Amb24 3
Amb24 3
Torque min. 180 in-lb, for control of damper surfaces up to 45 sq. ft.
Application
For on/off and floating point control of dampers in HVAC systems. Actuator
sizing should be done in accordance with the damper manufacturer’s
specifications.
Operation
The actuator is not provided with and does not require any limit switches, but
Technical Data 1471
is electronically protected against overload. The anti-rotation strap supplied
Power Supply 24 VAC ± 20%, 50/60 Hz, 24 VDC ± 10%
with the actuator will prevent lateral movement. The actuator provides 95° of
Power Consumption Running 2.5 W rotation and a visual indicator indicates position of the actuator. When reaching
Power Consumption Holding 0.5 W the damper or actuator end position, the actuator automatically stops. The
Transformer Sizing 5.5 VA (class 2 power source) gears can be manually disengaged with a button on the actuator cover. The
Shaft Diameter 1/2” to 1.05” round, centers on 1/2” and 3/4” actuators use a sensorless brushless DC motor, which is controlled by an
with insert, 1.05” without insert Application Specific Integrated Circuit (ASIC). The ASIC monitors and controls
Electrical Connection 3ft [1m], 18 GA plenum rated cable with 1/2” the actuator’s rotation and provides a digital rotation sensing (DRS) function
conduit connector protected NEMA 2 (IP54) to prevent damage to the actuator in a stall condition. Power consumption is
Overload Protection electronic throughout 0° to 95° rotation reduced in holding mode. The -S version is provided with 1 built-in auxiliary
switch. This SPDT switch is provided for safety interfacing or signaling, for
Input Impedance 600 Ω
example, for fan start-up. The switching function is adjustable 0 to 95°. The
Angle of Rotation Max. 95°, adjustable with mechanical stop auxiliary switch is double insulated so an electrical ground connection is not
Torque 180 in-lbs [20 Nm] minimum necessary. Add-on auxiliary switches or feedback potentiometers are easily
Direction of Rotation (Motor) reversible with built-in switch fastened directly onto the actuator body for signaling and switching functions.
Position Indication reflective visual indicator (snap on)
Manual Override external push button
Running Time (Motor) 95 sec constant, independent of load
Ambient Humidity 5 to 95% RH non condensing (EN 60730-1) Dimensions (Inches[mm])
Ambient Temperature Range -22°F to 122°F [-30°C to 50°C]
Date created, 06/26/2017 - Subject to change. © Belimo Aircontrols (USA), Inc.
2.49” [63.4]
Housing NEMA 2, IP54, UL enclosure type 2
2.2” [56]
1.18”
[30] 4.3” [109] 2” [50.8]
Accessories
K-SA Reversible NKQB(X)/AMB(X) clamp (1/2” to 3/4”). 24 VAC Transformer A 1 3 11
ZG-100 Univ. right angle bracket (17” H x 11-1/8” W x 6” base).
ZG-101 Univ. right angle bracket (13” H x 11” W x 7-7/16” base).
Line Blk (1) Common
ZG-103 Univ. right angle bracket (7-1/2” H x 11” W x 2-3/4” base).
ZG-104 Univ. right angle bracket (13-5/8” H x 7-1/2” W x 4” base).
Volts Red (2) + Hot
ZG-NMA AMB(X), NMB(X), NKQB(X) crankarm adaptor kit.
AV8-25 9.8” shaft extension for 5/16” to 1” diameter shafts.
ZG-JSA-1 1” diameter jackshaft adaptor (11” L). Wht (3) Y Input
ZS-T Terminal-strip cover for NEMA 2 rating (-T models).
ZS-100 Weather shield - galvaneal (13” L x 8” W x 6” D). On/Off
ZS-150 Weather shield - PC w/ foam seal (16” L x 8-3/8” W x 4” D).
ZS-260 Explosion proof housing. 24 VAC Transformer A
1 3 11
ZS-300 NEMA 4X, 304 stainless steel enclosure.
TOOL-06 8 mm and 10 mm wrench.
Line Blk (1) Common
PS-100 Actuator power supply and control simulator.
S1A Auxiliary switch, 1x SPDT, 3A (0.5A inductive) @250 VAC max. Volts Red (2) + Hot
S2A Auxiliary switch, 2x SPDT, 3A (0.5A inductive) @250 VAC max.
P370 Shaft mount auxiliary switch, 1/2” shaft.
P1000A GR Feedback potentiometer 1000Ω. Wht (3) Y Input
24 VAC Transformer
A Actuators with appliance cables are numbered.
Line
Provide overload protection and disconnect as required. Volts
A
6 1 11
Actuators may also be powered by 24 VDC.
Hot Com
Blk (1) Common
Actuators Hot wire must be connected to the control board common.
Only connect common to neg. (-) leg of control circuits. Terminal Red (2) + Hot
models (-T) have no-feedback.
Actuators may be connected in parallel if not mechanically linked. Power Wht (3) Y Input
consumption and input impedance must be observed.