SDO OCT

IEC 61850
OPTICAL CURRENT
TRANSFORMER
This document may be subject to changes.
Contact ARTECHE to confirm the characteristics and
availability of the products described here.

Moving together
DIGITAL
MEASUREMENT
FOR DIGITAL
SUBSTATIONS
New Intelligent Electronic Devices (IED)
for protection, control and metering
applications in primary substations can
receive and process voltage and current
measurements as digital values.

This change disrupts the traditional


substation engineering where lots of
low voltage cables had to be installed
between each IED and the instrument
transformers. IEC 61850-9-2 process
bus and IEC 61869-9 allow the operation
of different IEDs with the Sampled
Values provided by digital Instrument
Transformers regardless of the
manufacturer or the underlying voltage
and current measurement technology.

At the same time, the evolution of


technology allows new approaches
to voltage and current measurement
in HV grids. These non-conventional
instrument transformers can offer
some interesting features compared to
conventional instrument transformers
in terms of linearity, accuracy range,
insulation etc.

SDO OCT | Optical current transformer 3


OPTICAL CURRENT
TRANSFORMER
The SDO OCT is a highly accurate optical ARTECHE SDO uses the most advanced fiber
current transformer for high voltage systems, sensing technology based on a patented
based on a fully passive optical transducer technique that allows the construction of
(The SDO ICT). The SDO OCT provides a passive, interferometric transducers with
digital measurement solution for metering and Class 0.2 accuracy over an unlimited dynamic
protection applications in the next generation range.
of high voltage digital substations.
The SDO OCT is composed of these elements:
The operation of the SDO ICT is based on
› CAO, consisting of:
the Faraday Effect. The polarization state of
a linearly polarized optical signal is rotated | SDO ICT sensor head.
as it travels through a magnetic field. For an | Post type polymer insulator with solid and
optical signal which travels along a closed dry insulation with an embedded fiber
path, the angle of rotation is proportional to optic for sensor head connection.
the current enclosed by the path. › SDO MU Merging Unit.

The rotation of the polarization state of the


light is measured interferometrically as the
phase difference between circularly polarized
optical signals which travel in opposite
directions around a coil of fiber that encloses _ PASSIVE
the primary.
_ MODULAR
_ ACCURACY OVER AN
UNLIMITED DYNAMIC RANGE

4 SDO OCT | Optical current transformer


SDO ICT. Sensor Head. SDO MU. Merging Unit.
Measures AC or DC current with an optical Provides Sampled Values, fully digital
transducer. measurement output for metering and
protection applications as defined in IEC
61850-9-2 LE and IEC 61869-9 standards.

Protection and
control devices
Sensing Optical
fiber detector

Primary
conductor
Signal processing/ Digital output
Sampling/ IEC 61869-9/IEC 61850
A/D conversion/
Ethernet message
Formatting
Standard single mode
fiber optic links
Passive optical
network Optical Substation
source
Ethernet network

› Simplified block
diagram of SDO
OCT optical current
transformer.

SDO OCT | Optical current transformer 5


APPLICATIONS
SDO OCT is ideally suited for digital
measurement for metering & protection
based on the IEC 61850 process bus protocol
and IEC 61869.

SYSTEM ARCHITECTURE
The SDO ICT is connected to the primary
conductor in the switchyard. Typically it will
be mounted on an insulator column. However,
other options are possible, for example by using
suspension type HV links or by integrating the
sensor into other apparatus such as circuit
breakers or disconnecting switches.

The SDO MU is an integral part of the optical


current transformer. It sends and receives
the optical signal to and from the sensor
controlling up to three SDO ICT current
sensors. In addition to that, it can interface
with conventional CT’s and VTs.

The SDO MU performs all the necessary signal


processing and analog to digital conversion.
It samples the measured values according to
frequencies specified by IEC 61850-9-2LE and
IEC 61869-9.

Then it synchronizes and merges the current


and voltage channels before encoding the
output signal to the digital format of Sampled
Values (SV) and streams it via two redundant
Ethernet ports to the Process Bus network.

› CAO with SDO ICT


head and insulator.
A phase current
SDO OCT

B phase current
Supply
Power

SDO OCT

C phase current
SDO OCT Protection
Relay
Neutral current Conventional Current IEC 61850-9-2 LE
Instrument Transformer SDO Sampled Values
MU
A phase voltage Conventional Voltage
Instrument Transformer

B phase voltage
Meter
Conventional Voltage
Instrument Transformer
Synch
1PPS
1588

C phase voltage Conventional Voltage


Instrument Transformer

Neutral voltage Conventional Voltage


Instrument Transformer
› Interfaces of SDO MU
merging unit.

6 SDO OCT | Optical current transformer


COMPONENT DESCRIPTION
CAO SDO MU MERGING UNIT
| SDO ICT SENSOR HEAD › 19” 3U Rack mounted signal processing
IED installed in the protection and control
› Fully passive current transducer based on
panel.
optical fiber. No power supply required in
the switchyard. › Input interface:
› Full galvanic insulation. • 3x SDO ICT.
› No risk of open secondaries. • 4x Conventional VT.
› Maintenance free. • 4x Conventional CT.
› Reduced dimensions for an optimized › Time Synchronization: 1PPS / IEEE 1588
substation footprint and easy retrofit (PTP).
integration. › Digital output via dual Ethernet port.
› Class 0.2 accuracy as per IEC 61869-2 and Compliant with IEC 61850-9-2LE and IEC
full linearity over an unlimited dynamic 61869-9.
range. › Seamless fail over network redundancy:
› Single transducer for both metering and • High-availability Seamless Redundancy
protection applications. (HSR).
› The current transducer is independent • Parallel Redundancy Protocol (PRP).
from the voltage level.
› It can be designed for DC measurement.
› Redundancy (optional):
• Redundant measurement with a single
sensing coil.
• 2 sensing coils in one sensor head. _ SAFE
| INSULATOR _ ENVIRONMENTALLY FRIENDLY
› Dry solid insulation. No oil or SF6. Without _ LOW MAINTENANCE
risk of leakage or violent failure .
› Standard voltage levels: 145 kV, 245 kV, _ PTP (IEEE 1588)
300 kV, 420 kV and 550 kV. Additional
voltage levels available on request.
_ HSR & PRP

SDO OCT | Optical current transformer 7


SDO MU MERGING UNIT: FRONT AND REAR VIEW

1. 4x20 LCD display.


2. 8 LEDs for status indications & alarms.
3. Configuration port. Web based interface.
4. Optical links to SDO ICTs.
5. Analog VT inputs.
6. 1PPS input.
7. 2xEthernet 100FX Port Duplex LC connector.
8. Relay contact outputs.
9. Power supply.

1 2 3

5
6 7

8 9

› Routine tested in
ARTECHE’s laboratory.

8 SDO OCT | Optical current transformer


TECHNICAL SPECIFICATIONS
SDO ICT SENSOR HEAD

User specified for up to 2,500 A


Nominal current
(Higher current ratings available under request)
25 kA rms for 3 s, 62.5 kA peak
Rated short-time thermal and dynamic current 50 kA rms for 1 s, 125 kA peak
75 kA rms for 1 s, 187.5 kA peak
Rated continuous thermal current 2,500 A rms
Accuracy 0.2 s / P20
2.4 kHz at 80 samples/cycle
Bandwidth
7.6 kHz at 256 samples/cycle
Weight 15 kg
IP protection IP66
Primary terminal Aluminum
Temperature -40°C to +85°C
100% Storage
Humidity
90% Operating
Vibration 1G
Optical connectors 2 x SC/APC
Fiber type for connection with the SDO MU merging unit Standard duplex single mode

INSULATOR (CUSTOMER SPECIFIED)

Maximum system voltage (Um) kV ms 145 245 300 420 550


Rated power-frequency withstand voltage kV rms 275 460 460 630 680
Rated lightning impulse withstand voltage kV peak 650 1,050 1,050 1,425 1,550
Rated switching impulse withstand voltage kV peak 850 1,050 1,175
Minimum creepage distances 31 mm/kV mm 4,495 7,595 9,300 13,020 17,050
Minimum flashover distance mm 1,200 2,200 2,320 3,250 3,800
Static withstand loads FR N 3,000 4,000 4,000 5,000 5,000
MML N 3,000 4,000 4,000 5,000 5,000
SML min N 5,000 6,250 10,000 12,500 12,500

SDO OCT | Optical current transformer 9


SDO MU MERGING UNIT

MECHANICAL

Dimensions 482x285x123 mm • 19” 3U Rack

Weight 5 Kg

POWER SUPPLY

Voltage Range 100 – 230 Vdc/Vac 48 - 125 Vdc

Frequency 50/60Hz

Power Consumption 25 W

ENVIRONMENTAL

Operating temperature -5°C to +55°C

Storage temperature -40°C to +85°C

Humidity 90% Without Condensation

Maximum height 2,000 m

Vibration 0.5 G

OPTICAL INTERFACE

Number of channels Up to 3 Duplex SC/APC

Wavelength 1550 nm, 1300 nm

Power Output < 10dBm

Type of fiber SM G.652.D

ANALOG INPUTS

Current 4 x 1A / 5A

Voltage 4 x 300V

OUTPUT CONTACTS (Configurable by the user)

Contact 1 NC/NO Service

Description Contact 2 and 3 NC/NO

Contact 4 to 8 NO

SAMPLED VALUES

Number of ports 2

Physical interface 2 x 100 Base FX Ethernet

Type of connector LC type Optical MM

IEC 61850-9-2 LE
Protocol
IEC 61869-9

Grids F4000S1I4U4, F4800S1I4U4, F4800S2I4U4, F12800S8I4U4, F15360S8I4U4, F14400S6I4U4

SYNCHRONIZATION

1 PPS Optical MM ST

IEC 61588:2009 profile IEC PAS 61850-9-3


PTP
Sampled Values Port 1

USER-MACHINE INTERFACE

Display 4x20 Alphanumerical

LEDs 8 x User Configurable: status & alarms

Configuration port Front 10/100 Base TX

Software configuration Web Browser

10 SDO OCT | Optical current transformer


DRAWING DIMENSIONS
482
465
38,5

Optical Current Transformer


123,5

57

435
324

285

› SDO Merging Unit.

SDO OCT | Optical current transformer 11