0% found this document useful (1 vote)
219 views4 pages

Technical Specification - Dual Power Change-Over Switch EQ1 Series (ATS)

The document describes a dual power change-over switch system that provides continuous power supply by automatically switching between two electrical sources if one fails or operating parameters deviate. The system consists of two circuit breakers on a metal frame connected by a common operating mechanism controlled by a device that monitors parameters. It can switch power for heavy loads, switch to the backup source if any phase lacks power, and connect to a fire alarm to shut off both sources in an emergency.

Uploaded by

Marin Daniel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (1 vote)
219 views4 pages

Technical Specification - Dual Power Change-Over Switch EQ1 Series (ATS)

The document describes a dual power change-over switch system that provides continuous power supply by automatically switching between two electrical sources if one fails or operating parameters deviate. The system consists of two circuit breakers on a metal frame connected by a common operating mechanism controlled by a device that monitors parameters. It can switch power for heavy loads, switch to the backup source if any phase lacks power, and connect to a fire alarm to shut off both sources in an emergency.

Uploaded by

Marin Daniel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

TECHNICAL SPECIFICATION

Dual power change-over switch EQ1 series (ATS)

Description:
The system for dual power change-over switch EQ1 is designed to provide
continuous power supply and two electrical sources automatic switch in case of
failure or deviation from the set parameters. The system for dual power change-
over switch consists of two molded case circuit breakers mounted on a metal
frame connected with common operating mechanism and controlled by a
command device that controls the system parameters’ correspondence.

Functions:
 Switching on/off heavy loaded electrical circuits at main power supply
discrepancy
 Switching to dual power change-over at power supply phase lack
 With option to connect to fire alarm controller. In case of fire, the ATS
switches off both power supply sources
 Breaking of electrical circuits and control of powerful consumers
 Used as a main breaker in housing or industrial distributing installations
supplied with a generator or a second power supply source (hospitals, post
offices, military sites, control rooms)
 Remarkable with high reliability of current characteristics
 Control: motor
 Controls the following circuit parameters:
 presence of the three phases
 the phase voltage to be in the set limits
 overload
 short circuit at the outlet

Technical data:
 Rated operating voltage: 690V; 50/60Hz
 Surge voltage wear resistance: ≥6000V
 Joining terminal: bolt connection with 4 bolts to the power supply rail
 Connecting:
 copper rails
 flexible or rigid conductors
 Electrical wear resistance (number of cycles): ≥60000
 Mechanical wear resistance (number of cycles): ≥10000
 IP code: IP21
 Plastic material of the breakers of UV rays and non-flammable
 Ambient temperature: -10°C + 65°C
 Installation altitude: up to 2000m
 Mounting:
 clamping with bolts
 mounting position: vertical gradient – maximum 5°

Basic function of the control device:


 Overload protection
 Instantaneous short circuit protection
 Under phase protection
 Undervoltage protection
 Possibility for setting the change-over time be-tween the two sources – min
3s
 Possibility for automatic switch-over to the main power supply source after
restoring its parameters
 The system for dual power change-over switch is offered in two types:
 with display (control device) mounted on the mounting plate (integrated
type)
 with separated control display

Dimensions:

Type of the Type A B C D H


breaker
EQ1-100 inner type 480 240 450 210 140
EQ1-225 inner type 480 240 450 210 140
EQ1-400 inner type 620 300 590 270 235
EQ1-630 inner type 660 300 630 270 240
EQ1-800 inner type
EQ1-100* moved type 420 230 390 200 145
EQ1-225* moved type 420 230 390 200 145
EQ1-400* moved type 570 300 540 270 235
EQ1-630* moved type 610 300 580 270 240
EQ1-800* moved type
Variants
Type Rated Max. Operating Section of Electrical Mechanica Packing Catalogue
current breakin breaking the power wear l wear / Box number
In(A) g capacity supply resistance resistance (pcs)
capacity Ics (kA) conductor (number (number of
Icu (kA) (mm2) of cycles) cycles)
EQ1-100 100 50 35 35 2000 6000 1/1 44100
EQ1-225 225 50 35 70 2000 6000 1/1 44225

EQ1-400 400 100 65 180 2000 6000 1/1 44403


EQ1-630 630 100 65 240 1000 3000 1/1 44633
EQ1-800 800 100 65 240 1000 3000 1/1 44833
EQ1-100* 100 50 35 35 2000 6000 1/1 44101
EQ1-225* 225 100 35 70 2000 6000 1/1 44226

EQ1-400* 400 100 65 180 2000 6000 1/1 44404


EQ1-630* 630 100 65 240 1000 3000 1/1 44634
EQ1-800* 800 100 65 240 1000 3000 1/1 44834

Standards:
EN 60947-1
EN 60947-2
EN60947-6-1

You might also like