DR 120 Spec
DR 120 Spec
DR 120 Spec
■ Features :
AC input range selectable by switch
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
LED indicator for power on
100% full load burn-in test
Fixed switching frequency at 55KHz
3 years warranty
Bauar t gepruft
Sicherheit
egel ma ge
od o s
be wac g
SPECIFICATION
www. tuv.com
ID 2000000000
INPUT
AC CURRENT (Typ.) 2.6A/115VAC 1.6A/230VAC
INRUSH CURRENT (Typ.) COLD START 20A/115VAC 40A/230VAC
LEAKAGE CURRENT <3.5mA / 240VAC
105 ~ 150% rated output power
OVERLOAD
Protection type : Constant current limiting, recovers automatically after fault condition is removed
15 ~ 16.5V 29 ~ 33V 58 ~ 65V
PROTECTION OVER VOLTAGE
Protection type : Shut down o/p voltage, re-power on to recover
85℃±5℃ (TSW1) 90℃±5℃(TSW1) 90℃±5℃(TSW1)
OVER TEMPERATURE
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
WORKING TEMP. -10 ~ +60℃ (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -20 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 50℃)
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY STANDARDS UL508, UL60950-1, TUV EN60950-1, EAC TP TC 004 approved
SAFETY & WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2.0KVAC O/P-FG:0.5KVAC
EMC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
(Note 4) EMC EMISSION Compliance to EN55011,EN55032 (CISPR32) Class B, EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A, EAC TP TC 020
MTBF 432.1Khrs min. MIL-HDBK-217F (25℃)
OTHERS DIMENSION 65.5*125.2*100mm (W*H*D)
PACKING 0.79Kg; 20pcs/16.5Kg/1.29CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
NOTE
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
100
125.2
+V ADJ.
115VAC
230VAC
TB1 TB2
1 1
2
65.5
2
3 3
4
LED
2 AC/N
3 AC/L
NR
DETECTION
FG CIRCUIT
O.L.P. PWM
CONTROL
O.T.P. O.V.P.
48V 32 350
100
OUTPUT RIPPLE (mVp-p)
28 300
OUTPUT VOLTAGE (V)
80
24 250
60 12V,24V 20 200
LOAD (%)
16 150
40
12 100
20
8 80