SKEE2413 - Chapter 1 Part 2 Transformer-1
SKEE2413 - Chapter 1 Part 2 Transformer-1
Transformer
Azhar Khairuddin
School of Electrical Engineering
Faculty of Engineering
Universiti Teknologi Malaysia
INTRODUCTION
Introduction
Power transmission
Introduction
Power Transmission
Introduction
Supply N1 N2 Load
Primary
Winding
Multi-layer
Laminated Secondary
Iron Core Winding
X1
X2
H1 H2
Winding
Terminals
Construction
Iron core
Insulation
Secondary
winding
Terminals
IDEAL TRANSFORMER
Ideal Transformer
N1 m Im m
E1
2
N2 m V1 E1 N1 N2 E2 = V2
E2
2
4.44 N 2 m f
Im + I I2
1 m
V1 E1 1 2 E2 V2
Load
Turn ratio
If the primary winding has N1 turns and secondary
winding has N2 turns, then:
N1 E1 I2
a
N 2 E 2 I1
The input and output complex powers are equal
E1 I1* S1 S 2 E 2 I *2
Ideal Transformer
Transformer Rating
Practical transformers are usually rated
based on:
Voltage Ratio (V1/V2) which gives us the
turns-ratio
Power Rating, small transformers are
given in Watts (real power) and Larger
ones (Power Transformers) are given in
kVA (apparent power)
Ideal Transformer
Example 1
Determine the turns-ratio of a 5 kVA 2400V/120V
Power Transformer
Turns-Ratio = a = V1/V2 = 2400/120 = 20/1 = 20
This means it is a Step-Down transformer
Ideal Transformer
Example 2
A 480/2400 V (r.m.s) step-up ideal transformer
delivers 50 kW to a resistive load. Calculate:
the turns ratio,
(0.2)
the primary current,
(104.17A)
the secondary current.
(20.83A)
Ideal Transformer
Exercise 1
A 250kVA, 1100V/400v, 50Hz single-phase
transformer has 80 turns on the secondary.
Calculate:
the approximate values of the primary and secondary
currents
(227A, 625A)
the approximate number of primary turns
(220)
the maximum value of the flux
(22.5mWb)
Ideal Transformer
Nameplate of a transformer
Ideal Transformer
N1 E1 I 2
a
N 2 E 2 I1
Ideal Transformer
I1 I2
T
Vac V1 V2 Zload
Ideal Transformer
PRACTICAL TRANSFORMER
Practical Transformer
Equivalent Circuit
N1 E1 I 2
I1 I 0 I1 '
N 2 E 2 I1 '
Equivalent Circuit
R2 ' a R2
2
V2 ' aV2
X 2 ' a2 X 2 I1 ' I 2 / a
Approximate Equivalent Circuit
Example 3
A 100kVA transformer has 400 turns on the primary and 80
turns on the secondary. The primary and secondary
resistance are 0.3 ohm and 0.01 ohm respectively and the
corresponding leakage reactances are 1.1 ohm and 0.035
ohm respectively. The supply voltage is 2200V. Calculate:
the equivalent impedance referred to the primary circuit
(2.05 ohm)
the equivalent impedance referred to the secondary
circuit
(0.082)
Determination of equivalent circuit parameters
TRANSFORMER TEST
Transformer Test
Voc2
. Rc
Poc
Poc
0 cos 1
Voc I oc
Q Voc I oc sin 0
Voc2
. Xm
Q
Transformer Test – Short Circuit
V I sc
V sc
V I sc
V sc
Transformer Test – Short Circuit
Simplified circuit for calculation of series impedance
P sc
Re1 X e1
A W
V I sc
V sc
. Re1 R1 a R2 2
. X e1 X 1 a X 2 2
Transformer Test – Short Circuit
X e1 R e1
Xm Rc
Transformer Test
Example 4
Obtain the equivalent circuit of a 200/400V, 50Hz 1-
phase transformer from the following test data:-
O/C test : 200V, 0.7A, 70W - on L.V. side(LV data)
S/C test : 15V, 10A, 85W - on H.V. side(HV data)
Voltage Regulation
V1 V '
Voltageregulation 2
V1
V1 = no-load voltage
V2’ = secondary voltage referred to the primary (full-load condition)
Voltage Regulation
V2NL V2 Z2
I 2 Re 2 cos 2 I 2 X e 2 sin 2
Voltageregulation
V2 NL
(-) : leading power factor
(+) : lagging power factor
Voltage Regulation
V1 V2' Z’2
Example 5
Based on Example 3 calculate the voltage regulation
and the secondary terminal voltage for full load
having a power factor of
0.8 lagging
(0.0336pu,425V)
0.8 leading
(-0.0154pu,447V)
Approximate Equivalent Circuit
Example 3
A 100kVA transformer has 400 turns on the primary and 80
turns on the secondary. The primary and secondary
resistance are 0.3 ohm and 0.01 ohm respectively and the
corresponding leakage reactances are 1.1 ohm and 0.035
ohm respectively. The supply voltage is 2200V. Calculate:
the equivalent impedance referred to the primary circuit
(2.05 ohm)
the equivalent impedance referred to the secondary
circuit
(0.082)
Voltage Regulation
Losses in transformer
EFFICIENCY
Efficiency
Losses in a transformer
Copper losses in primary and secondary windings
Core losses due to hysteresis and eddy current. It
depends on maximum value of flux density,
supply frequency and core dimension. It is
assumed to be constant for all loads
Efficiency
Example 6
The following results were obtained on a 50 kVA
transformer:
open circuit test – primary voltage, 3300 V; secondary
voltage, 400 V; primary power, 430W.
Short circuit test – primary voltage, 124V;primary current,
15.3 A; primary power, 525W; secondary current, full load
value.
Calculate the efficiency at full load and half load for
0.7 power factor.
(97.3%, 96.9%)
Efficiency
Exercise 2
The primary and secondary windings of a 500kVA
transformer have resistance of 0.42 ohm and 0.0019
ohm respectively. The primary and secondary
voltages are 11000V and 400V respectively and the
core loss is 2.9kW, assuming the power factor of the
load to be 0.8. Calculate the efficiency on
Full load
half load
(98.3%, 98.1%)
Efficiency
Exercise 3
Assuming the power factor of the load to be 0.8,
find the output power at which the efficiency of the
transformer of Exercise 2 is a maximum and
calculate its value
(346.4kW, 98.4%)