Cat 860-9 SWP-H
Cat 860-9 SWP-H
Cat 860-9 SWP-H
Coils
• High efficiency enhanced corrugated fin design
• High coil performance and reduced static
pressure losses
• Interlaced and/or row split circuiting to keep
full face of the coil active and to eliminate air
temperature stratification and optimum part
load performance
Durable Construction
• Pre-painted or G90 galvanized steel exterior
cabinet panels
• Standard foam injected panels with R-13
insulation provide superior rigid double wall
construction and minimizes air leakage
• For better acoustics, an additional 2", 1.5# density
R-8 fiberglass insulation is an available option for
fan and plenum sections
• Double-sloped drain pans help eliminates
standing stagnant water
Blank Sections
• Available to mount air blenders, carbon or
charcoal filters, sound attenuators or other
specialty equipment
• Allow customization for maximum system
performance and efficiency
• Can reduce design and installation costs
Scroll Compressor(s)
• Durable and reliable multiple compressors
• Lower operating cost with High EERs
• Customize selections to match specific
application
Access Panels and Doors
• Mounted on resilient rubber isolation for • All panels and access doors shall be sealed
smooth and quiet operation with permanently applied bulb-type gasket
• Access doors are flush mounted to cabinetry,
with hinges, latch and handle assembly
Refrigerant Circuits
• Suction and discharge service valves, an available
option, to isolate each compressor
• Hot gas bypass, an available option, on units with
Shell and Tube Condensers
two refrigerant circuits
• Carbon steel Shell and Tube Condenser , non-
ferrous water channels and enhanced tubing for
high performance
• Integral sub-cooling circuit is provided as
standard to maximize efficiency
• Mechanically cleanable condenser and water
piping is rated for standard 300 psig waterside
working pressure & 450 psig is an available
option
• Two-way valve for head pressure control is
available for low condenser water temperatures
Economizer Options
• Waterside economizer effectively uses low cooling tower
water temperatures to offload compressor operation
• An airside economizer control package is available for
controlling field installed mixing dampers capable of 100%
outside airflow.
Condensers
Supply Fan • All units feature carbon steel mechanically cleanable shell
Section
and tube condenser.
• Includes non-ferrous water channels and enhanced tubing
for high performance.
Compressor/ • Serves an independent refrigerant circuit and includes a
Base Plates Condenser spring loaded high pressure relief valve
Section • Integral sub-cooling circuit provided as standard to
maximize efficiency.
Compressors
• All units feature multiple reliable scroll compressors for
efficient system part load control, quiet operation and
system redundancy.
• Suction and discharge service valves and gauge ports,
available option, on each compressor.
• Individual branch circuit fusing protects each compressor.
• To prevent compressor short cycling, MicroTech® III
control system incorporates timing functions.
• Compressors mounted on resilient rubber isolation for
smooth and quiet operation.
Figure 4: Compresors
• All units are leak tested, evacuated and shipped with a [full
operating charge of R-410A] [for modular design nitrogen
holding charge] and POE oil.
• Condenser assembly and all factory water piping rated for a
waterside working pressure of 300 psig as standard [450
psig] tested before shipment.
• Provided with a single supply and return water connections
• Unit available in both right-hand and left-hand piping
locations.
• Optional two-way valve provides accurate head pressure
control for condenser entering water temperatures as low as
40ºF.
8 'DLNLQ
Self-Contained Systems
Acoustical Advantages • Competitive supply duct work normally involves
SWP Self-contained units are provided with a high discharging air vertically into a ceiling, then routing it
efficient, SWSI airfoil plenum fan and have several acoustical horizontally, Figure 10. Daikin’s plenum fan discharge has
advantages: far less velocity pressure than competitive housed fan
• Airfoil fans are more efficient than forward curved fans discharge, resulting in:
contributing to less noise. • 90º duct elbows that generate far less turbulance.
• For specific unit sizes, several fan diameters are available, • Air flow that can be routed in any direction.
fan selection provides optimal efficiency.
h*
Expansion Loss
Economizer Options
Standard Exterior
Galvanized Surface
Waterside Economizer
Standard Injected Foam Panel • An energy saving, waterside economizer package, an
Optional Fiberglass Insulation Interior Optional
Perforated Liner
available option on all return air unit.
• Includes factory mounted 4-row [chemically cleanable coil]
[mechanically cleanable coil], control valves and piping.
• Rated for 300 psig as standard [450 psig] waterside working
pressure and the entire coil and piping assembly is factory
leak tested.
• Factory integrated MicroTech III controller to control
economizer operation and maximize free cooling potential.
• Unit enables economizer operation whenever cooling tower
water temperature is less than the unit entering air
temperature by a field adjustable value, generally 5-7°F.
Airside Economizer
• A mixing box containing outdoor air, return air and exhaust
air dampers are available using the Daikin Vision™ air
handling unit platform.
• Factory integrated MicroTech III controller controls
economizer operation and maximize free cooling potential.
• Airside economizer control package available to control
field installed mixing dampers capable of 100% outside
airflow.
• Unit enables economizer operation whenever outside air
enthalpy, comparative enthalpy or dry bulb temperature
changeover provides control flexibility to bring in most
amount of outside air for free cooling. Blank Sections
• Economizer damper control actuator modulates in response • Available to mount air blenders, pre-heat coils, sound
to the cooling load. attenuators or other specialty equipment using the Daikin
• MicroTech III controller positions outside air damper to Vision™ air handling unit platform and shipped loose.
maintain minimum ventilation requirements when • Allow customization for maximum system performance and
economizer is not in operation. efficiency and reduce design and installation costs.
Along with providing high quality and state-of-the-art discharge orientations. Piping and fan arrangement flexibility
innovation, SWP self-contained systems offer customized can simplify mechanical equipment room arrangement,
flexibility to satisfy a wide range of diverse applications. improve installation costs, and total system performance.
Communication Module
An optional communication module provides the means to
factory or field configure MicroTech III unit controls for
interoperability with an independent BAS. Communication
modules are available to support industry recognized
communication protocols including BACnet MS/TP, BACnet/
IP and LONWORKS.
www.
Dai
kinAppl
ied.
com
Alarm Priority
The various alarms that can occur are prioritized according to
the severity of the problem. See Table 1. Three alarm
categories are used: faults, problems, and warnings.
1 Faults are the highest priority alarms. If a fault condition
Project Ahead Algorithm
occurs, the complete unit shuts down until the alarm
Because the inherent lag effect in zone temperature control
condition is gone and the fault is manually cleared at the
applications can cause overshoot during warm-up or cool-
keypad. A fault example is Fan Fail alarm.
down periods, MicroTech III features a “Project Ahead”
control algorithm. Project Ahead calculates the rate at which 2 Problems are the next lower priority to alarms. If a
the Control Temperature is changing and reduces the unit’s problem occurs, the complete unit does not shut down,
cooling or heating output as the zone temperature nears its set but its operation is modified to compensate for the alarm
point, essentially eliminating overshoot. condition. A problem automatically clears when the
alarm condition that caused it is gone. Compressor Fail is
Duct Static Pressure Control an example of a problem where only the affected
On all VAV-DTC units, duct static pressure control is compressor is shut down.
maintained by the PI algorithm, which provides precise control 3 Warnings are the lowest priority alarms. No control
of the supply fan variable speed drive. The keypad action is taken when a warning occurs; it is indicated to
programmable set point can be set between 0.20-in. W.C. and alert the operator that the alarm condition needs
4.00-in. W.C. attention. To make sure that they are read, the operator
On larger buildings with multiple floors, multiple trunk runs or must manually clear all warnings. Dirty Filter indication
large shifts in load due to solar effects (east/west building is an example of a warning.
orientation), an optional second duct static sensor is offered. Generally, a specific alarm condition generates an alarm that
The MicroTech III controller automatically selects and uses the falls into only one of these categories. Under different sets of
lower of the two sensed pressures to control fan volume to circumstances, however, the freezestat and most of the sensor
provide adequate static pressure to the most demanding space failure alarm conditions can generate alarms that fall into
at all times. multiple categories.
36"
Front Side
NOTE: If water and condenser drains are on the motor side, 24" is required.
Filtration
Routinely replace filters to minimize filter loading. As filters
get dirty, the filter pressure drop increases, affecting system
airflow and energy requirements. The effect of filter loading is
the most critical when using high efficiency filters.
When making a fan selection, include a pressure drop
component in the system total static pressure to account for
dirty filters. Use a value midway between clean and dirty filter
ratings. If a minimum airflow is critical, make the fan selection
using the higher, dirty filter pressure drop value. For VAV
systems, consider setting the fan control device so part of its
modulation range can be used to maintain airflow as filters
become dirty. Following these recommendations should limit
airflow fluctuation as the filters load.
Airflow
Maximum cfm limits based on coil face velocity are listed in
the Physical Data tables starting on page 31.
Separate minimum design cfm limits by unit size are listed in
the physical data table for constant and variable air volume
applications. Limit fan modulation to 40% of the minimum
design cfm limit. Minimum airflow conditions are dependent
on fan selection criteria also. Contact your Daikin sales
(fan heat (MBh))
representative to answer questions on minimum airflow Fan temperature rise =
capability or for conditions not shown in this catalog. (1.085 × fan cfm)
VAV box minimum airflow settings should correspond with
the minimum VAV fan operating point. All units are provided A draw-through unit has the fan located after the DX cooling
with multigroove, fixed pitch sheaves. During system air coil. In this arrangement, fan heat is applied as reheat to the
balance, alternate fixed pitch sheaves may be needed to match cold, conditioned air coming off of the coil. This arrangement
final system requirements. Alternate sheaves are available has a lower sensible heat ratio and higher dehumidification
from Daikin. capability than a blow-through coil arrangement. The
discharge temperature available to the supply duct is always
Fan Heat the sum of the coil leaving air temperature plus the fan
temperature rise. Consider this when selecting the supply air
Sensible heat gain from the fan, fan motor, and drives occurs volume required to satisfy space requirements.
in all fan systems; consider its effect during equipment
Example:
selection. It is an added load in cooling and an added source
when in heating. The majority of the heat gain occurs through leaving fan discharge
the fan itself, as the air elevates from the low-pressure side to 52°F coil
temperature
+ 3°F temperature
rise
= 55°F air
temperature
the high-pressure side of the fan. Moving the motor out of the
air stream has a negligible effect on overall fan heat gain. A
unit with higher fan power requirements/higher fan heat has Condenser Water Flow
less net cooling capability and may not have enough left to
System capacity tables provide selections for a condenser flow
satisfy system loads.
rate of 3 gpm/ton. For a given entering condenser water
As a rule, typical supply fan heat gain is 3°F. However, fan temperature, 3 gpm/ton provides maximum unit performance.
heat gain can be calculated quickly once the fan is selected and Reducing condenser water flow rates to 2.5 or 2 gpm/ton can
the fan brake horsepower is determined. Using Figure 23, significantly reduce pumping energy costs and reduce piping
select your fan brake horsepower on the horizontal axis and costs. Compare and evaluate the reduction in pumping energy
move up vertically until you intersect with the heat gain curve. to the change in unit performance. Use the SWP capacity
Then move horizontally to find the fan heat gain in MBh. tables (Table 8, page 36) for condenser flow rates from 2 to 3
gpm/ton, using the appropriate leaving condenser water
temperature column (interpolation is allowed). The minimum
condenser flow rate is 2 gpm/ton.
Terms of Sale
All products are offered pursuant to Daikin’s standard terms
and conditions of sale including limited product warranty,
which can be accessed at www.DaikinApplied.com.
For a computer-generated, job-specific selection, contact your local Daikin sales representative. For 50 Hz applications, derate the total capacity by
0.89; derate the sensible capacity by 0.94. All capacities are gross and do not account for fan motor heat.
For a computer-generated, job-specific selection, contact your local Daikin sales representative. For 50 Hz applications, derate the total capacity by
0.89; derate the sensible capacity by 0.94. All capacities are gross and do not account for fan motor heat.
For a computer-generated, job-specific selection, contact your local Daikin sales representative. For 50 Hz applications, derate the total capacity by
0.89; derate the sensible capacity by 0.94. All capacities are gross and do not account for fan motor heat.
For a computer-generated, job-specific selection, contact your local Daikin sales representative. For 50 Hz applications, derate the total capacity by
0.89; derate the sensible capacity by 0.94. All capacities are gross and do not account for fan motor heat.
For a computer-generated, job-specific selection, contact your local Daikin sales representative. For 50 Hz applications, derate the total capacity by
0.89; derate the sensible capacity by 0.94. All capacities are gross and do not account for fan motor heat.
For a computer-generated, job-specific selection, contact your local Daikin sales representative. For 50 Hz applications, derate the total capacity by
0.89; derate the sensible capacity by 0.94. All capacities are gross and do not account for fan motor heat.
For a computer-generated, job-specific selection, contact your local Daikin sales representative. For 50 Hz applications, derate the total capacity by
0.89; derate the sensible capacity by 0.94. All capacities are gross and do not account for fan motor heat.
Table 19: SWP 023 through 033 (pressure drop in inches wg)
Nominal Standard Coil Filters Discharge Plenum
2
Air Flow 17.2 ft Left & Front
(cfm) 2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Evaporator Economizer Right & Back
4000 0.26 0.13 0.09 0.11 0.09 0.14 0.07 0.24 0.01 0.00
6000 0.48 0.25 0.18 0.20 0.16 0.25 0.13 0.43 0.01 0.01
8000 0.73 0.41 0.31 0.31 0.25 0.40 0.21 0.64 0.03 0.01
10000 1.02 0.6 0.45 0.42 0.34 0.57 0.29 0.88 0.04 0.01
Nominal Large Coil Filters Discharge Plenum
Air Flow 25.2 ft2 Left & Front
(cfm) 2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Evaporator Economizer Right & Back
6000 0.27 0.13 0.09 0.11 0.10 0.14 0.08 0.25 0.01 0.01
8000 0.41 0.21 0.16 0.17 0.14 0.22 0.12 0.37 0.02 0.01
10000 0.58 0.31 0.23 0.24 0.20 0.32 0.16 0.51 0.04 0.01
12000 0.75 0.43 0.32 0.32 0.26 0.42 0.21 0.66 0.06 0.02
14000 0.95 0.56 0.42 0.40 0.32 0.53 0.27 0.82 0.08 0.03
16000 1.11 0.6 0.53 0.48 0.39 0.65 0.33 0.99 0.10 0.04
Note: DX pressure drops are wet coil and economizers are dry coil.
All units must have a DX coil pressure drop.
Based on 32" high plenum with maximum allowed opening.
Table 20: SWP 039 through 050 (pressure drop in inches wg)
Nominal Standard Coil Filters Discharge Plenum
Air Flow 25.2 ft2 Left & Front
(cfm) 2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Evaporator Economizer Right & Back
6000 0.27 0.13 0.09 0.11 0.10 0.14 0.08 0.25 0.01 0.01
8000 0.41 0.21 0.16 0.17 0.14 0.22 0.12 0.37 0.03 0.01
10000 0.55 0.31 0.23 0.24 0.20 0.32 0.16 0.51 0.04 0.01
12000 0.72 0.43 0.32 0.32 0.26 0.42 0.21 0.66 0.06 0.02
16000 0.88 0.56 0.42 0.40 0.32 0.53 0.27 0.82 0.08 0.03
Nominal Large Coil Filters Discharge Plenum
2
Air Flow 29.8 ft Left & Front
(cfm) 2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Evaporator Economizer Right & Back
10000 0.45 0.24 0.17 0.19 0.16 0.24 0.13 0.40 0.04 0.01
12000 0.59 0.32 0.24 0.25 0.20 0.32 0.17 0.52 0.06 0.02
14000 0.74 0.42 0.31 0.31 0.25 0.41 0.21 0.65 0.08 0.03
16000 0.88 0.53 0.39 0.38 0.31 0.50 0.25 0.78 0.10 0.04
Note: DX pressure drops are wet coil and economizers are dry coil.
All units must have a DX coil pressure drop.
Based on 32" high plenum with maximum allowed opening.
Table 21: SWP 044 through 065 (pressure drop in inches wg)
Nominal Standard Coil Filters Discharge Plenum
Air Flow 40.8 ft2 Left & Front
(cfm) 2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Evaporator Economizer Right & Back
10000 0.28 0.14 0.10 0.12 0.10 0.15 0.08 0.26 0.03 0.01
12000 0.37 0.19 0.14 0.16 0.13 0.20 0.10 0.33 0.05 0.01
14000 0.46 0.24 0.18 0.20 0.16 0.25 0.13 0.42 0.06 0.02
16000 0.48 0.31 0.23 0.24 0.19 0.31 0.16 .050 0.08 0.02
18000 0.65 0.38 0.28 0.28 0.23 0.37 0.19 0.59 0.10 0.03
20000 0.76 0.45 0.34 0.33 0.27 0.44 .022 0.69 0.13 0.04
22000 0.86 0.53 0.40 0.38 0.31 0.51 0.26 0.79 0.16 0.04
24000 0.98 0.61 0.46 0.43 0.35 0.58 0.29 0.89 0.18 0.05
Nominal Large Coil Filters Discharge Plenum
Air Flow 45.8 ft2 Left & Front
(cfm) 2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Evaporator Economizer Right & Back
12000 0.32 0.16 0.11 0.13 0.11 0.17 0.09 .028 0.05 0.01
14000 0.40 0.21 0.15 0.17 0.14 0.21 0.11 0.35 0.06 0.02
16000 0.55 0.26 0.19 0.20 0.17 0.26 0.13 0.43 0.08 0.02
18000 0.56 0.32 0.23 0.24 0.20 0.31 0.16 0.50 0.10 0.03
20000 0.64 0.38 0.27 0.28 0.23 0.37 0.19 0.58 0.13 0.04
22000 0.74 0.44 0.32 0.32 0.26 0.42 0.22 0.67 0.16 0.04
24000 0.84 0.51 0.38 0.36 0.29 0.48 0.25 0.76 0.18 0.05
26000 0.94 0.59 0.43 0.41 0.33 0.55 0.28 0.85 0.22 0.06
Note: DX pressure drops are wet coil and economizers are dry coil.
All units must have a DX coil pressure drop.
Based on 32" high plenum with maximum allowed opening.
Table 22: SWP 062 through 088 (pressure drop in inches wg)
Nominal Standard Coil Filters Discharge Plenum
Air Flow 52.5 ft2 Left & Front
(cfm) 2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Evaporator Economizer Right & Back
12000 0.26 0.12 0.09 0.11 0.09 0.14 0.07 0.23 0.03 0.01
14000 0.38 .012 0.12 0.14 0.11 0.17 0.09 0.29 0.04 0.01
16000 0.45 0.16 0.15 0.16 0.14 0.21 0.11 0.35 0.05 0.01
18000 0.53 0.19 0.18 0.20 0.16 0.25 0.13 0.42 0.07 0.02
20000 0.62 0.23 0.22 0.23 0.19 0.30 0.15 0.48 0.09 0.02
22000 0.70 0.27 0.26 0.26 0.21 0.34 0.18 0.55 0.10 0.03
24000 0.80 0.31 0.30 0.30 0.24 0.39 0.20 .062 0.12 0.03
26000 0.91 0.35 0.34 0.33 0.27 0.44 0.23 0.70 0.14 0.04
28000 1.01 0.40 0.39 0.37 0.30 0.50 0.25 0.78 0.17 0.04
30000 1.13 0.45 0.44 0.41 0.33 0.55 0.28 0.86 0.19 0.05
Note: DX pressure drops are wet coil and economizers are dry coil.
All units must have a DX coil pressure drop.
Based on 32" high plenum with maximum allowed opening.
Table 23: SWP 065 through 130 (pressure drop in inches wg)
Nominal Standard Coil Filters Discharge Plenum
Air Flow 60.9 ft2 Left & Front
(cfm) 2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Evaporator Economizer Right & Back
16000 0.36 0.16 0.11 0.13 0.11 0.17 0.09 0.29 0.04 0.01
18000 0.43 0.19 0.14 0.16 0.13 0.20 0.11 0.34 0.05 0.02
20000 0.52 0.23 0.17 0.18 0.15 0.24 0.12 0.39 0.06 0.02
22000 0.60 0.27 0.20 .021 0.17 0.27 0.14 0.45 0.08 0.03
24000 0.68 0.31 0.23 0.24 0.20 0.31 0.16 0.51 0.09 0.03
26000 0.77 0.35 0.26 0.27 0.22 0.35 0.18 0.57 0.11 0.04
28000 0.86 0.40 0.30 0.30 0.24 0.40 0.20 0.63 0.13 0.04
30000 0.94 0.45 0.34 0.33 0.27 0.44 0.22 0.69 0.15 0.05
32000 1.03 0.51 0.38 0.37 0.30 0.49 0.25 0.75 0.17 0.06
34000 1.13 0.56 0.42 0.40 0.32 0.53 0.27 0.83 0.19 0.06
36000 1.22 0.62 0.47 0.43 0.35 0.58 0.29 0.90 0.21 0.07
Nominal Large Coil Filters Discharge Plenum
Air Flow 71.3 ft2 Left & Front
(cfm) 2", 30% 2", 75% 4", 30% 4", 65% 4", 75% 2", 85%
Evaporator Economizer Right & Back
18000 0.34 0.15 0.10 0.12 0.10 0.16 0.08 0.27 0.05 0.02
20000 0.41 0.17 0.13 0.15 0.12 0.19 0.10 0.31 0.06 0.02
22000 0.48 0.20 0.15 0.17 0.14 0.21 0.11 0.36 0.08 0.03
24000 0.54 0.24 0.17 0.19 0.16 0.25 0.13 0.40 0.09 0.03
26000 0.61 0.27 0.20 0.21 0.18 0.28 0.14 0.45 0.11 0.04
28000 0.68 0.31 0.23 0.24 0.20 0.31 0.16 0.50 0.13 0.04
30000 0.75 0.35 0.26 0.26 0.22 0.35 0.18 0.55 0.15 0.05
32000 0.83 0.39 0.29 0.29 0.24 0.38 0.19 0.61 0.17 0.06
34000 0.90 0.43 0.32 0.32 0.26 0.42 0.21 0.66 0.19 0.06
36000 0.97 0.47 0.35 0.34 0.28 0.46 0.23 0.72 0.21 0.07
38000 1.04 0.52 0.39 0.37 0.30 0.50 0.25 0.78 0.23 0.08
40000 1.13 0.57 0.43 0.40 .032 0.54 0.27 0.83 0.26 0.09
42000 1.21 0.62 0.46 0.43 0.35 0.58 0.29 0.89 0.28 0.10
Note: DX pressure drops are wet coil and economizers are dry coil.
All units must have a DX coil pressure drop.
Based on 32" high plenum with maximum allowed opening.
Figure 25: Standard Economizer Coil Figure 27: Large Economizer Coil
NOTE: Total water pressure drop varies depending on a units selected options. Only use the specific chart which reflects your
unit. The above figures illustrate total water pressure drop (WPD) for each associated model number.
• Use Figure 24 if no water side economizer coil or water regulating valve is provided.
• Use Figure 25 for standard economizer coils and Figure 27 for large economizer coils.
• Use Figure 26 if a water regulating valve is provided.
Figure 29: Standard Economizer Coil Figure 31: Large Economizer Coil
NOTE: Total water pressure drop varies depending on a units selected options. Only use the specific chart which reflects your
unit. The above figures illustrate total water pressure drop (WPD) for each associated model number.
• Use Figure 28 if no water side economizer coil or water regulating valve is provided.
• Use Figure 29 for standard economizer coils and Figure 31 for large economizer coils.
• Use Figure 30 if a water regulating valve is provided.
Figure 33: Standard Economizer Coil Figure 35: Large Economizer Coil
NOTE: Total water pressure drop varies depending on a units selected options. Only use the specific chart which reflects your
unit. The above figures illustrate total water pressure drop (WPD) for each associated model number.
• Use Figure 32 if no water side economizer coil or water regulating valve is provided.
• Use Figure 33 for standard economizer coils and Figure 35 for large economizer coils.
• Use Figure 34 if a water regulating valve is provided.
NOTE: Total water pressure drop varies depending on a units selected options. Only use the specific chart which reflects your
unit. The above figures illustrate total water pressure drop (WPD) for each associated model number.
• Use Figure 36 if no water side economizer coil or water regulating valve is provided.
• Use Figure 37 for standard economizer coils.
• Use Figure 38 if a water regulating valve is provided.
Figure 40: Standard Economizer Coil Figure 42: Large Economizer Coil
NOTE: Total water pressure drop varies depending on a units selected options. Only use the specific chart which reflects your
unit. The above figures illustrate total water pressure drop (WPD) for each associated model number.
• Use Figure 39 if no water side economizer coil or water regulating valve is provided.
• Use Figure 40 for standard economizer coils and Figure 42 for large economizer coils.
• Use Figure 41 if a water regulating valve is provided.
Figure 25: Standard Economizer Coil Figure 27: Large Economizer Coil
NOTE: Total water pressure drop varies depending on a units selected options. Only use the specific chart which reflects your
unit. The above figures illustrate total water pressure drop (WPD) for each associated model number.
• Use Figure 24 if no water side economizer coil or water regulating valve is provided.
• Use Figure 25 for standard economizer coils and Figure 27 for large economizer coils.
• Use Figure 26 if a water regulating valve is provided.
6.0
240
5.5 0 rp
m
5.0 10
220 bh
0 rp p
4.5 m
4.0 2000
rpm
3.5 7.5
1800
rpm
b hp
3.0
2.5 1600
r pm
2.0 1400 r
pm
1.5 5b
1200 rpm hp
1.0 1000 rpm
800 rpm
0.5 1.5 b 3 bh
600 rpm 1 bhp hp 2 bhp p
0.0
0.0
2.0
4.0
6.0
8.0
CFM (IN 1,000's)
7.5
7.0 2600 rpm
6.5
6.0 2400 rpm
5.5 15
b hp
5.0 2200 rpm
4.5
rpm
4.0 2000
3.5 1800 rpm
3.0 10
b hp
2.5 1600 rpm
2.0 1400 rpm
7.5
1.5 1200 rpm b hp
1.0 1000 rpm
800 rpm
0.5 600 rpm 1.5 bhp 2 bh 3b 5b
1 bhp p hp hp
0.0
0.0
2.0
4.0
6.0
8.0
10.0
7.5
00 rpm
7.0 24
6.5 20
bh
6.0 2200 rpm p
5.5
5.0 2000 rpm
4.5 15
4.0 1800 rpm b hp
3.5
1600 rpm
3.0
2.5 1400 rpm
2.0 10
1200 rpm b hp
1.5
1000 rpm
1.0 7.5
800 rpm b hp
0.5 600 rpm 1 bhp 1.5 bhp 2 bhp 3 bh 5 bh
400 rpm p p
0.0
0.0
2.0
4.0
6.0
8.0
10.0
12.0
CFM (IN 1,000's)
0 rp
7.5 2200 rpm m 25
7.0
b hp
6.5
6.0 2000 rpm
5.5
20
bh
p
5.0 1800 rpm
4.5
4.0 1600 rpm
15
3.5 b hp
3.0 1400 rpm
2.5
1200 rpm
2.0
1000 rpm 10 b
1.5 h p
1.0 800 rpm
7.5
600 rpm 3 bh 5 bh b hp
0.5
400 rpm 1 bhp 1.5 bhp 2 bhp p p
0.0
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
2000 rpm
7.5 30
bh
7.0 p
6.5
1800 rpm
6.0
25 b
5.5 hp
5.0 1600 rpm
4.5
20 b
4.0
1400 rpm
hp
3.5
3.0
1200 rpm 15 b
2.5 hp
2.0 1000 rpm
1.5
800 rpm
1.0 10 b
600 rpm 7.5 b h p
0.5 1 bhp 1.5 bhp 2 bhp 3 bh 5 bh h
400 rpm p p p
0.0
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
CFM (IN 1,000's)
6.5
6.0 1600 rpm
5.5 30
bh
p
5.0
1400 rpm
4.5 25
bh
4.0 p
3.5 1200 rpm
3.0 20 b
hp
2.5 1000 rpm
2.0
1.5 800 rpm 15 b
hp
1.0 600 rpm
0.5 1 bh 1.5 b 2 3b 7.5 b 10 b
400 rpm p hp bhp hp 5 bhp hp h p
0.0
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
20.0
22.0
7.5 p
1600 rpm
7.0
6.5 1500 rpm
6.0 40 b
1400 rpm hp
5.5
5.0 1300 rpm
4.5
4.0 1200 rpm 30 b
h p
3.5 1100 rpm
3.0 25 b
1000 rpm h p
2.5
900 rpm
2.0 800 rpm 20 b
h p
1.5 700 rpm
1.0 600 rpm
500 rpm 7.5 15 b
3b hp
0.5 400 rpm 1 bhp 1.5 bhp 2 bhp hp 5 bh
p
b hp 10 bhp
0.0
0.0
5.0
10.0
15.0
20.0
25.0
CFM (IN 1,000's)
7.5
7.0
1400 rpm
6.5 50
bh
p
6.0 1300 rpm
5.5
5.0 1200 rpm 40 b
4.5 hp
1100 rpm
4.0
3.5 1000 rpm
30 b
3.0 hp
900 rpm
2.5 25 b
800 rpm hp
2.0
700 rpm
1.5 20 b
600 rpm hp
1.0 500 rpm
1 7. 5 b 10 15
0.5 400 rpm
300 rpm 1 bhp .5 bhp 2 bhp 3 bh
p
5 bh
p hp b hp bhp
0.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
7.5
1300 rpm
7.0 60
bhp
6.5
1200 rpm
6.0
5.5 50
1100 rpm
bhp
5.0
4.5
1000 rpm
4.0 40
bhp
3.5 900 rpm
3.0
800 rpm 30
2.5 bhp
2.0 700 rpm
25
1.5 600 rpm bhp
1.0 500 rpm 20
400 rpm 7.5 b 15 bhp
0.5 1 bh 1.5 bh 2 b 3 bh 5 bhp 10 b b hp
300 rpm p p hp p h p hp
0.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
CFM (IN 1,000's)
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
1100 rpm m 10
7.5 0b
hp
7.0
6.5
1000 rpm
6.0
5.5
900 rpm
75
5.0 bh
p
4.5
4.0 800 rpm
60
3.5 bhp
3.0 700 rpm
50
2.5 bhp
600 rpm
2.0
500 rpm 40
1.5 bhp
1.0 400 rpm
300 rpm 7.5 b 10 b 15 b 20 25 30
0.5 1 bhp1.5 bhp2 bhp 3 bhp 5 bh hp h h bhp bhp bhp
200 rpm p p p
0.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
CFM (IN 1,000's)
Recommended Clearances
Table 24: Recommended Minimum Clearances
For good installation, service and maintenance access, follow
Location Clearance Length (Inches)
the recommended clearances given in this publication.
Front 36
Minimum clearances required by federal, state and local codes,
Rear 24
such as the NEC, take precedence over the dimensions given. Access Side 42
Clearance is required to allow room for side filter access, Opposite Access Side 18
mechanical cleaning of condenser tubes, economizer coil Note: For clearance requirements less than those indicated, contact
access to expansion valves and other control components and your local Daikin sales representative.
Rear Side
24"
Airflow
Evaporator Coil
18"
Opposite
Access
or 42" Access
24"
Side
Control Panel
Motor
Side See Note
36"
Front Side
NOTE: If water and condenser drains are on the motor side, 24" is required.
Figure 59: Self-Contained Top View (Left Hand Access Shown/without Discharge Plenum)
Left/Right Elevation
Small Tall 70 44
Depth Medium 86 48
Large 110 58
Large Tall 110 66
Height
Width
Height
Table 35: Unit and Component Weights for Small and Small Tall Cabinets
Small Cabinet Small Tall Cabinet
Component Description Unit Model Size
023 028 033 039 044 050
Basic Cabinet1 3587 3637 3651 3994 4008 4008
Cooling Coil Section–Drain Pan Only 1045 1081
Supply Fan/Control Panel Section 1061 993
Condenser/Compressor Section 1480 1530 1544 1920 1934 1934
Condenser Water Weight 29 31 35 44 47 50
Face Load Filter Rack
Rack Only 64 67
2"—MERV 7 15 16
4"—MERV 8 15 16
4"—MERV 11 62 63
4"—MERV 13 62 63
4"—MERV 14 62 63
Evaporator Coils
5 row–12 fpi 372 N/A
Large 5 row–12 fpi N/A 440
Waterside Economizer Coils
Large 4 row–12 fpi 316 371
Water Weight 117 152
Electric Heat
34 kW 20 20
Supply Fan Assembly
13" SWSI 106 N/A
15" SWSI 110 N/A
16" SWSI 122 N/A
18" SWSI 181 181
20" SWSI 195 195
22" SWSI 245 245
24" SWSI 267 267
27" SWSI N/A 395
Supply Fan Motor–ODP
3 HP 76 76
5 HP 88 88
7.5 HP 134 134
10 HP 158 158
15 HP 203 203
20 HP 235 235
Supply Fan Motor–TEFC
3 HP 77 77
5 HP 91 91
7.5 HP 150 150
10 HP 184 184
15 HP 253 253
20 HP 321 321
Variable Frequency Drive
3 HP 14 14
5 HP 14 14
7.5 HP 20 20
10 HP 20 20
15 HP 35 35
20 HP 35 35
Discharge Plenum
32" High without Sound Baffles 268
32" High with Sound Baffles 428
Note: 1 Basic unit consists of a cooling coil section without coils, a supply fan/control panel section without supply fans, supply fan motors or VFD and a
condenser/compressor section.
Table 36: Unit and Component Weights for Medium and Large Cabinets
Medium Cabinet Large Cabinet
Component Description Unit Model Size
044 050 056 062 065 062 073 080 088
Basic Cabinet1 4733 4747 5136 5136 5136 6179 8507 8563 8619
Cooling Coil Section–Drain Pan Only 1288 1542
Supply Fan/Control Panel Section 1377 1853
Condenser/Compressor Section 2067 2081 2470 2470 2470 2784 3506 3534 3562
Condenser Water Weight 52 55 61 64 68 67 85 88 91
Face Load Filter Rack
Rack Only 95 116
2"—MERV 7 22 27
4"—MERV 8 22 27
4"—MERV 11 91 112
4"—MERV 13 91 113
4"—MERV 14 91 113
Evaporator Coils
Large 5 row–12 fpi 668 776 — — —
Standard 6 row—12 fpi N/A — 776 776 776
Waterside Economizer Coils
Large 4 row–12 fpi 557 654
Water Weight 250 279
Electric Heat
34 kW 20 20
68 kW 40 40
Supply Fan Assembly
18" SWSI 181 N/A
20" SWSI 195 N/A
22" SWSI 245 245
24" SWSI 267 267
27" SWSI 395 395
30" SWSI 434 434
33" SWSI 592 592
36" SWSI 723 723
Supply Fan Motor–ODP
15 HP 203 N/A
20 HP 235 N/A
25 HP 290 290
30 HP 336 336
40 HP 434 434
50 HP N/A 723
Supply Fan Motor–TEFC
15 HP 253 N/A
20 HP 321 N/A
25 HP 354 354
30 HP 416 416
40 HP 538 538
50 HP N/A 612
Variable Frequency Drive
15 HP 35 N/A
20 HP 35 N/A
25 HP 53 53
30 HP 53 53
40 HP 53 53
50 HP N/A 152
Discharge Plenum
32" High without Sound Baffles 320 416
32" High with Sound Baffles 516 680
Note: 1 Basic unit consists of a cooling coil section without coils, a supply fan/control panel section without supply fans, supply fan motors or
VFD and a condenser/compressor section.
Table 37: Unit and Component Weights for Large Tall Cabinets
Large Tall Cabinet
Component Description Unit Model Size
065 073 080 088 099 105 120 130
Basic Cabinet1 6476 7199 7227 7255 7255 8300 8300 8300
Cooling Coil Section–Drain Pan Only 1610 1600
Supply Fan/Control Panel Section 2091 2276
Condenser/Compressor Section 2776 3498 3526 3554 3554 4424
Condenser Water Weight 70 85 88 91 102 128 134 141
Face Load Filter Rack
Rack Only 138
2"—MERV 7 32
4"—MERV 8 32
4"—MERV 11 132
4"—MERV 13 132
4"—MERV 14 132
Evaporator Coils
Large 5 row–12 fpi 1054 — — — — — — —
Large 6 row–12 fpi — 1054 1054 1054 1054 1054 1054 1054
Waterside Economizer Coils
Large 4 row–12 fpi 879
Water Weight 331
Electric Heat
34 kW 20
68 kW 40
Supply Fan Assembly
24" SWSI 267
27" SWSI 395
30" SWSI 434
33" SWSI 592
36" SWSI 723
40" SWSI 856
44" SWSI 1101
Supply Fan Motor–ODP
25 HP 290
30 HP 336
40 HP 432
50 HP 494
60 HP 675
Supply Fan Motor–TEFC
25 HP 354
30 HP 416
40 HP 538
50 HP 612
60 HP 905
Variable Frequency Drive
25 HP 53
30 HP 53
40 HP 53
50 HP 152
60 HP 152
Discharge Plenum
32" High without Sound Baffles 416
32" High with Sound Baffles 680
Note: 1 Basic unit consists of a cooling coil section without coils, a supply fan/control panel section without supply fans, supply fan motors or VFD and a
condenser/compressor section.
Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For
training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com and click on training, or call
540-248-9646 and ask for the Training Department.
Warranty
All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product
Warranty. Consult your local Daikin Representative for warranty details. Refer to Form 933-430285Y. To find your
local Daikin Representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787). To find your local service
office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date product
information, please go to www.DaikinApplied.com.