the indoor intake air temperature and outdoor air temperature in order to judge the operation mode.
From the above judgment, the decided operation will start operate earlier than the set time as shown below.
OFF timer can be set using remote controller, the unit with timer set will stop operate at set time.
www.ilmalämpöpumput.com
26
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
1. The compressor will not start for three minutes after stop of operation.
2. This control is not applicable if the power supply is cut off and on again or after 4-way valve deices condition.
1. Once the compressor starts operation, it will not stop its operation for 30 seconds.
2. However, it can be stopped using remote control or Auto Switch at indoor unit.
1. When the total outdoor unit running current (AC) exceeds X value, the frequency instructed for compressor operation will be
decreased a step to smaller frequency number.
2. If the running current does not exceed X value for five seconds, the frequency instructed will be increased a step at one time
to bigger frequency number.
3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for three minutes.
www.ilmalämpöpumput.com
27
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
2. If the set value is exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute.
If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
2. Compressor operation restarts after three minutes the temperature decreases to 95°C.
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The changes of frequency
are as below figure.
1. When the conditions listed in below table occur, the compressor stops and restarts after three minutes.
2. If this phenomenon is continuously occurring for twice within 20 minutes, all indoor and outdoor relays will be cut off.
3. This control is not applicable for deice operation.
www.ilmalämpöpumput.com
28
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
When the compressor operate at frequency lower than 26 Hz (E9CKP) or 28 Hz (E12CKP) for 240 minutes, the operation
frequency will be increased to 26 Hz (E9CKP) or 28 Hz (E12CKP) for two minutes.
When all the below conditions occur, minimum value (Freq. MIN) for the frequency instructed to compressor will change to 30 Hz
(E9CKP) and 32 Hz (E12CKP) for cooling mode operation, and 21 Hz (E9CKP & E12CKP) for heating mode operation.
1. When the power supply is cut off during the operation of air conditioner, the compressor will re-operate within three to four
minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to be selected randomly) after power
supply resumes.
1. For Cooling Mode and Soft Dry Mode operation, the compressor operating frequency is regulated in accordance to the outdoor
air temperature as shown in the diagram below. This control will begin one minute after the compressor starts.
www.ilmalämpöpumput.com
29
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
2. For Heating Mode operation, the compressor operating frequency is regulated in accordance to outdoor air temperature as
shown in the below figures. This control will begin 50 seconds after the compressor starts.
1. During cooling or soft dry operation with automatic fan speed, the unit will operate as state below for deodorizing purpose.
4. If the compressor still stops operation after three minutes, the step will start from 4.
5. This control is not applicable during sleep shift operation, ON timer preparation and anti-freezing control.
www.ilmalämpöpumput.com
30
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
1. When outdoor air temperature increases to 38.6°C, compressor operating frequency reduces to minimum of 30 Hz and 32 Hz
for E9CKP and E12CKP respectively.
2. Compressor operating frequency will resume to normal when outdoor air temperature decrease to 37.8°C.
1. When indoor heat exchanger temperature is lower than 2°C continuously for six minutes, compressor will stop operating.
2. Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 10°C.
3. At the same time, indoor fan speed increase its frequency as value of two steps up in Fan Speed Number compared to its
normal operation. (Refer Table on Fan Speed Level and Supplied Voltage).
4. If indoor heat exchanger temperature is higher than 10°C for five minutes, the fan speed will return to its normal operation.
1. When indoor fan speed is set at Me- or slower, the compressor operating frequency is regulated by operation time to prevent
fog discharged from indoor as shown in below table.
2. After 420 minutes, the operation restarts again from the beginning.
3. The operation will restart the above control whenever remote controller setting temperature or fan speed setting is changed.
www.ilmalämpöpumput.com
31
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in below figures.
Compressor will operate at maximum of 56 Hz or 68.5 Hz for E9CKP and E12CKP respectively if either one of the below conditions
occur:
1. When the intake air temperature is 10°C or above and remote controller setting fan speed is Lo or lower.
2. When the intake air temperature is 30°C or above.
Deice operation occurs when the deice operation starting signal is generated. This happens when one of he following condition
occurs. However, the first deice operation will begin one hour after the start of heating mode operation.
Once the deice operation signal produced, the instructed frequency for the operation of compressor will be set to zero hertz (0 Hz)
for 30 seconds. Then, deice operation starts with both indoor and outdoor fan motor, and 4-way valve turn off for 30 seconds. The
compressor operates following the frequency as shown in below chart that depending on outdoor heat exchanger temperature and
operation period, with a maximum of 10 minutes and 30 seconds. When the deice operation ends, before back to normal operation,
the instructed frequency for compressor will be set to zero hertz (0 Hz) again and outdoor fan motor will turn on for a period of 59
seconds.
www.ilmalämpöpumput.com
32
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
33
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Note:
• If POWER LED is blinking, the possible operations of the unit are Hot Start, during Deice operation, operation mode
judgment, or delay ON timer sampling.
• If Timer LED is blinking, there is an abnormality operation occurs.
1. When the switch is pressed between 0 to 5 seconds, Auto Mode operation starts to function.
2. When the switch is pressed between 5 to 8 seconds, the unit is forced to operate in Cooling Mode.
3. When the switch is pressed between 8 to 11 seconds, the unit is forced to operate in Heating Mode.
4. When the switch is pressed between 11 to 16 seconds and together with the signal from remote control, the unit can be
changed to different controlling setting (A-B mode).
5. When the switch is pressed between 16 to 21 seconds, either “H14” error detection selection mode or the remote controller´s
signal receiving sound can be cancelled or turned on.
www.ilmalämpöpumput.com
34
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
B. Purpose
To provide quiet cooling operation compare to normal operation.
C. Control condition
a. Quiet operation start condition
• When “quiet” button at remocon is pressed.
Quiet LED illuminates.
3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except fan only mode.
5. During quiet operation, if timer “on” activates, quiet operation maintains.
6. After off, when on back, quiet operation is not memorised.
D. Control contents
a. Air flow volume manual
1. Fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi & Me for 3dB & Lo for 2dB.
2. Quiet setting of fan speed is as shown in the following table. (Cool and fan mode)
E9CKP E12CKP
RPM 1.0 HP 1.5 HP
Quiet Hi Hi-100 Hi-100
Quiet Me Me-100 Me-100
Quiet Lo Lo-100 Lo-100
Normal Operation
www.ilmalämpöpumput.com
35
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Quiet Operation
8.2.25. Quiet operation under Soft Dry operation (Dry area at Dry Mode)
B. Control condition
a. Quiet operation start condition
• When “quiet” button at remocon is pressed.
Quiet LED illuminates.
3. When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
4. When operation mode is changed, quiet operation is shifted to quiet operation of the new mode, except fan only mode.
5. During quiet operation, if timer “on” activates, quiet operation maintains.
6. After off, when on back, quiet operation is not memorised.
www.ilmalämpöpumput.com
36
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
C. Control contents
a. Air flow volume manual
1. Fan speed is changed from normal setting to quiet setting of respective fan speed.
This is to reduce sound of Hi & Me for 3dB & Lo for 2dB.
2. Quiet setting of fan speed is as shown in the following table.
E9CKP E12CKP
Quiet Hi SHi-100 SHi-100
Quiet Me Me-100 Me-100
Quiet Lo HLo-100 HLo-100
Control Condition
www.ilmalämpöpumput.com
37
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
3. Ionizer operation status is not memorised after off. After OFF, when operation is “ON” again, air-conditioner operates without
ionizer operation.
However, during Cool mode etc. + ionizer operation, if there is a power failure & then power resume, A/con shall on at that
mode + ionizer operation.
Case 1a: Ionizer only operation (24h real time timer ON) Case 1b: Ionizer only operation (24h real time timer OFF)
Case 2a: Operation Mode + Ionizer (24h real time timer ON) Case 2b: Operation Mode + Ionizer (24h real time timer OFF)
Case 3a: Ionizer only operation (24h real time timer ON) Case 3b: Ionizer only operation (24h real time timer OFF)
www.ilmalämpöpumput.com
38
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Case 4b: Ionizer only operation (24h real time timer ON) Case 5b: Operation Mode + Ionizer (24h real time timer ON)
Case 6: Ionizer only operation (Auto Fan) & shift to Cool Mode
www.ilmalämpöpumput.com
39
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Note:
1. 24 times checking: Actual Ion ON for 10s & OFF for 10 min. continuously for 24 times.
2. 24 times count will be cleared when following conditions happen.
a) 24 times count over, b) Ionizer cancel if press Ion button or power reset, c) Ion f/b sgnl OK.
3. Error protection will be cleared when following conditions happen.
a) Power reset, b) Remocon operation ON/OFF button press, c) Forcible operation press, d) Opt OFF due to Timer OFF
4. Ion auto restart: Ion will auto restart if Actual Ion was ON with no error protection control before power shutdown. Otherwise
Ion will not auto restart.
www.ilmalämpöpumput.com
40
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
9 Operating Instructions
SAFETY PRECAUTIONS
■ Installation Precautions ■ Operation Precautions
Before operating, please read the following
“Safety Precautions” carefully.
! Warning ! Warning
● To prevent personal injury, injury to others and This sign warns of death or serious injury.
property damage, the following instructions must be ● Do not install, remove and reinstall the unit by
followed. yourself. ● Do not share outlet.
Improper installation will cause leakage, electric ● Do not insert plug to operate the unit. Do not
● Incorrect operation due to failure to follow instructions pull out plug to stop the unit.
shock or fire. Please engage an authorized dealer
will cause harm or damage, the seriousness of which or specialist for the installation work. ● Do not operate with wet hands.
is classified as follow:
● Do not damage or modify the power cord.
● Do not insert finger or other objects into the
! Warning indoor or outdoor units.
● Plug in properly.
● This room air conditioner must be ● Use specified power cord.
! Caution earthed.
Improper grounding could cause
This sign warns of damage to property. electric shock.
● Ensure that the drainage piping is OFF
These symbols (with a black background) denote ● Switch off the power supply before cleaning.
actions that are COMPULSORY. ● Ventilate the room regularly.
● Pay attention as to whether the installation
rack is damaged after long period of usage.
OFF
1 3
TTO
HE
A
AT
ON CO
OL
OF AU
F TTO DRY
AU FA
AN
N
3
TO
AU
TE FA
AN
N
TO
T
MP
MO
DE
AIR OF
EC F/O
Ste SW ON N
p ING OM
1 Y
ON SL
EE
OF 2 P
F FAN
SP
EE
CHE 3 D
CK TIM SE
RES ER T
ET CA
CLO NC
2
CK EL
BAT +
TER
IN Y
VE
RT
ER
87 6 5 4
● Remote Control Indication Sticker
1 Front Panel
1 Front Panel
2 Air Intake Vent
2 Air Filters
3 Power Supply Cord
3 Air Purifying Filter
4 Ionizer
www.ilmalämpöpumput.com
41
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
■ Remote Control
AT
1 Signal Transmitter CO
2 OF
AU
TO
OL
AU
TO DRY
FA
N
PO A
2 Operation Display
WER FA UTO
N
FUL
1 MO
DE
AU AIR
3 Ionizer Mode Operation Button
EC
TO SW ON
IN OM
1 MA G
Y
ON NU SL
AL E
OF 2
F FAN
AUTO
AUT 1.5
1.5 V
5 Operation Mode Selection Button V
AUTO
AUT
ON
OFF AUTO
AUT 6 Quiet Mode Operation Button 1
FAN
AN
TEMP
7 Vertical Airflow Direction Button
3 OFF/ON
# 8 ON-Timer Button
4 1 Slide down the remote control cover completely
5 $ 9 OFF-Timer Button
MODE QUIET POWERFUL
6
AIR SWING
$ 0 Reset Point 2 Insert the batteries
FAN SPEED
7 % (Press with fine-tipped object to clear the memory) – Be sure the direction is correct
8
1 2 3 – 12.00 at display - flashing
^
ON SET ! Check Point • Set the current time (CLOCK) immediately to
9 & To be used by the service technician only. prevent battery exhaustion.
OFF CANCEL
TIMER *
0 @ OFF/ON Button ● About the batteries
( • Can be used for approximately one year.
CHECK RESET CLOCK
(Illuminating button)
!
) ● Observe the following when replacing the
# Powerful Mode Operation Button
batteries
$ Fan Speed Selection Button • Replace with new batteries of the same type.
• Do not use rechargeable batteries (Ni-Cd).
● Remote Control Signal. % Horizontal Airflow Direction Button
• Remove the batteries if the unit is not going to be
• Make sure it is not obstructed. used for a long period.
• Maximum distance : 10 m.
^ Timer Set Button
• Signal received sound.
One short beep or one long beep.
& Timer Cancellation Button
● Notes for Remote Control.
• Do not throw or drop. * Time-Setting Button
• Do not get it wet.
• Certain type of fluorescent lamps may affect ( Clock Button
signal reception. Consult your dealer.
) Remote Control Cover
2 1 2 OF
F
O
AU L D
TO RY
AU
TO
FA
N HEAT : 20°C ~ 24°C
AU
TE FA
MP
AN TO
COOL : 26°C ~ 28°C
6 3 MO
DE DRY : Approx. room temperature
3 5 AIR OF
1
SW
QU F/O
IN IE N
1 T
5 4 OF
F
ON
2
G
FAN
PO
WER
FUL
6
SP
CH
EC
K
RE
SE
TIM
ER
SE
T
3
EE
D
4 ■ Automatic Operation
T CA
CL
OCK NC
• At the start of the Automatic operation, Heating,
1 Connect the power supply cord to an independent
EL
32°C O C
5 Insert the air filters AUTO F O
FAN ■ Setting Mode 31°C H T O
L
• Press 2 to select:- E I
A D
6 Close the front panel T R N
Y G
I
18°C N
■ Remote Control AUTO – Automatic Operation
16°C
G
– To set the current time HEAT – Heating Operation
COOL – Cooling Operation
13°C 19°C 21°C 23°C 25°C
AIR SWING DRY – Soft Dry Operation
Outdoor Temperature
FAN SPEED FAN – Fan Operation
1 2 3
ON SET
OFF CANCEL
TIMER 2
CHECK RESET CLOCK
1
1 Press 1.
2 Then press 2 to increase or decrease the time.
3 Press 1 again.
Set time at display will light up.
www.ilmalämpöpumput.com
42
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Maximum Temperature-Cooling 32 23 43 26
Fan
• The angle indicated on the remote (Maximum Temperature-Heating) (30) (-) (24) (18) • Heat is obtained from outdoor air to warm up the
control is different from that on the room. When the outdoor ambient air temperature
About 30°
indoor unit. Minimum Temperature-Cooling 16 11 16 11 falls, the heating capacity of the unit might be
About 30° (Minimum Temperature-Heating) (2) (-) (-5) (-6) reduced. We recommend that you use an additional
• The louver angle automatically
Heating
AUTO
FAN
www.ilmalämpöpumput.com
43
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
(Must be removed before washing) 2 Turn off the power supply and unplug.
1 Raise the front panel higher than the horizontal and ● Catechin Air Purifying Filter Note: If the unit is not switched off by the remote
pull to remove it. • The filter is coated with catechin to prevent growth control, it will start operating when you plug in
of bacteria and viruses. (because the unit is equipped with Auto Restart
2 Gently wash with water and a sponge.
• Reusable. Control).
• Do not press the front panel too hard when washing.
• When use kitchen cleaning fluid (neutral detergent), • Vacuum and fit it back in place 3 Remove the remote control batteries.
rinse throughly. (Recommended : every 6 months)
• Do not dry the front panel under direct sunlight. ■ Recommended Inspection
• Recommended to change these filters every 3 years. • After used over several seasons, the unit will
3 To fix the front panel, raise the front panel become dirty and thus decreases the unit’s
horizontally, match the protruding portion on the Do not reuse damaged filters.
Consult the nearest authorized dealer to purchase a performance. Depending on the operation
indoor unit to the fulcrum and push into place. conditions, a dirty unit may produce odour and dust
new filter. may pollute dehumidification system. Therefore, a
Catechin Air Purifying Filter No.: CZ-SF70P seasonal inspection is recommended in addition to
Triple Deodorizing Filter No.: CZ-SFD72P regular cleaning. (Consult an authorized dealer).
www.ilmalämpöpumput.com
44
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
TROUBLESHOOTING
Before calling your dealer, refer to the checklist
■ Call the Dealer Immediately
Problem? Check If the following conditions occur, turn off and unplug the
main power supply, and then call the dealer immediately.
• The unit does not operate • Has a circuit breaker been tripped or a fuse blown?
• Is the power supply plug disconnected from the outlet? • Abnormal noise is heard during operation.
• Is the Timer being used correctly? • Water or foreign material gets into the remote
control by mistake.
• The unit does not cool or heat effectively • Has the temperature been set correctly?
• Are the air filters dirty? • Water leak from the indoor unit.
• Are the air intake or outlet vents blocked? • Switches or buttons do not operate properly.
• Are all the windows and doors closed? • Circuit breaker trips or fuse blows frequently.
* Measure the temperature difference. Operation is • Power supply cord and plug become unusually warm.
normal if, 15 minutes after the start of operation,
the temperature difference between the air intake
• A smell of burning is emitted.
and outlet vents is 8°C or above for cooling and
14°C or above for heating.
■ When the Timer LED at indoor unit blinks
The Timer LED blinks indicating abnormality.
• The unit does not receive remote control signals, or • Are the batteries weak?
• Have the batteries been inserted with the e and r poles
Press the check button at remote control for 5 seconds,
the remote control display is weak or non-existent
in the correct position? error code will be displayed.
Remote Control
Problem? Reason Display.
ON
• Air is not discharged immediately • At Cooling • Soft Dry (auto Fan Speed)
Air will not be discharged for approximately 40 seconds. OFF
The unit is designed to prevent tobacco, cooking and body
odors from being discharged together with the cool air. Press TIMER or button to identify the error code.
• At Heating (POWER LED blinks) Beep sound (4 times) will be heard for the correct error code shown.
This is to prevent cold air from blowing out. Please wait. Turn off the power supply and remove the power supply plug.
• Operation stops suddenly • At Cooling • Soft Dry (auto Fan Speed) Inform the error code to an authorised dealer.
The indoor fan repeatedly stops for 80 seconds and • Depending on which 3 characters are displayed,
operates for 20 seconds to check the indoor temperature. temporary operation may be possible.
Whenever the temperature reaches the setting
temperature, operation starts again. Characters allowing Possible
temporary temporary Description
• At Heating (POWER LED blinks)
When the outdoor temperature is low and humidity is high, operation operations of operation
frost accumulates on the outdoor unit. The POWER LED
blinks when the unit is melting the frost. (Please wait as H23 Cooling Emergency
defrosting may take up to 10 minutes.) operation with
• Fog is blowing out from the unit • This occurs when the airflow from the air conditioner cools H27 Heating limited functions.
the room. (The Timer LED
H28 Cooling continues to blink.)
• There is a noise • A ‘passt’ sound is heard during defrosting or when the air
conditioner operation has been stopped. This is caused by
the refrigerant inside the air conditioner flowing in the ● Temporary operation
opposite direction.
• The air conditioner will expand or contract due to changes
in temperature, causing a cracking sound.
1. Press the MODE button and select Heating or
• The sound of water flowing is caused by the refrigerant Cooling.
flowing inside the unit. 2. Press the operation OFF/ON button
(‘beep! beep! beep! beep!’ sound is heard).
• The outdoor unit gives off water and steam • When defrosting, the frost melts and changes to water
and steam. * Use this operation temporarily, until repairs can be
made.
www.ilmalämpöpumput.com
45
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
46
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
*1) You can use the conventional (R22) flaring tool. If you need to buy a new tool, buy the R410A type.
*2) Use when it is necessary to detect small gas leaks.
For other installation work, you should have the usual tools, such as screwdrivers (+,-), a metal-cutting saw, an electrical drill, a hole
core drill (65 or 70 dia.), a tape measure, a level, a thermometer, a clamp meter, an insulation tester, a voltmeter, etc.
Table 4 Tools for serving
Type of work Ordinary tools R410A tools
Refrigerant charging Electronic scale for refrigerant charging
Refrigerant cylinder Charging orifice and
packing for refrigerant cylinder
Brazing (Replacing refrigerating cycle Nitrogen blow set (be sure to use nitrogen
part*1) blowing for all brazing), and brazing), and
brazing machine
*1) Always replace the dryer of the outdoor unit at the same time. The replacement dryer is wrapped in a vacuum pack. Replace
it last among the refrigerating cycle parts. Start brazing as soon as you have opened the vacuum pack, and begin the vacuuming
operation within 2 hours.
www.ilmalämpöpumput.com
47
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
3. Torque wrenches
Table 5
Conventional wrenches R410A wrenches
For 1/4 (opposite side x torque) 17 mm x 18 N.m (180 kgf.cm) 17 mm x 18 N.m (180 kgf.cm)
For 3/3 (opposite side x torque) 22 mm x 42 N.m (180 kgf.cm) 22 mm x 42 N.m (180 kgf.cm)
For 1/2 (opposite side x torque) 24 mm x 55 N.m (180 kgf.cm) 26 mm x 55 N.m (180 kgf.cm)
4. Manifold gauge
• Because the pressure is higher for the R410A type, the conventional type cannot be used.
Table 6 Difference between R410A and conventional high / low-pressure gauges
Conventional wrenches R410A wrenches
High-pressure gauge (red) -76 cmHg - 35 kgf/cm3 -0.1 - 5.3 Mpa -76 cmHg - 53 kgf/cm3
High-pressure gauge (blue) -76 cmHg - 17 kgf/cm3 -0.1 - 3.8 Mpa -76 cmHg - 38 kgf/cm3
• The shape of the manifold ports has been changed to prevent the possibility of mistakenly charging with another type of
refrigerant.
Table 7 Difference between R410A and conventional manifold port size
Conventional gauges R410A gauges
Port size 7/6 UNF 20 threads 1/2 UNF 20 threads
www.ilmalämpöpumput.com
48
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
5. Charging hose
• The pressure resistance of the charging hose has been
raised to match the higher pressure of R410A. The hose
material has also been changed to suit HFC use, and
the size of the fitting has been changed to match the
manifold ports.
www.ilmalämpöpumput.com
49
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
9. Refrigerant cylinders
• The R410A cylinders are labeled with the refrigerant
name, and the coating color of the cylinder protector is
pink, which is the color stipulated by ARI of the U.S.
• Cylinder equipped with a siphon tube are available to
allow the cylinder to stand upright for liquid refrigerant
charging.
www.ilmalämpöpumput.com
50
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Fig. 11 Relation between the flare nut structure and flaring tool end
www.ilmalämpöpumput.com
51
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Because the gas pressure of R410A is approximately 1.6 times as high as that of R22, copper pipes with the thickness shown
in Table 10, and with minimal impurities must be used. Care must also be taken during storage to ensure that pipes are not
crushed, deformed, or scratched, and that no dust, moisture or other substance enters the pipe interior. When storing sheathed
copper pipes or plain copper pipes, seal the openings by pinching or taping them securely.
2. Makings and management
a. Sheathed copper pipes and copper-element pipes
When using these pipes, check to make sure that they are the stipulated thickness. For flare nuts, be sure to used the same
nut that is used on the AC unit.
www.ilmalämpöpumput.com
52
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
b. Copper pipes
Use only copper pipes with the thickness given in table 10, and with minimal impurities. Because the surface of the pipe is
exposed, you should take special care, and also take measures such as marking the pipes to make sure they are easily
distinguished from other piping materials, to prevent mistaken use.
3. Precautions during refrigerant piping work
Take the following precautions on-site when connecting pipes. (Keep in mind that the need to control the entry of moisture and
dust is even more important that in conventional piping).
a. Keep the open ends of all pipes sealed until connection with AC equipment is complete.
b. Take special care when doing piping work on rainy days. The entering of moisture will degrade the refrigerating machine oil,
and lead to malfunctions in the equipment.
c. Complete all pipe connections in as short a time as possible. If the pipe must be left standing for a long time after removing
the seal, it must be thoroughly purged with nitrogen, or dried with a vacuum pump.
Precautions
• Be sure to read the instructions for the vacuum pump,
vacuum pump adaptor and manifold gauge prior to use,
and follow the instructions carefully.
• Make sure that the vacuum pump is filled with oil up to
the designated line on the oil gauge.
• The gas pressure back flow prevention valve on the
charging hose is generally open during use. When you
are removing the charging hose from the service port, it
will come off more easily if you close this valve.
www.ilmalämpöpumput.com
53
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
10.4.4. Refrigerant Compatibility (Using R410A Refrigerant in R22 ACs and Vice Versa)
Do not operate an existing R22 AC with the new R410A refrigerant. Doing so would result in improper functioning of the equipment
or malfunction, and might lead to a major accident such as an explosion in the refrigeration cycle. Similarly, do not operate an
R410A AC with R22 refrigerant. The chemical reaction between the refrigerating machine oil used in R410A ACs and the chlorine
that is contained in R22 would cause the refrigerating machine oil to degrade and lead to malfunction.
www.ilmalämpöpumput.com
54
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
5. Set the refrigerant cylinder onto the electronic scale, then correct the hose the cylinder and to the connection port for the
electronic scale. (1)(2)
Precaution:
Be sure to set up the cylinder for liquid charging. If you use a cylinder equipped with a siphon tube, you can charge the liquid
without having to turn the cylinder around
6. Remove the charging hose of the manifold gauge from the vacuum pump adaptor, and connect it to the connection port of the
electronic scale. (2)(3)
7. Open the valve of the refrigerant cylinder, then open the charging valve slightly and close it. Next, press the check valve of the
manifold gauge and purge the air. (2)(4) (Watch the liquid refrigerant closely at this point.)
8. After adjusting the electronic scale to zero, open the charging valve, then open the valve Lo of the manifold gauge and charge
with the liquid refrigerant. (2)(5) (Be sure to read the operating instructions for the electronic scale.)
9. If you cannot charge the stipulated amount, operate the unit in the cooling mode while charging a little of the liquid at a time
(about 150 g/time as a guideline). If the charging amount is insufficient from one operation, wait about one minute, then use the
same procedure to do the liquid charging again.
Precaution:
Never use the gas side to allow a larger amount of liquid refrigerant to be charged while operating the unit.
10. Close the charging valve, and after charging the liquid refrigerant inside the charging hose, fully close the valve Lo of the
manifold gauge, and stop the operation of the unit. (2)(5)
11. Quickly remove the charging hose from the service port. (6) If you stop midway through, the refrigerant that is in the cycle will
be discharged.
12. After putting on the caps for the service port and operating valve, inspect around the caps for a gas leak. (6)(7)
www.ilmalämpöpumput.com
55
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
10.4.6. Brazing
As brazing requires sophisticated techniques and experiences, it must be performed by a qualified person.
In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting
dry nitrogen gas (N2) flow.
<Brazing Method for Preventing Oxidation>
1. Attach a reducing valve to the nitrogen gas cylinder.
2. Attach a reducing valve to the nitrogen gas cylinder.
3. Apply a seal onto the clearance between the piping and inserted pipe for the nitrogen gas in order to prevent the nitrogen gas
from flowing backward.
4. When the nitrogen gas is flowing, be sure to keep the piping end open.
5. Adjust the flow rate of nitrogen gas so that it is lower than 0.05 m3/h, or 0.02 MPa (0.2 kgf/cm2) by means of the reducing valve.
6. After taking the steps above, keep the nitrogen gas flowing until the piping cools down to a certain extent (i.e. temperature at
which pipes are touchable with finger).
7. Completely remove the flux after brazing.
www.ilmalämpöpumput.com
56
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
11 Installation Instructions
Required tools for Installation Works
1. Philips screw driver 5. Spanner 9. Gas leak detector 13. Multimeter
2. Level gauge 6. Pipe cutter 10. Measuring tape 14. Torque wrench
18 N.m (1.8 kgf.m)
42 N.m (4.2 kgf.m)
55 N.m (5.5 kgf.m)
3. Electric drill, hole core drill 7. Reamer 11. Thermometer 15. Vacuum pump
(ø70 mm)
4. Hexagonal wrench (4 mm) 8. Knife 12. Megameter 16. Gauge manifold
This indication shows the possibility of causing injury or damage to properties only.
Symbol with background white denotes item that is PROHIBITED from doing.
• Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
1. Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or fire.
2. Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical shock or fire.
3. Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or
electrical shock.
4. Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly
done, the set will drop and cause injury.
5. For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and single
outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
6. Use the specified cable (1.5 mm 2) and connect tightly for indoor/outdoor connection. Connect tightly and clamp the cable so that no
external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
7. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will
cause heat-up at connection point of terminal, fire or electrical shock.
8. When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle.
Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.
9. When connecting the piping, do not allow air or any substances other than the specified refrigerant (R410A) to enter the
refrigeration cycle. Otherwise, this may lower the capacity, cause abnormally high pressure in the refrigeration cycle, and
possibly result in explosion and injury.
10. • When connecting the piping, do not use any existing (R22) pipes and flare nuts. Using such same may cause
abnormally high pressure in the refrigeration cycle (piping), and possibly result in explosion and injury. Use only
R410A materials.
• Thickness of copper pipes used with R410A must be more than 0.8 mm. Never use copper pipes thinner than 0.8
mm.
• It is desirable that the amount of residual oil is less than 40 mg/10 m.
11. Do not modify the length of the power supply cord or use of the extension cord, and do not share the single outlet with
other electrical appliances. Otherwise, it will cause fire or electrical shock.
www.ilmalämpöpumput.com
57
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
1. The equipment must be earthed. It may cause electrical shock if grounding is not perfect.
2. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at
surrounding of the unit, it may cause fire.
3. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the
furniture.
www.ilmalämpöpumput.com
58
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Attached accessories
INDOOR UNIT
• There should not be any heat source or steam near the
unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into
consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall,
ceiling, fence or other obstacles.
• Recommended installation height for indoor unit shall be
at least 2.3 m.
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
• This illustration is for explanation purposes only.
fence or other obstacles.
The indoor unit will actually face a different way.
• Do not place any obstacles which may cause a short
circuit of the discharged air.
• If piping length is over the common length, additional
refrigerant should be added as shown in the table.
www.ilmalämpöpumput.com
59
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
The mounting wall is strong and solid enough to prevent it from Caution
the vibration. When the wall is hollow, please be sure to use the
sleeve for tube ass’y to prevent dangers caused by
mice biting the connecting cable.
www.ilmalämpöpumput.com
60
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
(This can be used for left rear piping & left bottom piping also.)
www.ilmalämpöpumput.com
61
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
• Secure the cable onto the control board with the holder
(clamper).
www.ilmalämpöpumput.com
62
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
63
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
11.3.4. (a) EVACUATION OF THE EQUIPMENT (FOR EUROPE & OCEANIA DESTINATION)
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the
following procedure.
1. Connect a charging hose with a push pin to the Low and High side of a charging set and the service port of the 3-way valve.
• Be sure to connect the end of the charging hose with the push pin to the service port.
2. Connect the center hose of the charging set to a vacuum pump with check valve, or vacuum pump and vacuum pump adaptor.
3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to
-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not
move after approximately five minutes.
Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.
5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6. Tighten the service port caps of the 3-way valve at torque of 18 N.m with a torque wrench.
7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal
wrench (4 mm).
8. Mount valve caps onto the 2-way valve and the 3-way valve.
• Be sure to check for gas leakage.
CAUTION
• If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:
• If the leak stops when the piping connections are tightened further, continue working from step 3.
• If the leak does not stop when the connections are retightened, repair the location of leak.
• Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause
frostbite.
www.ilmalämpöpumput.com
64
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
3. Secure the cable onto the control board with the holder
(clamper).
4. Attach the control board cover back to the original position EVALUATION OF THE PERFORMANCE
with the screw. • Operate the unit at cooling operation mode for fifteen
minutes or more.
• Measure the temperature of the intake and discharge air.
11.3.6. PIPE INSULATION • Ensure the difference between the intake temperature and
the discharge is more than 8°C.
www.ilmalämpöpumput.com
65
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
12 Servicing Information
Caution:
• Pb free solder has a higher melting point than standard solder; Typically the melting point is 50 - 70°F (30 - 40°C) higher. Please use
a high temperature soldering iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).
• Pb free solder will tend to splash when heated too high (about 1100° F/600°C).
12.1. Troubleshooting
During troubleshooting and servicing, rated compressor operating frequency must be obtained in order to check the
specification and technical data. Below are the methods used to obtain rated compressor operating specification.
(a) Cooling
(i) Press the Auto button continuously for 5 seconds or less than 8 seconds, the air conditioner starts operation at Cooling rated frequency.
(“beep” will be heard at the 5th second.)
(ii) Short the service terminal (CN-S) of the outdoor printed circuit board. The operation of air conditioner is Cooling rated frequency.
(b) Heating
Press the Auto button continuously for 8 seconds or less than 11 seconds, the air conditioner starts operation at Heating rated
frequency. (“beep” “beep” will be heard at the 8th second.)
www.ilmalämpöpumput.com
66
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
67
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
1. Relationship between the condition of the air conditioner and pressure and electric current
Cooling Mode Heating Mode
Condition of the air
conditoner Low Pressure High Pressure Electric current Low Pressure High Pressure Electric current
during operation during operation
Insufficient refrigerant
(gas leakage)
Heat radiation
deficiency of the
outdoor unit
Inefficient compression
• Carry on the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
Once abnormality detected during operation, the unit will immediately stop its operation (Timer LED is blinking) and maximum of
three error codes (abnormality) will be saved in memory. The abnormality of the operation can be identified through the below
breakdown diagnosis method:
• Press “CHECK” button at remote controller continuously for more than five seconds to turn on the diagnosis mode, “H11” will
be displayed at remote controller.
• By pressing the TMER “ ” button once, next error code will be displayed; press “V” button once, previous error code will be
displayed.
• If error code displayed matches the error code saved in unit memory (abnormality detected), four “beep” sounds will be heard
and Power LED will light on. Otherwise, one “beep” sound is heard.
If “CHECK” button is press again or without any operation for 30 seconds, the diagnosis mode will turn off.
www.ilmalämpöpumput.com
68
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
H11 Indoor / outdoor abnormal > 1 min after starting Indoor fan operation • Internal / external cable connections
communication operation only
• Indoor / Outdoor PCB
H14 Indoor intake air temperature sensor — — • Intake air temperature sensor
abnormality (defective or disconnected)
H15 Outdoor compressor temperature sensor Continue for 5 sec. — • Compressor temperature sensor
abnormality (defective or disconnected)
H16 Outdoor Current Transformer open — — • Outdoor PCB
circuit
• IPM (Power transistor) module
H19 Indoor fan motor merchanism lock — — • Indoor PCB
• Fan motor
H23 Indoor heat exchanger temperature Continue for 5 sec. O • Heat exchanger temperature sensor
sensor abnormality (Cooling only) (defective or disconnected)
H27 Outdoor air temperature sensor Continue for 5 sec. O • Outdoor temperature sensor
abnormality (defective or disconnected)
H28 Outdoor heat exchanger temperature Continue for 5 sec. O • Outdoor heat exchanger
sensor abnormality temperature sensor (defective or
disconnected)
H33 Indoor/Outdoor wrong connection — — • Indoor/Outdoor supply voltage
H98 Indoor high pressure protection — — • Air filter dirty
• Air circulation short circuit
H99 Indoor heat exchanger anti-freezing — — • Insufficient refrigerant
protection
• Air filter dirty
F11 Cooling / Heating cycle changeover 4 times occurance — • 4-way valve
abnormality within 30 minutes
• V-coil
F90 PFC control 4 times occurance — • Voltage at PFC
within 10 minutes
F91 Refrigeration cycle abnormality 2 times occurance — • No refrigerant
within 20 minutes
(3-way valve is closed)
F95 Cool high pressure protection 4 times occurance — • Outdoor refrigerant circuit
within 20 minutes
F96 IPM (power transistor) overheating — — • Excess refrigerant
protection
• Improper heat radiation
• IPM (Power transistor)
F97 Outdoor compressor overheating 4 times occurance — • Insufficient refrigerant
protection within 10 minutes
• Compressor
F98 Total running current protection 3 times occurance — • Excess refrigerant
within 20 minutes
• Improper heat radiation
F99 Outdoor Direct Current (DC) peak 7 times occurance — • Outdoor PCB
detection continuously
• IPM (Power transistor)
• Compressor
Note:
“O” - Frequency measured and fan speed fixed.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard
following by pressing the “RESET” button at remote controller.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error
Codes Table) by using remote controller or Auto Switch at indoor unit. However, the remote controller signal receiving sound is
changed from one “beep” to four “beep” sounds.
www.ilmalämpöpumput.com
69
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
When the batteries are inserted for the first time, or the
batteries are replaced, all the indications will blink and the
remote control might not work.
If this happen, remove the cover of the remote control and
push the reset point once to clear the memory data.
When there are more than one indoor units installed in the
same room, it is possible to set different remote control
receiving signal by modifying the jumpers inside remote
controller.
www.ilmalämpöpumput.com
70
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Fig. 2
Fig. 1
Fig. 3
Fig. 4
Fig. 5
Fig. 6
www.ilmalämpöpumput.com
71
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Fig. 7 Fig. 10
Fig. 8 Fig. 11
Fig. 9
www.ilmalämpöpumput.com
72
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Fig. 13
Fig. 15
Fig. 14
www.ilmalämpöpumput.com
73
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
Fig. 16
Fig. 17
Fig. 18
Fig. 19
www.ilmalämpöpumput.com
74
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
13 Technical Data
www.ilmalämpöpumput.com
75
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
76
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
77
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
14 Exploded View
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
www.ilmalämpöpumput.com
78
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
(Note)
• All parts are supplied from MAICO, Malaysia (Vendor Code: 061).
• “O” marked parts are recommended to be kept in stock.
www.ilmalämpöpumput.com
79
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
16 Exploded View
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
www.ilmalämpöpumput.com
80
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
(Note)
• All parts are supplied from MAICO, Malaysia (Vendor Code: 061).
• “O” marked parts are recommended to be kept in stock.
www.ilmalämpöpumput.com
81
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
• CS-E9CKP / CS-E12CKP
SCHEMATIC DIAGRAM 1/3
TO OUTDOOR
1 1
2 2
3 3
1 2 3 4 5 6 7 8 9 10 CN-MAIN
PH10
(WHT)
WHT AC5 R14 510
WHT AC3
TEMPERATURE C29
FUSE 3300p R4 R5 R7
250VAC 20k 20k 20k
6 11 5 12
FG1
R3 IC2 IC2 R6 R8 5.1k
100 C1 100 C2
FG2 0.1µ 0.022µ
C30
3300p C5 R9
250VAC 100µ + 330
16V
AC4
RY-PWR
C6
C3
+ 47µ
1000p
25V
AC2
R1 43 R2 43
POWER SUPPLY 1/2W 1/2W 9
AC1 16 1
15 2
RY-PWR
14 3
13 4
HA 10 7
R17 1k 8
4
3 BZ
2 BZ1 IC2
DISPLAY 1 4KHz TD62003AF
C9 R20 R21
0.01µ 10k 1k
D401
ION1
D402
ION2
R19 C10
POWER MONITOR D403 10k 0.01µ
(PH10)
HIGH
D404 CN-DISP1 CN-DISP
2
R42 110
LOW D405 1 1
R45 270
2 2
3 3 R46 270
SW401 R47 270
AUTO SW AD11008 4 4
R18 1k
5 5
D406 R48 330
TIMER 6 6
R49 330
D407 7 7
QUIET R50 330
8 8
D408 R51 270
POWERFUL 9 9
D409 10 10
POWER
CN-DISP
L6
5
R40
4
3
2
1 C22 C23
R38
10k
6 3 JP8
D0 CS
5 1
D1 BUSY
IC3
7 BR9080F
www.ilmalämpöpumput.com
82
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
RECEIVER
A67C3859 (MX-3)
CN-RCV CN-RCV1
R12 1k C4 R13 1 1 3
1000p 20k 2 2 2
C14 3300p
R15 3 3 1
1k + 5
4
(PH5)
IC5
TD62003AF CN-STM1
9
1 16
5 5
2 15
4 4
3 14
3 3
4 13
2 2
5 12
1 1
6 11
7 10 VERTICAL
(PH5)
8
CN-STM2
9
1 16
5 5
2 15
4 4
3 14
3 3
4 13
2 2
5 12
6 11 1 1
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
7 10
HORIZONTAL
P47
P46
P45
P44
P43
P42
P41
P40
P67
P66
P65
P64
BUZ
P74
P73
P72
8
P71
1 P50 48
P51 TD62003AF
POWER RELAY
ON/OFF 15V
INTP3
BUZZER
3 P52 46
DATA RECEPTION
RxD INTP2
4 P53 45
50/60Hz
DETECTION INTP1
5 P54 44
JP4 8 MHz
10 Vdd0 IC(VPP) 39 (15pF X 2)
CSTS0800MG03
P30 INTAKE AIR TEMP XT1
11 OPERATION LED 38
IC4
P31 XT2
12 QUIET LED PIPE TEMP 37 R32 IC-PST600DMT
100k
P32 Reset 36 JP3 O I
13 TIMER LED TEST RESET
C19 + G C18
P33 2.2µ
14 AUTO OPERATION POWER P80 35 0.01µ
50V
TXD2 DATA AVref
15 34 CN-
TRANSMISSION GROUND
C11 R29
RXD2 1µ 4
16 ANI0 33 15k
3
RXD0
SCK1
TXD0
Vdd1
ANI3
ANI2
ANI1
Avss
P36
S1L
S01
P25
P17
P16
P15
P14
2
2.2k 1
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 b
C21
JP1
1µ 2.2k
Q2
R28
1k
JP2
Q1 C12
D2 R27 1k JP5 JP7
c 0.01µ
b CN-TH
R26 10k R41 10k JP6
R38 R39 1 AIR TEMP. SENSOR
6.2k 6.2k e C13
0.01µ 2 (15k 3950)
3 PIPE TEMP. SENSOR 1
R54 10k
R31 10k
www.ilmalämpöpumput.com
83
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
F001
CN001
L001 C003
11
Z001 C002 C005
10
9 C004 DB004
8
7
6
5
4
3
2 TH002 TH001
1
D007 R030 R046
CN002
1 1
FAN MOTOR
2 2
3 3 L002 R003
4 4 R028
5 5
6 6
e PC005
Q002 b R029 4 1
7 7
c R113
PC001
R008
R114 1 4 3 2
PC004
R002 1 4
e Q001
2 3 R004
R116 ZD005 10k
PC002 23 PC006
1 4.7k b 4 1
4 feedback
R001 PC003
1 4
R118
Q102 ZD001
e
CN002
1
2
3
4
5
6
7
1
2
3
4
5
CN101
R020
T02
R016 R026 5 9 D101
C105
R048 R025 +
7
C009 C010
6
R060
3
R058 R048
c
R021
ZD004
b
R053
C016
CN2
F1 T01 D101 HV
CH1
4 R101
R2 R3 R6
3
VIN
2 R16
1
GND
ERR D102
c c Q4
EH-4P Q1 R13 R9 C5
b b
Q2 C* R102
c D6
e C3 D1 e D3 -5.7kV
b Q5 R15 C10 D5
c
C2 C1 e C3 R4 b Z02
C9
4.7k 10k e
R3 R14 R10
C6 R12 C7
D1 CN3
D2 Z01 GND
www.ilmalämpöpumput.com
84
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
• CU-E9CKP / CU-E12CKP5
REACTOR
FG1
C-PFC2
BLUE
DC+2 FUSE101
ZNR109 R196 RED 3A
+ +
100k DC-2
+ BLACK R33 R148
R195 232k 232k
PTC2 100k
JP5 1/4W 1% 1/4W 1%
ZNR107 DC-1 R194 JP6 R197 R199
BLACK 100k 232k 232k
PTC1 JP7
1/4W 1% 1/4W 1%
R34 R149
232k 232k
ZNR108 RY-PWR 2 3 1 1/4W 1% 1/4W 1%
TERMINAL CORE A00156 RED R198 R200
AC-BLK RY-C 4 DB101 232k 232k
1 1 A00156 15A 1/4W 1% 1/4W 1%
C49 600V
2 2 ZNR102 LF101 4700pF
3 3 ERZVEAV511 250VAC R35 R150
11.5k 11.0k
C48 1/4W 1% 1/4W 1%
ZNR103 4700pF
ERZVEAV511 250VAC
AC-WHT 3
2 1 DB102
D6 D5 15A R139
600V 200Ω
4 Q6 PC3
FAN MOTOR Q4 2SC2411KRTX c TLP421
D4 D3 b 4 1
B FM1 C GT4DM101
R36
R FM2 G 47Ω e
e 3 2
Y FM3 C-FM CR102 R145 Q7
J0HBJY000004 b DTA1036KRTX
R62 10k
1.65k 1V D8 E
R144 PC5
RY-FM c TLP421
R81 1/4W 1% 33Ω 1 4
R143
R61 D7
590Ω + R82 C131 R37
HOT1 CR101
J0HBJY000004 1V 1/4W 1500p 10k 2 3
1%
VR1
200Ω
HOT2 RY-HOT
R170 22k A00207M
4-WAYS VALVE D2 ERA15-10
ZD2 PC4
D1 R5 1.6k TLP421 D17
DATA ERA15-06 R171 (GR) ERA15-01
R30
39k 2WS 4 PC2 R32
RED 2W 15k R64 4 1k
2 1 3 4 680Ω ZD1 Q3
C140 + R7 c
1000p 4.7k 2SC2412KRTX
PC1 R66 b
250V 2
TLP421 3 4 1 100k
R31
3 3
(BL) ZD3 R8 e C132
39k 2WS 0.01
4.7k
R140 R147
22k 10k c
c 4.7k b
b
R172 5.6k Q5 e 10k
R9 47k e 3 2 13 10 4 5
Q1
DTC143XK 3 2 13 10 4 5
C413
R401 R400 1000p
+ + R402 374k 1% 37.4k (JC)
1.8k D400
1%
C402 R403
0.01 51.1k
1%
e Q402
e
10k 10k
b 4.7k 4.7k b
11 11
R404 12 12
49.9k c c
1% R405 R406
IC401 C412 100Ω 7.87k
1000p 1%
R407 R408
D12 ZD4 AN1393S C404 15k 2.74k
ERA15-01 RD10EB2 0.01 1% 1%
R415
Q403 R409 R412 R414 3.74k
A55C2411KRTX 1.8k 3.74k D401 3.74k 1% 1%
IC402
RY-C 14 14 c 1% C414
b 1000p
C407 0.01 8 8
R411 R410 R416 9 9
e 10k 100Ω R413
5.0k 82.5k
1% 1%
6 7 1
6 7 1
RY-HOT
RY-PWR
PY-FM
R141
10Ω
www.ilmalämpöpumput.com
85
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
16 40 30 38 37 36 35 41 1 42
1 10 9 8 7 6 5 11 1 12
R239
1k
4 4
10 10 R202
100k
R205 R245
10k 0Ω
INTP4
INTP3
INTP2
INTP1
INTP0
NMI
AVREF
AVSS
ANI7
ANI6
ANI5
RTPO7
RTPO6
RTPO5
RTPO4
RTPO3
RTPO2
Vss
7 GND Vcc 2
R233
ANI4 1k
6 D0 CS 3 R206 R207 R208 1 P16 60
10k 10k 10k
COMPRESSOR
U V W U V W ANI3
REVOLUTION
5 D1 SK 4 2 T06 59
DETECTION
DC VOLTAGE
RXD ANI2
DC PEAK
2 2 3 58
DATA RECEPTION COMPRESSOR TEMP
ANI1
3 3 4 TXD 57
DATA TRANSMISSION OUTDOOR AIR TEMP
5 S1 ANI0 56 15 15
PIPE TEMP
6 S0 AVDD 55
+
7 SCK Vdd 54
RESET
A52PST600DR R204 8 RESET Vss 53
IC203 100k 6 MHz (47pF X 2)
9 Vdd P37 52
CSTCC6-00
X201 X2 IC201 P36 51
+ 10
6 MHz A52D953AGA17
11 X1 OSC P35 50
P54
P55
P56
P57
P60
P61
P41
P42
P43
P44
P45
P46
P47
P50
P51
P52
P62
P63
Vss
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
11 11 3 33
D201
RD501V-40
R217
10k
4 34
R232 51k R235 1k
26 11
9
16 1
5 5
15 2
6 6
14 3 12 12
9 9
13 4 R231 47k JP201 5 20
R210 R211
12 5 1k 1k 8 23
R209 R216
IC202 11 6 10k 7 22
R237 10k
TD62003AF 10 7 R238 R240 R241 6 21
10k 10k 1k 1k
8
3 18
R213 R214
7 7 1k 10k
ECU1
10 9 15 4 8 13 14
25 24 30 19 8 43 44
R73
R74 10k
10k
TEST
www.ilmalämpöpumput.com
86
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
D9 NJM78M15F
ERA2204-04 IC2
+ +
L1
D10 ERB83-006 (JUMPER)
+
NJM78M05F
R104 IC1
R101
R102
R103 +
110Ω
D11
ERA22-04
+
R126
4.7k
1/4W
D13 ERA22-06 Q2
+ R106 +
33Ω HV1C1
D RED
Vcc C
CORE
IN HO
R56 U RED
680Ω COM CE
D14
ERA22-06
+
HV1C2
Vcc C
IN HO
R55 V BLUE
680Ω COM CE
D15
ERA22-06
+ COMPRESSOR
HV1C3
Vcc C
IN HO
R54 W YELLOW
680Ω COM CE
LVIC
C122
C121
C120
C107
C108
C109
C110
Vcc U OUT
1000p 0.047
IN(X)
R53 680Ω
V OUT
IN(Y)
R52 680Ω
IN(Z) C114
R51 680Ω 0.47
W OUT 630V
VFO
C119
C118
C117
5600p roc
GND CCT N
R105 82.5Ω
R112 R113
R114 R115
R116 R117
R118 R119
R120 R121
R122 R123
R125
R186
R110 R111
R187
CN-S
1
2
www.ilmalämpöpumput.com
87
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
88
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
89
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
90
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
91
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
92
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
93
CS-E9CKP CU-E9CKP5 / CS-E12CKP CU-E12CKP5
www.ilmalämpöpumput.com
94 [MAICO] Printed in Malaysia