50ZPC

Single---Packaged Air Conditioner System


With Puronr (R---410A) Refrigerant Single Phase
2 to 5 Nominal Tons (Sizes 024---060)

Product Data

such as coil cleaning are sped up with the multiple access side
panels.
NO--RUST BASEPAN WITH INTEGRATED DRAIN PAN is
standard on all units. The unit features a tough, hightech,
composite material basepan with integrated drain pan. The
composite material eliminates the potential problems of rust and
premature replacement which are common with standard metal
basepans.
DURABLE PRE--PAINTED STEEL CABINET protects
against harsh weather. The watertight construction and corrosion--
resistant finish will keep it looking like new for years. The paint
treatment process ensures quality protection against the elements.
A compact, low--profile design utilizes a louvered coil enclosure
for protection against vandalism and hail damage.
INDOOR AIR QUALITY is designed into the unit. A sloped
drain pan minimizes the amount of standing water inside the unit,
which limits mold and mildew growth. The drain pan is made of a
rust--proof material and will not deteriorate or release foreign
matter into the airstream.
LIGHTWEIGHT, COMPACT CONSTRUCTION is ideal for
A10165
manufactured housing and residential applications. This unit is one
Unit 50ZPC of the lightest, most compact packaged units ever designed. It’s
Certified to leak 2% or less of nominal air conditioning CFM light weight (230 lb [104 kg]) for the 024 size) makes the unit
delivered when pressurized to 1--in. W.C. with all present air easier to handle. The low height keeps ductwork connections to a
inlets, air outlets, and condensate drain port(s) sealed. minimum and makes units less visible.
This unit is a packaged air conditioner for manufactured housing, This unit utilizes a structural beam design to form the four sides of
residential, and light commercial applications. The unit design is the cabinet. Only 12 different pieces of sheet metal are used in the
the result of our firm commitment to the development of the finest unit construction to simplify the unit for greater reliability.
air conditioners that modern technology can offer. EFFICIENT, DEPENDABLE PERFORMANCE with durable
The unit is built in one basic cabinet size and features a round or compressors designed for efficiency. The unit offers up to 14.5
rectangular side--by--side duct configuration. SEER (Seasonal Energy Efficiency Ratio) cooling performance
efficiencies. This performance level can reduce cooling expenses
FEATURES/BENEFITS by as much as 30% compared to older cooling equipment.
FACTORY--ASSEMBLED PACKAGE is a compact, fully DURABLE, DEPENDABLE, COMPRESSORS are designed
self--contained, electric cooling unit with horizontal supply and for high efficiency. Each compressor is hermetically sealed against
return ducts. The unit is available in a variety of standard cooling contamination to help promote longer life and dependable
sizes to meet residential and light commercial requirements. Unit operation. Vibration isolation provides quiet operation.
installs easily on a ground level pad. Compressors have internal overcurrent protection.
EASY TO INSTALL -- The unit is small, compact, and easy to DIRECT--DRIVE MULTISPEED, BLOWER MOTOR is
handle. Every unit has an identical 32 x 51--in. (813 x 1295 mm) standard on all models. It’s high efficiency design ensures high
footprint to make planning simple. The concise design uses less performance with most duct systems.
sheet metal and makes the unit lighter than other units. The unit DIRECT--DRIVE, PSC CONDENSER--FAN MOTORS are
can be easily positioned on the job site with the hand holds built designed to help reduce energy consumption and provide for
into the unit basepan. cooling operation down to 40F (4.4° C).
AERODYNAMIC FAN BLADE DESIGN reduces the overall
sound now as low as 72dBA.
SERVICE ACCESS makes installation and maintenance quicker
and easier. This unit is designed to be serviced from both the side
and front. The design allows easy access for installation and
maintenance procedures on the unit. Routine maintenance tasks

1
REFRIGERANT SYSTEM is designed to provide dependability. ACCESSORY ELECTRIC HEATERS — A variety of
Liquid refrigerant filter driers are used to promote clean, accessory electric heaters are available. These heaters are comprised
unrestricted operation. Each unit leaves the factory with a full of a separate heater module mounted on the blower inlet and
refrigerant charge. Refrigerant service connections make checking remote mounted controls located in the unit control box. Single
operating pressures easier. point electrical connections are available for powering both the
heater and the unit.

TABLE OF CONTENTS
Page
FEATURES/BENEFITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--2
MODEL NUMBER NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
AHRI CAPACITIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
BASE UNIT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--6
50ZPC

SELECTION PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
PERFORMANCE DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8--12
TYPICAL WIRING SCHEMATICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
OPERATING SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
APPLICATION DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
TYPICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

MODEL NUMBER NOMENCLATURE


50ZPC 024 --- --- --- 3 0 --- ---

Type of Unit
50ZPC--- Single Packaged Air
Conditioner System

Options

Nominal Cooling Capacity TP --- Base unit with tin plated indoor coil hairpins
024 --- 2.0 Tons
030 --- 2.5 Tons Only used if ordering an option
036 --- 3.0 Tons
042 --- 3.5 Tons
048 --- 4.0 Tons
060 --- 5.0 Tons
Series

Electrical Supply
N/A 3 --- 208/230--- 1--- 60

Use of the AHRI Certified


TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.

2
AHRI* CAPACITY RATINGS
Cooling Capacities and Efficiencies
NET COOLING
CAPACITY
UNIT SIZE NOMINAL TONS STANDARD CFM EER† SEER**
AT 95° F (35° c)
(Btuh)
024 2 800 22400 11.5 14
030 2.5 1000 28600 11.5 14
036 3 1200 35000 11.5 14
042 3.5 1400 41000 11.5 14.5
048 4 1600 47000 11.5 14
060 5 1850 54000 11.3 14
LEGEND Notes:
dB--- --- ---Sound Levels (decibels) 1. Ratings are net values, reflecting the effects of circulating fan heat.
db—Dry Bulb Ratings are based on:
SEER—Seasonal Energy Efficiency Ratio Cooling Standard: 80° F (26.7° C) db, 67° F wb (19.4° C) indoor
wb—Wet Bulb entering--- --- ---air
COP--- --- ---Coefficient of Performance temperature and 95° F db (35° C) outdoor entering--- --- ---air temperature.
* Air Conditioning Heating & Refrigeration Institute 2. Before purchasing this appliance, read important energy cost and effi-
† At ”A” conditions--- ---80° F (26.7° C) indoor db/67° F ciency information available from your retailer.

50ZPC
(19.4° C) indoor wb & 95° F (35° C) outdoor db.
** Rated in accordance with U.S. Government DOE
Department of Energy) test procedures and/or AHRI
Standards 210/240 --- --- ---08, 270 ---1995.

A--Weighted Sound Power Level (dBA)


TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)
UNIT SIZE STANDARD RATING (dBA)
125 250 500 1000 2000 4000 8000
024 72 54.4 54.9 58.8 67.5 53.7 48.5 39.4
030 75 55.4 63.9 62.8 59.0 54.7 45.5 37.9
036 75 60.4 58.9 62.8 63.0 58.7 52.5 45.4
042 75 59.9 64.4 69.3 68.0 65.2 63.0 60.4
048 76 58.4 61.9 65.3 65.5 59.7 55.0 47.4
060 80 72.9 65.4 68.8 70.5 65.2 60.5 50.9

PHYSICAL DATA
UNIT SIZE 024 030 036 042 048 060
NOMINAL CAPACITY (ton) 2 2.5 3 3.5 4 5
SHIPPING WEIGHT (lb) 286 298 329 352 368 402
(kg) 130 136 150 160 167 183
COMPRESSOR TYPE RECIPROCATING SCROLL
REFRIGERANT R-410A
REFRIGERANT QUANTITY (lb) 3.3 5.2 5.5 7.3 6.3 7.5
QUANTITY (kg) 1.5 2.4 2.5 3.3 2.9 3.4
METERING DEVICE ID Piston TXV
ORIFICE OD (in.) 0.057 0.063 0.067 0.076 0.080
N/A
(mm) 1.45 1.60 1.70 1.93 2.03
OUTDOOR COIL
ROWS...FINS/in. 1...20 1...20 2...20 2...20 2...20 2...20
FACE AREA (sq. ft) 9.1 9.1 9.1 10.2 13.0 15.5
OUTDOOR FAN
NOMINAL AIRFLOW (CFM) 2400 2400 2700 2700 2700 3000
DIAMETER (in.) 20 20 20 20 20 20
DIAMETER (mm) 508 508 508 508 508 508
MOTOR HP (RPM) 1/8 (825) 1/8 (825) 1/4 (1100) 1/4 (1100) 1/4 (1100) 1/3 (1110)
INDOOR COIL
ROWS...FINS/in. 2...12 3...12 3...12 3...12 3...15 3...15
FACE AREA (sq. ft) 4.3 4.3 4.3 4.9 4.9 6.1
INDOOR BLOWER
NOMINAL COOLING AIRFLOW
(CFM) 800 1000 1200 1400 1600 1850
NOMINAL SIZE W x D (in.) 8 x 11 8 x 11 9 x 12 9 x 12 11 x 12 11 x 12
(mm) 254 x 203 254 x 203 279 x 229 279 x 229 279 x 229 267 x 305
MOTOR (HP) 1/3 1/3 1/2 1/2 3/4 1
HIGH-PRESSURE SWITCH (psig)
CUTOUT 650 +/- 15
RESET (AUTO) 420 +/- 25
RETURN-AIR FILTERS
THROWAWAY (in.) 20x20x1 20x24x1 24x30x1 24x36x1
(mm) 508x508x25 508x610x25 610x762x25 610x914x25
*Required filter sizes shown are based on the AHRI (Air Conditioning, Heating and Refrigeration Institute) rated airflow at a velocity of 300 ft/min for throwaway
type or 450 ft/min for high capacity type. Recommended filters are 1 ---in. (25.4 mm) thick.

3
OPTIONS AND ACCESSORIES
FACTORY FIELD
ITEM DESCRIPTION INSTALLED INSTALLED
OPTION ACCESSORY
Coil Options Base unit with tin plated indoor coil hairpins X
Compressor Start Kit assists compressor start---up by providing
Compressor Start Kit X
additional starting torque on sing phase units only.
Thermostats provide control for the system heating and cooling
Corporate Thermostats X
functions.
Crankcase Heater provides anti---floodback protection for low---
Crankcase Heater X*
load cooling applications.
Electric Heaters Electric Heat Supplement X
Low Ambient Kit (Motormaster II Control) allows the use of mech-
Low Ambient Kit anical cooling down to outdoor temperatures as low as 0°F X
( ---18° C) when properly installed.
Automatically prevents the compressor from restarting for at least
Time Guard II 4 minutes and 45 seconds after shutdown of the compressor. Not X
required when a corporate programmable thermostat is applied.
*Refer to Price Page for application detail.

Accessory Electric Heaters


USED WITH SIZES
50ZPC

NOMINAL
CATALOG CIRCUIT
CAPACITY
ORDERING NO. BREAKER STAGES 024 030 036 042 048 060
(kW)
(Yes/No)
ELECTRIC HEATERS (208/230 -- SINGLE PHASE-- 60Hz)
CPHEATER125A0* 3.8 / 5.0 No 1      
CPHEATER126A0* 3.8 / 5.0 Yes 1      
CPHEATER127A0* 5.6 / 7.5 No 2      
CPHEATER128A0* 5.6 / 7.5 Yes 2      

CPHEATER129A0* 7.5 / 10.0 No 2     

CPHEATER130A0* 7.5 / 10.0 Yes 2      

CPHEATER131A0* 11.3 / 15.0 Yes 2    

CPHEATER132A0* 15.0 / 20.0 Yes 2  

 =Approved combination

Multiplication Factors
HEATER kW RATING VOLTAGE DISTRIBUTION MULTIPLICATION FACTOR
200 .69
208 .75
240
230 .92
240 1.00
Example: 15.0 kW (at 240v) heater on 208v
= 15.0 (.75 mult factor)
= 11.25 capacity at 208v

4
DIMENSIONAL DRAWINGS — 024--036

50ZPC

A14413

5
DIMENSIONAL DRAWINGS — 042--060
50ZPC

A14414

6
SELECTION PROCEDURE C. SELECT ELECTRIC HEAT.
A. DETERMINE COOLING AND HEATING The required heating capacity is 15,000 Btuh (given).
REQUIREMENTS AT DESIGN CONDITIONS. Determine the electric heat capacity in kW.
Given: 15,000 Btuh
= 3.8 kW of heat required
3414 Btuh/kW
Required Cooling Capacity (TC) . . . . . . . . . . 34,000 Btuh
Sensible Heat Capacity (SHC) . . . . . . . . . . . . 25,000 Btuh Enter the Accessory Electric Heater table on page 4 for 208/230,
single--phase, 036 unit. The 5--kW heater at 240v most closely
Required Heating Capacity . . . . . . . . . . . . . . . 15,000 Btuh
satisfies the heating required. To calculate kW at 230 V, multiply
Outdoor Entering--Air Temperature . . . . . . . . 95° F (35° C) the heater kW by multiplication factor 0.92 found in the
Indoor Entering--Air Temperature . . . 80° F edb (26.7° C); Multiplication Factors table on page 4.
67° F (19.4° C) ewb 5 kW x 0.92 = 4.6 kW
Indoor--Air Quantity . . . . . . . . . . . . . . . . . . . . . 1200 CFM 4.6 kW x 3414 Btuh/kW = 15,704 Btuh
External Static Pressure . . . . . . . . . . . . . . . . . 0.20 IN. W.C.
Electrical Characteristics (V--Ph--Hz) . . . . . . . . . 230--1--60 D. DETERMINE FAN SPEED AND POWER
REQUIREMENTS AT DESIGN CONDITIONS.
B. SELECT UNIT BASED ON REQUIRED COOLING Before entering the air delivery tables, calculate the total static
CAPACITY (3--TON EXAMPLE) pressure required. From the given, Filter Pressure Drop table, and
the Accessory Electric Heat Pressure Drop table find:
Enter Cooling Capacities table at condenser entering temperature
External static pressure 0.20 IN. W.C.
of 95° F (35° C), indoor air entering at 1200 CFM and 67° F

50ZPC
Filter 0.10 IN. W.C.
(19.4° C) ewb. The 036 unit provides a total cooling capacity of
Electric Heat 0.04 IN. W.C.
34,500 Btuh and a sensible heat capacity of 26,040 Btuh.
Total static pressure 0.34 IN. W.C.
For indoor--air temperature other than 80° F (26.7° C) edb,
calculate sensible heat capacity correction, as required, using the
formula found following the Cooling Capacities tables. Enter the table for Dry Coil Air Delivery — Horizontal Discharge.
At 0.4 IN. W.C. external static pressure and medium speed, the
NOTE: Unit ratings are net capacities.
motor delivers 1236 CFM.

7
50ZPC

PERFORMANCE DATA
Cooling Capacities
024
EVAPORATOR CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
AIR 75 (24) 85 (29) 95 (35) 105 (41) 115 (46)
Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total
EWB _F
CFM Sys Sys Sys Sys Sys
(_C) Total Sens Total Sens Total Sens Total Sens Total Sens
KW KW KW KW KW

57 (14) 23.14 23.14 1.61 21.24 21.24 1.74 19.25 19.24 1.86 17.04 17.04 1.96 14.82 14.82 2.07
62 (17) 24.27 20.27 1.62 21.95 19.60 1.75 19.62 18.81 1.87 17.08 17.08 1.96 14.84 14.84 2.07
700 63 (17) 24.78 16.65 1.62 22.42 15.97 1.76 20.01 15.23 1.89 17.24 14.26 1.96 14.37 13.22 2.05
67 (19) 26.88 17.28 1.64 24.42 16.63 1.79 21.93 15.96 1.93 19.35 15.21 2.06 16.25 14.17 2.13
71 (22) 28.93 14.81 1.66 26.42 14.21 1.81 23.86 13.55 1.96 21.29 12.86 2.10 18.38 12.02 2.23
57 (14) 24.22 24.22 1.63 22.22 22.22 1.77 20.22 20.22 1.91 17.96 17.96 2.01 15.58 15.58 2.12
62 (17) 24.93 21.65 1.63 22.58 20.97 1.77 20.25 20.22 1.91 18.01 18.01 2.02 15.61 15.61 2.12
800 63 (17) 25.39 17.60 1.64 22.96 16.93 1.78 20.50 16.21 1.91 17.69 15.26 2.00 14.75 14.19 2.08
67 (19) 27.49 18.23 1.66 24.95 17.62 1.80 22.40 16.95 1.95 19.79 16.23 2.08 16.66 15.24 2.16
71 (22) 29.52 15.44 1.68 26.95 14.86 1.83 24.33 14.21 1.98 21.69 13.53 2.13 18.83 12.79 2.26
57 (14) 25.14 25.14 1.65 23.05 23.05 1.79 20.97 20.97 1.93 18.76 18.76 2.06 16.25 16.25 2.16
62 (17) 25.51 22.89 1.65 23.16 22.17 1.79 20.99 20.99 1.93 18.80 18.80 2.07 16.27 16.27 2.16
900 63 (17) 25.88 18.45 1.66 23.38 17.81 1.80 20.87 17.11 1.93 18.08 16.21 2.03 15.08 15.10 2.11
67 (19) 27.96 19.09 1.68 25.39 18.51 1.82 22.76 17.88 1.97 20.11 17.19 2.10 17.01 16.23 2.19
71 (22) 29.97 16.02 1.70 27.36 15.45 1.85 24.70 14.82 2.00 21.98 14.14 2.15 19.16 13.46 2.28
See Legend and Notes on page 11.

8
030
CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
EVAPORATOR AIR
75 (24) 85 (29) 95 (35) 105 (41) 115 (46)
Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total
EWB _F
CFM Sys Sys Sys Sys Sys
(_C) Total Sens Total Sens Total Sens Total Sens Total Sens
KW KW KW KW KW

57 (14) 29.36 29.36 1.98 27.29 27.29 2.18 25.09 25.09 2.38 22.44 22.44 2.55 19.75 19.75 2.74
62 (17) 30.31 26.51 1.99 27.78 25.23 2.19 25.20 24.98 2.39 22.49 22.49 2.55 19.80 19.80 2.74
875 63 (17) 30.88 21.56 1.99 28.27 20.35 2.20 25.55 19.11 2.40 22.14 17.60 2.54 18.72 16.09 2.69
67 (19) 33.55 22.45 2.02 30.80 21.29 2.23 28.03 20.09 2.45 24.81 18.76 2.65 21.11 17.24 2.80
71 (22) 36.25 19.13 2.05 33.44 18.02 2.27 30.56 16.92 2.50 27.57 15.80 2.73 23.82 14.43 2.92
57 (14) 30.74 30.74 2.01 28.55 28.55 2.22 26.32 26.32 2.44 23.64 23.64 2.63 20.76 20.76 2.81
62 (17) 31.21 28.48 2.02 28.78 26.89 2.23 26.36 26.36 2.44 23.68 23.68 2.63 20.80 20.80 2.81
1000 63 (17) 31.61 22.92 2.02 28.92 21.71 2.23 26.15 20.48 2.44 22.71 18.94 2.58 19.19 17.36 2.74
67 (19) 34.29 23.85 2.05 31.45 22.70 2.27 28.60 21.50 2.49 25.44 20.23 2.70 21.63 18.64 2.85
71 (22) 36.94 20.07 2.07 34.08 18.99 2.30 31.12 17.87 2.53 28.07 16.75 2.76 24.30 15.42 2.97
57 (14) 31.88 31.88 2.05 29.60 29.60 2.26 27.29 27.29 2.48 24.63 24.63 2.70 21.60 21.60 2.88
62 (17) 31.96 31.67 2.05 29.63 29.63 2.26 27.33 27.33 2.49 24.67 24.67 2.70 21.64 21.64 2.88
1125 63 (17) 32.18 24.17 2.05 29.42 23.00 2.26 26.61 21.75 2.47 23.18 20.21 2.63 19.65 18.50 2.79
67 (19) 34.84 25.17 2.08 31.96 24.02 2.30 29.03 22.83 2.52 25.96 21.57 2.74 22.07 19.95 2.90
71 (22) 37.48 20.94 2.10 34.56 19.87 2.33 31.50 18.78 2.56 28.44 17.64 2.80 24.69 16.39 3.02
See Legend and Notes on page 11.
COOLING CAPACITIES (CONT)

036
CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
EVAPORATOR AIR
75 (24) 85 (29) 95 (35) 105 (41) 115 (46)
Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total
EWB _F
CFM Sys Sys Sys Sys Sys
(_C) Total Sens Total Sens Total Sens Total Sens Total Sens
KW KW KW KW KW

57 (14) 34.95 34.95 2.39 32.78 32.78 2.65 30.54 30.54 2.91 28.13 28.13 3.18 25.17 25.17 3.42
62 (17) 36.15 32.02 2.40 33.49 31.07 2.66 30.78 29.99 2.92 28.17 28.17 3.18 25.21 25.21 3.42
1050 63 (17) 36.83 26.05 2.40 34.09 25.10 2.67 31.22 24.06 2.93 28.11 22.91 3.17 24.25 21.41 3.37
67 (19) 39.89 27.04 2.42 37.06 26.18 2.70 34.15 25.24 2.99 31.05 24.22 3.28 27.26 22.90 3.51
71 (22) 43.61 21.93 2.45 40.81 21.13 2.74 37.84 20.24 3.04 34.70 19.28 3.34 31.35 18.25 3.66
57 (14) 36.52 36.52 2.43 34.27 34.27 2.70 31.94 31.94 2.99 29.43 29.43 3.26 26.39 26.39 3.51
62 (17) 37.10 34.24 2.43 34.48 33.26 2.70 31.97 31.97 2.99 29.47 29.47 3.27 26.44 26.44 3.51
1200 63 (17) 37.64 27.56 2.44 34.83 26.64 2.71 31.89 25.65 2.98 28.72 24.50 3.23 24.81 22.99 3.43
67 (19) 40.69 28.57 2.46 37.82 27.76 2.74 34.80 26.85 3.03 31.65 25.87 3.32 27.90 24.63 3.58
71 (22) 44.31 22.79 2.48 41.49 22.03 2.77 38.44 21.17 3.07 35.23 20.23 3.39 31.83 19.23 3.70
57 (14) 37.79 37.79 2.47 35.48 35.48 2.74 33.04 33.04 3.03 30.50 30.50 3.33 27.45 27.45 3.59
62 (17) 37.98 36.24 2.47 35.53 35.53 2.74 33.08 33.08 3.03 30.54 30.54 3.33 27.50 27.50 3.60
1350 63 (17) 38.27 28.95 2.47 35.39 28.07 2.74 32.40 27.11 3.02 29.23 26.00 3.29 25.31 24.46 3.49
67 (19) 41.27 29.95 2.49 38.36 29.20 2.77 35.29 28.34 3.06 32.11 27.40 3.36 28.45 26.26 3.64
71 (22) 44.83 23.55 2.51 41.97 22.83 2.80 38.88 22.01 3.11 35.62 21.09 3.42 32.18 20.13 3.74
See Legend and Notes on page 11.

9
042
CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
EVAPORATOR AIR
75 (24) 85 (29) 95 (35) 105 (41) 115 (46)
Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total
EWB _F
CFM Sys Sys Sys Sys Sys
(_C) Total Sens Total Sens Total Sens Total Sens Total Sens
KW KW KW KW KW

57 (14) 41.68 41.68 2.75 38.94 38.94 3.11 35.98 35.98 3.49 32.25 32.25 3.87 28.66 28.66 4.32
62 (17) 42.95 38.93 2.75 39.78 36.79 3.12 36.43 34.57 3.50 32.28 32.28 3.87 28.71 28.71 4.32
1225 63 (17) 43.70 31.61 2.75 40.44 29.72 3.12 36.99 27.79 3.51 32.43 25.38 3.87 27.98 23.06 4.30
67 (19) 47.16 32.78 2.77 43.74 30.91 3.13 40.27 29.04 3.52 36.10 26.97 3.96 31.37 24.61 4.39
71 (22) 51.59 26.51 2.78 47.98 24.89 3.15 44.33 23.26 3.55 40.57 21.60 3.99 36.10 19.78 4.49
57 (14) 43.43 43.43 2.79 40.56 40.56 3.15 37.56 37.56 3.55 33.84 33.84 3.94 30.06 30.06 4.39
62 (17) 44.02 41.66 2.79 40.84 39.39 3.16 37.60 37.60 3.55 33.90 33.90 3.94 30.11 30.11 4.40
1400 63 (17) 44.60 33.50 2.79 41.26 31.57 3.16 37.77 29.61 3.55 33.24 27.21 3.92 28.66 24.78 4.36
67 (19) 48.06 34.74 2.81 44.57 32.83 3.17 41.00 30.90 3.56 37.08 28.93 4.01 32.09 26.48 4.45
71 (22) 52.46 27.65 2.82 48.78 26.00 3.19 45.03 24.35 3.59 41.21 22.67 4.03 36.86 20.91 4.53
57 (14) 44.86 44.86 2.83 41.89 41.89 3.19 38.82 38.82 3.59 35.20 35.20 4.02 31.25 31.25 4.47
62 (17) 45.00 44.04 2.83 41.94 41.94 3.20 38.88 38.88 3.59 35.25 35.25 4.02 31.28 31.28 4.47
1575 63 (17) 45.28 35.25 2.83 41.88 33.29 3.20 38.36 31.31 3.59 33.90 28.93 3.98 29.21 26.39 4.41
67 (19) 48.74 36.57 2.84 45.17 34.62 3.21 41.56 32.62 3.60 37.71 30.65 4.05 32.66 28.22 4.50
71 (22) 53.13 28.71 2.86 49.38 27.04 3.23 45.55 25.35 3.63 41.66 23.65 4.07 37.49 21.93 4.58
See Legend and Notes on page 11.

50ZPC
50ZPC

COOLING CAPACITIES (CONT)


048
CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
EVAPORATOR AIR
75 (24) 85 (29) 95 (35) 105 (41) 115 (46)
Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total
EWB _F
CFM Sys Sys Sys Sys Sys
(_C) Total Sens Total Sens Total Sens Total Sens Total Sens
KW KW KW KW KW

57 (14) 46.69 46.69 3.18 43.96 43.96 3.55 41.20 41.20 3.97 38.15 38.15 4.45 34.26 34.26 4.96
62 (17) 48.24 40.86 3.19 45.07 40.07 3.56 41.86 39.18 3.99 38.39 38.02 4.46 34.32 34.32 4.97
1400 63 (17) 49.13 33.18 3.19 45.86 32.38 3.57 42.55 31.50 4.00 38.89 30.43 4.47 34.04 28.78 4.95
67 (19) 53.03 34.45 3.21 49.63 33.69 3.59 46.16 32.87 4.03 42.51 31.94 4.54 38.08 30.67 5.10
71 (22) 58.07 27.87 3.25 54.53 27.15 3.63 50.89 26.37 4.07 47.09 25.48 4.58 43.08 24.48 5.17
57 (14) 48.69 48.69 3.24 45.86 45.86 3.62 42.97 42.97 4.06 39.87 39.87 4.56 35.98 35.98 5.08
62 (17) 49.45 43.78 3.24 46.24 42.96 3.62 43.08 42.83 4.06 39.93 39.93 4.56 36.04 36.04 5.08
1600 63 (17) 50.14 35.19 3.25 46.79 34.40 3.62 43.38 33.54 4.06 39.71 32.52 4.55 34.85 30.91 5.04
67 (19) 54.04 36.51 3.27 50.57 35.78 3.65 47.00 35.00 4.09 43.31 34.10 4.60 39.07 33.00 5.18
71 (22) 59.08 29.08 3.31 55.45 28.38 3.69 51.71 27.61 4.13 47.83 26.75 4.64 43.74 25.74 5.24
57 (14) 50.32 50.32 3.30 47.39 47.39 3.68 44.38 44.38 4.12 41.24 41.24 4.63 37.45 37.45 5.19
62 (17) 50.52 46.35 3.30 47.46 47.46 3.68 44.44 44.44 4.12 41.29 41.29 4.63 37.50 37.50 5.19
1800 63 (17) 50.90 37.05 3.30 47.50 36.30 3.68 44.02 35.46 4.12 40.35 34.49 4.62 35.52 32.90 5.12
67 (19) 54.81 38.44 3.33 51.26 37.75 3.70 47.64 36.98 4.14 43.89 36.11 4.65 39.74 35.07 5.24
71 (22) 59.83 30.17 3.37 56.13 29.51 3.75 52.32 28.76 4.19 48.35 27.90 4.70 44.21 26.91 5.30
See Legend and Notes on page 11.

060
CONDENSER ENTERING AIR TEMPERATURES ° F (° C)
EVAPORATOR AIR

10
75 (24) 85 (29) 95 (35) 105 (41) 115 (46)
Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total Capacity MBtuh Total
EWB _F
CFM Sys Sys Sys Sys Sys
(_C) Total Sens Total Sens Total Sens Total Sens Total Sens
KW KW KW KW KW
50ZPC060 Outdoor Section With NA Indoor Section
57 (14) 52.95 52.95 3.74 50.23 50.23 4.14 47.43 47.43 4.61 44.47 44.47 5.15 41.30 41.30 5.78
62 (17) 55.05 45.97 3.75 51.84 44.39 4.16 48.53 42.78 4.62 45.08 41.06 5.16 41.48 39.18 5.78
1500 63 (17) 56.01 37.50 3.76 52.73 36.05 4.17 49.33 34.54 4.63 45.76 32.97 5.17 42.01 31.33 5.79
67 (19) 59.99 38.77 3.80 56.43 37.29 4.20 52.75 35.77 4.67 48.90 34.18 5.21 44.88 32.53 5.83
71 (22) 65.50 31.45 3.84 61.58 30.06 4.25 57.53 28.62 4.72 53.33 27.13 5.26 48.93 25.58 5.89
57 (14) 54.98 54.98 3.81 52.11 52.11 4.21 49.12 49.12 4.68 45.98 45.98 5.23 42.63 42.63 5.85
62 (17) 56.20 49.14 3.82 52.89 47.48 4.22 49.49 45.72 4.69 46.04 46.04 5.23 42.69 42.69 5.86
1700 63 (17) 57.05 39.66 3.83 53.64 38.16 4.23 50.11 36.61 4.70 46.43 34.99 5.23 42.56 33.29 5.85
67 (19) 61.05 41.09 3.86 57.35 39.56 4.26 53.53 37.99 4.73 49.57 36.36 5.27 45.42 34.64 5.89
71 (22) 66.61 32.86 3.91 62.53 31.43 4.31 58.37 29.96 4.78 54.02 28.44 5.33 49.49 26.85 5.95
57 (14) 56.30 56.30 3.86 53.30 53.30 4.27 50.20 50.20 4.74 46.93 46.93 5.28 43.46 43.46 5.91
62 (17) 56.95 51.37 3.87 53.60 49.58 4.27 50.27 50.27 4.74 46.99 46.99 5.28 43.52 43.52 5.91
1850 63 (17) 57.68 41.23 3.87 54.17 39.68 4.27 50.58 38.10 4.74 46.82 36.45 5.28 42.89 34.72 5.90
67 (19) 61.67 42.77 3.90 57.88 41.20 4.31 54.00 39.60 4.78 49.95 37.93 5.32 45.73 36.18 5.94
71 (22) 67.25 33.87 3.95 63.10 32.42 4.36 58.84 30.93 4.83 54.41 29.38 5.37 49.81 27.77 6.00
See Legend and Notes on page 11.
* At 75° F entering dry bulb --- Tennessee Valley Authority (TVA) rating conditions; all others at 80° F dry bulb.
LEGEND
BF — Bypass Factor total capacity (Btuh)
hlwb = hewb --
Ewb — Entering Wet---Bulb
kW — Total Unit Power Input 4.5 x cfm
SHC — Sensible Heat Capacity (1000 Btuh) Where: hewb = Enthalpy of air entering evaporator coil3. The SHC is
TC — Total Capacity (1000 Btuh) (net) based on 80 F (26.7C) edb temperature of air entering indoor coil.
NOTES: Below 80 F (26.7C) edb, subtract (corr factor x cfm) from SHC.
1. Direct interpolation is permissible. Do not extrapolate. Above 80 F (26.7C) edb, add (corr factor x cfm) to SHC.
2. The following formulas may be used: Correction Factor = 1.10 x (1 --- BF) x (edb --- 80).
tldb = tedb - Sensible capacity (Btuh)
1.10 x cfm

Wet--bulb temperature corresponding to enthalpy


tlwb =
air leaving evaporator coil (hlwb)

11
50ZPC
Filter Pressure Drop (IN. W.C.)
FILTER SIZE CFM
in. (mm) 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200
20X20X1
0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15 — — — — — — — — — —
(508X508X25)
20X24X1
— — — 0.08 0.09 0.10 0.11 0.13 0.14 0.15 0.16 — — — — — — —
(508X610x25)
24X30X1
— — — 0.04 0.05 0.06 0.07 0.07 0.08 0.09 0.10 — — — — — — —
(610X762x25)
24X36X1
— — — — — — — 0.06 0.07 0.07 0.08 0.09 0.09 0.10 0.11 0.12 0.13 0.14
(610X914X25)

Accessory Electric Heat Pressure Drop (IN. W.C.)


CFM
HEATER kW
800 1000 1200 1400 1600 1800 2000 2200
5-- 20 0.033 0.037 0.042 0.047 0.052 0.060 0.067 0.075

Wet Coil Delivery*— (Deduct 10% for 208--Volt Operation)


50ZPC

EXTERNAL STATIC PRESSURE (in. W.C.)


UNIT SIZE SPEED TAP AIR DELIVERY2
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
1 SCFM 965 818 777 731 670 617 563 489 451 391
024 2 SCFM 1003 921 890 850 809 756 700 659 597 539
3 SCFM 1103 1068 1034 996 962 930 892 821 791 742
1 SCFM 1052 1018 984 943 914 879 833 795 732 678
030 2 SCFM 1141 1107 1069 1036 1006 974 932 899 856 784
3 SCFM 1246 1213 1181 1144 1108 1078 1043 1015 973 931
1 SCFM 1281 1225 1178 1142 1098 1053 1008 935 878 840
036 2 SCFM 1359 1321 1278 1236 1201 1160 1109 1068 992 941
3 SCFM 1476 1441 1403 1366 1323 1289 1245 1201 1159 1117
1 SCFM 1453 1408 1373 1337 1295 1255 1215 1177 1134 1068
042 2 SCFM 1544 1507 1475 1436 1397 1359 1326 1290 1246 1201
3 SCFM 1614 1575 1542 1509 1467 1430 1395 1358 1323 1267
1 SCFM 1657 1625 1590 1554 1517 1486 1448 1417 1381 1340
048 2 SCFM 1707 1673 1644 1614 1586 1549 1515 1479 1449 1407
3 SCFM 1931 1900 1870 1840 1809 1778 1749 1714 1683 1646
1 SCFM 1931 1881 1833 1787 1746 1698 1670 1622 1577 1514
060 2 SCFM 2038 1994 1935 1894 1851 1811 1774 1738 1691 1648
3 SCFM 2144 2113 2052 2001 1974 1928 1898 1860 1824 1773
*Air delivery values are based on operating voltage of 230v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain
static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at air-
flows below this point.
2. Standard Cubic Feet per Minute.

12
TYPICAL CONNECTION WIRING SCHEMATIC—208/230--1--60 024--060

50ZPC

A14548

13
TYPICAL LADDER WIRING SCHEMATIC—208/230--1--60 024--060
50ZPC

A14549

14
TYPICAL FIELD WIRING

Wires to be removed

50ZPC
A14444
NOTE: 20 kW shown. Smaller heaters have fewer elements and controls.

Single--Phase Accessory Electric Heater Wiring

15
Electrical Data
Voltage Nominal Heater
Nominal Compressor OFM IFM MCA MOCP**
Model Range kW* FLA
V-PH-HZ
Min Max RLA LRA FLA FLA 208/240 208 240 208 230 208/230
-/- - - 14.6 14.6 20
3.8/5 18.0 20.8 26.0 29.5 30/30
024 208/230-1-60 197 253 8.7 45 0.9 2.8
5.6/7.5 27.0 31.3 37.3 42.6 40/45
7.5/10 36.1 41.7 48.6 55.6 50/60
-/- - - 17.7 17.7 25
3.8/5 18.0 20.8 26.0 29.5 30/30
030 208/230-1-60 197 253 11.2 57 0.9 2.8
5.6/7.5 27.0 31.3 37.3 42.6 40/45
7.5/10 36.1 41.7 48.6 55.6 50/60
-/- - - 23.4 23.4 35
3.8/5 18.0 20.8 27.6 31.1 35/35
036 208/230-1-60 197 253 14.1 78 1.7 4.1 5.6/7.5 27.0 31.3 38.9 44.3 40/45
7.5/10 36.1 41.7 50.3 57.3 60/60
11.3/15 54.1 62.5 72.8 83.3 80/90
-/- - - 25.7 25.7 40
3.8/5 18.0 20.8 27.6 31.1 40/40
50ZPC

042 208/230-1-60 197 253 15.9 112.3 1.7 4.1 5.6/7.5 27.0 31.3 38.9 44.3 40/45
7.5/10 36.1 41.7 50.3 57.3 60/60
11.3/15 54.1 62.5 72.8 83.3 80/90
-/- - - 32.2 32.2 50
3.8/5 18.0 20.8 32.2 33.5 50/50
5.6/7.5 27.0 31.3 41.3 46.6 50/50
048 208/230-1-60 197 253 19.6 130 1.7 6.0
7.5/10 36.1 41.7 52.6 59.6 60/60
11.3/15 54.1 62.5 75.1 85.6 80/90
15/20 72.1 83.3 97.6 111.6 100/125
-/- - - 39.1 39.1 60
3.8/5 18.0 20.8 39.1 39.1 60/60
5.6/7.5 27.0 31.3 43.3 48.6 60/60
060 208/230-1-60 197 253 23.7 152.5 1.9 7.6
7.5/10 36.1 41.7 54.6 61.6 60/70
11.3/15 54.1 62.5 77.1 87.6 80/90
15/20 72.1 83.3 99.6 113.6 100/125
** HACR Type Circuit breaker
LEGEND
FLA --- Full Load Amps
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
RLA --- Rated Load Amps
NOTES:
1. In compliance with NEC (National Electrical Code) requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be Power Supply fuse or circuit breaker.
2. Minimum wire size is based on 60_C copper wire. If other than 60_C wire is used, or if length exceeds wire length in table, determine size from NEC.

*Heater capacity (kW) based on heater voltage of 208v & 240v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accord-
ingly.

OPERATING SEQUENCE APPLICATION DATA


Cooling Operation Condensate trap — A 2--in. (51 mm) condensate trap must be field
supplied.
With a call for cooling (Y/G), the contactor is energized which
brings on the compressor and outdoor fan. The indoor fan is also 1” (25 mm) MIN.
energized. When the cooling demand is met, Y and G are TRAP
de--energized shutting off the contactor. The indoor fan stops after OUTLET
a 60 second delay.
2” (51 mm) MIN.
Heating Operation
With a call for heating (W2), the auxiliary or electric heat energizes
along with the indoor blower. In case of staged heating, W3 is A08001
energized if the demand is not met. The highest airflow selected is Maximum cooling airflow — To minimize the possibility of
run while the electric heat is in operation. When heating demand is condensate blow--off from the evaporator, airflow through the units
met, W3 and W2 sequentially de--energize shutting off the indoor should not exceed 450 CFM/ton.
fan and the electric heater. Minimum cooling airflow — The minimum cooling airflow is
Continuous Fan 350 cfm/ton.
With the continuous indoor fan option selected on the thermostat, Minimum cooling operating outdoor air temperature — All
G is continuously energized keeping the indoor fan running at all standard units have a minimum ambient operating temperature of
times. 40F (4.4C). With accessory low ambient temperature kit, units
can operate at temperatures down to 0F (--17.8C).
Maximum operating outdoor air temperature — Maximum
outdoor operating air temperature for cooling is 125F (51.7C).

16
TYPICAL INSTALLATION
INDOOR
THERMOSTAT

RETURN
AIR

FROM
TOP COVER POWER
SOURCE

50ZPC
POWER DISCONNECT
ENTRY PER NEC
(UNIT AND
COMPOSITE ELECTRIC
RUST-PROOF HEATER)
BASEPAN
Power Wiring CONDENSATE
Control Wiring DRAIN
LOW VOLTAGE CONNECTION
ENTRY
Condenser Airflow

Evaporator Airflow

A10135

17
ENGINEERS’ SPECIFICATION GUIDE
GENERAL EVAPORATOR SECTION
Furnish and install outdoor package, electrically controlled, air Fan shall be multi--speed with direct drive motor as shown on the
conditioner utilizing a reciprocating or scroll compressor for equipment drawings.
cooling duty. Unit shall discharge supply air horizontally as shown Fan wheel shall be made from steel, be double--inlet type with
on contract drawings. forward--curved blades with a corrosion--resistant finish and
Nominal unit electrical characteristics shall be ______ v, ______ dynamically balanced.
ph, 60 Hz. The unit shall be capable of satisfactory operation Evaporator coils shall have aluminum--plate fins mechanically
within voltage limits of ______ v to ______ v. Unit power wiring bonded to copper tubes with all joints brazed.
shall enter unit cabinet at a single location. Tube sheet openings shall be belled to prevent tube wear.
Separate power supply shall not be required for electric heat.
MOTORS
COOLING CAPACITY Compressor motors shall be of the refrigerant cooled type with line
Total cooling capacity of the unit shall be _____ Btuh or greater, break thermal and current overload protection.
and sensible capacity shall be ______ Btuh or greater at conditions All fan motors shall have permanently lubricated bearings, and
of ______ cfm indoor air entering unit at ______F dry bulb, inherent automatic reset thermal overload protection.
_____ F wet bulb and outdoor entering air of ______F dry bulb.
Total design conditions shall be a minimum of ______ Btuh/Watt. Condenser fan motor shall be totally enclosed.
50ZPC

The unit shall be capable of cooling operation down to 40_F


(4.4_C) as shipped from the factory. REFRIGERANT SYSTEM
Refrigerant system shall include fixed orifice or TXV metering
CABINET system.
Unit cabinet shall be constructed of phosphated, bonderized,
zinc--coated, prepainted steel. Basepan shall be made of a CONTROLS
single--piece non--corrosive, composite material. Unit shall be complete with self--contained low voltage control
Evaporator--fan compartment interior cabinet surfaces shall be circuit.
insulated with a minimum 1/2--in. (12.7 mm) thick, flexible
fiberglass insulation, coated on the air side with aluminum foil. APPROVALS
Cabinet panels shall be easily removable for servicing. Unit shall be UL listed as a total package for safety requirements.
Outdoor coil shall be protected by metal louvered panels. All wiring shall be in accordance with NEC.
Unit shall be rated in accordance with AHRI Standards 210/240.
COMPRESSOR Cabinet insulation shall conform to ASHRAE Standard 62.2
Compressor shall be fully hermetic type with external vibration Insulation and adhesive shall meet NFPA 90A requirements for
isolation. flame spread and smoke generation.
Unit shall have a sloped drain pan that conforms to ASHRAE
CONDENSER SECTION Standard 62.2.
Condenser fan shall be of the direct--driven propeller type blades,
riveted to corrosion--resistant spiders, and shall be dynamically ACCESSORIES
balanced and discharge air vertically upwards. Field--installed accessories shall include solid--state compressor
Condenser coils shall have aluminum--plate fins mechanically short--cycle device, outdoor thermostat, room thermostats, electric
bonded to copper tubes with all joints brazed. heaters with single--point connection, crankcase heater, and